Column
Column
Column
- ALL DIMENSIONS SHOWN IN MILLIMETERS AND LEVELS ARE IN METERS, UNLESS OTHERWISE
SPECIFIED.
REINFORCED CONCRETE NOTES
- ALL CONCRETE WORKS SHOWN ON THESE DRAWINGS SHALL BE DETAILED BASED ON THE RELATED
PARTS OF THE AMERICAN CODE (ACI 318M-14) .
- ASTM TYPE-V (SULPHATE RESISTING CEMENT) FOR ALL CONCRETE EXPOSED TO EARTH.
- THE CLEAR CONCRETE COVER FOR THE DIFFERENT STRUCTURAL ELEMENTS SHALL COMPLY WITH
THOSE SPECIFIED IN THE CODES ABOVE AND NOT LESS THAN THE FOLLOWINGS:
a- FOR ALL CONCRETE IN CONTACT WITH SOIL, COVER SHALL BE 50mm,IF PROTECTED.
b- FOR ALL CONCRETE IN CONTACT WITH SOIL,COVER SHALL BE 75mm, IF UNPROTECTED.
c- FOR ABOVE GROUND CONCRETE MEMBERS,COVER SHALL BE :
*COLUMNS : 40mm
*BEAMS 200MM WIDTH :25mm
*BEAMS 300MM WIDTH :40mm
*SLABS AND WALLS :30mm
*WATER TANKS WALLS :40mm
B A B A - CURING OF CAST CONCRETE ELEMENTS SHALL BE AS PER SPECIFIED IN APPROVED CODES AND
PER THE ENGINEER RECOMMENDATIONS.
- ALL REINFORCED CONCRETE PARTS SHALL BE CONSTRUCTED USING FAIR FACE FORMS UNLESS
OTHERWISE DIFFERENTLY SPECIFIED BY ARCHITECTS.
2700
2700
- ALL MATERIALS AND CONCRETE PARTS SHALL BE SUBJECTED TO APPROVED TESTING AS PER
200 200
300 300 SPECIFIED IN LOCAL STANDARDS OR APPROVED INTERNATIONAL CODES UNLESS OTHERWISE
150 150
150 150 SPECIFIED IN THE PROJECT STANDARDS.THESE TESTS SHALL BE MONITORED AND APPROVED
150
150
BY THE ENGINEER
1 1
300
300
150
150
1 1
400
400
CP CP REINFORCING STEEL BARS NOTES
C1 C1
- ALL REINFORCING STEEL BARS IN ALL STRUCTURAL ELEMENTS (STRAIGHT BARS AND STIRRUPS)
ARE TO CONFORM TO ASTM A615 DEFORMED HIGH GRADE STEEL , G60 (fy - 60000 PSI - 420 MPa).
- SPLICE LENGTH, DEVELOPMENT LENGTHS BAR BENDING SPECIFICATIONS AND CUTOFF POINTS
OF STEEL BARS ARE TO COMPLY WITH THE REQUIREMENTS OF RELATED , ACI-318-04
OR APPROVED ADEQUATE.
- CONTRACTOR IS REQUIRED TO PREPARE AND SUBMIT SHOP DRAWINGS . THESE DRAWINGS
SHALL BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO ANY CONSTRUCTION WORKS.
5100
5100
5100
5100
- FOR BARS LOCATED IN WIDE CONCRETE STRUCTURES(RAFT FOUNDATIONS, SLABS...), SPLICES
(IF REQUIRED) ARE TO BE ARRANGED IN STAGGERED PATTERN.
Key Plan:
200 200
300 300
150 150
N
150 150
150
150
250
250
2 2
300
300
400
400
2 2 CP CP
C1 C1
B A B A
C1 CP
GROUND FLOOR COLUMN PLAN ROOF Column PLAN
1 : 50 1 : 50
40
40
40 40
200
40 40
300
40
Client:
40
300
200 400
120
220
10 00
220
220
120
1
0
10 00
T10-L=880 mm
600
T10-L=880 mm
1
0
40
120 220
200
40 40
40
320
CP 300 200
10 00
220
220
100 100
1
T10-L=1280 mm
0
500
220
ROOF BEAM
Designer:
120
120
PB1
10 00
T10-L=880 mm 320
1
0
200
2T12mm - L =1445 mm
1T10/75mm
HORIZENTAL STEEL BARS (TIES) 500 Othman Ben Affan Road, P.O Box
295246 Riyadh 11351, KSA
1145
500
2950
40
2450
2T10/75mm
40
6T14mm - L = 3400 mm
817
400
10T14mm Consultant:
120 VERTICAL STEEL BARS
3500
10 00
220
220
1
0
T10-L=880 mm
120 Suite No. 419 Al Akaria Tower No.
2900
2T10/250mm
320 HORIZENTAL STEEL BARS (TIES) 2, Olaya St. Riyadh, Kingdom of
2450
10 00
220
1
T10-L=1280 mm
0
Riyadh 12244
320
C1
600
GRAND BEAM
1000
Contractor :
600
SECTION1 SECTION
1 1/25 1/25
IFC NUMBER DRAWING NAME REV
GS-002 GENERAL NOTES 1
SB-101 FOUNDATION PLAN COLUMN & AXIS PLAN 1
SF-301 STRUCTURAL SECTIONS & DETAILS 1
Project:
TMC-G10-SD-CIV-A0-DWG-52-3