1.1 Introduction
The RM30110A is a telecommunications grade rectifier with the following features:
Hot pluggable
Forced Air Cooled
Thermally Protected
Power Factor Corrected
Wide input AC Voltage
Constant Power Output Limit
Input/Output Voltage and Current Protected
Active Load Sharing
Serial alarm and control interface
Microprocessor controlled
1.2 Indicators
There are 3 LED indicators on the front panel indicate the operational state of the rectifier.
: This green LED indicates that mains power is connected to the unit and that the primary stages of
the rectifier are operating.
: This yellow LED indicates a Non-Urgent alarm state within the rectifier. This could be caused by
the following:
Fan failed
: This red LED indicates an Urgent alarm state within the rectifier. This could be caused by the
following:
Rectifier Failed
The maximum ambient operating temperature range at full power is: -25 to 65 ºC.
The rectifier will operate in ambient temperatures up to 65ºC but the rectifier will de-rate its output power to
keep internal temperatures within the allowable range.
1.8 Reverse Polarity Protection
The rectifier has an internal reverse polarity protection fuse and crowbar diode fitted. These parts are not
user serviceable, and the rectifier will require returning for servicing if incorrect polarity is applied to the
output.
1.9 Active Load Share
The rectifier will actively current share with other rectifiers in the same DC system. The rectifiers are
interconnected through pin 12 of their connector. The hardware in each rectifier looks at this current share
bus and adjusts its output current to align with other rectifiers. In addition to this control, the monitor can
compare rectifier output currents and adjust individual rectifiers to achieve current share. The rectifier
current share bus is generally used within one rack of rectifiers and the monitor control is used to make
separate racks share with each other.
1.10 Fan Cooling
The rectifier constantly monitors its internal temperature, ambient temperature and output current, then
adjusts fan speed to ensure continued operation. This control of fan speed ensures that rectifier acoustic
noise and dust accumulation are minimized.
If the fan fails and cannot be restarted then the current limit will further reduce to 25A. The rectifier will
continue to operate as long as the internal temperature stays within allowable limits.
1.11 Serial Alarm and Control Interface
The rectifier, when installed in an our company ARS-4 rectifier shelf, is controlled via the serial interface by
the system monitor. The system monitor can set up control parameters and receive alarm information via
this interface.
If this interface is disconnected or fails for some reason the rectifier will operate with the parameters last
sent from the monitor. Current share will revert to the rectifier current share bus.
The rectifier voltages are set by the system monitor via the serial communications bus. The rectifier
voltage can be set to any value between 90V and 155V. The monitor operates in a number of modes that
will affect the rectifier voltage setting.
The monitor sets the float voltage to its target level at start up, and then resends this same level at
regular intervals thereafter. The voltage control is open loop.
The monitor sets the system voltage to its target float voltage, then monitors the system voltage
and adjusts rectifier voltages to maintain the system voltage at the desired float voltage.
The monitor sets the system voltage to an elevated level (e.g. 126V) for a fixed period, and then
resets the system voltage to the float voltage setting.
The monitor sets the system voltage to an elevated level after a battery discharge. This keeps the
rectifiers in current limit for a longer period, leading to a faster battery recharge. When the battery
is recharge the monitor resets the system voltage to the float voltage level.
The rectifier will report the following states to the monitor via the serial communications:
Rectifier Fail The rectifier is not functioning. This could be due to high output voltage, AC failure
or a fault with the rectifier internally.
Over Temperature The internal temperature of the rectifier is too high and the rectifier has begun to limit
its output to control this temperature.
Current Limit The rectifier output has reached maximum and the output current is being limited.
Shutdown The rectifier has been shutdown by the monitor. It will restart again in 5 minutes
unless the shutdown instruction is repeated.
EEPROM Fault The rectifier microprocessor has encountered an error while reading from EEPROM.
Soft Start The rectifier has just turned on and is slowly increasing its output.
The rectifier can be remotely forced to shutdown, via the serial communications, by the system monitor
and/or remote supervisory software. The rectifier will shut down for 5 minutes then restart. If a further
shutdown signal is received by the rectifier before the 5 minutes is up, the timer will reset to 5 minutes.
Hence, if a rectifier is to be kept shutdown a shutdown signal must be sent to it at regular intervals.
1.12 Post-mate Connection
The rectifier is “hot plug” capable. This is achieved by having one pin on the rear connector that mates
after the other pins. This pin must be connected to negative bus volts and the rectifier will not start until
this pin engages. If a rectifier will not start, ensure the rectifier is fully engaged in the connector in the
rectifier shelf.
Connector pin Layout (on the backplane)(view from rectifier plugging side):
Pin descriptions
DANGER
Do not operate the rectifier if the covers are damaged or removed in any way
- The rectifier contains voltages that may be lethal even after the input supply has
been removed
- The rectifier contains components at High Temperatures that may burn if touched
The air at the front of the rack is at ambient temperature and not being heated by other equipment.
Ensure the rectifier shelf has at least 75mm clear horizontal space behind it. This space must be
clear of cables and any other components that may restrict air movement.
(Note: if multiple rectifier shelves are installed then there should be at least 75mm clear horizontal
space per shelf.)
The free space in the rack should continue vertically to the exhaust point at the top of the rack,
without impediment.
The hot exhaust air should not be allowed to re-circulate to the front of the rack as this will be
drawn into the rectifiers again, in effect raising the apparent ambient temperature.
The rectifier should be operated in a low dust environment. If this cannot be guaranteed, then the rack
should be fitted with air filters to prevent dust passing into the rectifier units. These filters need to be
designed for adequate air volume and regularly maintained.
Note: If you are designing your own rectifier shelf, then particular care must be taken to ensure that any
metalwork, cable or printed circuit boards are placed to maximise the flow of cooling air.
2) Plug the rectifier into the rectifier shelf using the following steps:
Locate the metal tag (at the bottom/rear of the rectifier) into the chosen slot in the backplane.
Engage the plastic front panel into the slot at the front of the rectifier shelf.
Push the rectifier into the rectifier shelf until the connector is fully engaged.
Lock the rectifier in position using the plastic retainers in the front panel.
3) Once the rectifier is installed into the rectifier shelf, the AC power can be turned on. After the initial
start up period the rectifier will be set to the desired system parameters by the monitor module via
the serial communications.
Due to ongoing product development specifications are subject to change without prior notice
3.1 AC Input
Nominal 220V
Protection
Input Voltage Auto shutdown, auto restart when correct voltage restored.
3.2 DC Output
Nominal 110V
Regulation
Line ±0.1%
Protection
Isolation
3.3 Environmental
Operating Ambient Temperature
Rated 25± 5 ºC
3.4 Mechanical
Dimensions (W, H, D) 156mm, 40mm, 270mm
Weight 2.5kg
3.5 Compliances
Safety EN60950
AC Harmonics EN 61000-3-2
If the rectifier develops an operational fault, or is damaged in any way, an Authorised Service Centre
should service it immediately.
4.1 Warnings
This rectifier contains no user serviceable components. Do not disassemble the rectifier.
DANGER
Do not operate the rectifier if the covers are damaged or removed in any way.
- The rectifier contains voltages that may be lethal even after the input supply has
been removed
- The rectifier contains components at High Temperatures that may cause burns if
touched
4.2 Troubleshooting
If the red LED is alight:
4.3 Fuses
Although there are fuses inside the rectifier, these are rated such that their failure indicates a fault requiring
qualified service. Do not attempt to repair these fuses.
Rectronic Ltd. warrants that this product is free from defects in material and workmanship and agrees to
remedy any defect (or at its option replace the product) for a period of two year from the date of purchase.
This warranty covers both parts and labour. Parts may be replaced under this warranty with new or
remanufactured parts.
This warranty will not apply to any product that has been improperly installed (as described in the
installation manual), misused, abused, used in ways the product was not designed, altered or repaired in
any way which may affect the performance or reliability of operation, sustained damage by power surges
or electrical storms, or sustained shipping damage, or repaired by any unauthorised repair centre.
Please contact Rectronic Customer Service to obtain a Returned Materials Authorisation (RMA) prior to
shipping any products for repair. All shipments must be shipped prepaid and include proof of the date of
your original purchase. Please include your name, address, phone number, email address and a brief
description of the problem.
Rectronic Ltd makes no other warranties, express or implied, including any warranty of fitness for a
particular purpose. In no event shall Rectronic be responsible for indirect or consequential damages or lost
profits even if Rectronic Ltd has been advised of the possibility of such damages. Rectronic Ltd’s sole
obligation to you shall be the repair or replacement of a non-conforming product.