NOTES

- ALL DIMENSIONS SHOWN IN MILLIMETERS AND LEVELS ARE IN METERS, UNLESS OTHERWISE
SPECIFIED.
REINFORCED CONCRETE NOTES

- ALL CONCRETE WORKS SHOWN ON THESE DRAWINGS SHALL BE DETAILED BASED ON THE RELATED
PARTS OF THE AMERICAN CODE (ACI 318M-14) .

- COMPRESSIVE STRENGTH OF STRUCTURAL CONCRETE AT 28 DAYS USING CYLINDER SAMPLES


SHALL BE f'c = 35 MPa.

- COMPRESSIVE STRENGTH OF LEAN CONCRETE AND MASS CONCRETE = 20MPa.

- ASTM TYPE-V (SULPHATE RESISTING CEMENT) FOR ALL CONCRETE EXPOSED TO EARTH.

- THE CLEAR CONCRETE COVER FOR THE DIFFERENT STRUCTURAL ELEMENTS SHALL COMPLY WITH
THOSE SPECIFIED IN THE CODES ABOVE AND NOT LESS THAN THE FOLLOWINGS:
a- FOR ALL CONCRETE IN CONTACT WITH SOIL, COVER SHALL BE 50mm,IF PROTECTED.
b- FOR ALL CONCRETE IN CONTACT WITH SOIL,COVER SHALL BE 75mm, IF UNPROTECTED.
c- FOR ABOVE GROUND CONCRETE MEMBERS,COVER SHALL BE :
*COLUMNS : 40mm
*BEAMS 200MM WIDTH :25mm
*BEAMS 300MM WIDTH :40mm
*SLABS AND WALLS :30mm
*WATER TANKS WALLS :40mm

- FOR SUPER STRUCTURAL ELEMENTS, ORDINARY PORTLAND CEMENT TYPE (1)


,WHILE FOR SUB - STRUCTURAL ELEMENTS, SULPHATE RESISTANCE TYPE (v) WAS
ASSUMED CONSIDERED UNLESS OTHERWISE SPECIFIED IN THE FINAL PROJECT SOIL REPORT.

- ADMIXTURES TO BE USED IN CONCRETE ARE SUBJECTED TO THE APPROVAL OF THE ENGINEER


AND AS PER THE PREVAILING CONDITIONS DURING CONCRETE CASTING.

B A B A - CURING OF CAST CONCRETE ELEMENTS SHALL BE AS PER SPECIFIED IN APPROVED CODES AND
PER THE ENGINEER RECOMMENDATIONS.
- ALL REINFORCED CONCRETE PARTS SHALL BE CONSTRUCTED USING FAIR FACE FORMS UNLESS
OTHERWISE DIFFERENTLY SPECIFIED BY ARCHITECTS.
2700
2700
- ALL MATERIALS AND CONCRETE PARTS SHALL BE SUBJECTED TO APPROVED TESTING AS PER
200 200
300 300 SPECIFIED IN LOCAL STANDARDS OR APPROVED INTERNATIONAL CODES UNLESS OTHERWISE
150 150
150 150 SPECIFIED IN THE PROJECT STANDARDS.THESE TESTS SHALL BE MONITORED AND APPROVED

150

150
BY THE ENGINEER
1 1

300

300
150

150
1 1

400

400
CP CP REINFORCING STEEL BARS NOTES
C1 C1
- ALL REINFORCING STEEL BARS IN ALL STRUCTURAL ELEMENTS (STRAIGHT BARS AND STIRRUPS)
ARE TO CONFORM TO ASTM A615 DEFORMED HIGH GRADE STEEL , G60 (fy - 60000 PSI - 420 MPa).
- SPLICE LENGTH, DEVELOPMENT LENGTHS BAR BENDING SPECIFICATIONS AND CUTOFF POINTS
OF STEEL BARS ARE TO COMPLY WITH THE REQUIREMENTS OF RELATED , ACI-318-04
OR APPROVED ADEQUATE.
- CONTRACTOR IS REQUIRED TO PREPARE AND SUBMIT SHOP DRAWINGS . THESE DRAWINGS
SHALL BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO ANY CONSTRUCTION WORKS.

5100

5100
5100

5100
- FOR BARS LOCATED IN WIDE CONCRETE STRUCTURES(RAFT FOUNDATIONS, SLABS...), SPLICES
(IF REQUIRED) ARE TO BE ARRANGED IN STAGGERED PATTERN.

Key Plan:
200 200
300 300
150 150
N
150 150

150
150
250
250

2 2

300

300
400
400

2 2 CP CP
C1 C1

GROUND TO ROOF COLUMN SCHEDULE ( 1/20 )


2700
2700

B A B A
C1 CP
GROUND FLOOR COLUMN PLAN ROOF Column PLAN
1 : 50 1 : 50

40

40
40 40

200
40 40

300

40
Client:

40
300
200 400
120
220

10 00
220

220

120
1
0

10 00
T10-L=880 mm

600
T10-L=880 mm

1
0
40

120 220
200

40 40
40

320
CP 300 200

10 00
220

220
100 100

1
T10-L=1280 mm

0
500
220
ROOF BEAM
Designer:
120

120

PB1
10 00

T10-L=880 mm 320
1
0

200

220 Al Taawun Commercial Building,


600

2T12mm - L =1445 mm

Office No.4 to 9, Al Taawun


VERTICAL STEEL BARS
400

1T10/75mm
HORIZENTAL STEEL BARS (TIES) 500 Othman Ben Affan Road, P.O Box
295246 Riyadh 11351, KSA
1145

Tel: +966 11 2399995| Fax:


500

500

+966 11 460 2981 OR +966 11


600

T12/100mm 300 2395400

2950
40

HORIZENTAL STEEL BARS (TIES)


40 40 Email:
300

[email protected]

2450
2T10/75mm
40

HORIZENTAL STEEL BARS (TIES)


4T14mm - L = 3800 mm

6T14mm - L = 3400 mm
817

VERTICAL STEEL BARS

VERTICAL STEEL BARS

400
10T14mm Consultant:
120 VERTICAL STEEL BARS
3500
10 00
220

220
1
0

T10-L=880 mm
120 Suite No. 419 Al Akaria Tower No.
2900

2T10/250mm
320 HORIZENTAL STEEL BARS (TIES) 2, Olaya St. Riyadh, Kingdom of
2450
10 00

Saudi Arabia P.O. Box 250092,


817
220

220
1

T10-L=1280 mm
0

Riyadh 12244
320

C1
600

GRAND BEAM
1000

2T10/75mm DAR International for Engineering Consultancy


817

HORIZENTAL STEEL BARS (TIES) P.O. Box #87236, Riyadh – 11642


Kingdom of Saudi Arabia
40 40

Contractor :
600

T12/100mm E-mail :[email protected]


HORIZENTAL STEEL BARS (TIES)
Phone :0531330505
Mail box :Riyadh 3321
Fax :0112937272
Address :Al Tameer Al Motakadima Company
Saudi Arabia - Riyadh

SECTION1 SECTION
1 1/25 1/25
IFC NUMBER DRAWING NAME REV
GS-002 GENERAL NOTES 1
SB-101 FOUNDATION PLAN COLUMN & AXIS PLAN 1
SF-301 STRUCTURAL SECTIONS & DETAILS 1

Project:

SEDRA 1A -G10 Garden COLLECTION


VILLAS
DRAWING Title:

COLUMN PLAN & SCHEDULE


B03 - GUARD HOUSE (MIRROR)

MOHAMED THARWAT AS SHOWN


MAIKEL NASHAAT 12/5/2024

TMC-G10-SD-CIV-A0-DWG-52-3