HBGS Gas Instructions Manual 006 UK
HBGS Gas Instructions Manual 006 UK
HBGS Gas Instructions Manual 006 UK
Safety Instructions
CAUTION! Always read the instruction manual before commencing work! Read all warnings to the letter! Installation
of the sensor requires technical knowledge of both refrigeration and electronics. Only qualified personnel should work
with the product. The technician must be aware of the consequences of an improperly installed sensor and must be
committed to adhering to the applicable local legislation.
If changes are made to type-approved equipment, this type approval becomes void. The product's input and output, as
well as its accessories, may only be connected as shown in this guide. HB Products assumes no responsibility for
damages resulting from not adhering to the above.
Explanation of the symbol for safety instructions. In this guide, the symbol below is used to point out important
safety instructions for the user. It will always be found in places in the chapters where the information is relevant. The
safety instructions, and the warnings, must always be read and adhered to.
NOTE! Contains important information about the product and provides further tips.
The person responsible for operation must commit to adhering to all the legislative requirements,
prevent accidents, and do everything to avoid damage to people and materials.
Intended use, terms of use. The leakage sensor is designed for leakage measurement in and around industrial
refrigeration systems. If the sensor is to be used in a different way and if the operation of the product in this function is
determined to be problematic, prior approval must be obtained from HB Products.
Prevention of collateral damage Make sure that qualified personnel assess any faults and take necessary precautions
before attempting to make replacements or repairs, so as to avoid collateral damage.
Disposal instructions: The sensor is constructed so that the modules can easily be removed and sorted for disposal.
Technical Data
Supply voltage: 24 V DC – Power consumption max 3watt
Connection: Screw terminals
Cable glands: 2 x PG7
Alarm: Can be configured with HB-tool and an USB cable and an adapter
Measurement accuracy NH3 Repeatability +/-10%
Measurement accuracy CO2 Repeatability +/-2%
Output:
Analog output: 4-20 mA Installation conditions:
Max load: 500 ohm Ambient temperature: -30…+50°C
Alarm output: 3 x SPDT, 0,5A Waterproof rating: IP20, box IP65
1) The sensor may be installed and supplied with a standard unshielded cable. If the EMC is higher
than described in EN 61326, a shielded cable must be used.
2) If the sensor is mounted in dusty conditions or where water is used for cleaning the sensor head
should be pointing downwards as the sensor might be block or damaged by the water. A protection
of the head is recommended during cleaning using water. Remember to remove the protection after
cleaning
3) It is recommended to install the sensor in stairways and other places where gas pockets can form.
4) If a ventilation system is installed, it would make sense to place a sensor at the inlet.
1) The sensor must be mounted at a distance of at least 150 cm from the floor.
2) By safety valves, the sensor must be placed 1-2 m above the outlet to secure fast reaction.
1) The sensor must be mounted maximum 50 cm above the lowest point in the room.
2) If there is a basement in open connection which the machine room, it should be placed there
3) By safety valves, the sensor must be placed below the outlet to secure fast reaction.
The sensor can be connected directly to a siren using the Alarm A, Alarm B, Alarm C and ground. At the same time the
mA signal can be send to a PLC
Functionality
LED Indication
On the front of the sensor, LED indication is integrated
for power supply ON and alarm indication A, B, & C.
Alarm Reset
In case of a leak, an alarm is triggered. The alarm can be reset by holding down “R” for a
few seconds. If the alarm activates again after reset, there is still a gas leak in the room.
Unscrew the two Philips screws on the top and connect the HBxC-USB to the
HBGS-USB-ADAPTOR. Connect the HBGS-USB-ADAPTOR to the M12 circular
connector of the main unit. Supply the sensor with 24VDC.
The alarm settings can be typed in and saved to the sensor. All alarms can be
configured both as NO (normally open) and NC (normally closed) which refers to
the contactor, so NO means the contactor will be closed when an alarm occur, and
the siren will start if connected. NC can be used to make the installation safer and
detect a broken wire, but it requires siren with a similar function, which means it
makes alarm when the signal is removed.
Sensor Repair
A new sensor head can be ordered with product no. HBGS-NH3-UNIT or HBGS-CO2-UNIT
The sensor head can be replaced directly and requires no calibration.
If you have questions to the product, please contact HB Products’ dealers/distributors. Please consider their complaint
procedures before returning the sensor.