School buildings are often built and operated within tight financial
constraints but, at the same time, require high standards of indoor
air quality (IAQ) to promote good learning and health. This article
Sponsor of this month's CPD will reflect on the application of natural ventilation as a method of
maintaining IAQ, and consider the application and control of natural
ventilation for school buildings.
As discussed more fully in the December 2016 CPD article Hybrid ventilation for schools, ventilation
in buildings can be broadly categorised as natural, mechanical or hybrid ventilation. All three
ventilation types have appropriate applications; however, determining whether there is an
opportunity for natural ventilation would be the normal starting point for a project.
Natural ventilation in buildings will be driven by the velocity of the wind impinging on the building’s
fabric, as well as by the pressure differences developed through air temperature variations, and the
resulting ‘buoyancy’ effect.
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 1/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
Figure 1: A ‘flattened’ representation of a rectangular building showing example pressure coefficients for a particular wind
direction
CIBSE Guide A4 and application manual AM10 provide detailed methods and examples for
assessing the practical potential for natural ventilation that are based on networks of airflow paths
through openings (including cracks) in the building fabric, and the available driving pressure. The
driving wind pressure (Pa) is related to the velocity pressure pv = Cp·(0.5·ρ·v2), where ρ is air
density (typically taken as 1.2 kg·m−3) and v is the undisturbed wind velocity measured (in m·s−1) as
if there were no buildings or other obstructions at an appropriate height. Cp is the pressure
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 2/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
coefficient, and will depend on the shape of the building and the direction of the wind. The value of
Cp will vary across the building’s surfaces, as illustrated in the ‘flattened’ rectangular building in
Figure 1.
So, for example, for the building represented in Figure 1, the effective pressure being felt in the
centre of the short windward wall, for a windspeed of 5 m·s-1, will be 0.9·(0.5 x 1.2 x 52) = 13.5 Pa.
Values of Cp are typically determined using wind tunnel tests (as well as computational methods).
There are tabulated average face values of Cp for a selection of common building aspect ratios and
heights in CIBSE Guide A4. Wind pressure will, of course, be variable and is subject to interference
at ground level from obstructions.
For stack ventilation, the pressure difference is caused by the difference in mass between the air in
the building and that of the air outdoors. Pressure (Pa) at the base of a column of fluid (such as air)
is simply 9.81·ρ·z, where z is the column height (m). By including a relationship that determines the
value of air density at a specific temperature, the available pressure for driving ventilation between
two openings in a building can be determined. If one opening is at height z2 (m) and the other at z1
(m), with inside air temperature θai (ºC) and outside air temperature θao (ºC), the driving pressure
difference is given by
So, for example, the available pressure between two windows – one 3m above the other in a room
with air temperature 21ºC when outdoor temperature is 1ºC – would be -3455 x 3m x (1/(1ºC+273)-
1/(21ºC+273)) = -2.57 Pa (the minus sign indicating that the flow would, in this case, be from top to
bottom).
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 3/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
Figure 2: Integrating a ventilation tower to provide top-down natural ventilation (Source: Monodraught)
Both wind and stack will provide a pressure differential that will cause air to flow through openings –
by design and fortuitously (fortuitous flow being termed ‘infiltration’ or air leakage). Flow will vary
approximately with the square root of pressure difference ñ so a doubling of driving pressure would
provide √2 = 1.41 times the natural ventilation.
As shown in the preceding calculations, the available pressure to drive natural ventilation is likely to
be relatively small. For comparison, in a mechanical ventilation system a clean panel filter is likely to
require a minimum of 40 Pa and a standard louvre will need around 20 Pa to pass a desired airflow.
The methods by which spaces are naturally ventilated may be split into four groups.
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 4/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
system. As the air moves across the space, it will pick up heat and pollutant from the internal
environment before it leaves the room. This can provide effective ventilation for a room width of up
to four-to-five times the room height. Stack assisted ventilation provides a more reliable
opportunity for natural ventilation, as it depends on the temperature ñ and so density ñ differences in
air. In simpler applications it may be from a low-level window, or louvre, on one side of the room to a
high-level window or louvre on the same side, or on the opposite side of the space. This can provide
air flowrates during hot, still days – and work in deeper plan spaces. Systems can include chimneys
(possibly solar or waste-heat assisted) that are used to increase the stack effect, and windtowers
that use the wind’s velocity to induce airflow using the ‘venturi’ effect. Top-down ventilation (as
shown in Figure 2) takes advantage of both wind-driven and buoyancy-driven ventilation. However, it
is not completely reliant on either. Stack-driven buoyant air rises within the space and, as it leaves
through a purpose-made ventilation tower, is replaced with outdoor air that enters the tower through
the positively pressured windward side. The leeward faces of the ventilation tower have a lower
pressure that helps to extract the buoyant, stale, warm air from the space below.
Air introduced from high level is typically less likely to carry airborne pollutants, and less prone to
noise pollution compared with ground-level sources. These systems can ventilate deep plan areas
that do not otherwise have direct access to outdoor air, and are not affected by the depth of the
room.
Figure 3: Windtower components that include both geometric and functional parametric information can be ‘dropped in’ to a
standard modelling environment (Source: Monodraught/IES)
Whichever method is employed, the ‘ventilation effectiveness’ should be considered. The system will
only be successful if the supply air not only removes the pollutants and heat, but also provides fresh
(as opposed to stale or already contaminated) air to the occupants. It is this consideration that will
affect the practical effective depth of a naturally ventilated space. The complexities of airflow
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 5/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
movement within the space and the building itself mean that computational fluid dynamics is often
required to evaluate properly the patterns and resulting effectiveness.
It is challenging to forecast properly natural ventilation because of the multiple variable parameters,
including: wind speed; wind fluctuation; ambient temperatures; opening sizes; internal pathways;
and flow characteristics. And, as the wind direction changes, so does the whole pattern of flow paths
through the building, as the pressure coefficients alter across the building surfaces. As discussed
earlier, the practical driving pressures are likely to be small, and so require particularly careful
consideration to determine the flow through appropriately low resistance networks of openings.
There are models (such as Liddament’s simple but effective AIDA algorithm2) that can provide
predictions for simple natural ventilation networks. As discussed in the December CIBSE Journal
CPD article, there is great opportunity to use the computational fluid dynamics (CFD) and dynamic
thermal simulation software to provide a model. However, as reflected in that article, CFD still
requires expert input to provide credible output. Manufacturers of natural ventilation systems have
joined with simulation software suppliers to produce robust tools that require fewer inputs than
normal commercially available simulation tools. This can provide a useful tool for sizing natural
ventilation systems, particularly during the early stages of a project, when full details of a building
are not always readily available.
Libraries of predefined objects are also increasingly available for dynamic thermal simulation
software (as shown in Figure 3) that provide both a geometric representation and functional
parameters. These are likely to become more common as building information modelling (BIM)
methods further permeate the industry. This allows the assessment of performance to investigate
the capabilities of a potential scheme within a standard modelling environment.
Ventilation controls may be used to monitor CO2, temperature and humidity. They can typically be
linked into the building management system so that they can be integrated into wider building
monitoring and control, with the operational data collected and processed for system management.
For example, this allows time zoning of the building to accommodate periods of occupancy and
times when ‘night cooling’ may take place, and to provide frost protection control. They can be linked
in to hybrid systems (see December 2016 CPD article) to maximise opportunities for introducing
larger volumes of lower enthalpy outdoor ‘fresh’ air.
The use of accessible linked visual display interfaces can help educate end users about how the
systems operate so that they may better maintain a comfortable, productive environment with
minimum energy use.
A natural ventilation system was used as part of the building system for a French school renovation
that subsequently received a Green Building Solutions Award from the Construction 21 Network for
Health and Comfort.3 The Simone Veil nursery and primary school wanted control of its year-round
energy consumption, and to ensure low carbon emissions, while maintaining high levels of IAQ (and
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 6/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
New UK guidelines5 on ventilation, thermal comfort and indoor air quality in schools are soon to be
published. An appropriately designed and controlled natural ventilation system should be considered
as a potential option to meet these requirements as, in many applications, it is possible to maintain
IAQ levels while meeting the comfort requirements with low energy consumption.
Further reading
For key guidance on natural ventilation CIBSE Applications Manual AM106 and the recently revised
CIBSE Guide A Section A42 are both excellent references, featuring practical examples.
References
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 7/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 8/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
OPINION
Why embodied carbon must be
regulated
Embodied carbon makes up 80% of total
emissions in buildings, says Anastasia Mylona
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 9/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
Kevin Mitchell: I challenge you to share your knowledge. and communicate how your expertise is
positively impacting… twitter.com/i/web/status/1…
Webinar
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 10/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
SPONSORED BY
White paper
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 11/12
5/22/24, 8:59 PM Module 107: Predicting and delivering good building IAQ using natural ventilation - CIBSE Journal
CIBSE Journal
CPD Programme
Features
CIBSE links
https://www.cibsejournal.com/cpd/modules/2017-01-iaq/ 12/12