Thesis On HERIC Inverter Closed Loop Control
Thesis On HERIC Inverter Closed Loop Control
INTRODUCTION
1
A power quality issue is when there is an abnormality in the voltage, current,
or frequency that causes end-user equipment to malfunction or fail. Numerous sorts of
outages and service interruptions occur in utility distribution networks, sensitive
industrial loads, and crucial commercial operations, which can result in severe
financial losses. The problem of power quality is expected to take on additional
dimensions as a result of the restructuring of power networks and the changing trend
toward distributed and scattered generation. It is crucial to make progress in this
approach, especially in developing nations like India where the volatility in power
frequency and many other factors affecting power quality are important issues in and
of themselves.
Inverters serve as an interface to transfer electrical energy into the electrical
system in a power plant that uses renewable energy sources in addition to converting
DC to AC voltage. The requirement for an inverter to perform this role is high
generating power quality and efficiency, namely voltage and current. Similar
requirements apply to inverters used in photovoltaic generation (PV-inverter).
Numerous studies have been conducted to increase output power quality and
efficiency. For this purpose, a few PV-inverter topologies have been created through
the development of an inverter base topology and the optimization of their operational
model.
The ideal inverter output voltage has a sinusoidal wave and is stable. The
voltage, however, is frequently not a pure sine wave, indicating the presence of
harmonics. The performance of the supplied electrical load as well as the electrical
power distribution components will be subpar due to large harmonics. The
components will be harmed the longer it continues.
2
2. LITERATURE SURVEY
3
module application that takes into account solar panel and grid requirements. In order
to conduct a size and cost comparison, the selected solutions are constructed and
simulated in accordance with the benchmark, obtaining ratings for passive and
semiconductor components. The examined topologies are discussed in relation to the
measured ratings and ground currents. Topological solutions that meet the application
benchmark are suggested in the recommendations.
Renewable energy sources like wind, sun, and water are thought to be
unreliable alternatives for conventional energy sources like oil, natural gas, or coal.
Germany, Denmark, Japan, and the United States are in the forefront of the
development of systems for distributed power generation (DPGSs) that use renewable
energy. As stated by Blaabjerg et al [4] new and stronger criteria for power quality,
safe operation, and islanding protection are provided as a result of the growing
number of DPGSs linked to the utility network. In order to achieve the criteria for grid
connectivity, distributed generation system control should be enhanced. The paper
provides a summary of the fuel cell, photovoltaic, and wind turbine-based DPGS
structures. Additionally, grid-side converter control mechanisms are provided, and the
prospect of compensating for low-order harmonics is also covered. Additionally, the
treatment of control strategies when operating with grid faults. An overview of
synchronization techniques and a discussion of their significance in the control are
included at the conclusion of this study.
4
Wang et al [6] derived rules summarized from existing high-performance
inverters with H6-type configuration, which makes new topologies possible.
Additionally, a brand-new, highly efficient, single-phase photovoltaic inverter without
a transformer is also suggested and assessed as an example. In a non-isolated system
with a H6-type configuration, input split capacitors are not required, which eliminates
common-mode voltage and leakage current problems. Additionally, the feature of a
three-level output voltage in the middle of the inverter bridge aids inductors and
improves power quality. With a hybrid modulation method and unipolar and bipolar
pulse width modulation schemes, the detailed operating principles are described. A
2200VA prototype's experimental findings validate the suggested topology with
hybrid modulation.
5
the suggested CPG control mechanism. PV system operation examples are provided
to demonstrate the viability of the CPG control method for unloading the distributed
grid.
Due to their high efficiency, low cost, and light weight, among other advantages,
transformer-less photovoltaic (PV) inverters are more extensively used. Numerous
innovative topologies have been developed, tested, and used, with a particular focus
on active power injection only without a leakage current problem. PV inverters must,
nevertheless, be able to inject reactive power into the utility for grid support under
some new grid rules. An enhanced hybrid modulation technique is presented and
tested for one non-isolated H6 topology in order to map the challenge by J. Wang et al
[10] as an example. Variable reactive power generation capability and 0% crossing
distortion are obtained with only straightforward switching pattern modifications and
6
a phase shift for current reference, and the common mode voltage issue is also
resolved. The revised hybrid modulation approach's operation modes are also
discussed in detail. There are also some design factors offered. The SMPLIS
simulation and extensive findings from a 4000VA prototype both support the
suggested hybrid modulation technique.
7
inverter's efficiency, size, and cost. But the elimination of the transformer can lead to
substantial ground currents, which are now a key design element for PV inverters.
The system's errant parts have an impact on the ground currents. There is no simple
model or method for studying the common mode behaviour of a PV system, which is
required to analyse the ground currents. This paper provides a more thorough
explanation of the common mode problem in single-phase transformer-free PV
systems using a simple model. Additionally, Gubia [12] created a process to evaluate
a PV inverter's overall performance, efficiency, grid current quality, and common
mode behaviour as a consequence of its unique structure and modulation method.
8
3. HYBRID UNIPOLAR-PWM TECHNIQUE
Photovoltaic (PV) energy is one of the most well-liked renewable sources due to its
environmental friendliness and the fact that module prices are still declining. Huge
power electronic converters are used as the interface to connect PV systems with the
utility grid. Power converter performance has been improved in a number of ways,
including topologies, modulation schemes, control methods, and other elements.
The inverter may deliver reactive power on demand with the traditional BP-
PWM scheme, but efficiency and power quality are sacrificed. The typical UP-PWM
approach, in contrast, can improve power quality and system efficiency by reducing
switching losses, inductor ripple currents, but it is unable to provide reactive power.
9
Numerous hybrid modulation techniques or innovative transformer-less
topologies have been suggested to accomplish this. For example, a new transformer-
free inverter with a simple modulation mechanism has been presented, and the
efficiency has been risen. The additional six diodes, however, result in a higher
hardware cost and complexity compared to the HERIC inverter. The H5 inverter's
reactive power capacity was proposed in by combining the UP-PWM, BP-PWM
systems.
Additionally, ZCD, which impairs power quality, was not addressed by the
aforementioned strategies. Typically, the grid-connected application has two ZCD
situations. One is at the zero-crossing output voltage point (ZCP). This will result in
ZCD in the injected currents because of the minimum pulse width restriction that
assures the proper operation of power switches.
A worldwide sliding mode control system that can somewhat lower the ZCD
was proposed as a solution to this problem. The literature has not yet adequately
addressed the ZCD, which is created by the limiting of modulation. The grid-
connected current ZCP hosts a second instance of the ZCD. Generally speaking,
modulation methods heavily rely on current polarity detection.
10
voltage (ZCP). The minimum pulse width restriction that guarantees ZCD in the
injected currents as a result of the proper operation of power switches in this scenario.
To address this issue, the global sliding mode control mechanism was
developed, and it has the ability to somewhat reduce ZCD. The literature has not yet
given the ZCD, which is truly caused by the limiting of modulation, enough
consideration. A second ZCD case is present on the grid-connected current ZCP.
In contrast, this problem was fixed by modifying the phase angle of the grid-
connected current reference. However, the entire region of the ambiguous polarity
cannot be contained within the changing area of either. To be considered for
transformer-free PV systems, it is important to take into account a converter's high
efficiency, high power quality, and changeable reactive power.
However, as was said above, the current plans cannot accomplish this
simultaneously. For HERIC inverter, the research suggests a hybrid UP-PWM design.
This paper's primary contribution can be broken down into two sections. A normal
UP-PWM, a UP-PWM with modified dead time, and a modulation that simply
requires the activation of AC bypass power switches are the three modulation
methods combined in the suggested approach.
11
3.1. PRIOR-ART MODULATION SCHEMES
(3.1)
L = L1 + L2, where L1 and L2 represent the grid filter, ig(t) denotes the grid-
connected current, vg(t) denotes the grid voltage, and VAB(t) is the differential-mode
voltage. The DC-link voltage U dc is taken to be constant since only the modulation
mechanism of the single-phase single-stage grid-connected HERIC inverter is
detailed. Additionally, in Fig. 3.1, the direction of ig is the definition of the forward
current.
12
3.1.1. Typical Modulation Schemes
Fig. 3.2 The classic UP-PWM and the UP-PWM with dead time are two modulation approaches
for the HERIC inverter, where lim and ina are ZCD regions near the voltage ZCP and the
current ZCP, respectively.
13
The idea in Fig. 2(a) states that S6 is ON and S1,4 operate at a high frequency when
Vref 0 is present. To reach zero voltage, the forward current passes through S6 and
D5. The reverse current, however, has no path. Similar to this, S5 is ON and S2,3
function at a high frequency when Vref 0. Reverse current is sent to S5 and D6,
resulting in zero voltages. The forward current, however, is also unable to locate a
path for flow. As a result, the traditional UP-PWM is incapable of handling reactive
power. When Vref 0, S5,6, and S1,4 in Fig. 2(b) operate with a high frequency. S5,6,
and S2,3 operate with a high frequency when Vref 0. To prevent short-circuiting, the
dead time is incorporated into the commutation process. There is a bidirectional
channel for the current because S5, S6, and S7 are all ON at zero volts. The UP-PWM
with dead time can therefore supply reactive power.
The ZCD is an additional problem for the HERIC inverter. Thus, this section looks at
the causes of the ZCD in the HERIC inverter.
3.1.3.1 To protect power switches from damage when the output voltage is ZCD ZCP,
the minimum pulse width must be kept to a tolerable value. Assuming that the
power factor angle is, the grid voltage is, and the grid current is, respectively (t-). If
(1) is accurate,
(3.2)
To protect power switches from damage, the minimum pulse width must be kept to a
manageable level. Considering that the grid current is equal to Im sin and the grid
voltage is vg(t) = Vm sin(t), and the power factor angle is (t-).If (1) is true, then
(3.3)
in which vAB = -dd Udc. assuming that dlim is the minimum pulse width restriction.
Then
14
(3.4)
(3.5)
As a result, the minimum pulse width restriction occurs around the grid voltage ZCP.
When the condition (5) is met, there are two approaches to handle the minimum pulse
width limitation. The first method sets dd = 0, while the second one sets dd = dlim.
1) The real grid current's derivative is expressed as in the first way (when dd = 0).
(3.6)
(3.7)
(3.8)
2) In the second technique (i.e., dd = dlim), the derivative of the real grid current is
stated as follows:
The current distortion I can then be obtained using a process similar to that described
in. (3.9)
15
(3.10)
No matter which of the two approaches is used, it is obvious that the grid current will
be distorted at the ZCP of the grid voltage.
(a) the ideal modulation scheme, (b) the current flowing paths,
Figure 3.3 displays an optimal modulation for the reactive power injection (a).
The operating principle for producing positive power is the same as that of traditional
UP-PWM.
Only the AC bypass switches are used to generate negative power, and they do
it at a high frequency. To produce positive or negative VAB, the current travels via the
four diodes, and to reach zero voltages, the current flows through S5 (D5) and D6
(S6). Theoretically, the modulation technique shown in Fig. 3.3(a) can inject reactive
power while achieving small ripple currents and good efficiency, just as the
16
traditional UP-PWM. The actual current I g will be constrained to zero crossing for a
considerable amount of time, but, if the current polarity is wrongly identified at the
ZCP, as shown in Fig. 3.3(b), with VAB 0, the measured current is positive while the
actual current is negative. The scenario is shown in Fig. 3.3. (c).
Fig. 3.3(b) depicts the actual current, however the actual current is
(3.11)
(3.12)
(3.13)
The distortion may, in the worst situation, also activate the inverter protection,
which would shut the system down. In Fig. 3, this occurrence is represented by the
first cycle (c). For an extended duration, the current is restricted to zero crossing. The
difference in inaccuracy between the reference current and the actual current increases
as a result. The overshoot is consequently seen in the grid current in Fig. 3.3. (c). The
overshoot value exceeded 1.5 times the rated current, which is the maximum
overcurrent capacity permitted by most standards, according to the simulation results
(notably, this can be changed according to the specific application). In practical use,
this situation can lead to the over current protection turning on.
As was previously indicated, signal noises are mostly responsible for the
inaccuracy. Current ripples, transmission noise, and sampling noise are common
examples of signal noise. The majority of the errors are caused by the current waves.
The hardware design should take special care to regulate the current ripple rate r. In
the majority of engineering systems, the present ripple rate r should be intended to be
smaller than 0.2.
17
To avoid this, the current polarity's inaccuracy must have a maximum quantity
of noise, which can be a fixed value. Since the inverter's rated output current's root
mean square (RMS) is measured in ierms, the accuracy must be between -0.1ierms
and 0.1ierms. (note, this can be adjusted depending on the specific design). The
accuracy range might therefore be written as
(3.14)
where ina is the border and Igrms is the real-time grid current's RMS. In order
to counteract this influence caused by the incorrect estimate of the current polarity,
the target voltage must be arbitrarily built up around the grid current ZCP.
Overall, the modulation techniques for the HERIC inverter that were
previously addressed have ZCD problems. The ZCD regions lim and ina match the
UP-PWM as-is while running at unity power factor. However, only the ZCD at the
voltage ZCP is audible when using a UP-PWM with additional dead time. Both ZCD
zones will materialise as described earlier when the HERIC inverter employs the
modulation approach in Fig. 3(a) with non-unity power factor operation. To lessen the
ensuing distortions, the modulation algorithms must be modified.
In this section, a hybrid UP-PWM technique for the HERIC inverter is advised
in order to attain a high efficiency, good power quality, and appropriate reactive
power capabilities. Fig. 3.4 provides an illustration of the operating principles. During
an inverter
18
Fig.3.4 To improve power quality and efficiency, hybrid UP-PWM is advised for the HERIC
inverter, both while operating (a) at unity power factor and when operating at (b) non-unity
power factor.
(1) Regions 3 and 7 employ traditional UP-PWM. Using the standard UP-
PWM technique, low switching power losses and low ripple currents can be
accomplished.
(3) UP-PWM for the creation of negative power in regions 1 and 5. The
modulation is applied to the HERIC inverter, necessitating just the operation of AC
bypass switches like Fig. 3(a), in order to provide reactive power and decrease
switching power losses.
19
It should be noted that in the case of the unity power factor operation, Regions
1 and 5 are absent. Thus, as shown in Fig. 3, the proposed method simply employs the
conventional UP-PWM and UP-PWM with dead time working modes (a).
Region 1: As shown in Fig. 3(a) and (b), both four-leg power switches are in the off-
state while the additional two power switches are operating at a high frequency. The
grid-connected current ig running between diodes D1 and D4 produces a positive
voltage VAB, whereas diodes S5 and D6 provide a negative voltage.
Region 2: At the current ZCP, the leg power switches S1, S4, as well as the other two
power switches S5, S6, all function at a high frequency. There are currently two
options available.
ii) According to Fig. 5(e) and (f), a grid-connected current that passes through
S1 and S4 produces a positive voltage VAB, whereas a current that passes via S6 and
D5 produces a zero voltage VAB. The dead time between changes in operation mode
must be taken into account.
Region 3: As seen in Figs. 5(g) and 5(h), S6 is always in the on-state whereas S1 and
S4 are swapped at a high frequency (h). After passing through S1 and S4 to create a
positive voltage VAB and S6 and D5 to create a zero voltage, the grid-connected
current ig continues on its path.
Region 4: At the voltage ZCP, there are two transitioning modes. 1) S1 and S4 are in
an on-state to produce a positive voltage VAB, and current g flows through S1 and S4
as shown in Fig. 5(e) and (f). Following the activation of S5 and S6 to reach zero
voltage, the current ig passes through S6 and D5. 2) S2 and S3 are in an on-state, as
indicated in Fig. 5(i) and (j), resulting
20
Fig. 5 modes of operation for the HERIC inverter's hybrid UP-PWM.
to a negative voltage VAB, and the current ig flows through D2 and D3. The grid-
connected current ig then passes through S6 and D5 while S5 and S6 are in an on-state
21
for a zero voltage. To prevent short-circuiting the DC side during mode transitions,
the dead time should be used.
Region 5: As seen in Fig. 5(k) and (l), the four leg power devices are all off, and S5
and S6 operate at a high frequency. The remaining grid-connected current (ig) then
travels through D2 and D3 to generate a negative voltage (VAB), then S6 and D5 to
generate a zero voltage.
Region 6: The extra switches S5, S6, as well as switches S2, S3, operate at a high
frequency close to the current ZCP. Right now, there are two possibilities. 1) Fig. 5(i)
and (j) show how the current ig first flows through S6 and D5 to produce zero
voltage, then passes through D2 and D3 to produce a negative voltage (VAB). 2) As
indicated in Fig. 5(m) and Figure 6, the grid-connected current ig passes through S2
and S3 to ensure a negative voltage VAB and then through S5 and D6 to achieve a
zero voltage (n). Dead time in between mode changes must be accounted for.
Region 8: At the ZCP voltage, there are two modes. 1) The grid-connected current ig
travels via S2 and S3 as shown in Figures 5(m) and (n), where S2 and S3 are in an on-
state to maintain a negative voltage VAB. The grid-connected current ig goes through
S5 and D6 after switching S5 and S6 to obtain zero voltage. 2) As shown in Figures
5(c) and (d), at a positive voltage VAB, S1 and S4 are in an on-state, and the grid-
connected current ig flows through D1 and D4. When S5 and S6 are in the on state,
the grid-connected current ig flows through S5 and D6 in order to reach zero voltage.
The dead time is required when changing operating modes.
When UP-PWM is used at voltage ZCP with additional dead time, the reference
output voltage is impacted by the dead time. As previously mentioned, the minimum
pulse width constraint should be considered in close proximity to the voltage ZCP.
When the duty cycle dd is lower than the minimum pulse width ratio dlim, it is driven
to zero or dlim. Thus, the current cannot perfectly follow the reference. To overcome
those issues, dead time compensation and minimum pulse width limiting are
22
necessary. Therefore, the duty cycle of the enhanced compensation method can also
be represented as
(3.15)
where dplu is the additional duty cycle of dead time applied to account for the
minimum pulse width limitation and is the duty cycle of the dead time. Dplu should
be twice as large as Dlim in order to assure a successful switching process. Notably,
dlim is consistently determined.
Fig. 6. Principle of compensation for the dead period and minimum pulse width
restriction
by the switching speed of the power devices. Generally, dlim is equal to 2(ton+toff),
where ton and toff are the turn-on time and the turn-off time of switches, respectively.
Dplu is then equal to 4 (ton + toff). The device datasheet contains the turn-on and
turn-off times of the power devices.
23
(1) Fig. 6 illustrates the dead time compensation principle when dd > dlim (a). One
switching period, Ts, as observed, consists of two dead periods intervals. Due to the
negative voltage in the dead time, the duty cycle is then changed to D = dd+3 (15). In
this case, the inverter output voltage is as follows:
(3.16)
(2) The compensatory strategy for the minimum pulse width limitation is depicted in
Fig. 6 when dd dlim (b). It is necessary for the duty cycle to be higher than the
necessary dlim minimum pulse width ratio. 10 can be used to calculate the inverter's
output voltage, and
(3.17)
As opposed to the modulation in Fig. 3, the proposed method employs the UP-
PWM with dead time in the region [-ina, ina] at the grid current ZCP (a). This allows
for the guarantee of the desired output voltage even if the polarity of the feedback
current is overestimated. For instance, region 6 in Figure 4 and the grid current ZCP
in Figure 3(a) are similar (b). High frequency operation is used by the power switches
S2,3 and the extra switches S5,6. The red dotted line in Fig. 7 represents the required
inverter voltage - VAB, which is obtained when the current is positive and runs via D2
and D3. The current flow via S2 and S3, which is seen as the blue line, allows for the
achievement of the desired voltage - VAB when the current is negative.
24
Fig. 3.8 Switching losses using two alternative UP-PWM techniques: (a) the traditional method
and (b) the dead time method.
Solid line in Fig. 7 Overall, the suggested modulation technique adopts the
UP-PWM with dead time in the region at the grid-connected current ZCP to offer a
bidirectional way for the current commutation. In this way, the ZCD brought on by
the incorrect current polarity can be reduced.
Conduction losses and switching losses are the two types of power
semiconductor losses. Conduction losses typically depend less on the modulation
techniques than they do on the system load. The profile of switching losses is
however impacted by modulation techniques. Calculations for the switching losses of
an IGBT with an anti-parallel diode include,
The turn-on energy losses (EonM), turn-off energy losses (EoffM), and diode reverse-
recovery energy losses (EonD) under certain test conditions are all included in the
datasheet. where fs denotes the switching frequency, PM denotes the IGBT losses, PD
denotes the diode losses, and PSW denotes the overall switching losses. The datasheet
has these numbers. The reference commutation voltage and current, respectively, are
the test voltage VCC and current ICC. Thus, according to equation, the instantaneous
collector-emitter voltage Vce and the collector current ic during the switching period
would have an impact on the overall power losses associated to the modulation (18)
(3.18)
25
Figure 8 shows Vce and ic for the traditional UP-PWM (a). Due to the grid's
fundamental frequency of operation, only diode losses—not the switching losses of
S5, 6—are included. The overall switching losses can be calculated as follows:
(3.19)
However, as shown in Fig. 8(b), the switching losses of the UP-PWM with
inserted dead time are given as
(3.20)
The switching losses of the UP-PWM with dead time are more than twice as
great as those of the standard UP-PWM, presuming that toff and ton are equal. With
added dead time, the differential-mode voltage VAB equals 0. Additionally, VAB in the
standard UP-PWM shifts from Udc to 0, whereas it shifts from Udc to -Udc in the UP-
PWM with dead time. As a result, the traditional UP-ripple PWM's currents are
minimal. The modulation of the suggested method, which only calls for the activation
of AC bypass switches, has the same switching losses and ripple currents as the
traditional UP-PWM. It should be noted that both the standard modulation technique
and the modulation that just requires the activation of AC bypass switches frequently
function with the recommended hybrid UP-PWM approach. Only the areas 2, 4, 6,
and 8 of the compensation range in Fig. 4(b) should use the UP-PWM with dead time.
26
3.3. CLOSED LOOP CONTROL SYSTEM
The input and output of a control system must have a clear mathematical
relationship in order for it to function. A system is considered to be a linear control
system when its input and output can be explained by a linear proportionality. Once
more, a system is referred to as a non-linear control system when the relationship
between input and output cannot be expressed by a single linear proportionality and
must instead be related by some non-linear connection.
27
• Stability: It's an essential component of a control system. The control system
is considered to be stable if the input signal is bounded, the output must
likewise be bounded, and if the input signal is zero, the output signal must also
be zero.
• Bandwidth: The operational frequency band determines the control system's
bandwidth. The band width should be as wide as possible for the frequency
response of a successful control system.
• Speed: It is the amount of time the control system needs to provide a stable
output. A good control system moves quickly. For such a system, the
transitory duration is quite brief.
• Oscillation: A few oscillations or oscillations that are constant in the output
usually indicate that the system is stable.
• 3.3.2. Feedback Loop of Control System
A feedback is a common and useful element when creating a control system.
By taking into consideration the system output, the feedback loop is a mechanism that
enables the system to modify its performance in order to attain the intended system
result. The output of any control system will be affected by any disturbance or
environmental change. One signal from the output is therefore sent back into the
input. An error signal is produced as a result of comparing this signal to the reference
input. This error signal is received by the controller, and the output is then corrected..
A system like this is known as a feedback system. The feedback system's block
diagram is shown in Figure 5.3 below.
28
Positive feedback systems are those that receive positive feedback. The error
signal in a positive feedback system is created by adding the reference input signal
and the feedback signal. Negative feedback systems are those that receive negative
feedback signals. The error signal for a system with negative feedback is determined
by the difference between the reference input signal and the feedback signal.
29
4. SIMULINK RESULTS
SIMULATION RESULTS:
Fig 4.1 Simulink diagram of proposed system with lagging power factor
Fig.4.2 Simulation power factor wave form of proposed system with lagging power factor
30
Fig.4.3 Simulation Grid Voltage wave form of proposed system with lagging power factor
Fig. 4.4 Simulation Grid Current wave form of proposed system with lagging power factor
31
Fig.4.5 Simulink diagram of proposed system with leading power factor
Fig.4.6 Simulation power factor wave form of proposed system with leading power factor
32
Fig.4.7 Simulation Grid Voltage wave form of proposed system with leading power factor
33
Fig.4.8 Simulation Grid Current wave form of proposed system with leading power factor
Fig.4.10 Simulation power factor wave form of proposed system with Unity power factor
34
Fig.4.11 Simulation Grid Voltage wave form of proposed system with Unity power factor
Fig.4.12 Simulation Grid Current wave form of proposed system with Unity power factor
35
Fig.4.13 Simulink diagram of proposed system with lekage current condition
Fig.4.14 Simulation Grid Voltage, Grid current, and Leakage Current Wave form of proposed
system with Closed loop Controller
36
Fig. 4.15 Simulink diagram of proposed system with Closed loop Controller
Fig.6.14 Simulation input voltage wave form of proposed system with Closed loop Controller
37
Fig.6.15 Simulation output voltage wave form of proposed system with Closed loop Controller
Fig.6.15 Simulation output voltage without filter wave form of proposed system with Closed loop
Controller
38
5. CONCLUSION
For the HERIC inverter, a hybrid UP-PWM method was put forth in this
study. The suggested approach combines the benefits of reactive power capability
modulation, conventional UP-PWM, and UP-PWM with dead time. The suggested
method uses the traditional UP-PWM as its operational manner of producing positive
power. Furthermore, when the negative power generation is activated, just two extra
power switches are functioning at a high frequency. In that situation, the suggested
PWM method can produce currents with less ripple and low switching power losses.
Additionally, the voltage and current ZCPs employ UP-PWM with dead time
to provide steady inverter operation and to reduce distortions. The hybrid UP-PWM
technique was used to compensate for the effects of the dead time and minimum pulse
width limitation in order to further improve power quality. The simulation and
experimental findings have confirmed the hybrid UP-PWM scheme's efficacy in
terms of better efficiency, improved power quality, and—most importantly—flexible
reactive power controllability.
39
REFERENCES
[1] Zhongting Tang, Mei Su, Yao Sun, Bin Cheng, Yongheng Yang, Frede Blaabjerg
and Lina Wang “Hybrid UP-PWM Scheme for HERIC Inverter to Improve Power
Quality and Efficiency,” IEEE TRANSACTIONS ON POWER ELECTRONICS,
VOL. 34, NO. 5, MAY 2019
[5] H. Xiao and S. Xie, “Leakage current analytical model and application in single-
phase transformerless photovoltaic grid-connected inverter,” IEEE Trans.
Electromagnetic Compatibility, vol. 52, no. 4, pp. 902-913, 2010.
40
[9] M. Islam, N. Afrin, and S. Mekhilef, “Efficient single phase transformerless
inverter for grid-tied PVG system with reactive power control,” IEEE Trans.
Sustainable Energy, vol. 7, no. 3, pp. 1205-1215, July 2016.
[10] J. Wang et al., “An improved hybrid modulation method for the single phase H6
inverter with reactive power compensation,” IEEE Trans. Power Electron. doi:
10.1109/TPEL.2017.2768572.
[11] S. Deng, Y. Sun, J. Yang, Q. Zhu, and M. Su, “Optimized hybrid modulation
strategy for AC bypass transformerless single-phase photovoltaic inverters,” J. Power
Electron., vol. 16, no. 6, pp. 2129-2138, Nov. 2016.
[15] G. Dušan and P. Marco, “IGBT power losses calculation using the data-sheet
parameters,” Infineon Handbook, 2009, 1st ed., pp. 5–6.
[16] S. Maniktala, Switching Power Supplies A-Z. Elsevier, pp. 72-74, 2012.
41