System Config: Operating Mode (Out of Service..Local or Remote) Local or Remote
System Config: Operating Mode (Out of Service..Local or Remote) Local or Remote
File :
SYSTEM CONFIG
System Frequency (50..60) 50Hz
Setting Dependencies (Disabled..Enabled) Enabled
Favourite Meters Timer (Off..60) 1min
Backlight timer (Off..60) 5min
Curr Set Display (xNom..Secondary) xNom
E/F Curr Set Display (xNom..Secondary) xNom
Select Grp Mode (Edge triggered..Level triggered)
Edge triggered
Clock Sync. From BI (Disabled..Minutes) Disabled
Operating Mode (Out Of Service..Local Or Remote)
Local Or Remote
Disk Activity Symbol (Disabled..Enabled) Disabled
Unexpected Restart Blocking (Disabled..Enabled) Disabled
Setting Password (Password) NONE
Control Password (Password) 340701675
Trip Alert (Disabled..Enabled) Disabled
General Alarm Alert (Disabled..Enabled) Enabled
Relay Identifier (16 Character String) 7SR11···········
Circuit Identifier (16 Character String) ················
CT/VT CONFIG
Phase Current Input (1..5) 5A
Phase CT Ratio Prim ( 6 Character String) 800···
Phase CT Ratio Sec (0.2..7) 5
Earth Current Input (1..5) 5A
Earth CT Ratio Prim ( 6 Character String) 800···
Earth CT Ratio Sec (0.2..7) 5
Phase Rotation (A,B,C..A,C,B) A,B,C
FUNCTION CONFIG
Gn Phase Overcurrent (Enabled..Disabled) Enabled
Gn Cold Load (Enabled..Disabled) Disabled
Gn Derived E/F (Enabled..Disabled) Enabled
Gn Sensitive E/F (Enabled..Disabled) Disabled
Gn Restricted E/F (Enabled..Disabled) Disabled
Gn NPS Overcurrent (Enabled..Disabled) Disabled
Gn Under Current (Enabled..Disabled) Disabled
Gn Thermal (Enabled..Disabled) Disabled
Gn CB Fail (Enabled..Disabled) Disabled
Gn CT Supervision (Enabled..Disabled) Disabled
Gn Broken Conductor (Enabled..Disabled) Disabled
Gn Trip Cct Supervision (Enabled..Disabled) Enabled
Gn Close Cct Supervis'n (Enabled..Disabled) Disabled
Gn Inrush Detector (Enabled..Disabled) Disabled
Gn CB Counters (Enabled..Disabled) Disabled
Gn I^2t CB Wear (Enabled..Disabled) Disabled
Gn Arc Flash Detector (Enabled..Disabled) Disabled
CURRENT PROT'N
PHASE OVERCURRENT
Gn 50 Measurement (RMS..Fundamental) RMS
Gn 51 Measurement (RMS..Fundamental) RMS
51-1
Gn 51-1 Element (Disabled..Enabled) Enabled
Gn 51-1 Setting (0.05..2.5) 0.2xIn
Gn 51-1 Char (DTL..ANSI-EI) IEC-NI
Gn 51-1 Time Mult (IEC/ANSI)(0.025..100) 0.2
Gn 51-1 Min Operate Time (0..20) 0s
Gn 51-1 Follower DTL (0..20) 0s
Gn 51-1 Reset ((IEC/ANSI) Decaying..60) 0s
51-2
Gn 51-2 Element (Disabled..Enabled) Disabled
50-1
Gn 50-1 Element (Disabled..Enabled) Enabled
Gn 50-1 Setting (0.05..50) 2xIn
Gn 50-1 Delay (0..14400) 0s
50-2
Gn 50-2 Element (Disabled..Enabled) Disabled
DERIVED E/F
51N-1
Gn 51N-1 Element (Disabled..Enabled) Enabled
Gn 51N-1 Setting (0.05..2.5) 0.1xIn
Gn 51N-1 Char (DTL..ANSI-EI) IEC-NI
Gn 51N-1 Time Mult (IEC/ANSI)
( 0.025..100) 0.175
Settings Editor Page 2 of 4