Assignment 2 EE601 EMD1
Assignment 2 EE601 EMD1
Q. N. Question PO
1. Determine (i) Number of l.v. and h.v. turns per phase (ii) Cross sectional area of l.v. and h.v. 2,3
windings for a 1250 KVA, 33/6.6 KV, 50Hz, 3-phase, delta/star, core type, power transformer.
Assume suitable values for various design parameters.
2. What is the effect of variation of frequency on Hysteresis Loss, Eddy Current loss, Leakage 2
reactance and winding resistance?
3. Determine the dimensions of core and Yoke of a 200KVA, 50Hz, single phase core type 2,3,4
transformer. A square core is used with distance between limbs equal to 1.8 times the diameter of
Circumscribing circle of the core. Assume voltage per turn to be 14V, window space factor to be
0.32, Max. flux density to be 1Tesla, current density to be 3A/mm2. Where Ai=0.45d2. Show all
dimensions in a sketch.
4. Compare the Power Transformer & Distribution Transformer in terms of design. 2,3
5. Calculate the main dimensions of a 100KVA 2000/400V, 50hz, single phase shell type, oil 2
immersed, self cooled transformer. Assume,
Voltage per Turn = 10V
Flux density in the core = 1.1Wb/m2
Current density = 2A/mm2, Window space factor = 0.33
The ratio of window height to window width and ratio of core depth to width of central limb is 2.5.
The stacking factor is 0.9.
6. Explain the procedure for design of winding of transformer. 2,3,4
7. Compare Core Type Transformer and Shell Type Transformer. 2,3,4
8. Determine the dimensions for core and yoke for a 5KVA, 50Hz, single phase core type 2,3
Transformer. A rectangular core is used with long side twice as long as short side. The window
height is 3 times the width. Voltage per turn is 1.8V; space factor 0.2; current density 1.8A/mm2.
Flux density 1Wb/m2.
9. A 3-phase 50Hz, oil cooled core type transformer has the following dimensions: Distance between 2,3
core centers=0.2m; Height of Window=0.24m; Diameter of circumscribing circle=0.14m. The flux
density in the core is 1.25Wb/m2 and current density in the conductors is 2.5A/mm2. Estimate the
KVA Rating. Assume a window space factor of 0.2 and core area factor=0.56. The core is 2-
stepped.
10. Calculate approximate overall dimensions for a 100KVA, 6600/440V, 50Hz, 3 phase core type 2
transformer. The following dimensions may be assumed: emf per turn = 10V; Maximum flux
density 1.3 Wb/m2 ; current density = 2.5A/mm2 ; window space factor = 0.3;
overall height = overall width ; stacking factor = 0.9. Use a 3 stepped core.
For a 3 stepped core :
Width of largest stamping 0.9d, and
Net iron area = 0.6d2 where d is the diameter of circumscribing circle.
11. Write in short disadvantages of 3-phase transformer over a bank of three 1-phase transformers. 2,3,4
12. Derive the output equation of a 3-phase Transformer.
13. Calculate the main dimensions of a 200KVA 2000/400V, 50hz, single phase shell type, oil 2,3,4
immersed, self cooled transformer. Assume,
Voltage per Turn = 10V
Flux density in the core = 1.3Wb/m2
Current density = 2.2A/mm2, Window space factor = 0.33
The ratio of window height to window width and ratio of core depth to width of central limb is 2.5.
The stacking factor is 0.9.