Pol955 DS

The document describes a Climatix I/O extension module with 14 inputs and outputs. It has 8 universal inputs that can be configured as analog or digital signals, 4 relay outputs, and 2 analog outputs. The module connects to Climatix controllers and provides flexible I/O expansion for applications like air handling units.

Uploaded by

Abdul Shamil M S
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views10 pages

Pol955 DS

The document describes a Climatix I/O extension module with 14 inputs and outputs. It has 8 universal inputs that can be configured as analog or digital signals, 4 relay outputs, and 2 analog outputs. The module connects to Climatix controllers and provides flexible I/O expansion for applications like air handling units.

Uploaded by

Abdul Shamil M S
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

s 3 262

Climatix™

Climatix I/O extension POL955.00/XXX


module with 14 I/Os

The POL955.00/XXX is a versatile Climatix I/O extension module that can be


connected to any type of Climatix POL6XX controller. Its high flexibility of
universal inputs meets the requirements of the compact air handling unit
industry plus those of other air conditioning applications and other
applications. It is part of the Climatix product range (refer to Data Sheet 3900
and Mounting Instructions M3910).
The extension module offers the following features:
· Power supply AC 24 V or DC 24 V via the controller
· 8 universal I/Os for analog or digital signals (configurable inputs/outputs)
· 4 relay outputs (NO contacts)
· 2 analog outputs (DC 0…10 V)
· Peripheral bus interface for local/remote extension I/Os

CB2N3262en_04
2019-07-12 Smart Infrastructure
Climatix product range Installation concept

Disposal

The devices are considered electronics devices for disposal in term of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
· Dispose of the device via the channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.

Technical data

Power supply Operating voltage AC 24 V ±20%; DC 24 V ±10%


Frequency 45…65 Hz
Max. AC-Current consumption 600 mA at AC 24 V
Max. DC-Current consumption 340 mA at DC 24 V
Connection Peripheral bus

Power distribution Max. pass through current 3.4 A at AC 24V


3.66 A at DC 24 V

Relay outputs Q1...Q4 Relay: type, contact Monostable, NO contact


Contact rating
Switching voltage AC 24…230 V (-20%, +10%)
Nominal current (res. / ind.) Max. AC 4 A / 3 A (cosφ 0.6)
Switching current at AC 19 V Min. AC 30 mA

Connecting indicator lamps to relay output

2 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Universal I/Os Configurable By software
X1…X8 Reference potential Terminals ┴
Contact voltage Max. DC 24 V (SELV)
Over voltage protection Up to 40 V

Analog inputs (X1…X8)


Ni1000
Sensor current 1.4 mA
Resolution 0.1 K
Accuracy within the range -50…150 °C 0.5 K
Pt1000
Sensor current 1.8 mA
Resolution 0.1 K
Accuracy within the range -40…120 °C 0.5 K
NTC 10k (B25/85 = 3977K)
Sensor current 140 μA
Temperature range Accuracy Resolution
-50…-26 °C 1K 0.2 K
-25…74 °C 0.5 K 0.1 K
75…99 °C 1K 0.3 K
100…124 °C 3K 1.0 K
125…150 °C 6K 2.5 K
NTC 100k (B25/85 = 3977K)
Sensor current 140 μA
Temperature range Accuracy Resolution
-25…-11 °C 3K 0.2 K
-10…9 °C 1K 0.1 K
10…99 °C 0.5 K 0.1 K
100...150 °C 1K 0.2 K
0...2,500 Ω
Sensor current 1.8 mA
Resolution 1Ω
Accuracy 4Ω

Connecting a ratiometric sensor to universal I/Os


Connecting NTC to universal I/Os

3 / 10

Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04


Smart Infrastructure 2019-07-12
Analog inputs (X1…X8)
DC 0...10 V input
Resolution 1 mV
Accuracy at 0 V 2 mV
Accuracy at 5 V 25 mV
Accuracy at 10 V 50 mV
Input resistance 100 kΩ
DC 0/4…20 mA input
Resolution 1 μA
Accuracy at 4 mA 25 μA
Accuracy at 12 mA 70 μA
Accuracy at 20 mA 120 μA
Impedance of DC 0/4…20 mA input Typ. 450 Ω

Voltage input DC 0…10 V


Current input 4…20 mA

Digital inputs (X1…X8)


0/1 digital signal (binary) For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay 10 ms
Pulse frequency Max. 30 Hz

Connecting floating contacts to universal I/O

4 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Analog outputs (X1…X8)
DC 0…10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA (short-circuit-proof)
DC 4…20 mA output
Resolution 22 μA
Accuracy at 4 mA 150 μA
Accuracy at 12 mA 196 μA
Accuracy at 20 mA 243 μA

Connecting voltage output and current output to universal I/O

Analog outputs DC 0…10 V output


Y1...Y2 Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA

Connecting voltage output and offboard relays to analog output

Connection terminals Optional plugs for IO signals Phoenix FKCVW 2,5 / x-ST

5 / 10

Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04


Smart Infrastructure 2019-07-12
Phoenix FKCT 2,5 / x-ST
Phoenix MVSTBW 2,5 / x-ST
Solid wire 0.5…2.5 mm²
Stranded wire (twisted and with ferrule) 0.5…1.5 mm²
Cable lengths In compliance with load, local regulations
and installation documents

Peripheral bus Power supply Ueff = AC 24 V ± 20%, fmain = 45...65 Hz


or U = DC 24 V ± 10%, no internal fuse
Bus termination selectable (680 Ω / 120 Ω +1 nF / 680 Ω )
Solid wire 0.2…1.0 mm²
Stranded wire (twisted and with 0.2…1.0 mm²
ferrule)
Cable lengths Max. 30 m
Addressing DIP switch 1…5
Termination DIP switch 6

Environmental Operation IEC 60721-3-3 class 3K5


conditions Temperature -40...70 °C
Humidity <90% r.h. (non-condensing)
Atmospheric pressure Min. 700 hPa, corresponding to
Max. 3,000 m above sea level
Transport IEC 60721-3-2 class 2K3/2K4
Temperature -40...70 °C
Humidity <95% r.h. (non-condensing)
Atmospheric pressure Min. 260 hPa, corresponding to
Max. 10,000 m above sea level

Protection Degree of protection IP20 (EN 60529)


Safety class Suitable for use in plants with safety
class II

Standards Product standard EN 60730-1


Automatic electrical controls for
household and similar use
Electromagnetic compatibility For use in residential, commerce, light-
(applications) industrial and industrial environments.
EU conformity (CE) CB1T3920xx *)
RCM conformity (EMC) CB1T3909en_C1
Listings UL916, UL873 http://database.ul.com/
CSA Class 4812
http://www.csagroup.org

Environmental The product environmental declaration CB1E3920en contains data on


compatibility environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).

*) The document can be downloaded from http://siemens.com/bt/download.

General data Dimensions of controller 108 x 110 x 75 mm


Weight excl. packaging 183.5 g
Base Plastic, pigeon-blue RAL 5014
Housing Plastic, light-grey RAL 7035

6 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Status of LEDs The status of BSP LED is defined as follows:

Status Meaning
Red flashing at 2 Hz BSP error or slave address error
Green on BSP running

The status of BUS LED is defined as follows:

Status Meaning
Red on Communication error
Green on Communication running
Orange on Communication running but parameter not
successfully configured

DIP switch The extension module is equipped with DIP switch to communicate with the
controller. Switch 1, 2, 3, 4, and 5 are configurable to set the slave address, while
switch 6 serves as peripheral bus termination. If the extension module works as the
termination in the network, switch 6 must be set to ON.

The order of bit is from 5 to 1. The lowest bit is 5 while the highest bit is 1. Max. 31
slave addresses can be configured as follows:
DIP Switch configuration of Extension Module

No. Schematics No. Schematics No. Switch 5 No. Schematics

1 9 17 25

2 10 18 26

3 11 19 27

4 12 20 28

5 13 21 29

6 14 22 30

7 / 10

Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04


Smart Infrastructure 2019-07-12
DIP Switch configuration of Extension Module

No. Schematics No. Schematics No. Switch 5 No. Schematics

7 15 23 31

8 16 24

Note
F The same address of extension module must be set respectively in the application
program of the controller. 0 cannot be set as the slave address.

Ordering data Climatix I/O extension module 14 I/Os 1 pcs POL955.00/STD


Connector set (spring cage, cable top entry) or 1 pcs POL095.56/STD
Connector set (screw, cable side entry) 1 pcs POL095.55/STD

Accessories Connector set (spring cage, cable top entry) POL095.56/STD


1 x Phoenix FKCT 2,5/2-ST GY7035
1 x Phoenix FKCT 2,5/3-ST GY7035
3 x Phoenix FKCT 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Connector set (screw, cable side entry) POL095.55/STD
1 x Phoenix MVSTBW 2,5/2-ST GY7035
1 x Phoenix MVSTBW 2,5/3-ST GY7035
3 x Phoenix MVSTBW 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Board-to-wire connector POL002.43/STD
2 x Phoenix ZEC 1,0 / 4-ST-3,5 GY35AUC1R1,4 50 pcs

Engineering notes

To ensure protection against accidental contact with relay connections carrying


voltages above 42 Veff, the extension module must be installed in an enclosure
(preferably a control panel). It must be impossible to open the enclosure without
the aid of a key or tool.
AC 230 V cables must be double-insulated against safety extra low-voltage (SELV)
cables.

8 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Dimensions

Right side Left side

9 / 10

Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04


Smart Infrastructure 2019-07-12
Published by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd 2017
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change

10 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12

You might also like