Soft Starters Peter Electronic - Dimensioning Rules en
Soft Starters Peter Electronic - Dimensioning Rules en
Soft Starters Peter Electronic - Dimensioning Rules en
23
All data sheets and commissioning instructions are available on our homepage at
www.peter-electronic.com.
Configuration Instructions
The two following diagrams for an 11kW-drive operated at nominal load show the waveforms of electrical and mechanical quantities of
the drive during the ramp-up phase, both with and without soft starter:
motor current
motor voltage
torque
driving speed
Ramp-up of the three-phase asynchronous motor directly connected to the mains (at nominal load)
motor current
motor voltage
torque
driving speed
Ramp-up of a three-phase asynchronous motor with soft starter (at nominal load)
Both groups of curves show the complete acceleration and deceleration phase.
In this connection, especially the waveform of the current during ramp-up with a soft starter is of interest. Depending on the adjusted
starting voltage (boost), the current increases more or less steeply until nominal speed is reached. For the following load diagrams
(thermal load), the mean value of that current is to be used which is formed by the current flowing at the starting point and the current
flowing when nominal speed is reached (see example).
The following diagrams show how the maximum starting frequency (in starts per hour) depends on the ramp-up time and the mean
starting current flowing during ramp-up.
The curves represent the thermal ratio oft he heat generated in the power semiconductors and the possible dissipation of heat by the
integrated heat sinks, i.e., a high starting frequency in combination with a large mean starting current causes intense heating by the
power demiconductors. If, in addition, a long ramp-up time is required for the starting operation, the number of starts possible within a
certain unit of time reduces accordingly.
07/17
1.24 Dimensioning Rules for Soft Starters
In compliance with the power rating of the motor, a VersiStart II 400-25 soft starter is selected (acc. to the data sheet it is suitable for
11kW motors, Ie = 25A).
However, when checking the number of starts per hour possible with this device under these conditions, it turns out that this device is not suitable:
35 Starts/h
Ramp-up-time 6s
When dividing the starting current of 65A to be expected by the nominal current of 25A of the soft starter VersiStart II 400-25, this gives
approx. 3 x Ie (65A/25A) of the soft starter. Consequently, a maximum starting frequency of 35 starts per hour is permissible for this
device, i.e., in this case VersiStart II 400-25 would be overloaded.
This is only possible by reducing the ramp-up time. As demonstrated by the two below diagrams, the ramp-up time maximally possible
for the application of a VersiStart II 400-25 would be approx. 4s.
50 Starts/h
If it is due to technological reasons not possible to go below the specified ramp-up time of 6s, a device that complies with the requested
parameters has to be used.
When looking at the characteristic curves, it becomes clear that, for this case of application, a VersiStart II 400-32 is suitable. With a
twofold nominal current of the soft starter, i.e., 2 x Ie (65A/32A), and a ramp-up time of 6s, this device has a starting frequency of approx.
55 starts/h.
Since only 50 starts/h are required, this device is optimally designed to withstand the most the most unfavorable thermal loading.
55 Starts/h
Ramp-up time 6s
07/17
1.26 Dimensioning Rules for Soft Starters
Load diagrams:
Dimensioning Rules for Soft Starters 1.27
07/17
1.28 Dimensioning Rules for Soft Starters
Dimensioning Rules for Soft Starters 1.29
07/17
1.30 Dimensioning Rules for Soft Starters
Dimensioning Rules for Soft Starters 1.31
07/17
1.32 Dimensioning Rules for Soft Starters
Dimensioning Rules for Soft Starters 1.33
Dimensioning of pre-fuses:
Notes
- On the basis of the I²t-value of the power semiconductors, the ramp-up time and possibly the max. starting current, the fuse
supplier is able to select a suitable type. Due to the great variety of producers, sizes and types. PETER electronic does not
recommend any particular fuses.
- If the value oft he fuse or the cutoff-I²t-value is selectred too small, it may happen that the semiconductor fuse reacts during
the starting phase or during deceleration.
- In the case of special devices having increased ramp-up or deceleration times, the recommended fuse value may have to be
adapted.
07/17
1.34 Dimensioning Rules for Soft Starters
Table 1
nominal/rated
fuse value in the case of starting frequency
device type device current
allocation type 1 starts / h (3xIe 5s)
(techn. data)
VS II 3,5A 10A 150
VS II-3LDS, VS II 6,5A 16A/20A 120/75
VS III 9A 20A 50
VS II-5,5LDS, VS II 12A 20A/32A 65/30
VS II-7,5LDS 15A 35A 100
VS II, VS III 16A 32A 15/30
VS II 17A 35A 60
VS II, VS II-11LDS, VS III 25A 50A 40/65/20
VS II, VS II-15LDS 32A 63A 30/35
VS III 37A 63A 15
VS II, VS III 45A 100A/80A 10