Drawing Package For Schneider RMU-Layout6

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CUBICLE NUMBER A1 A2 A3

CUBICLE NAME Incoming cabinet Incoming cabinet Feeder cabinet


SWITCHGEAR TYPE SM6 SM6-IM375 SM6-IM500 SM6-DM1-A-SF1-630

RATED CURRENT 630A

SINGLE LINE DIAGRAM

RATED VOLTAGE 12kV


SERVICE VOLTAGE 6.6kV
INSULATION LEVEL 42kV
INSULATION LEVEL PEAK 48kV
RATED FREQUENCY 60Hz
WITHSTAND CURRENT 25kA 1s
PEAK WITHSTAND CURRENT 63kA
PROTECTION DEGREE IP2XC
DIELECTRIC SF6 GAS
PAINTING RAL9002
CONTRAL POWER 110VDC
RATED CURRENT
SWITCH
SWITCH MECHANISM
CIRCUIT BREAKER
CB OPERATING MECHANISM RI
MODE OF OPERATION AUTO AUTO MANUAL&AUTO
CURRENT TRANSFORMER TYPE 3*ARJP2/N2F 3*ARJP2/N2F 3*ARJP2/N2F
RATIO/CLASS: 100/1 CL0.5 100/1 CL0.5 100/1 CL1 5P20
ZERO CURRENT TRANSFORMER TYPE ARJP2/N2F
RATIO/CLASS: 100/1 CL1
Contained within the three position switch and
EARTHING SWITCH Contained within the three position switch Contained within the three position switch the circuit breaker grounding switch

VOLTAGE INDICATOR VIPS VIPS VIPS


HEATER POWER 220VAC 50W 50W 50W
METER PM5350P PM5350P PM5350P
PROTECTION RELAY TYPE Sepam 40
ANSI CODE 50/51
CABINET W*D*H(mm) 375*840*2050 500*840*2050 750*840*2050

PROJECT NAME SUBSTATION


0.38kV structure layout drawing