F Lect 5
F Lect 5
1
Network Loadability
• We can calculate load active and reactive power by phasor diagram.
where Pn and Qn are the real and reactive power demand of the load at the rated voltage V n.
But Qn = Pn tan ϕ
Simplify
We get
Express in PU by (V/E)
PU
Part 1 : V-P relation
The non-linear behavior of voltage power characteristics
Stability limit
❑ For a lagging power factor (curves 1 and 2) the voltage decreases as the real load increases.
❑ For a leading power factor (curve 4) the voltage initially increases and then decreases.
❑ The difference between a current load and the maximum load determined by the peak of the characteristic is equal to the
stability margin for a given power factor.
❑ for Qn = 0, that is for ϕ = 0, the peak of the nose curve occurs at p = 0.5, that is for Pn = 0.5E2/X = E2/2X .
❑ Nose curves V(P) illustrate the dependency of the voltage on real power of a composite load assuming that PF is a
parameter.
Exercise# 1.1: Apply the “Per unit voltage power equation”(Eq 8.8 on the textbook) on Matlab by sweeping
the PF from 0.4 lag to 0.4 lead in 0.1 step
Part 2 : P-Q relation
• The curves Q(P) discussed below are derived assuming that the voltage is a parameter.
Rearrange
➢ The parabola described by the equation defines the shape of the envelope that encloses the possible solutions to the network equation .
➢ Each point (Pn, Qn) on the parabola satisfies one network solution corresponding to only one value of voltage.
5
Influence of the Load Characteristics(Non-Stiff Load: the load power depends on the voltage)
Sub in yields
7
Stability Criteria “voltage stability”
8
1. d∆Q/dV criterion
9
1. d∆Q/dV criterion
Unstable Stable
d∆Q/dV
10
2. d𝐸/dV criterion
2. d𝐸/dV Criterion
• It is based on capability of the power system to supply the load with emf for a given real and reactive power
demand
Solving
➢ Proof that:
E(V)= (𝐸𝑐𝑜𝑠𝛿)2 + 𝐸𝑠𝑖𝑛𝛿 2
But now
After some math
12
3. dQG/dQL criterion
• The system is stabile if change in reactive load demand produces a change in the generation which
has the same sign:
The main advantage of this criterion is that it can be used easily with load flow program:
1- Generated reactive power QG is replaced by the sum of all generated reactive powers at all generator nodes.
2- Load reactive power QL is replaced by the sum of all load reactive powers at all load nodes.
13
Summary
➢ A power system at a given operating state and subjected to a given disturbance is voltage stable if voltage
near loads approaches post disturbance equilibrium values.
➢ Criterion#1:
It is based on the capability of the system to supply the load with reactive power for a given real power demand.
𝑑Δ𝑄
<0
𝑑𝑉
➢ Criterion#2:
It is based on capability of the power system to supply the load with emf for a given real and reactive power
demand
𝑑𝐸
>0
𝑑𝑉
➢ Criterion#3:
It is based on capability of the generator's reactive power to change with the load reactive power demand
proportionally.
𝑑𝑄𝐺
>0
𝑑𝑄𝐿
14
METHODS OF VOLTAGE CONTROL
1. Excitation control.
2. Shunt capacitors.
3. Series capacitors.
4. Tap-changing transformers.
5. Boosters.
6. Synchronous condensers. Sivanagaraju and Sreenivasan, “Power System Operation and Control” Ch 10
1. Excitation control
• Due to the voltage drop in the synchronous reactance of armature circuit, the generator terminal
voltage changes and hence the load on the supply system also undergoes a change.
• This can be maintained constant by changing the field current of the alternator. This process is
called excitation control.
❑Shunt capacitors offer the cheapest means of reactive power supply, but these
are not as flexible as synchronous condensers.
❑Capacitors are connected to a bus bar or to the tertiary winding of a main
transformer.
❖The concern is : for light loads, when the voltage is high, the capacitor output
is large, and the voltage tends to become excessive.
• The voltage can be varied by varying a number of tappings on the secondary side
which requires the disconnection of the transformer from the load when the tap
setting is to be changed.
• The output of the secondary side of the transformer changes with the change in the
tap position of the secondary winding.
• The secondary voltage is minimum when the arm at 1, whereas it is maximum
when it is in N.
• When the load on the transformer increases, the voltage across secondary decreases.
This can be increased to the desired value by adding the number of turns on the
secondary of the transformer by changing taps.
• The main drawback is that the taps are changed only after the removal of the load.
This can be overcome by using an on-load tap-changing transformer with reactors.
Disadvantages
When used in conjunction with main transformer:
1. More expensive than a transformer with on-load tap changes.
2. Less efficient due to losses in booster.
Booster transformers
3. Requires more space.
Advantages
1. Flexibility for use in all load conditions because when the machine is under excited, it consumes reactive power.
2. There is a smooth variation of reactive VAR.
3. It can be overloaded for short periods.
Disadvantages
1. Possibility of falling out of control in case of sudden changes in voltage.
2. These machines add to short-circuit capacity of the system during fault condition.