Climatix product range Installation concept
Disposal
The devices are considered electronics devices for disposal in term of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
· Dispose of the device via the channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
Technical data
2 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Universal I/Os Configurable By software
X1…X8 Reference potential Terminals ┴
Contact voltage Max. DC 24 V (SELV)
Over voltage protection Up to 40 V
3 / 10
4 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Analog outputs (X1…X8)
DC 0…10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA (short-circuit-proof)
DC 4…20 mA output
Resolution 22 μA
Accuracy at 4 mA 150 μA
Accuracy at 12 mA 196 μA
Accuracy at 20 mA 243 μA
Connection terminals Optional plugs for IO signals Phoenix FKCVW 2,5 / x-ST
5 / 10
6 / 10
Siemens Climatix I/O extension module with 14 I/Os CB2N3262en_04
Smart Infrastructure 2019-07-12
Status of LEDs The status of BSP LED is defined as follows:
Status Meaning
Red flashing at 2 Hz BSP error or slave address error
Green on BSP running
Status Meaning
Red on Communication error
Green on Communication running
Orange on Communication running but parameter not
successfully configured
DIP switch The extension module is equipped with DIP switch to communicate with the
controller. Switch 1, 2, 3, 4, and 5 are configurable to set the slave address, while
switch 6 serves as peripheral bus termination. If the extension module works as the
termination in the network, switch 6 must be set to ON.
The order of bit is from 5 to 1. The lowest bit is 5 while the highest bit is 1. Max. 31
slave addresses can be configured as follows:
DIP Switch configuration of Extension Module
1 9 17 25
2 10 18 26
3 11 19 27
4 12 20 28
5 13 21 29
6 14 22 30
7 / 10
7 15 23 31
8 16 24
Note
F The same address of extension module must be set respectively in the application
program of the controller. 0 cannot be set as the slave address.
Engineering notes