Measuring The Voltage of A Three-Phase Circuit in A Generator Set Control System
Measuring The Voltage of A Three-Phase Circuit in A Generator Set Control System
DOI: 10.12716/1001.15.04.21
ABSTRACT: The article proposes a technical implementation of a high-speed voltage sensor in a three-phase
circuit of a generator set, the frequency of which changes in transient processes. Sequential differentiation,
rectification and intensification of phase voltages allows one to substantially reduce the influence of the current
frequency on the measured voltage during one current period.
877
voltage stabilization of synchronous generators, T T T
2 U T 2
( t ) dt = 02U m sin
multiple excitation current forcing systems are used. ui = 2u t dt == − m cos t 2 =
Excitation of the asynchronous generator through
0 T 2 T
0
the stator circuit allows realizing a voltage regulation
U mT U T 2U m
system that is practically invariant from the load, [5- =− ( cos − cos 0 ) = m =
8]. 2
The voltage control of the asynchronous generator The integration period is set by a
is carried out by switching to the three-phase stator synchronizing pulse which action in during positive
winding of the capacitor banks using triacs at certain value of the measured voltage. At the end of the
times when the voltages on the capacitor and the measurement process, the amplitude of the sync pulse
phase winding of the generator are equal. In this case, becomes equil zero, the value of the integral is
capacitors of different phases are switched at different memorized and stored until the next measurement
times, in accordance with the shifts of the phase period.
voltages. Therefore, the whole process of connecting a Simple circuit solutions of analog voltage sensors
three-phase unit takes time slightly less than the are proposed for both single-phase and three-phase
network period. circuits, which made it possible to significantly reduce
the dependence of the output signal of the voltage
sensor on the current frequency , [5,6], Fig. 1. In
2.1 Main part the frequency range from 40 to 50 Hz, the voltage
measurement error is about 2%, at it is -
The features of switching capacitor units determine 0.6%, and at it is +0.9%.
the requirements for the speed of the voltage sensor of
a three-phase network. The maximum speed of the
voltage stabilization system requires reliable
measurements of the RMS voltage for the three-
phase current period :
T
1 2
Us = u ( t ) dt
T
0
In most of the known sinusoidal voltage sensors,
the average voltage value is measured instead of
the RMS value, which significantly reduces the
computational complexity of their implementation.
With insignificant nonlinear distortions, the RMS
voltage value is proportional to its amplitude ,
therefore such a replacement is quite justified.
The calculation of the voltage average value is
associated with the integration of the voltage
instantaneous value during the positive half-
cycle of the alternating current , [6,9]. In this Figure 1. Dependence of the output signal of the AC voltage
case, the fixation of the voltage measurement period is sensor on the current frequency: – integration of the
carried out when the phase voltage passes through rectified voltage; – preliminary differentiation,
zero. rectification, and integration of voltage
A significant disadvantage of such sensors is the A diagram of the analog implementation of the
dependence of the output signal not only on the proposed method for a three-phase network is shown
voltage , but also on the frequency of the current in Fig. 2.
, as shown in our article [1]:
878
However, with unbalanced voltages, the form of
the charge of the capacitor ceases to be strictly
linear, but at the end of the half-period , the
value of the output signal is proportional to the
average value of the unbalanced phase voltages.
When regulating the voltage of an autonomous
generator, the deviation of the average value of the
phase voltages from the given one is used, depending
on which a control action is formed on the excitation
system of the generator.
Therefore, the authors checked the error of
measuring the average value of the asymmetric phase
voltages. The voltage amplitude of one of the phases
varied from 0 to 150% of the nominal value at
100% amplitudes of the other two phases. The
Figure 2. Analog part of the sensor for the average voltage obtained values of the output voltage of the
of a three-phase network sensor in relative units were compared with the
theoretical ones shown by the dotted line. These
Galvanic isolation and lowering of phase voltages results are shown in Fig. 4.
are provided by three transformers TR1, TR2 and TR3
with two output windings having a common point,
which makes it possible to realize full-wave
rectification of the alternating voltage of each phase
using diodes . Differentiation of input
signals is performed by RC - circuits .
Further addition and integration of the measured
signals is carried out by the operational amplifier
, the integration constant of which is determined
by the product of the capacitance on the
resistance (R14, R15). Synchronization with the
mains and discharge of the integrating capacitor is
performed by pulse shunting with the field-effect Figure 4. Accuracy and error in measuring the average
transistor , which is controlled by the operational value of asymmetric phase voltages
amplifier . Synchronizing circuit is
connected to the secondary winding of the phase When one of the voltages changes from 80 to 120%,
transformer. Oscillograms of the rectified phase the average value of the three voltage phases changes
voltages and the sensor output signal are shown in from 0.933 to 1.067. In this case, the sensor error is
Fig. 3. within the range of 0.1 - 0.6%.
Computer and physical modeling of the proposed
three-phase voltage sensor has shown that with an
asymmetry of the generator phase voltage up to 50%,
the output voltage of the sensor retains a sawtooth
shape, close to linear.
With a complete disconnection of one of the
phases, the error was 3.2%. Oscillograms are shown in
Fig. 5.
879
The voltage waveform in Fig. 5 is already Transformers TR1-TR3 reduce phase voltages and
significantly different from the linear one. The voltage provide electrical isolation of power and measuring
sensor circuit of a three-phase network remains circuits. Capacitors C1-C6 and resistors R1, R2, R4, R5,
operational even when two phases are disconnected, R7, R8 perform differentiation, and diodes D1-D6
i.e. for single-phase use. Oscillograms are shown in rectify phase voltages. Then the analog signals are fed
Fig. 6. to the analog ports A1-A3 of the controller. The
controller interface (terminals 1 to 8) outputs some
bytes of information from the voltage sensor in digital
form, and digital-to-analog conversion of the output
signal of the three-phase circuit voltage sensor is
performed on the resistors R15-R22 and R6.
A resistor-diode divider R10-D7-R11 is used for
synchronizing with the mains voltage, the output
signal of which is put to port A0.
880
control law. In Fig. 9, a, b, the upper diagram reflects 2. Vishnevsky, L.V.: Optimal voltage control of an
the output signal of the integral regulator, and the asynchronous generator. In: Vishnevsky, L.V. and
lower diagram illustrates the result of software Novosad, I. (eds.) Automation of ship technical facilities:
integration of the sensor signal of a three-phase scientific and technical collection of works. pp. 19–28
Odessa: OHMA (1993).
circuit. 3. Vishnevsky, L.V., Mukha, M.Y., Drankova, A.O.:
Digital integration of the sensor signal of a three- Improving the Energy Efficiency of Ship Electric
phase circuit and the formation of a synchronizing Installations by Using Asynchronous Generators. The
pulse allows you to optimize the ratio of the analog Proceedings of the Institute of Electrodynamics of the
National Academy of Sciences of Ukraine. 56, 40–56
and digital parts of the sensor according to the ease of (2020). https://doi.org/10.15407/publishing2020.56.040.
implementation criterion. 4. ISO 8528-3:2005: Reciprocating internal combustion
engine driven alternating current generating sets – Part
3: Alternating current generators for generating sets.
(2005).
3 CONCLUSIONS 5. Vishnevsky, L.V., Mukha, M.Y., Kuan, D.M.: Voltage
control of stand-alone asynchronous generating sets.
The developed sensor of the average value of three- LAP LAMBERT Academic Publishing (2016).
6. Vishnevsky, D.: Optimization of the voltage regulation
phase voltage measures in half the period of the law of an asynchronous generator. Energy saving,
alternating voltage. energy, energy audit. 12, 131, 40–46 (2014).
Preliminary differentiation of phase voltages made 7. Vishnevsky, L.: Time Constants of an Asynchronous
it possible to reduce the dependence of the sensor Generator with Capacitor Excitation. In: Vishnevsky, L.
and Mukha, M. (eds.) Electrical engineering and
output signal on the current frequency by 9 ... 12 electrical equipment. pp. 21–26 (1999).
times. 8. Vishnevsky, L.: Transient quality in pulsed voltage
The linearity of the sawtooth output of a three- stabilization systems for marine diesel generators. In:
Vishnevsky, L., Mukha, M., and Veretennik, A. (eds.)
phase transducer can significantly improve the
Automation of ship technical facilities. pp. 13–18 ,
performance of the transducer. Odessa: OSMA (2002).
The proposed method and scheme for the 9. Mustafa, G.: Modular multilevel converters for
implementation of a three-phase sensor remains balancing and filtering mains voltage in the vicinity of
AC traction substation. In: Mustafa, G., Gusev, S.,
operational in case of phase failure and for single- Ershov, A., and Luganskay, I. (eds.) Vesnik NTU. pp.
phase use. 495–500 (2015).
10. Electrical Installations in Ships: Part 101: Definitions and
General Requirements, IEC Standard 60092-101. (2018).
11. ISO 3046-4:2009: Reciprocating internal combustion
REFERENCES engines – Performance – Part 4: Speed governing. (2018).
12. ISO 8528-1:2018: Reciprocating internal combustion
1. Vishnevsky, L., Mukha, M., Vishnevsky, O., Vishnevsky, engine driven alternating current generating sets — Part
D.: Voltage Sensor of the Autonomous Generating Set. 1: Application, ratings and performance. (2018).
In: 2020 IEEE 15th International Conference on 13. Bulatov, R.: Improving the voltage asymmetry sensors of
Advanced Trends in Radioelectronics, three-phase electric machine generator sets. Bulletin of
Telecommunications and Computer Engineering UlSTU. 4, 40–41 (2011).
(TCSET). pp. 712–715 (2020).
https://doi.org/10.1109/TCSET49122.2020.235525.
881