0% found this document useful (0 votes)
224 views1 page

Water Flow Switch Data Sheet.

The document describes a water flow detector that contains two switches actuated by a flow of 10 GPM or more. The detector is FM approved and UL listed for use on steel pipe in sizes from 50mm to 200mm. It provides dimensions, material specifications, and electrical ratings for the detector.

Uploaded by

Tanay Karmokar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
224 views1 page

Water Flow Switch Data Sheet.

The document describes a water flow detector that contains two switches actuated by a flow of 10 GPM or more. The detector is FM approved and UL listed for use on steel pipe in sizes from 50mm to 200mm. It provides dimensions, material specifications, and electrical ratings for the detector.

Uploaded by

Tanay Karmokar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Data Sheet 2.

20 FM
Issue A
Water Flow Detector
Fig. RDWFDR-2

Product Description
The Rapidrop Model RDWFDR-2 is a Vane type Waterflow detector
for use on wet sprinkler systems. It is FM Approved & UL Listed for
use on steel pipe. Available in sizes 50mm to 200m. The Vane insert
is non-corrosive and the enclosure is suitable for indoor or outdoor
use.
The waterflow detector switch contains two single pole, double
throw, snap action switches and an adjustable pneumatic retard.
The switches are actuated when a flow of 10 GPM (38 LPM) or more
occurs downstream of the device. This flow condition must exist for
a period of time long enough to overcome the selected retard
period.

Maximum Working Pressure


25 bar (365 psi)

Temperature Range
0°C to 68°C (32ºF to 154ºF)

Coating
Fusion Bonded Epoxy Coating in accordance with ANSI /AWWA C550

Electrical Ratings
125 / 250 VAC 5A 24/30 VDC 3A

Dimensions
Enclosure Rating
Size Hole
IP54 A B C D E
mm inch Dia.

DN50 2” 116 100 59.5 140 79.5 29


Material Specifications
DN65 2 1/2” 120 100 59.5 140 79.5 29
Part No. Description Material DN80 3” 145 100 59.5 140 80.9 51
1 Body ASTM A536 65-45-12 DN100 4” 185 100 59.5 140 98.5 51
2 Cover Aluminium Alloy DN125 5” 212 100 59.5 140 82.6 51
3 Gasket EPDM DN150 6” 254 100 59.5 140 90.4 51
4 Delay Device Plastic DN200 8” 298 100 59.5 140 90.5 51
5 Signal Connection N/A
6 Connection Plate Aluminium Alloy
SWITCH 1
7 Vane Plastic
NC
8 U-Bolts Carbon Steel Zinc Plated Fire Alarm Control COM End of Line Resistor
Panel Supervisory NO
9 Nuts Carbon Steel Zinc Plated Or Next Device
Circuit

GROUND
SWITCH 2
NC
COM
Voltage Source NO Audio Device

DS: 2.20 Rapidrop Global Ltd


Issue A T: +44 (0) 1733 847 510 F: +44 (0) 1733 553 958
22/12/2020 e: [email protected]
© 2020 Rapidrop w: www.rapidrop.com Page 1 of 1

Rapidrop Global Ltd reserves the right to change the design, materials and specifications without notice to continue product development