Examples Tutorials
Examples Tutorials
Protective device functional elements Protective Device Operation: Protective Devices and Characteristics - I
The protective system always measures certain system quantities, such as Any intentional time delays should be precise.
voltages and currents, and compares these system quantities, or some
• Selectivity: A relay system should provide maximum possible service
combination of these quantities, against a threshold setting that is computed
continuity with minimum system disconnection.
by the protection engineer and is set into the device
• Simplicity: Minimize protection equipment and circuitry.
If this comparison indicates an alert condition, a decision element is triggered
• Economy: Provide maximum protection at minimum cost.
3 4
Protection systems have 3 basic components:
1. Instrument transformers Any fault protective device must be selected with regard to three different
2. Protective Relays ratings: the voltage rating, the continuous (load) current rating, and the
3. Circuit breakers interrupting rating
5 6
Select the suitable rating of fuse for each load and incoming circuit using fuse
time-current characteristic in Figure (next-slide).
9 10
Solution
Fuse selection for each circuit
20kW
I lighting 27.8 A
3 415V
select 32 A fuse
30kW
I heating 41.7 A
3 415V
select 50 A fuse
11 12
• From the time-current curve, an 80A fuse would withstand 383A for only
6 seconds.
(3) Motor load:
• Therefore, for a 100A fuse, which would withstand 383A for longer than
Pout 30 kW 10 seconds, would be necessary.
Pin 32.6 kW
0.92 • To provide discrimination the fuse at incoming circuit must meet the
following requirements:
The motor full load current is • It must carry the normal load current:
32.6kW
I 27.8 41.7 54.7 124.2A
I motor 54.7 A
3 415V 0.83 • It must carry the load + the starting current of the motor
I 27.8 41.7 383 452.5A for 10 s
The starting current for 10 seconds is 7 time than the full load
• From time-current curve, a 125 A fuse would withstand 452.5 A for more
current, therefore
than 10 s.
I 7 54.7 383A
Power fuses are used at installations where the cost of an oil circuit breaker
and all of its associated equipment is not considered economical
13 14
• Detect system failures when they occur and isolate the faulted section • Electromagnetic Relays (EMRs)
from the remaining of the system. – Simplicity
– Not expensive
• Mitigating the effects of failures after they occur. Minimize risk of fire, – Mechanical Wear
danger to personal and other high voltage systems. • Solid-state Relays (SSRs)
– No Mechanical movements
– Faster than EMR
• Features of a digital relaying system:
– No sparking between contacts
1. Economics: cost effective
• Microprocessor-based Relay
2. Reliability: continuously active providing a high level of self-diagnosis.
– Much higher precision and more reliable and durable.
3. Flexibility: Revisions or modifications made necessary by changing – Improve the reliability and power quality of electrical power systems
operational conditions before, during and after faults occur.
4. System interaction: The availability of digital hardware that monitors – Capable of both digital and analog I/O.
continuously the system performance at remote substations. – Higher cost
17 18
Protective Devices Comparison (next lesson) Protective Devices and Characteristics –II (Circuit Breakers)
• Relays send signals to circuit breakers. Based the sending signals circuit On the other hand, a C.B. in a station serves exactly the same purpose but it
breakers will open/close. has many added and much more complex features
The basic construction of any circuit breaker requires the separation of
Fuses V.S. Relays contacts in an insulating fluid which serves two functions here:
• Relays have different settings and can be set based on protection (1) It extinguishes the arc drawn between the contacts when the C.B. opens
requirements.
(2) It provides adequate insulation between the contacts and from each
• Relays can be reset.
contact to earth
• Fuses only have one specific characteristic for a individual type.
Many insulating fluids are used for arc extinction and the fluid chosen depends
• Fuses cannot be reset but replaced if they blow.
upon the rating and type of C.B.
19 20
Initiation of the Arc: The separation of the C.B. contacts which are carrying Thus each emitted electron tends to create others and these in turn derive
current gives rise to an arc without changing much the current waveform energy from the field and multiply
Finally, if the current is high, the discharge attains the form of an arc having a
Initially when the contacts just begin to separate the magnitude of current is
temperature high enough for thermal ionization, which results in lower voltage
very large but the contact resistance being very small, a small voltage appears
gradient
across them
Thus an arc is initiated due to field effect and then maintained due to thermal
But the distance of separation being very very small, a large voltage gradient ionization
is set up which is good enough to cause ionization of the particles between the
Deionization: The arc consists of ionized particles of gases. This arc can be
contacts
interrupted if the contact gap could be deionized.
This high voltage gradient exists only for a fraction of a micro-second. This is the basic principle of arc interruption in all circuit breakers. The
• But in this short period a large number of electrons would have been process of deionization is possible in the following ways:
liberated from the cathode and these electrons while reaching anode, on (i) high pressure
their way would have collided with the atoms and molecules of the gases. (ii) forced convection and turbulence, and
(iii) arc splitting
21 22
• Unit type schemes protect a specific area of the system, i.e., a transformer,
transmission line, generator or busbar.
• The most obvious example of unit protection schemes is based on
Kerchief’s current law – the sum of the currents entering an area of the
system must be zero.
25
One line diagram of a system showing primary protection zones 26
Coordination of protective devices is the determination of graded settings to Assume that breaker K operates normally leaving the fault connected to the
achieve selectivity bus terminated by breakers IJM
Primary relays (primary sensitivity) are relays within a given protection Backup relays at locations I and M should be set to operate for the fault on
zone that should operate for prescribed abnormalities within that zone line JK, but only after a suitable delay that would allow breaker J to open
first, if possible
Example: Consider a fault on line JK.
For this condition, relays supervising breakers J and K should trip before any
Local backup relays are an alternate set of relays in a primary protection
others and these relays are called primary relays
zone that operate under prescribed conditions in that protection zone
Often such local backup relays are a duplicate set of primary relays set to
Backup relays are relays outside a given primary protection zone, located in
operate independently for the same conditions as the primary set
an adjacent zone, which are set to operate for prescribed abnormalities within
the given primary protection zone and independently of the primary relays
Example: Suppose a fault on line JK of Figure cannot be cleared by breaker J This constitutes an OR logic trip scheme and is an effective safeguard against
due to relay or breaker J malfunction relay failures
27 28
Example-2: Consider a Δ/Y-connected, 15-MVA, 33/11-kV transformer with Solution: The primary line current 15 x 10 6
Ip
differential protection applied, for the current transformer ratios shown. is given by 3 33 x10 262.43 A
3
Note that we multiply by √3 to obtain the values on the line side of the Δ-
connected C.T.'s. The relay current on normal load is therefore,
i r i p i s 4.37 3.41 0.9648 A
20MVA
Ip 349.91 A
3 33kV
20MVA
Is 1049.73 A
3 11kV
31 32
Apparatus Protection – II (partly)
The C.T. current on the primary side is thus [Bus-bar, transmission line, distance, feeder…]
5
i p 349.91 5.832 A
300
The C.T. current in the secondary side is
5
is 1049.73 A 3 4.545
2000
Note that we multiply by 3 to obtain the values on the line side of the Δ
connected C.T.’s. The relay current on normal load is therefore
ir is i p 5.832 4.545 1.287 A
33 34
Transmission Line Over-current Protection A simple radial system illustrates the point
For transmission line protection in interconnected systems, it is necessary to
provide the desired selectivity such that relay operation results in the least F
service interruption while isolating the fault
Time/current gradings are involved in three basic methods for radial or loop
circuits where there are several line sections in series
The shortcoming of the method is that the longest fault-clearing time is associated
with the sections closest to the source where the faults are most severe
37 Current grading for a Radial System 38
Solution:
Example-4: Consider the radial system shown. Calculate the fault currents
The system voltage is 11 kV;
for faults FA, FB, Fc, FD, and FE.
hence the fault current is given by,
Propose relay settings on the basis of current grading, assuming a 30 percent
V 11,00
relay error margin I
Xf Xf 3 where Xf is the reactance
from the source to the fault point
11,000
I FA 2189.95 A
2. 9 3
39 40
For fault FB we have, Since FD is very close to FC,
we conclude that
X FB 0.5 0.25 0.05 0.8
I FD I FC 8467.8 A
Thus, the fault current is
11,000
I FB 7938.57 A
0 .8 3
For a fault at E we have.
For a fault at C we have,
X FE 0.5
X FC 0.5 0.25 0.75
Thus,
Thus, the fault current is
11,000 11,000
I FC 8467.8 A I FE 12701.71A
0.75 3 0 .5 3
41 42
In practice, there would be variations in the source fault level that result
typically in a reduction of source apparent power by 50 percent 43 44
Solution: The following are the revised currents: Inverse-time overcurrent relaying: Each of the two methods considered so far
has a disadvantage
11,000 11 , 000
I FA 1867.90 A I FC I FD 5080 . 68 A
3.4 3 1 . 25 3 Therefore the inverse-time overcurrent relay method has evolved because of the
11,000 11 , 000 limitations imposed by the use of either current or time alone
I FB 4885.27 A I FE 6350 . 85 A
1.3 3 1 3 With this third method, the time of operation is inversely proportional to the fault
current, and actual characteristics are a function of both time and current settings
Relay 1 will still respond to faults FB and Fc. Relay 2 will not respond to any fault Some typical inverse-time
including FE. relay characteristics
• Relay type CO-7 is in
Note the presence of the transformer with X = 2.1 is the main reason for relay 1 to
common use
operate properly
Comparison of CO Curve
Current grading is therefore not a practical proposition to protect the circuit
Shapes
between breakers 2 and 1.
• However, when there is a significant impedance between the breakers, the
scheme is practical.
45 multiples of current tap (pickup)
A radial system There are two settings for this type of relay:
with time-graded 1. Pickup current is determined by adjusted current coil taps or current tap
inverse relays settings (C.T.S.). The pickup current is the current that causes the relay to
applied at breakers operate and close the contacts.
1, 2, and 3
2. Time dial refers to the reset position of the moving contact, and it varies the
Time-graded
time of operation at a given tap setting and current magnitude
inverse relaying
applied to a radial The time characteristics are plotted in terms of time versus multiples of
system current tap (pickup) settings, for a given time dial position
For faults close to the relaying points, the inverse-time over-current method
can achieve appreciable reductions in fault-clearance times
The operating time of the time-overcurrent relay varies with the current
magnitude. 47 48
Detailed characteristics of relay types (CO-7 and CO-8)
(a) CO-7 Time-delay overcurrent relay characteristics 49 (b) Type CO-8 Time-current curves 50