Frequency Regulation in A Hybrid Renewable Power Grid: An Effective Strategy Utilizing Load Frequency Control and Redox Flow Batteries
Frequency Regulation in A Hybrid Renewable Power Grid: An Effective Strategy Utilizing Load Frequency Control and Redox Flow Batteries
Frequency Regulation in A Hybrid Renewable Power Grid: An Effective Strategy Utilizing Load Frequency Control and Redox Flow Batteries
com/scientificreports
Keywords Fuzzy-PID + (T I Dµ) controller, Crayfish optimization algorithm, Load frequency control,
Renewable energy resources, Controlled redox flow batteries, Communication delay time
Abbreviations
RESs Renewable energy resources
PV Photovoltaic
ESSs Energy storage systems
SMES Superconducting magnetic energy storage
SSSC Static synchronous series compensator
PEVs The plug-in electric vehicles
CRFBs The controlled redox flow batteries
P.u The value of the per unit
ACE The area control error
Ush Undershoot
RLD Random load disruption
Osh Overshoot
SLD Step load disruption
AGC The automatic generation control
MW Mega-watt
LFC Load frequency control
CDT Communication delay time
FLC Fuzzy logic control
Tsim Total simulation time
dt Error signal sampling interval
1
Department of Electrical Engineering, Faculty of Engineering, Aswan University, Aswan 81542,
Egypt. 2Department of Electrical Engineering, Faculty of Engineering, Sohag University, Sohag 82524,
Egypt. *email: [email protected]
Vol.:(0123456789)
www.nature.com/scientificreports/
Background
Energy storage systems (ESSs) are becoming increasingly important as RESs become more prevalent in power
systems. ESSs provide distinct benefits while also posing particular barriers in the field of energy storage , engag-
ing a critical role in spanning the gap between energy generation and demand while integrating renewable
Vol:.(1234567890)
www.nature.com/scientificreports/
energy sources , but necessitating careful technological advances in selection , adaptability , and incorporation
into existing infrastructure. On the other hand , it is essential to maintain equilibrium among power generation
and demand in order to reinstate the power grid frequency to its desired orientation value. This task have been
achieved by LFC1. In recent times , the significance of LFC has grown substantially due to the expansion and
complexity of interconnected power grids , rising operational costs , and the limitations of traditional units.
These factors can potentially result in inadequate control performance. To address these challenges , extensive
research has been conducted considering LFC , with a particular revolve around exploring the potential benefits
of demand response. Numerous studies in the literature have aimed to investigate and comprehend how demand
response2 , ESSs3–5 , RESs for example photovoltaic (PV) p lants6 , flexible alternative current transmission system
controllers7 , and wind turbine g enerators8.
Harmony Search35,36 , Quasi-opposition Pathfinder Algorithm37 , Chaotic Chimp Sine Cosine Optimization
Algorithm38 , Quasi-oppositional Whale Optimization A lgorithm39. These alternative approaches have gained
attention as they offer a way to overcome these limitations and find optimal solutions more efficiently. By
leveraging meta-heuristic optimization techniques, researchers can enhance the performance of LFC controllers
and find more robust and effective parameter settings. Accordingly , the authors propose appling the COA
algorithm to determine the finest constraints of the considered controller. As, the considered COA method has
been developed to address the limitations associated with traditional optimization techniques. The COA method
offers advantages over conventional optimization algorithms by employing a gradient-free mechanism, which
helps overcome the issue of getting stuck in local solutions. Moreover, the COA algorithm has the capability
to find global solutions using a small number of search agents, further enhancing its superiority over other
optimization methods40. In this work, it is the first time to apply the COA technique in handling the LFC issue.
From a different perspective, when there is a large impact as well as a high penetration of renewable energy,
the frequency and tie line may be different for a long time, and oscillations may still occur. In this case, the
LFC response may not be sufficient to absorb the frequency change due to the slowness and poor quality of the
response. As a result, it is necessary to apply ESSs. However, different studies have applied different energy storage
Vol.:(0123456789)
www.nature.com/scientificreports/
strategies with rapid rejoinder, like superconducting magnetic energy storage (SMES) , fuel cell systems (FCSs) ,
plug-in electric vehicles (PEVs) , and redox flow batteries (RFBs) , for addressing the LFC issue. The utilization
of these devices has emerged as a new and intriguing research a rea3,4,41–47. Among these, RFB has shown its
advantages over other electronic devices (such as SMES) due to its ability to operate at normal temperature,
low loss and long service life. Consequently, RFBs is anticipated to be the most effective s olution48. In a study
described in 49 , the influence of RFBs and SMES units on enhancing the performance of a power grid was
investigated. Simulation outcomes indicated that the incorporation of RFB units more effectively dampened
dynamic responses in comparison to the SMES units. Additionally, the authors of demonstrated the superior
performance of RFBs in combination with the Unified Power Flow Controller and Interline Power Flow
Controller in Automatic Generation Control (AGC) on nonlinear power s ystems43,50. Furthermore, the stability
is achieved in a nonlinear power system by incorporating integral control of the LFC model with RFBs storage
and a Static Synchronous Series C ompensator51.
Research gap
Despite the pre-mentioned studies successfully achieved their objectives, these studies did not focus on the high
incorporation of RESs in the presence of high load demand. For example, more than one previous study focused
on conventional power plants and did not adequately consider the impact of RESs7,22,41,42. Nevertheless, the
present study emphasizes high renewables penetration like wind and solar energy, which are commonly utilized
in both areas of the power grid under examination. Additionally, numerous studies overlook the influence of
diverse load perturbation shapes, which can be essential for evaluating the applied controller25,26,28,30,31. However,
this study considered numerous load perturbation profiles like, step load disruptions (SLD) , series SLD, and
random load disruptions (RLD) which represent the forced outage of power plants or high change on the load
demand. Moreover, most previous studies considered applying different types of ESSs without applying any
controller to control their output5,43. However, this study consider the controlled ESSs to control the amount
of the power which will injected to the overall system. The standard IEEE 39 buses test system is considered.
Furthermore, the durability of the indicated controller is examined in this work by considering the challenge of
the communication delay time (CDT). The purpose is to validate the effectiveness of the proposed controller in
achieving stability and reliability in a practical power system setting. Furthermore, this paper’s main objective is
to address the limitations uncovered in previously published investigations concerning the frequency stability
problem. Therefore, Table 1 provides a clear overview of the variances between this study and other researches
in the literature, emphasizing the unique contributions and approaches taken in this paper.
• Proposing a concerted strategy based on enhanced LFC in coordination with ESSs (i.e., CRFBs) improves
power grid stability during periods of disturbances in load and high RESs penetration. Where the proposed
controller in LFC is (fuzzy-PID) + (T I Dµ ) controller, whose superiority is confirmed by comparing its
performance with other controllers like the (PID, FO-PID, PD-PI and FO-(PD-PI)).
• Considering the COA technique to select the optimal parameters of the considered controllers, according to
its good optimization properties (i.e., balancing between exploration and exploitation) in order to enhance
the performance of the analyzed power grid.
• The superiority of the proposed strategy is validated considering high RESs, load disturbances as well as
CDT in considered hybrid power grid. Furthermore, the standard IEEE 39 buses is considered to confirm
the superiority of the proposed strategy.
References 5 7 16 22 49 51
This work
Fuzzy logic
Fuzzy fine-tuning (fuzzy-PID) + (T
Controller design Combining TD-TI Cascaded TID based self- PI I
approach I Dµ)
tuning PID
High penetration
√ × × × × × √
levels of RESs
Additional
Considered series Considered RFBs/ Considered RFBs/
improvements Considered PEVs Considered capacitor not considered Considered CRFBs
capacitors SMES SSSC
incorporation
Real-time validation
IEEE-39 bus system/
considering various × × × × × ×
SLD
load patterns
Real-time validation
considering high × × × × × × √
RESs penetration
Real-time validation
× × × × × × √
considering CDT
Table 1. Comparison of the present work’s motivation to those of other published studies.
Vol:.(1234567890)
www.nature.com/scientificreports/
The remaining content of the manuscript is structured as follows: "Background" provides a detailed overview
of the power grid under investigation, emphasizing its substantial penetration of renewable energy sources and
the integration of controlled redox flow battery (CRFB) systems within the proposed strategy. "State-of-the-art
literature review" describes the recommended approach, which involves the fuzzy-PID and (T I Dµ) controller,
and formulates the problem under analysis. "Research gap" outlines the methodology employed for the cray-
fish optimization algorithm (COA) procedure. "Article motivations and contributions" presents the simulation
results obtained from the aforementioned scenarios. Finally, in "Modeling of an investigated system", the study’s
conclusions and key findings are discussed and reviewed.
Re-heat Re-heat
thermal thermal
Turbine Hydro Turbine
Hydro Turbine
Turbine
RFB 1 RFB 2
fa fb
LFC Area 1 LFC Area 2
Load Load
Gas AC Gas
Turbine Transmission Link Turbine
Vol.:(0123456789)
www.nature.com/scientificreports/
RESs
1/R2 +
1/R3 +
Wind Kwind
Ba
farm Twind.s+1
Controller
1
ــ
1 Kr.Tr.s+1 1
KT fa
ACEa + Tsg.s+1 Tr.s+1 Tt.s+1
ــ Controller Thermal Reheater a Thermal
ــ 2 Governor a Turbine a + +
ــ 1 Trs.s+1 -Tw.s+1 + + Kpsa
KH + ــ
Controller + Tgh.s+1 Trh.s+1 (0.5).Tw.s+1 Tpsa.s+1
3 ــ
Hydro Transient Droop Hydro Power
Governor a Compensation a Turbine a System a
ــ Xc.s+1 1 Tcr.s+1 1
KG
Optimized via bg.s+cg Tfc.s+1 Tcd.s+1 Load
+ Yc.s+1
COA variation a
Secondary
Secondary
Gas Turbine Valve Fuel System & Gas Turbine
Speed Positioner a Combuster a Dynamics a
control
control loop a Governor a
loops 1 Ptie (2.pi.Tab) +
s ــ
a Optimized via PV Kpv
ab
+
+
Wind Kwind
Controller
farm Twind.s+1 fb
1
ACEb
ــ Controller ــ
+ + Kpsb
ــ 2 1 Kr.Tr.s+1 1
KT + Tpsb.s+1
ــ Tsg.s+1 Tr.s+1 Tt.s+1 ــ
Controller Power
Thermal Reheater Thermal
3
Governor b b Turbine b + System b
Bb + 1 Trs.s+1 -Tw.s+1 +
KH + Load
ــ Tgh.s+1 Trh.s+1 (0.5).Tw.s+1 variation b
Hydro Transient Droop Hydro
Secondary Governor b Compensation b Turbine b
+ Xc.s+1 1 Tcr.s+1 1
control loop b KG
ــ Yc.s+1 bg.s+cg Tfc.s+1 Tcd.s+1
Gas Turbine Valve Fuel System & Gas Turbine
Speed Positioner b Combuster b Dynamics b
Governor b
the air density, ρ (in kg /m3) , the wind speed, VW (in m/ s ) , and the blade pitch angle, β. The Cp can be expressed
as follow53:
3600 × R
i = (5)
1609 ×
ωB × R
= (6)
VW
where ωB specifies the angular velocity value of the blade (rad/sec).
The wind farm at Zafarana, Egypt, with a total installed capacity of 85 MW, is included in this study. Addi-
tionally, Fig. 3 presents the real output power data for the Zafarana windmill. One may theoretically describe
Vol:.(1234567890)
www.nature.com/scientificreports/
Hydro governor 1
Tgh ·s+1
Thermal governor 1
Tsg .s+1
Thermal turbine 1
Tt .s+1
Gas turbine’s speed governor xc ·s+1
Yc ·s+1
Table 2. The mathematical formulas regarding the considered power grid blocks.
the characteristics of the transfer function, which depicts the behavior of the integrated induction generator
in a wind power plant, as 0.3 s for the time constant (Twind ) and a unity gain ( Kwind ). Additionally, the overall
capacity applied in this work is ten Zafarana wind farms, with a total capacity of 850 MW .
0.3
0.25
0.2
ΔPwt (pu)
0.15
0.1
0.05
0
0 100 200 300 400 500 600 700 800
Time (min)
Figure 3. Energy generated by the Zafarana windmill s tation53.
Vol.:(0123456789)
www.nature.com/scientificreports/
This study focuses on a specific power grid and examines a realistic 50 MW PV system. The southern Egypt
represents the location of this aforementioned realistic PV power plant. Whereas, the realistic PV power plant
is modeled by a transfer function with 10 ms time constant (TPV ) and a unity gain ( KPV ). The output power
of this PV system is depicted in Fig. 4 illustrates the diagram of the output power produced by the PV system.
Appendix B provides the results of the analysis of data gathered for identifying the correlation between bright-
ness and PV temperature. Furthermore, the characteristics of the studied PV system are displayed in Figs. 5,6,
which emphasize the associations between the produced active power, the values of brightness, the produced
active power, and the temperature of the surroundings. Additionally, the overall capacity applied in this work is
ten realistic PV power plants, with a total capacity of 500 MW .
0.25
0.2
ΔPpv (pu)
0.15
0.1
06:00 AM
0.05
06:00 PM
0
0 100 200 300 400 500 600 700 800
Time (min)
Figure 4. The exact PV power plant power g eneration53.
Vol:.(1234567890)
www.nature.com/scientificreports/
Figure 6. Power generation characteristics and ambient temperature of the PV energy station.
offers excellent features such as improved power quality, load compensation, higher capacity compared to
conventional batteries, quick response time, and independence from self-discharge issues. During low load
demand periods, the CRFBs stores and saves the energy that is equivalent to the demand variations. This stored
energy can then be unrestricted back into the grid during load fluctuations, aiding in the elimination of power
grid oscillations.
In this study, a significant aspect of CRFBs modeling is the utilization of a comprehensive and realistic
dynamic model of redox flow batteries, rather than the simplistic first-order transfer function models commonly
used in several recent papers. The model incorporates the f (change in frequency) as an input. This paper
presents a controller design that incorporates a feedback path to generate control signals for CRFBs. This design
enables the CRFBs to respond efficiently to disturbances, resulting in improved performance. The designed
controller, denoted as K(s), is considered as a PID controller in this work. The relevant parameters of the CRFBs
are provided in the Appendix B. Figure 7 illustrates the block diagram of CRFBs. Equation (8) indicates how the
CRFBs unit is woven into the studied power g rid45.
1+s
�PCRFBi = kp,CRFBi �fi × − initial value × K(s)
1 + kr,CRFBi + s Tr,CRFBi + Td,CRFBi + s2 Tr,CRFBi Td,CRFBi
(8)
1 fi (s)
Td,CRFBi .s+1 + kP,CRFBi
pCRFBi
K(s)
+ -
Kkr,CRFBi
- r,RFPi
Tr,CRFBi .s+1
Designed controller
Initial value
Figure 7. CRFBs unit’s transfer function m
odel45.
Vol.:(0123456789)
www.nature.com/scientificreports/
exactly the same, with one significant difference. Instead of the proportional component, the TID controller
incorporates a tilted component with a transfer function of s−(1/n) , where n represents the FOCs. The TID
controller has numerous benefits over a typical PID controller. It exhibits better disturbance rejection, simplified
tuning process, and reduced sensitivity to variations in system parameters, resulting in improved dynamic
response. Additionally, another type of FOCs called the fractional-order-integral-derivative (FO-ID) controller
is available, which offers enhanced system performance and flexibility. Thus, this study replaced the second and
third gains in TID controller by the FO-I and FO-D terms to attain the T I Dµ controller. Where the frequency
fluctuations of the area (fi ) attends as the T I Dµ controller’s input signal. Furthermore, the mathematical
expression of T I Dµ controller is expressed according to the next equation:
Kti,i Ki,i
TI Dµ (s) = 1 + + Kd,i Sµ (9)
S n S
The constraints of gain values, kti,i(TI Dµ ) , ki,i(TI Dµ ) , kd,i(TI Dµ ) , n(TI Dµ ) , (TI Dµ ) , and µ(TI Dµ ) utilized in
this work in both areas of the considered power grid are expressed as follows:
kti,i(TI Dµ )max ≥ kti,i(TI Dµ ) ≥ kti,i(TI Dµ )min (10)
controller
kt 1
s 1/n
fi +
1 + + Ui
Input ki ∑ ∑
s ++ Control
signal +
signal
kd s
k1 k3
ACEi +
Input +
signal d k2 k4
dt Fuzzy Logic
Derivative gain Integral gain
Controller
fuzzy-PID controller
Vol:.(1234567890)
www.nature.com/scientificreports/
mathematics that decreases computational load. Triangular membership functions are typically used with PID
controllers and exhibit abundantly symmetric characteristics in both output as well as input. Furthermore, the
mathematical expression of (fuzzy-PID) controller is expressed according to the following equation:
K4,i
fuzzy − PID(s) = K1,i + K3,i + + K2,i s (16)
s
The constraints of gain values, K1,i , K2,i , K3,i , and K4,i utilized in this work in both areas of the analyzed power
grid are expressed as follows:
k1,i(fuzzy−PID)max ≥ k1,i(fuzzy−PID) ≥ k1,i(fuzzy−PID)min (17)
NB NS Z PS PB
1
0
_ _ _ _ _
1 0.8 0.6 0.4 0.2 0 0.2 0.4 0.6 0.8 1
Figure 9. The triangular membership functions of the FLC’s input and output.
dACE/dt
ACE NB NS Z PS PB
NB NB NB NB NS Z
NS NB NB NS Z PS
Z NB NS Z PS PB
PS NS Z PS PB PB
PB Z PS PB PB PB
Vol.:(0123456789)
www.nature.com/scientificreports/
I Dµ) controller, which combines two concepts. The first (fuzzy-PID) controller term receives the ACE signal
as an input. The extra (T I Dµ) controller term employs the f signal to improve system performance. It is
obviously true that the total arrangement of the proposed controller demonstrates superior rejection of existing
disturbances by mitigating all low- and high-frequency d isturbances4,6.
In this study, the authors propose the utilization of the integral time absolute error (ITAE) criteria as a means
for minimizing the value of the cost function. Optimizing development is improved by adding the element of a
time term to the ITAE criteria and the system constancy will be more enhanced compared to using the integral
of squared error (ISE) criteria. Increased efficacy in error reduction is achieved by multiplying the factor of time
by the integral of the absolute error. The ITAE principles can be expressed as follows:
Tsim
(21)
J = ITAE = t. |fa | + |fb | + ptie .dt
0
Where J denotes the value of proposed cost function which seeks to be the lowest possible value in this
work, |fa | represents the area-afrequency waveform’s absolute error, |fb | represents the area-b frequency
waveform’s absolute error, ptie represents the tie-line’s power flow change absolute error, Tsim denotes the
overall simulation runtime, and the variable dt symbolizes the error signal sampling period throughout the
simulation procedure.
where X refers the initial population position, N refers the population number, dim refers the population
dimension.
The fitness solution, which represents the solution with the best fitness value among the obtained solutions,
is calculated as following:
ffitness = [f 1f 2f 3 . . . . . . . . . . . . fN ]T (24)
Vol:.(1234567890)
www.nature.com/scientificreports/
Among them, σ and C1 is used to regulate crayfish intake at various temperatures, while µ refers to the optimal
crayfish temperature.
Where t refers the current iteration number, and t+1 refers the number of the next generation iteration,C2
refers the decreasing curve, as proved by Eq. (29).
C2 = 2 − (t/T) (29)
where t indicates the maximum iterations’ number.
Crayfish’s goal at the summer resort stage is to go close to the cave, which represents the optimal solution.
Consequently, crayfish will move towards the cave in an effort to get closer to the optimal solution. Individuals
become closer to the best solution through this process, which also improves the COA algorithm’s exploitation
capability, thus allowing for faster convergence.
Vol.:(0123456789)
www.nature.com/scientificreports/
While No The food intake P and food size Q are While Yes
Crayfish shreds food
temp <30 obtained using Eq. (15) and Eq. (22) Q <2 using Eq. (23)
Yes No
Determine cave Xshade using Crayfish foraging Crayfish foraging
Eq. (16) using Eq. (25) using Eq. (24)
t=t+1 Foraging stage
While Yes Crayfish conducts the summer
rand > 0.5 resort stage using Eq. (17)
Update fitness values XG
No Crayfish compete for caves using and XL
Eq. (20)
Summer resort stage
No While
t> T
Yes
End
largest food’s quantity as a benchmark for determining the size of food. When Q surpasses (C3+1)/2, it implies
a large amount of the food. Here, the crayfish is going to utilize their first claw foot for ripping the food. The
mathematical equation representing this action is provided as follows:
Xfood = exp −1Q × Xfood (34)
This mechanism enables crayfish to adapt their feeding behavior depending on the size of the food available,
ensuring efficient consumption and utilization of resources.
When the food becomes crumbly and smaller, the crayfish will pick it up with their second and third paws
alternatively and put it in their mouth. A sine and cosine function combination is utilized to describe this
alternating process. Furthermore, the crayfish’s food intake is related to the food they get. Foraging is calculated
as follows:
t+1 t
Xi,j = Xi,j + Xfood × p × (cos(2 × π × rand) − sin(2 × π × rand) (35)
When Q ≤ (C3+1)/2, the crayfish only needs to proceed forward to the food and devour it immediately. The
equation for this behavior is provided as follows:
t+1 t t
Xi,j = Xi,j − Xfood × p + p × rand × Xi,j (36)
Crayfish use a variety of feeding strategies during the foraging stage, which are determined by their food
size, denoted as Q . The food location Xfood represents the optimal solution in this context. If the food Q ’s size is
appropriate for crayfish feeding, they will approach the food and consume it. However, if Q is too large, it shows
that there is a significant difference between the optimal solution and the crayfish. In such cases, Xfood needs to
be adjusted to reduce the difference as well as moving it up close to the food. Furthermore, the randomness of
the crayfish food intake enhancement algorithm is under executive control. This ensures that the crayfish can
approach the optimal solution more effectively during the foraging stage. Through this process, the COA algo-
rithm gradually converges towards the optimal solution, enhancing its exploitation ability and achieving good
convergence performance. Here, Fig. 10 depicts the COA method’s flowchart.
Ethical approval
This article does not contain any studies with human participants or animals performed by any of the authors.
Vol:.(1234567890)
www.nature.com/scientificreports/
controllers. The proposed algorithm’s performance is additionally assessed in comparison to different techniques.
To optimize the suggested controller, the COA technique is employed to alleviate system frequency excursions.
The simulations are conducted using MATLAB/SIMULINK® program (R2016a) on a computer with specific
hardware specifications. For optimizing the proposed control structure, an m-file containing the original COA
algorithm code and paired with the stipulated power grid model is employed. The several simulation scenarios
are executed on a PC with the following specifications: 8.00 GB of RAM with a 2.60 GHz Intel Core i5 processor.
Furthermore, the frequency stability assessing takes into consideration varied operational conditions in the
scenarios listed below:
Scenario A Evaluating the analyzed power grid’s performance with different varied load pattern profiles.
Scenario B Evaluating the examined power grid’s performance involving high renewables penetration, aiming
to examine the grid’s capability to handle this issue.
Scenario C Evaluating the suggested controller’s robustness in real-time for stability and reliability using the
IEEE-39 bus system. The validation includes considering the impact of SLD.
Scenario D Evaluating the efficacy of the recommended controller utilizing a real-time IEEE-39 bus system,
considering high renewables penetration within the system, to assess its effectiveness with the goal to attain
dependability and stability.
Scenario E Evaluating the performance of the proposed controller under varying CDT conditions before and
after the LFC in the IEEE-39 bus system. This evaluation also considers high renewable energy penetrations.
Scenario F Evaluating the proposed strategy’s effectiveness by comparing the effectiveness of the IEEE 39 buses
system with and without the proposed strategy, considering high renewables penetration.
Scenario G Stability analysis of the proposed (fuzzy-PID) + (T I Dµ) controller.
When optimizing the proposed (fuzzy-PID) + (T I Dµ) controller using the COA algorithm, certain arrange-
ments should be considered. These include employing 30 search agents and performing 50 iterations. Figure 11
shows the obtained convergence curve, which provides insights into the investigated power grid’s performance
with the recommended COA-based controller. It should be noted that the presented convergence curve in the
figure is obtained assuming a 1% SLD occurring to area-a at t = 10 s within the examined power grid, without
considering a high renewables penetration. Whereas, the behavior of proposed controller based on COA is
summarized as beginning with a value of the objective function near 0.00201 and dropping with each attempt
until it achieves a value near 0.00188.
Scenario A Evaluating the analyzed power grid’s performance with different varied load pattern profiles.
The following scenario is intended to provide an initial comparison for accurately verifying the suggested
controller’s efficiency and algorithm in achieving frequency stabilization of the analyzed power grid. To conduct
a more detailed analysis, a comparison is made among various aforementioned published controllers.
Case A.1 In this case, it is assumed that area-a of the assessed power grid includes a step load. The purpose
is to assess the effectiveness of the COA algorithm in addressing the frequency stability issue through the use
of the supplementary control loop. Assuming a step load of 1% magnitude at t = 10 s, representing either the
disconnection of generation power plants or the disconnection of a variety of electrical loads. The obtained
controller parameters for the proposed controller and the other mentioned controllers are presented in Table 4.
Additionally, the system’s performance is depicted in Fig. 12.
The values of maximum overshoots (Osh) and maximum undershoots (Ush) obtained from the various con-
sidered dynamic responses of the analyzed power grid using the recommended controller relied on the COA
method are considerably lower than the results obtained with other mentioned controllers via various different
0.00202
0.002
0.00198
The objective function value
0.00196
0.00194
0.00192
0.0019
0.00188
0.00186
0.00184
0.00182
0.0018
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
Iteration No.
Figure 11. Obtained convergence curve of the suggested controller tuned by the COA method.
Vol.:(0123456789)
www.nature.com/scientificreports/
10-3
0
1% SLP
-2 PID based AOA [18]
FOPID based ESAOA [18]
PD-PI based HHO [3]
Δfa (pu)
-8
-10
0 5 10 15 20 25 30 35 40
Time (sec)
10-3
0
1% SLP
-1 PID based AOA [18]
FOPID based ESAOA [18]
Δfb (pu)
-3
-4
0 5 10 15 20 25 30 35 40
Time (sec)
-4
10
0
-2 1% SLP
ΔPtie (p.u. MW)
-10
-12
0 5 10 15 20 25 30 35 40
Time (sec)
Figure 12. LFC controllers’ dynamic responses to step load disruption for Case A.1.
Vol:.(1234567890)
www.nature.com/scientificreports/
Table 5. Specifications of the analyzed system’s transient response for scenario A.1. All values are multiplied
by (10−3).
Table 6. Percentage improvements in Osh and Ush for Case A.1. Optimal percentage values are highlighted in
bold format.
techniques, as shown in Fig. 12. Furthermore, Table 5 provides an in-depth overview of the system performance
in Case A.1. Then, Table 6 further highlights the percentage improvements in Osh and Ush for this specific case,
illustrating the enhancements achieved compared to the previous controllers.
Case A.2 A series SLD pattern is applied in this case to assess the performance of the proposed (fuzzy-
PID) + (T I Dµ) controller. This pattern involves a succession of forced switches of generators or outages of
connected loads, which can potentially lead to power grid instability. Figure 13 depicts the series SLD form.
Then, Fig. 14 presents the system’s various dynamic responses for this case.
Figure 14 illustrates that the maximum Osh and maximum Ush values obtained from the system’s dynamic
responses using the proposed (fuzzy-PID) + (T I Dµ) controller relied on COA are significantly lower than the
results obtained from the aforementioned published controllers. Furthermore, Table 7 provides the precise values
of Osh and Ush for the power flowing in the tie-line and frequencies for both areas. Additionally, Table 8 highlights
the system’s overall improvement percent achieved in this case.
Case A.3 Additionally, in area-a of the analyzed power grid, a random load fluctuation form is assumed,
occurring at t = 100 s. This form represents a wide range of disruptions in series in industrially interconnected
loads, producing similar grid effects, such as grid instability and the occurrence of blackouts. Figure 15 clarifies
the applicable RLD pattern. Furthermore, Fig. 16 provides a comparative analysis of the examined power grid’s
0.04
ΔPL (pu)
0.03
0.02
0.01
0
0 100 200 300 400 500 600
Time (sec)
Vol.:(0123456789)
www.nature.com/scientificreports/
0.01
0.005
Δfa (pu)
-0.005 PD-PI based HHO [3]
FO-(PD-PI) based MRFO [3]
-0.015
0 100 200 300 400 500 600
Time (sec)
-3
10
0
Δfb (pu)
-3
0 100 200 300 400 500 600
Time (sec)
10-4
4
2
ΔPtie (p.u. MW)
0
-2 PD-PI based HHO [3]
FO-(PD-PI) based MRFO [3]
-4 λ µ
Fuzzy-PID+(TI D ) based COA
-6
-8
0 100 200 300 400 500 600
Time (sec)
Figure 14. LFC controllers’ dynamic responses to series step load disruption for Case A.2.
Table 7. Specifications of the analyzed system’s transient response for scenario A.2. All values are multiplied
by (10−3).
Vol:.(1234567890)
www.nature.com/scientificreports/
Table 8. Percentage improvements in Osh and Ush for Case A.2. Optimal percentage values are highlighted in
bold format.
dynamic performance according to the recommended controller scheme and the other two aforementioned
controllers.
Figure 16 shows that the maximum Osh and maximum Ush values obtained from the considered power grid’s
dynamic responses utilizing the recommended (fuzzy-PID) + (T I Dµ) controller relied on COA are significantly
lower than the values obtained from the aforementioned published controllers. Furthermore, Table 9 shows the
precise values of Osh and Ush for the power flowing in the tie-line and frequencies for both areas. Table 10 also
shows the system’s overall improvement percent.
Scenario B Evaluating the examined power grid’s performance involving high renewables penetration, aiming
to examine the grid’s capability to handle this issue.
The scenario’s purpose is to examine the disturbances caused by a significant penetration of renewables in
both of the analyzed power grid’s areas. Specifically, area-a has been incorporated by 10 windmills and 10 PV
power plants at 100 min and 400 min, respectively, utilizing a random demand fluctuation pattern. In area-b, the
identical integration parameters for the penetration of renewables are applied; PV power plants integrate at 700
min and windmills at 600 min. The generated power from the RESs integrated into the analyzed power grid, as
well as various system dynamic responses, are elucidated in Figs. 17,18, respectively.
Furthermore, Table 11 shows the different acquired values of Osh and Ush for the power flowing in the tie-line
and frequencies for both areas applying all of the previously mentioned controllers. Table 12 also clarifies the
system’s overall improvement percent for this case.
Scenario C: Evaluating the suggested controller’s robustness in real-time for stability and reliability using
the IEEE-39 bus system. The validation includes considering the impact of SLD.
For evaluating the suggested (fuzzy-PID) + (T I Dµ) controller approach for load frequency management, the
standard real-world New England IEEE-39 bus system is applied in this scenario. The standard real-world New
England IEEE-39 bus system consists of ten reheat thermal generators, nineteen loads, thirty-eight transmission
lines, and twelve transformers, as shown in Fig. 19. The system is divided into three interconnected areas, namely
area 1, area 2, and area 3, with respective rated area power capacities of Pr1 = 1500MW, Pr2 = 2000MW, and
Pr3 = 1500MW . Appendix B provides the system parameter values. In this approach, each area’s generating
units are substituted with a single equivalent generation unit. The following equations are used to calculate the
equivalent inertia constant and speed regulation p arameters54:
H1 S1 + H2 S2 + · · · + Hn Sn
Heqv = (37)
Ssystem
1
Revq = HZ/MW pu
(38)
1 S1 1 S2 1 Sn
R1 Ssystem + R2 Ssystem + ··· + Rn Ssystem
Ssystem = S1 + S2 + · · · + Sn (39)
0.02
ΔPL (pu)
0.015
0.01
0.005
0
0 100 200 300 400 500 600
Time (sec)
Vol.:(0123456789)
www.nature.com/scientificreports/
-3
10
Δfa (pu)
0
-2
-8
0 100 200 300 400 500 600
Time (sec)
10-4
0
Δfb (pu)
-5
PD-PI based HHO [3]
FO-(PD-PI) based MRFO [3]
-10 Fuzzy-PID+(TIλ Dµ) based COA
2
ΔPtie (p.u. MW)
-2
PD-PI based HHO [3]
FO-(PD-PI) based MRFO [3]
Fuzzy-PID+(TIλ Dµ) based COA
-4
0 100 200 300 400 500 600
Time (sec)
Table 9. Specifications of the analyzed system’s transient response for scenario A.3. All values are multiplied
by (10−3).
Vol:.(1234567890)
www.nature.com/scientificreports/
Table 10. Percentage improvements in Osh and Ush for Case A.3. Optimal percentage values are highlighted in
bold format.
where Si , Ri and Hi refer the specified generation unit’s power rating, the factors of both speed regulation and
inertia constant respectively related to ith generation units.
The simulation results, using the optimized parameters of the suggested controller listed in Table 13, show
improved performance compared to previous studies. The frequencies of the three interconnected areas and the
power exchange in various tie lines demonstrate shorter settling times, decreased overshoots, and undershoot.
Specifically, the suggested controller outperforms the I controller and FO-(PD-PI) controller used i n3,54 respec-
tively. Figure 20 displays the distinct SLD profiles experienced by the three interconnected areas. The dynamic
responses of the system, presented in Fig. 21, highlight the proposed controller’s substantial performance in
minimizing excursions and preserving system stability.
Figure 21 depicts that the proposed controller improves the system performance by 96.43% and 94.74% when
compared to the I controller and FO-(PD-PI) controller, respectively.
Scenario D: Evaluating the efficacy of the recommended controller utilizing a real-time IEEE-39 bus system,
considering high renewables penetration within the system, to assess its effectiveness with the goal to attain
dependability and stability.
Similarly, this scenario involves the suggested controller’s real-time validation using the IEEE-39 bus sys-
tem, but with a specific focus on diminishing frequency excursions. The evaluation takes into account the high
renewable energy penetrations within the system as depicted in Fig. 19. In this study, ten wind power plants
and ten PV power plants have penetrated into areas 1 and 2 of the IEEE-39 bus system via switches (s1) and (s2)
respectively. Figure 22 depicts a fair maiden comparison clarifying the superior performance of the proposed
controller in attaining the system frequency to a closely predefined value (≈50 HZ) over the performance of PID
controller tuned by COA. Table 14 presents the obtained optimal PID controller parameters optimized by COA.
Figure 22 shows that the proposed controller strengthens the system performance by 75.19% when compared
to the PID controller tuned via COA considering high renewables penetration in the studied system.
Scenario E: Evaluating the performance of the proposed controller under varying CDT conditions before
and after the LFC in the IEEE-39 bus system. This evaluation also considers high renewable energy penetrations.
To validate the proposed controller, experiments were conducted on the IEEE-39 bus system. The system was
designed to incorporate high penetration levels RESs. In these experiments, different CDT values were introduced
before and after the supplementary controllers. When the CDT challenge is executed, Fig. 23 provides a sufficient
comparison of the considered system dynamic responses.
The proposed controller demonstrates its capability to effectively handle the perturbations caused by RESs
and the challenges posed by CDT. It successfully maintains the frequencies of different areas within predefined
values. This highlights the proposed controller’s durability in addressing the complexities introduced by RESs
and communication delays, ultimately ensuring stable and reliable operation of the system.
Scenario F: Evaluating the proposed strategy’s effectiveness by comparing the effectiveness of the IEEE 39
buses system with and without the proposed strategy, considering high renewables penetration.
PV power in Area a
0.2
0.15
0.1
0.05
0
0 200 400 600 800 1000 1200 1400
Time (min)
Figure 17. The high renewable energy penetration’s generated output power in areas (a) and (b) for Case B.
Vol.:(0123456789)
www.nature.com/scientificreports/
Δfa (pu)
connect wind power area-b
10-3
5 PD-PI based HHO [3]
FO-(PD-PI) based MRFO [3]
connect wind power area-b Fuzzy-PID+(TIλ D µ) based COA
ΔPtie (p.u. MW)
-5
0 200 400 600 800 1000 1200 1400
Time (min)
Figure 18. LFC controllers’ dynamic responses to high penetration levels of RESs and RLD pattern for Case B.
Table 11. Specifications of the analyzed system’s transient response for scenario B. All values are multiplied by
(10−3).
Vol:.(1234567890)
www.nature.com/scientificreports/
Table 12. Percentage improvements in Osh and Ush for Case B. Optimal percentage values are highlighted in
bold format.
G8
Area 1
37 S1
G10
Wind farm
25 26 28 29
30
27 38
2
18 S3
RFB 1 G9
17
24
1
G6
16
G1 3
15 35
21
4
22
14 19
5 12
S4 39
6
13 23
RFB 2 7
11 20 33
10
8
Area 2 9 36
G4
34
32
31 G7
PV Area 3
array G5
S2 G3
G2
Table 13. The optimal optimized coefficients of the recommended controller for scenario C.
In this specific scenario, the IEEE-39 bus system performance is examined while considering a significant
integration of RESs. Whereas, wind energy is integrated into area 1 at t = 100 min, and PV energy is integrated
into area 2 at t = 200 min. The proposed coordinated strategy involves the incorporation of CRFBs systems in
area 1 and area 2. These CRFBs systems work collaboratively by closing switches (s3) and (s4) over different
simulation durations. When wind energy penetrates area 1, the CRFBs included in area 1 share their active power
with the assessed power system. Additionally, when PV energy penetrates area 2, the CRFBs included in area 2,
share their extra active power with the assessed power system. The CRFBs utilize stored energy to enhance LFC
and optimize the overall performance of the power system under unusual circumstances. The major objective is
to regulate the system frequency, which is prone to considerable fluctuations as a result of the high renewables
penetration in both areas. Table 15 illustrates the PID controller variables that were obtained for the proposed
Vol.:(0123456789)
www.nature.com/scientificreports/
0.8 Applying SLP with 0.90 pu Applying SLP with 0.95 pu Applying SLP with 0.98 pu
ΔPL (pu)
0.6
0.2
0
0 20 40 60 80 100 120 140 160 180 200
Time (sec)
strategy. Figure 24 depicts the CRFBs systems’-controlled output signal, which denotes the outcome of the active
power quantity. Additionally, Fig. 25 compares the total dynamic responses of the entire system in the IEEE-39
bus system with and without the proposed strategy.
Figure 25 indicates that the proposed strategy, which includes the LFC besides CRFBs, demonstrates its
capability to successfully handle the perturbations caused by RESs in the studied system. It successfully maintains
the frequencies of different areas within predefined values. Whereas, the proposed strategy improves the system
performance by 50% as compared to without it.
Conclusion
This study has presented significant findings that contribute to power system stability when transitioning from
traditional power stations to renewable energy sources (RESs). Firstly, an effective structure has been presented
to ensure stable frequency in the power system during this transition. This structure combines the improved
load frequency controller (LFC) and controlled redox flow batteries (CRFBs) to effectively manage frequency
fluctuations in considered grid. Furthermore, the controller in LFC depend on (fuzzy-PID) + (T I Dµ) controller.
The proposed controller improves the system performance than more on controller such as (PID, FO-PID,
PD-PI, and FO-(PD-PI)) controllers. Furthermore, the proposed controller contributes with CRFBs to maintain
the system stability during high renewables. The constraints for this proposed scheme have been determined
using the crayfish optimization algorithm. LFC controller effectiveness has been validated by comparing its
performance to that of other published controllers. Importantly, the proposed strategy demonstrates the ability
to maintain system reliability even during periods of high renewable energy penetration. The authors intend
to incorporate more ESSs into the system in future research, ensuring its seamless operation throughout the
day. Furthermore, as all generation sources will be renewable, the design process took into account the virtual
synchronous generator.
Vol:.(1234567890)
www.nature.com/scientificreports/
Figure 21. LFC controllers’ dynamic responses considering SLD in a standardized IEEE system for Case C.
Vol.:(0123456789)
www.nature.com/scientificreports/
Figure 21. (continued)
Vol:.(1234567890)
www.nature.com/scientificreports/
50.01
Δf1 (HZ)
50.005
50
connect PV power area-2
50.006
Δf2 (HZ)
50.004
50
connect wind power area-1
49.998
0 200 400 600 800 1000 1200 1400
Time (min)
50.006
Δf3 (HZ)
50.004
50
connect wind power area-1
49.998
0 200 400 600 800 1000 1200 1400
Time (min)
Figure 22. LFC controllers’ considered dynamic responses with high renewables penetration in a standardized
IEEE system for Case D.
Vol.:(0123456789)
www.nature.com/scientificreports/
With CDT=0.98s
50.004 With CDT=0.70s
With CDT=0.40s
Without CDT
50.003
connect PV power area-2
Δf1 (HZ)
50.002
50.001
50
49.999
connect wind power area-1
50.0002
Δf2 (HZ)
50
connect PV power area-2
49.9998
connect wind power area-1
49.9996
49.9994
0 200 400 600 800 1000 1200 1400
Time (min)
50.0001
50
Figure 23. LFC controllers’ considered dynamic responses with high renewables penetration and CDT
challenge in a standardized IEEE system for Case E.
Table 15. The optimum values of the PID controller tuned by COA for the proposed strategy.
Vol:.(1234567890)
www.nature.com/scientificreports/
0.2
0.15
0.1
0.05
0
0 200 400 600 800 1000 1200 1400
Time (min)
Figure 24. The controllable generated power of the CRFBs systems in both local areas for Case F.
Vol.:(0123456789)
www.nature.com/scientificreports/
Δf1 (HZ)
50.001
50
50.0006
LFC based fuzzy-PID + (TIλ D µ)
Proposed strategy
50.0004
50.0002
Δf2 (HZ)
50
49.9994
0 200 400 600 800 1000 1200 1400
Time (min)
50.0001
50.0001
50
Figure 25. LFC controllers’ considered dynamic responses considering a coordinated strategy besides high
renewables penetration in the IEEE-39 bus system for Case F.
Vol:.(1234567890)
www.nature.com/scientificreports/
100 λ µ
Magnitude (dB)
combining (fuzzy-PID)+TI D based COA
-100
-200
-45
-90
Phase (deg)
-135
-180
-225
-270
10-2 100 102 104
Frequency (rad/sec)
Figure 26. The bode plot of the power grid loop gains with the proposed (fuzzy-PID) + (T I Dµ) controller.
Data availability
All data generated or analysed during this study are included in this published article and its supplementary
information file.
References
1. Elkasem, Ahmed. H. A., Kamel, S., Khamies, M., Kabalci, E. & Shahinzadeh, H. Frequency Stability Enhancement of Hybrid
Multi-area Power Grid Considering High Renewable Energy Penetration Using TID Controller. 2022 4th Global Power, Energy
and Communication Conference (GPECOM) https://doi.org/10.1109/gpecom55404.2022.9815729. (2022).
2. Meng, J. et al. Dynamic frequency response from electric vehicles considering travelling behavior in the Great Britain power
system. Appl. Energy 162, 966–979 (2016).
3. Elkasem, A. H. A., Khamies, M., Hassan, M. H., Nasrat, L. & Kamel, S. Utilizing controlled plug-in electric vehicles to improve
hybrid power grid frequency regulation considering high renewable energy penetration. Int. J. Electr. Power Energy Syst. 152,
109251 (2023).
4. Ahmed, M., Khamies, M. & Kamel, S. A robust control approach integrating with optimal fuel cells to strengthen the frequency
stability of a diverse-sources power system including renewables. ISA Trans. 143, 420–439 (2023).
5. Elkasem, A. H. A., Khamies, M., Hassan, M. H., Agwa, A. M. & Kamel, S. Optimal design of TD-TI controller for LFC considering
renewables penetration by an improved chaos game optimizer. Fract. Fract. 6, 220 (2022).
6. Ahmed, M., Khamies, M., Hassan, M. H., Domínguez-García, J. L. & Kamel, S. A modified controller scheme for frequency stability
enhancement of hybrid two-area power grid with renewable energy sources. IET Renew. Power Gener. 17, 1035–1067 (2022).
7. Khezri, R., Oshnoei, A., Oshnoei, S., Bevrani, H. & Muyeen, S. M. An intelligent coordinator design for GCSC and AGC in a two-
area hybrid power system. Appl. Soft Comput. 76, 491–504 (2019).
8. Khamies, M., Kamel, S., Hassan, M. H. & Elnaggar, M. F. A developed frequency control strategy for hybrid two-area power system
with renewable energy sources based on an improved social network search algorithm. Mathematics 10, 1584 (2022).
9. Ogar, V. N., Hussain, S. & Gamage, K. A. A. Load frequency control using the particle swarm optimisation algorithm and Pid
controller for effective monitoring of transmission line. Energies 16, 5748 (2023).
10. Zamani, A., Barakati, S. M. & Yousofi-Darmian, S. Design of a fractional order PID controller using GBMO algorithm for load–
frequency control with governor saturation consideration. ISA Trans. 64, 56–66 (2016).
11. Debbarma, S., Saikia, L. C. & Sinha, N. Automatic generation control using two degree of freedom fractional order PID controller.
Int. J. Electr. Power Energy Syst. 58, 120–129 (2014).
12. Arya, Y. & Kumar, N. BFOA-scaled fractional order fuzzy PID controller applied to AGC of multi-area multi-source electric power
generating systems. Swarm Evol. Comput. 32, 202–218 (2017).
13. Mi, Y. et al. The sliding mode load frequency control for hybrid power system based on disturbance observer. Int. J. Electr. Power
Energy Syst. 74, 446–452 (2016).
14. Sharma, G., Panwar, A., Arya, Y. & Kumawat, M. Integrating layered recurrent ANN with robust control strategy for diverse
operating conditions of AGC of the power system. IET Gener. Trans. Distrib. 14, 3886–3895 (2020).
15. Oshnoei, A., Kheradmandi, M. & Muyeen, S. M. Robust control scheme for distributed battery energy storage systems in load
frequency control. IEEE Trans. Power Syst. 35, 4781–4791 (2020).
16. Guha, D., Roy, P. K. & Banerjee, S. Maiden application of SSA-optimised CC-TID controller for load frequency control of power
systems. IET Gener. Trans. Distrib. 13, 1110–1120 (2019).
17. Abdulnasser, G., Ali, A., Shaaban, M. F. & Mohamed, E. E. M. Stochastic multi-objectives optimal scheduling of energy hubs with
responsive demands in smart microgrids. J. Energy Storage 55, 105536 (2022).
18. Elkasem, A. H. A., Kamel, S., Hassan, M. H., Khamies, M. & Ahmed, E. M. An eagle strategy arithmetic optimization algorithm
for frequency stability enhancement considering high renewable power penetration and time-varying load. Mathematics 10, 854
(2022).
19. Mudi, R. K. & Pal, N. R. A self-tuning fuzzy PI controller. Fuzzy Sets Syst. 115, 327–338 (2000).
20. Chang, C. S. & Fu, W. Area load frequency control using fuzzy gain scheduling of PI controllers. Electr. Power Syst. Res. 42, 145–152
(1997).
21. Yeşil, E., Güzelkaya, M. & Eksin, İ. Self tuning fuzzy PID type load and frequency controller. Energy Conversat. Manag. 45, 377–390
(2004).
Vol.:(0123456789)
www.nature.com/scientificreports/
22. Ahmadi, S. et al. FUZZY aided PID controller is optimized by ga algorithm for load frequency control of multi-source power
systems. In 2020 IEEE 18th World Symposium on Applied Machine Intelligence and Informatics (SAMI) (eds Ahmadi, S. et al.) (IEEE,
2020). https://doi.org/10.1109/sami48414.2020.9108759.
23. Kwatny, H. G., Kalnitsky, K. C. & Bhatt, A. An optimal tracking approach to load-frequency control. IEEE Trans. Power Appar.
Syst. 94, 1635–1643 (1975).
24. Aoki, M. Control of large-scale dynamic systems by aggregation. IEEE Trans. Automat. Contr. 13, 246–253 (1968).
25. Sharma, M., Dhundhara, S., Arya, Y. & Prakash, S. Frequency excursion mitigation strategy using a novel COA optimised fuzzy
controller in wind integrated power systems. IET Renew. Power Gener. 14, 4071–4085 (2020).
26. Ali, T., Malik, S. A., Daraz, A., Aslam, S. & Alkhalifah, T. Dandelion optimizer-based combined automatic voltage regulation and
load frequency control in a multi-area, multi-source interconnected power system with nonlinearities. Energies 15, 8499 (2022).
27. Ahmed. H. A., E., Kamel, S., Korashy, A. & Jurado, F. Application of Harris Hawks Algorithm for Frequency Response Enhancement
of Two-Area Interconnected Power System with DFIG Based Wind Turbine. 2019 21st International Middle East Power Systems
Conference (MEPCON) https://doi.org/10.1109/mepcon47431.2019.9007991. (2019).
28. Ali, T. et al. Load frequency control and automatic voltage regulation in a multi-area interconnected power system using nature-
inspired computation-based control methodology. Sustainability 14, 12162 (2022).
29. Hamdy, A., Kamel, S., Nasrat, L. & Jurado, F. Frequency stability of two-area interconnected power system with doubly fed induc-
tion generator based wind turbine. Power Syst. https://doi.org/10.1007/978-3-030-54275-7_11 (2020).
30. Dhanasekaran, B., Siddhan, S. & Kaliannan, J. Ant colony optimization technique tuned controller for frequency regulation of
single area nuclear power generating system. Microprocess. Microsyst. 73, 102953 (2020).
31. Hasanien, H. M. Whale optimisation algorithm for automatic generation control of interconnected modern power systems includ-
ing renewable energy sources. IET Gener. Trans. Distrib. 12, 607–614 (2017).
32. Paliwal, N., Srivastava, L. & Pandit, M. Application of grey wolf optimization algorithm for load frequency control in multi-source
single area power system. Evol. Intell. 15, 563–584 (2020).
33. Kumar, N. K. et al. Fuzzy logic-based load frequency control in an island hybrid power system model using artificial bee colony
optimization. Energies 15, 2199 (2022).
34. Arya, Y. ICA assisted FTIλDN controller for AGC performance enrichment of interconnected reheat thermal power systems. J.
Ambient Intell. Hum. Comput. 14, 1919–1935 (2021).
35. Shiva, C. K. et al. Load frequency stabilization of stand-alone hybrid distributed generation system using QOHS algorithm. Int. J.
Numer. Model. Electr. Netw. Dev. Fields 35, e2998 (2022).
36. Vigya, Shiva, C. K., Vedik, B. & Mukherjee, V. Comparative analysis of PID and fractional order PID controllers in automatic
generation control process with coordinated control of TCSC. Energy Syst. 14, 133–170 (2021).
37. Saxena, A., Shiva, C. K., Shankar, R. & Vedik, B. Impacts of wind farms with multi-terminal HVDC system in frequency regulation
using quasi-opposition pathfinder algorithm. Int. J. Syst. Assurance Eng. Manag. 12, 1434–1446 (2021).
38. Vigya, et al. A novel chaotic chimp sine cosine algorithm part-II: Automatic generation control of complex power system. Chaos,
Solitons Fract. 173, 113673 (2023).
39. Mudi, J., Shiva, C. K. & Mukherjee, V. Quasi-oppositional whale optimization optimized load frequency stabilization of hybrid
power systems integrated with electric vehicle. Adv. Theory Simul. https://doi.org/10.1002/adts.202100510 (2022).
40. Jia, H., Rao, H., Wen, C. & Mirjalili, S. Crayfish optimization algorithm. Artif. Intell. Rev. 56, 1919–1979 (2023).
41. Pappachen, A. & Fathima, A. P. Load frequency control in deregulated power system integrated with SMES–TCPS combination
using ANFIS controller. Int. J. Electr. Power Energy Syst. 82, 519–534 (2016).
42. Pradhan, P. C., Sahu, R. K. & Panda, S. Firefly algorithm optimized fuzzy PID controller for AGC of multi-area multi-source power
systems with UPFC and SMES. Eng. Sci. Technol. Int. J. 19, 338–354 (2016).
43. Chidambaram, I. A. & Paramasivam, B. Optimized load-frequency simulation in restructured power system with redox flow bat-
teries and interline power flow controller. Int. J. Electr. Power Energy Syst. 50, 9–24 (2013).
44. Oshnoei, S., Oshnoei, A., Mosallanejad, A. & Haghjoo, F. Novel load frequency control scheme for an interconnected two-area
power system including wind turbine generation and redox flow battery. Int. J. Electr. Power Energy Syst. 130, 107033 (2021).
45. Heshmati, M., Noroozian, R., Jalilzadeh, S. & Shayeghi, H. Optimal design of CDM controller to frequency control of a realistic
power system equipped with storage devices using grasshopper optimization algorithm. ISA Trans. 97, 202–215 (2020).
46. Peddakapu, K. et al. A state-of-the-art review on modern and future developments of AGC/LFC of conventional and renewable
energy-based power systems. Renew. Energy Focus 43, 146–171 (2022).
47. Choudhary, R., Rai, J. N. & Arya, Y. Cascade FOPI-FOPTID controller with energy storage devices for AGC performance advance-
ment of electric power systems. Sustain. Energy Technol. Assess. 53, 102671 (2022).
48. Enomoto, K., Sasaki, T., Shigematsu, T. & Deguchi, H. Evaluation study about Redox flow battery response and its modeling. IEEJ
Trans. Power Energy 122, 554–560 (2002).
49. Selvaraju, R. K. & Somaskandan, G. Impact of energy storage units on load frequency control of deregulated power systems. Energy
97, 214–228 (2016).
50. Gorripotu, T. S., Sahu, R. K. & Panda, S. AGC of a multi-area power system under deregulated environment using redox flow
batteries and interline power flow controller. Eng. Sci.Technol. Int. J. 18, 555–578 (2015).
51. Shankar, R., Bhushan, R. & Chatterjee, K. Small-signal stability analysis for two-area interconnected power system with load
frequency controller in coordination with FACTS and energy storage device. Ain Shams Eng. J. 7, 603–612 (2016).
52. Parmar, K. P. S., Majhi, S. & Kothari, D. P. Load frequency control of a realistic power system with multi-source power generation.
Int. J. Elect. Power Energ. Syst. 42(1), 426–433. https://doi.org/10.1016/j.ijepes.2012.04.040 (2012).
53. Hasanien, H. M. & El-Fergany, A. A. Salp swarm algorithm-based optimal load frequency control of hybrid renewable power
systems with communication delay and excitation cross-coupling effect. Electr. Power Syst. Res. 176, 105938 (2019).
54. Pathak, N. & Hu, Z. Hybrid-peak-area-based performance index criteria for AGC of multi-area power systems. IEEE Trans. Ind.
Inform. 15, 5792–5802 (2019).
Acknowledgements
The icons used through this paper were developed by Freepik, Amethyst Design, Arkinasi and Smash icons
from www.flaticon.com.
Author contributions
AHAE contributed to conceptualization, methodology, software; SK contributed to conceptualization,
methodology, software; MK contributed to conceptualization, methodology, software; LN contributed to
conceptualization, software, writing— original draft preparation.
Vol:.(1234567890)
www.nature.com/scientificreports/
Funding
Open access funding provided by The Science, Technology & Innovation Funding Authority (STDF) in coopera-
tion with The Egyptian Knowledge Bank (EKB).
Competing interests
The authors declare no competing interests.
Additional information
Supplementary Information The online version contains supplementary material available at https://doi.org/
10.1038/s41598-024-58189-2.
Correspondence and requests for materials should be addressed to S.K.
Reprints and permissions information is available at www.nature.com/reprints.
Publisher’s note Springer Nature remains neutral with regard to jurisdictional claims in published maps and
institutional affiliations.
Open Access This article is licensed under a Creative Commons Attribution 4.0 International
License, which permits use, sharing, adaptation, distribution and reproduction in any medium or
format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the
Creative Commons licence, and indicate if changes were made. The images or other third party material in this
article are included in the article’s Creative Commons licence, unless indicated otherwise in a credit line to the
material. If material is not included in the article’s Creative Commons licence and your intended use is not
permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from
the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.
Vol.:(0123456789)