6AG11556AA017BN0 Datasheet en
6AG11556AA017BN0 Datasheet en
6AG11556AA017BN0 Datasheet en
General information
Product type designation IM 155-6 PN ST
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot Yes; Single hot swapping
swapping)
● Isochronous mode No
Engineering with
● PROFINET as of GSD version/GSD revision V2.3 / -
Configuration control
via dataset Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Short-circuit protection Yes
Input current
Current consumption (rated value) 450 mA
Current consumption, max. 550 mA
Inrush current, max. 3.7 A
I²t 0.09 A²·s
Power
Infeed power to the backplane bus 4.5 W
Power loss
Power loss, typ. 1.9 W
Address area
Address space per module
● Address space per module, max. 256 byte; per input / output
Address space per station
● Address space per station, max. 512 byte; Dependent on configuration
Hardware configuration
Rack
● Modules per rack, max. 32; + 16 ET 200AL modules
Submodules
● Number of submodules per station, max. 256
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
● Number of ports 2
● integrated switch Yes
● RJ 45 (Ethernet) Yes; Pre-assembled BusAdapter BA 2x RJ45
● BusAdapter (PROFINET) Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; PROFINET MRP
Interface types
RJ 45 (Ethernet)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 10 Mbps Yes; for Ethernet services
● 100 Mbps Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● Autonegotiation Yes
Protocols
PROFINET IO Device
Services
— Isochronous mode No
— Open IE communication Yes
— IRT Yes; with send cycles of between 250 µs and 4 ms in increments
of 125 µs
— PROFIenergy Yes
— Prioritized startup Yes
— Shared device Yes
— Number of IO Controllers with shared 2
device, max.
Redundancy mode
● PROFINET system redundancy (S2) No
Media redundancy
— MRP Yes
— MRPD No
Open IE communication
● TCP/IP Yes
● SNMP Yes
● LLDP Yes
Isochronous mode
Isochronous operation (application synchronized up No
to terminal)
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Connection display LINK TX/RX Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics No
between PROFINET and all other circuits Yes; 1 500 V AC
between supply and all other circuits No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max. 70 °C; = Tmax
● vertical installation, min. -40 °C; = Tmin
● vertical installation, max. 50 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure- Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
altitude Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● With condensation, tested in accordance with 100 %; RH incl. condensation / frost (no commissioning in
IEC 60068-2-38, max. bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available Yes; Incl. diesel and oil droplets in the air
coolants and lubricants
Use in stationary industrial systems
— to biologically active substances according Yes; Class 3B2 mold, fungus and dry rot spores (with the
to EN 60721-3-3 exception of fauna); Class 3B3 on request
— to chemically active substances according Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
to EN 60721-3-3 52 (severity degree 3); *
— to mechanically active substances Yes; Class 3S4 incl. sand, dust, *
according to EN 60721-3-3
Use on ships/at sea
— to biologically active substances according Yes; Class 6B2 mold and fungal spores (excluding fauna); Class
to EN 60721-3-6 6B3 on request
— to chemically active substances according Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
to EN 60721-3-6 52 (severity degree 3); *
— to mechanically active substances Yes; Class 6S3 incl. sand, dust; *
according to EN 60721-3-6
Usage in industrial process technology
— Against chemically active substances acc. Yes; Class 3 (excluding trichlorethylene)
to EN 60654-4
— Environmental conditions for process, Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
measuring and control systems acc. to concentrations up to the limits of EN 60721-3-3 class 3C4
ANSI/ISA-71.04 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
Connection method
ET-Connection
● via BU/BA Send Yes; + 16 ET 200AL modules
Dimensions
Width 50 mm
Height 117 mm
Depth 74 mm
Weights
Weight, approx. 190 g; IM 155-6 PN BA with 2x RJ45 ports and server module