Product Data Sheet Rosemount 3144p Temperature Transmitter en 73128
Product Data Sheet Rosemount 3144p Temperature Transmitter en 73128
Product Data Sheet Rosemount 3144p Temperature Transmitter en 73128
00813-0100-4021, Rev TB
May 2022
For every responsibility you have, you are confronted with a number of challenges. You have aggressive
production and quality targets, but inaccurate or unavailable temperature measurements create
unscheduled downtime and products that don't meet specifications. You may be manually running loops,
because you don’t trust your temperature measurement; this requires the attention of your maintenance
staff and cost money in lost production. Additionally, it is difficult to improve safety and comply with
government and company regulations when you don’t have the information or tools needed to prove your
compliance.
Companies are coming to Emerson because they know they need reliable measurements and visibility into
their temperature measurements in order to address these challenges and achieve their business
objectives. With the Rosemount 3144P Transmitter, you gain greater visibility into your temperature
processe, so you can improve safety, comply with regulations, make the most of your limited resources,
and reach your production and quality targets. By leveraging Rosemount X-well Technology, advanced
diagnostic capabilities, and the unparalleled reliability and accuracy of the transmitter, you can minimize
off-spec product, reduce maintenance and downtime, improve the usage of your limited resources, and
meet regulatory demands.
Rosemount 3144P May 2022
™
Complete Point Solution for accurately measuring process temperature in
monitoring applications without the requirement of a thermowell or process
penetration
■ Simplify temperature measurement point specification, installation, and
maintenance and eliminate possible leak points.
■ Calculate a repeatable and accurate process temperature measurement with an
in-transmitter thermal conductivity algorithm.
■ Measure pipe surface and ambient temperature and use the thermal conductivity
properties of the installation and process piping in order to provide an accurate
process measurement.
Contents
Features and benefits........................................................................................................................................................................ 2
Ordering information........................................................................................................................................................................ 5
How to order Rosemount X-well Technology...................................................................................................................................12
Specifications.................................................................................................................................................................................. 13
Product certifications...................................................................................................................................................................... 26
Dimensional drawings..................................................................................................................................................................... 35
2 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Emerson.com/Rosemount 3
Rosemount 3144P May 2022
Looking for a wireless temperature solution? For wireless applications that require superior performance and unmatched reliability,
consider the Rosemount 648 Wireless Temperature Transmitter.
4 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Ordering information
The industry-leading Rosemount 3144P Single Point Temperature
Transmitter delivers unmatched field reliability and innovative process
measurement solutions and diagnostics.
Transmitter features include:
■ Temperature measurement assembly with Rosemount X-well
Technology (option code PT)
■ Dual and single sensor input capabilities
■ Transmitter-sensor matching (option code C2)
■ Integral transient protector (option code T1)
■ IEC 61508 Safety Certificate of Compliance (option code QT)
■ Advanced sensor and process diagnostics (option codes D01 and
DA1)
■ Large, easy to read LCD display (option code M5)
■ “Assemble to Sensor” option (option code XA)
Model codes
Model codes contain the details related to each product. Exact model codes will vary; an example of a typical model code is shown
in Figure 1.
Figure 1: Model code example
Emerson.com/Rosemount 5
Rosemount 3144P May 2022
Model
Code Description
3144P Temperature transmitter ★
Housing style
Transmitter output
Code Description
A 4—20 mA with digital signal based on HART® Protocol ★
F FOUNDATION™ Fieldbus digital signal (includes three analog input function block and backup link active scheduler) ★
Measurement configuration
Code Description
1 Single-sensor input ★
2 Dual-sensor input ★
6 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Product certification
Code Description
NA No approval ★
E5 USA explosion proof, dust ignition proof, and non-incendive ★
I5(1) USA intrinsically safe (IS) and non-incendive (includes standard IS and FISCO for Fieldbus units) ★
K5(1) USA IS, non-incendive, and explosion-proof combination (includes standard IS and FISCO for Fieldbus units) ★
KB(1) USA and Canada IS, explosion-proof, and non-incendive combination (includes standard IS and FISCO for Fieldbus ★
units)
I6(1) Canada IS/FISCO, and Division 2 (includes standard IS and FISCO for Fieldbus units) ★
K6(1) Canada IS, FISCO Division 2, and explosion-proof combination (includes standard IS, FISCO for Fieldbus units) ★
E1 ATEX flameproof approval ★
N1 ATEX type n approval ★
I1(1) ATEX intrinsic safety approval (includes standard IS and FISCO for Fieldbus units) ★
K1(1) ATEX IS, flameproof, dust ignition-proof and type n combination (includes standard IS and FISCO for Fieldbus units) ★
ND ATEX dust ignition-proof approval ★
KA(1) ATEX/Canada intrinsic safety, explosion-proof combination (includes standard IS and FISCO for Fieldbus units) ★
E7 IECEx flameproof approval ★
N7 IECEx Type 'n' approval ★
I7(1)(2) IECEx intrinsic safety ★
K7(1)(2) IECEx intrinsic safety, flameproof, dust ignition-proof and type n combination ★
E2(2) Brazil flameproof ★
I2(2) Brazil intrinsic safety ★
E4(2) Japan flameproof approval ★
E3(2) China flameproof approval ★
I3(1)(2) China intrinsic safety ★
N3 China type n ★
KM Technical Regulations Customs Union (EAC) flameproof, intrinsic safety ★
IM Technical Regulations Customs Union (EAC) intrinsic safety ★
EM Technical Regulations Customs Union (EAC) flameproof ★
(1) When IS approval is ordered on a FOUNDATION® Fieldbus, both standard IS and FISCO IS approvals apply. The device label is marked appropriately.
(2) Consult factory for availability when ordering with HART® or FOUNDATION Fieldbus models.
Additional options
Code Description
A01 FOUNDATION™ Fieldbus advanced control function block suite ★
Emerson.com/Rosemount 7
Rosemount 3144P May 2022
Code Description
D01 FOUNDATION™ Fieldbus sensor and process diagnostic suite: thermocouple diagnostic, minimum/maximum tracking ★
DA1 HART™ sensor and process diagnostic suite: thermocouple diagnostic, minimum/maximum tracking ★
Enhanced performance
Code Description
PT(1) Temperature measurement assembly with Rosemount X-well Technology ★
P8(2) Enhanced transmitter accuracy ★
(1) Not available with FOUNDATION Fieldbus models.
(2) Enhanced accuracy only applies to RTDs; however the option can be ordered with any sensor type.
Mounting bracket
Code Description
B4 “U” mounting bracket for 2-in. pipe mounting - all SST ★
B5 “L” mounting bracket for 2-in. pipe or panel mounting - all SST ★
BH "L" mounting bracket for 2-in pipe or panel mounting - 316 SST ★
Display
Code Description
M5 LCD display ★
External ground
Code Description
G1 External ground lug assembly ★
Transient protector
Code Description
T1 Integral transient protector ★
Software configuration
Code Description
C1 Custom configuration of date, descriptor, and message (requires Configuration Data Sheet with order) ★
8 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Line filter
Not available with FOUNDATION Fieldbus models.
Code Description
F5 50 Hz line voltage filter ★
Code Description
A1 NAMUR alarm and saturation levels, high alarm ★
CN NAMUR alarm and saturation levels, low alarm ★
Low alarm
Code Description
C8 Low alarm (standard Rosemount alarm and saturation values) ★
Sensor trim
Code Description
C2 Transmitter-sensor matching – trim to PT100 RTD calibration schedule (Callendar-Van Dusen constants) ★
C7 Trim to non-standard sensor (special sensor–customer must provide sensor information)
Five-point calibration
Code Description
C4 5-point calibration (requires the Q4 option code to generate a calibration certificate) ★
Calibration certification
Code Description
Q4 Calibration certificate (3-point calibration) ★
QG Calibration certificate and GOST verification certificate ★
QP Calibration certificate and tamper evident seal ★
Code Description
U1 Hot Backup™ ★
U2(1) Average temperature with Hot Backup and sensor drift alert – warning mode ★
U3(1) Average temperature with Hot Backup and sensor drift alert – alarm mode ★
Emerson.com/Rosemount 9
Rosemount 3144P May 2022
Code Description
U5 Differential temperature ★
U6 Average temperature ★
U7 First good temperature ★
U4 Two independent sensors
(1) Not available with FOUNDATION™ Fieldbus models.
Custody transfer
Not available with FOUNDATION™ Fieldbus models.
Code Description
D3 Custody transfer approval (Canada)
D4 MID custody transfer (Europe)
Cold temperature
Code Description
BR6 -76 °F (-60 °C) cold temperature operation ★
Code Description
GE M12, 4-pin, male connector (eurofast®) ★
GM A size mini, 4-pin, male connector (minifast®) ★
Code Description
HR7 Configured for HART Revision 7 ★
Assemble to option
Code Description
XA Sensor specified separately and assembled to transmitter ★
10 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Emerson.com/Rosemount 11
Rosemount 3144P May 2022
Code Description
D1-D4 Aluminum field mount housing
PT Temperature measurement assembled with Rosemount X-well Technology
A 4–20 mA with digital signal based on HART™ Protocol
XA Sensor specified separately and assembled to transmitter
C1 Custom configuration of date, descriptor, message, and wireless parameters (requires Configuration Data Sheet with
order)
HR7 Configured for HART Revision 7
Table 2: Rosemount 0085 Pipe Clamp Sensor option code requirements for use with X-well Technology
Code Description
N No connection head
3 Sensor connection
P1 Sensor type
J Extension type
0080 Extension length
XA Assemble sensor to specific temperature transmitter
Rosemount X-well assemblies are available in most Rosemount 0085 Pipe Clamp Sensor diameter sizes.
12 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Specifications
® ™
HART and FOUNDATION Fieldbus
Functional specifications
Inputs
User-selectable. See Table 3 for sensor options.
Output
Two-wire device with either 4–20 mA/HART®, linear with temperature or input, or completely digital output with FOUNDATION™
Fieldbus Communication (ITK 6.0.1 compliant).
Isolation
Input/output isolation specified to 500 Vdc (500 Vrms 707 V peak) at 50/60 Hz.
Humidity limits
0–99 percent relative humidity, non-condensing
Update time
Approximately 0.5 seconds for a single sensor (one second for dual sensors).
Physical specifications
Material selection
Emerson provides a variety of Rosemount products with various product options and configurations, including materials of
construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented
is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser’s sole responsibility
to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives,
contaminants, etc.), when specifying product, materials, options, and components for the particular application. Emerson is not in
a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options,
configuration, or materials of construction selected.
Conformance to specification (±3σ [Sigma])
Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at
least ±3σ.
Conduit connections
The standard field mount housing has ½–14-in. NPT conduit entries. Additional conduit entry types are available, including PG13.5
(PG11), M20 3 1.5 (CM20), or JIS G ½. When any of these additional entry types are ordered, adapters are placed in the standard
field housing so these alternative conduit types fit correctly.
Materials of construction
Mounting specification
Transmitters may be attached directly to the sensor. Optional mounting brackets (codes B4 and B5) allow for remote mounting.
See Figure 6.
Emerson.com/Rosemount 13
Rosemount 3144P May 2022
Transmitter weight
Enclosure ratings
Type 4X
IP66 and IP68
Stability
RTDs: ±0.1 percent of reading or 0.1 °C (0.18 °F), whichever is greater, for two years for RTDs.
Thermocouples: ±0.1 percent of reading or 0.1 °C (0.18 °F), whichever is greater, for one year for thermocouples.
Five-year stability
RTDs: ±0.25% of reading or 0.25 °C, whichever is greater, for five years.
Thermocouples: ±0.5% of reading or 0.5 °C, whichever is greater, for five years.
Vibration effect
Tested to the following with no effect on performance per IEC 60770-1, 1999:
Frequency Vibration
10 to 60 Hz 0.21 mm displacement
60 to 2000 Hz 3 g peak acceleration
Self calibration
The analog-to-digital measurement circuitry automatically self-calibrates for each temperature update by comparing the dynamic
measurement to extremely stable and accurate internal reference elements.
Radio frequency interference (RFI) effect
Worst case RFI effect is equivalent to the transmitter’s nominal accuracy specification, according to , when tested in accordance
with IEC 61000-4-3, 30 V/m (HART®)/20 V/m (HART thermocouple (T/C)) /10 V/m (FOUNDATION Fieldbus), 80 to 1000 MHz, with
unshielded cable.
Electromagnetic compatibility (EMC)
Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation <1% span during EMC
disturbance.
Note
During surge event, device may exceed maximum EMC deviation limit; however, device will self-recover and return to normal
operation within specified start-up time.
14 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Hardware tag
■ No charge
■ Two lines of 28 characters (56 characters total)
■ Tags are stainless steel
■ Permanently attached to transmitter
■ Character height is 1/16-in. (1.6 mm)
■ A wire-on tag is available upon request. Five lines of 12 characters (60 characters total)
Software tag
■ HART® transmitter can store up to eight characters in HART 5 mode and 32 characters in HART 7 mode. FOUNDATION Fieldbus
transmitters can store up to 32 characters.
■ Can be ordered with different software and hardware tags.
■ If no software tag characters are specified, the first eight characters of the hardware tag are the default.
Transmitter accuracy
Table 3: Transmitter accuracy
Sensor options Sensor Input ranges Minimum span(1) Digital accuracy(2) Enhanced D/A
reference accuracy(3) accuracy
(4)(5)
Emerson.com/Rosemount 15
Rosemount 3144P May 2022
Sensor options Sensor Input ranges Minimum span(1) Digital accuracy(2) Enhanced D/A
reference accuracy(3) accuracy
(4)(5)
16 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Sensor options Sensor Input ranges Minimum span(1) Digital accuracy(2) Enhanced D/A
reference accuracy(3) accuracy
(4)(5)
DIN Type U DIN 43710 –200 to –328 to 25 45 ± 0.35 ± 0.63 N/A ±0.02% of
600 1112 span
Type W5Re/ ASTM E 988-96 0 to 32 to 25 45 ± 0.70 ± 1.26 N/A ±0.02% of
W26Re 2000 3632 span
GOST Type L GOST R –200 to –392 to 25 45 ± 0.25 ± 0.45 N/A ±0.02% of
8.585–2001 800 1472 span
Differential capability exists between any two sensor types (dual-sensor option)
For all differential configurations, the input range is X to Y where:
■ X = Sensor 1 minimum – Sensor 2 maximum and
■ Y = Sensor 1 maximum – Sensor 2 minimum
Digital accuracy for differential configurations (dual-sensor option, HART Protocol only)
■ Sensor types are similar (e.g., both RTDs or both thermocouples (T/Cs)): Digital accuracy = 1.5 times worst case accuracy of
either sensor type
■ Sensor types are dissimilar (e.g., one RTD, one T/C): Digital accuracy = Sensor 1 accuracy + Sensor 2 accuracy
Sensor options Sensor reference Effect per 1.0 °C (1.8 °F) Input temperature (T) D/A effect(3)
change in ambient(1)(2)
2-, 3-, or 4-wire RTDs
Pt 100 (α = 0.00385) IEC 751 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Emerson.com/Rosemount 17
Rosemount 3144P May 2022
Sensor options Sensor reference Effect per 1.0 °C (1.8 °F) Input temperature (T) D/A effect(3)
change in ambient(1)(2)
Rosemount X-well Pt IEC 751 0.0058 °C (0.0104 °F) Entire sensor input 0.001% of span
100 (α = 0.00385) range
Pt 200 (α = 0.00385) IEC 751 0.0023 °C (0.00414 °F) Entire sensor input 0.001% of span
range
Pt 500 (α = 0.00385) IEC 751 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Pt 1000 (α = 0.00385) IEC 751 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Pt 100 (α = 0.003916) JIS 1604 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Pt 200 (α = 0.003916) JIS 1604 0.0023 °C (0.00414 °F) Entire sensor input 0.001% of span
range
Ni 120 Edison curve no. 7 0.0010 °C (0.0018 °F) Entire sensor input 0.001% of span
range
Cu 10 Edison copper winding 0.015 °C (0.0027 °F) Entire sensor input 0.001% of span
no. 15 range
Pt 50 (α = 0.00391) GOST 6651-94 0.003 °C (0.0054 °F) Entire sensor input 0.001% of span
range
Pt 100 (α = 0.00391) GOST 6651-94 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Cu 50 (α = 0.00426) GOST 6651-94 0.003 °C (0.0054 °F) Entire sensor input 0.001% of span
range
Cu 50 (α = 0.00428) GOST 6651-94 0.003 °C (0.0054 °F) Entire sensor input 0.001% of span
range
Cu 100 (α = 0.00426) GOST 6651-94 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Cu 100 (α = 0.00428) GOST 6651-94 0.0015 °C (0.0027 °F) Entire sensor input 0.001% of span
range
Thermocouples
Type B NIST monograph 175, 0.014 °C T ≥ 1000 °C 0.001% of span
IEC 584 0.029 °C – 0.0021% of (T 300 °C ≤ T < 1000 °C
– 300) 100 °C ≤ T < 300 °C
0.046 °C – 0.0086% of (T
– 100)
Type E NIST monograph 175, 0.004 °C + 0.00043% of N/A 0.001% of span
IEC 584 T
Type J NIST monograph 175, 0.004 °C + 0.00029% of T ≥ 0 °C 0.001% of span
IEC 584 T T < 0 °C
0.004 °C + 0.0020% of
abs. val. T
18 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Sensor options Sensor reference Effect per 1.0 °C (1.8 °F) Input temperature (T) D/A effect(3)
change in ambient(1)(2)
Type K NIST monograph 175, 0.005 °C + 0.00054% of T ≥ 0 °C 0.001% of span
IEC 584 T T < 0 °C
0.005 °C + 0.0020% of
abs. val. T
Type N NIST monograph 175, 0.005 °C + 0.00036% of All 0.001% of span
IEC 584 T
Type R NIST monograph 175, 0.015 °C T ≥ 200 °C 0.001% of span
IEC 584 0.021 °C – 0.0032% of T T < 200 °C
Type S NIST monograph 175, 0.015 °C T ≥ 200 °C 0.001% of span
IEC 584 0.021 °C – 0.0032% of T T < 200 °C
Type T NIST monograph 175, 0.005 °C T ≥ 0 °C 0.001% of span
IEC 584 0.005 °C + 0.0036% of T < 0 °C
abs. val. T
DIN Type L DIN 43710 0.0054 °C + 0.00029% of T ≥ 0 °C 0.001% of span
R T < 0 °C
0.0054 °C + 0.0025% of
abs. val. T
DIN Type U DIN 43710 0.0064 °C T ≥ 0 °C 0.001% of span
0.0064 °C + 0.0043% of T < 0 °C
abs. val. T
Type W5Re/W26Re ASTM E 988-96 0.016 °C T ≥ 200 °C 0.001% of span
0.023 °C + 0.0036% of T T < 200 °C
GOST Type L GOST R 8.585–2001 0.005 > 0 °C N/A 0.001% of span
0.005 - 0.003% < 0 °C
Other input types
Millivolt Input 0.00025 mV Entire sensor input 0.001% of span
range
2-, 3-, 4-wire Ohm Input 0.007 Ω Entire sensor input 0.001% of span
range
(1) Change in ambient is in reference to the calibration temperature of the transmitter (20 °C [68 °F]).
(2) Ambient temperature effect specification valid over minimum temperature span of 28 °C (50 °F).
(3) Applies to HART/4–20 mA devices.
Sensor option Sensor reference Effects per 1.0 °C(1.8 °F) Input temperature (T)
difference in ambient and
process temperature(1)
Rosemount X-well Pt 100 (α = IEC 751 ± 0.01 °C (0.018 °F) Entire sensor input range
0.00385)
(1) Valid under steady state process and ambient conditions.
Emerson.com/Rosemount 19
Rosemount 3144P May 2022
®
HART /4-20 mA specifications
Power supply
External power supply required. Transmitters operate on 12.0 to 42.4 Vdc transmitter terminal voltage (with 250 ohm load, 18.1
Vdc power supply voltage is required). Transmitter power terminals rated to 42.4 Vdc.
20 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Wiring diagram
See Figure 8.
Alarms
Custom factory configurations of alarm and saturation levels are available for valid values with option code C1. These values can
also be configured in the field using a Field Communicator.
Local display
Optional five-digit LCD display includes 0–100% bar graph. Digits are 0.4 inches (8 mm) high. Display options include engineering
units (°F, °C, °R, K, ohms, and millivolts), percent, and milliamperes. The display can also be set to alternate between engineering
units/milliamperes, Sensor 1/Sensor 2, Sensor 1/Sensor 2/Differential Temperature, and Sensor 1/Sensor2/Average Temperature.
All display options, including the decimal point, may be reconfigured in the field using a Field Communicator or AMS Device
Manager.
Turn-on time
Performance within specifications is achieved less than six seconds after power is applied to the transmitter when the damping
value is set to zero seconds.
Temperature limits
Table 6: Temperature limits
Emerson.com/Rosemount 21
Rosemount 3144P May 2022
Failure mode
The Rosemount 3144P features software and hardware failure mode detection. An independent circuit is designed to provide
backup alarm output if the microprocessor hardware or software fails.
The alarm level is user-selectable using the failure mode switch. If failure occurs, the position of the hardware switch determines
the direction in which the output is driven (HIGH or LOW). The switch feeds into the digital-to-analog (D/A) converter, which drives
the proper alarm output even if the microprocessor fails. The values at which the transmitter drives its output in failure mode
depends on whether it is configured to standard, or NAMUR-compliant (NAMUR recommendation NE 43) operation. The values for
standard and NAMUR-compliant operation are as follows:
Table 7: Operation parameters
Standard(1) NAMUR-compliant(1)
Linear output 3.9 ≤ I ≤ 20.5 3.8 ≤ I ≤ 20.5
Fail high 21 ≤ I ≤ 23 (default) 21.5 ≤ I ≤ 23 (default)
Fail low I ≤ 3.75 I ≤ 3.6
(1) Measured in milliamperes.
Load limitations
Maximum load = 40.8 x (Supply voltage - 12.0) without transient protection (optional).
Note
HART communication requires a loop resistance between 250 and 1100 ohms. Do not communicate with the transmitter when
power is below 12 Vdc at the transmitter terminals.
22 Emerson.com/Rosemount
May 2022 Rosemount 3144P
™
FOUNDATION Fieldbus specifications
Power supply
Powered over FOUNDATION Fieldbus with standard Fieldbus power supplies. Transmitters operate on 9.0 to 32.0 Vdc, 12 mA
maximum. Transmitter power terminals are rated to 42.4 Vdc.
Wiring diagram
See Figure 9.
Alarm
The AI function block allows the user to configure the alarms to HIGH-HIGH, HIGH, LOW, or LOW-LOW with a variety of priority
levels and hysteresis settings.
Local display
Displays all DS_65 measurements in the transducer and function blocks including Sensor 1, Sensor 2, differential, and terminal
temperatures. The display alternates up to four selected items. The meter can display up to five digits in engineering units (°F, °C,
°R, K, Ω, and millivolts). Display settings are configured at the factory according to the transmitter configuration (standard or
custom). These settings can be reconfigured in the field using a Field Communicator or DeltaV. In addition, the LCD display
provides the ability to display DS_65 parameters from other devices. In addition to the configuration of the meter, sensor
diagnostic data is displayed. If the measurement status is Good, the measured value is shown. If the measurement status is
Uncertain, the status indicating uncertain is shown in addition to the measured value. If the measurement status is Bad, the reason
for the bad measurement is shown.
Note
When ordering a spare electronics module assembly, the LCD display transducer block will display the default parameter.
Emerson.com/Rosemount 23
Rosemount 3144P May 2022
Turn-on time
Performance within specifications is achieved less than 20 seconds after power is applied to the transmitter when the damping
value is set to zero seconds.
Status
The device is compliant to NAMUR NE 107, ensuring consistent, reliable, and standardized device diagnostic information.
The new standard is designed to improve the way device status and diagnostic information is communicated to operators and
maintenance personnel in order to increase productivity and reduce costs.
If self-diagnostics detect a sensor burnout or a transmitter failure, the status of the measurement will be updated accordingly. The
status may also send the PID output to a safe value.
Function blocks
■ All blocks will ship with unique block names, e.g. AI_1400_XXXX.
■ All blocks shall be instantiated to avoid invalid defaults.
■ All Rosemount 3144P FOUNDATION Fieldbus have parameter COMPATIBILITY_REV for backward compatibility.
■ Parameters will be initialized to common values for easier bench configuration.
■ All default block tags are less than or equal to 16 characters in length to avoid inconvenience of apparently identical tags.
■ Default block tags include underscores, “_”, instead of whitespaces for easier configuration.
Resource block
■ Contains physical transmitter information including available memory, manufacture identification, device type, software tag,
and unique identification.
■ Plantweb™ Alerts enable the full power of the PW digital architecture by diagnosing instrumentation issues, communicating the
details, and recommending a solution.
Transducer block
■ Contains the actual temperature measurement data, including sensor 1, sensor 2, and terminal temperature.
■ Includes information about sensor type and configuration, engineering units, linearization, range, damping, and diagnostics.
■ Device Revision 3 and above includes Hot Backup functionality in the transducer block.
24 Emerson.com/Rosemount
May 2022 Rosemount 3144P
■ All devices ship with the AI blocks scheduled, meaning no configuration is needed if the factory default channels are used.
Emerson.com/Rosemount 25
Rosemount 3144P May 2022
Product certifications
Rev 2.15
North America
26 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Europe
E1 ATEX flameproof
Certificate DEKRA 19ATEX0076 X
Standards
EN IEC 60079-0: 2018, EN 60079-1: 2014
Process temperature range at sensor Ambient temperature range (°C) Temperature class
connection(1) (°C).
-60 °C to +70 °C -60 °C to +70 °C T6
-60 °C to +80 °C -60 °C to +80 °C T5…T1
(1) Sensor connection is where the sensor threads into the transmitter or junction box housing
Emerson.com/Rosemount 27
Rosemount 3144P May 2022
N1 ATEX Type n
Certificate BAS01ATEX3432X [HART]; Baseefa03ATEX0709X [Fieldbus]
Standards EN IEC 60079-0:2018, EN 60079-15:2010
Markings
HART: II 3 G Ex nA IIC T5/T6 Gc; T6(-40 °C ≤ Ta ≤ +50 °C), T5(-40 °C ≤ Ta ≤ +75 °C);
ND ATEX dust
Certificate DEKRA 19ATEX0076 X
Standards EN IEC 60079-0:2018, EN 60079-31:2014
Markings
II 2 D Ex tb IIIC T130 °C Db, (-60 °C ≤ Ta ≤ +80 °C)
Process temperature range at sensor Ambient temperature range (°C) Maximum surface temperature “T”
connection(1) (°C).
-60 °C to +80 °C -60 °C to +80 °C T130 °C
(1) Sensor connection is where the sensor threads into the transmitter or junction box housing
International
E7 IECEx flameproof
Certificate IECEx FMG 12.0022X
Standards IEC 60079-0:2011, IEC 60079-1:2014-06
Markings Ex db IIC T6…T1 Gb, T6(-50 °C ≤ Ta ≤ +40 °C), T5…T1(-50 °C ≤ Ta ≤ +60 °C)
See Process temperature limits for process temperatures.
28 Emerson.com/Rosemount
May 2022 Rosemount 3144P
IECEx Dust
Emerson.com/Rosemount 29
Rosemount 3144P May 2022
N7 IECEx Type n
Certificate IECEx BAS 07.0003X [HART®]; IECEx BAS 07.0005X [Fieldbus]
Standards IEC 60079-0:2017, IEC 60079-15:2010
Markings HART: Ex nA IIC T5/T6 Gc; T6(-40 °C ≤ Ta ≤ +50 °C), T5(-40 °C ≤ Ta ≤ +75 °C);
Fieldbus: Ex nA IIC T5 Gc; T5(-40 °C ≤ Ta ≤ +75 °C);
Brazil
30 Emerson.com/Rosemount
May 2022 Rosemount 3144P
China
E3 China flameproof
Certificate GYJ21.1277X
Standards GB3836.1-2010, GB3836.2-2010
Markings Ex d IIC T6~T1 Gb
N3 China Type n
Certificate GYJ20.1086X [Fieldbus]; GYJ20.1091X [HART®]
Standards GB3836.1-2010, GB3836.8-2014
Markings Ex nA IIC T5 Gc [Fieldbus]; Ex nA IIC T5/T6 Gc [HART]
Emerson.com/Rosemount 31
Rosemount 3144P May 2022
KM Technical Regulation Customs Union (EAC) flameproof, intrinsic safety, and dust
Standards GOST 31610.0-2014, GOST IEC 60079-1-2013, GOST IEC 60079-11-2014, GOST IEC 60079-31-2013
Markings Ex tb IIIC T130 °C Db X (-40 °C ≤ Ta ≤ +70 °C), IP66 in addition to markings listed for EM and IM above.
Japan
E4 Japan flameproof
Certificate CML 17JPN1316X
Markings Ex db IIC T6…T1 Gb; T6 (-50 °C ≤ Ta ≤ +40 °C); T5...T1 (-50 °C ≤ Ta ≤ +60 °C)
Korea
EP Korea flameproof
Certificate 10-KB4BO-0011X (flameproof), 17-KA4BO-0356X (dust)
Markings Ex db IIC Gb T6…T1; T6(-40 °C ≤ Tamb ≤ +40 °C), T5(-40 °C ≤ Tamb ≤ +60 °C)
Ex tb IIIC T130 °C Db
32 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Combinations
K1 Combination of E1, I1, N1, and ND
K2 Combination of E2 and I2
K5 Combination of E5 and I5
KB Combination of K5, I6, and K6
KP Combination of EP and IP
Tables
Process temperature limits
Table 8: Sensor only (no transmitter installed)
Table 9: Transmitter
Adhering to the process temperature limitations of Table 10 will ensure that the service temperature limitations of the LCD display
cover are not exceeded. Process temperatures may exceed the limits defined in Table 10 if the temperature of the LCD display
cover is verified to not exceed the service temperatures in Table 10 and the process temperatures do not exceed the values
specified in Table 9.
Emerson.com/Rosemount 33
Rosemount 3144P May 2022
Entity parameters
Table 11: Entity parameters
Additional certifications
SBS American Bureau of Shipping (ABS) type approval
Certificate 21-2097596-PDA
Intended use Measurement of temperature for marine and offshore applications
Certificate 23154
Requirements Bureau Veritas rules for the classification of steel ships
Application Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS; temperature transmitter type 3144P cannot be
installed on diesel engines.
Certificate TAA00001JK
Intended use Det Norske Veritas’ rules for classification of ships, high speed, and light craft and Det Norske Veritas' offshore
standards
Application Table 12: Location classes
Temperature D
Humidity B
Vibration A
34 Emerson.com/Rosemount
May 2022 Rosemount 3144P
EMC A
Enclosure D
Certificate LR21173788TA
Application Environmental categories ENV1, ENV2, ENV3, and ENV5
Dimensional drawings
Figure 2: Transmitter exploded view
F
E
Emerson.com/Rosemount 35
Rosemount 3144P May 2022
4.37-
in.(110,9 m m )
4.40-
in.(111,8 m m )
A. Switches(1)
B. LCD display connector
Dimensions are in inches (millimeters).
Figure 4: Transmitter view
B 5.12-in.
A (129,9 mm) with
LCD display
4.33-in.
(110 mm)
C
1.93-in.
(49,0 mm)
A
3/8-16 UN-2B
A. Conduit entry
B. Display cover
C. Name plate
Dimensions are in inches (millimeters).
(1) Alarm and write protect (HART®), simulate and write protect (FOUNDATION™ Fieldbus).
36 Emerson.com/Rosemount
May 2022 Rosemount 3144P
4.37-in.
(110,0 mm)
1.93-in.
(49,0 mm) 3/8–16
UN–2B
Emerson.com/Rosemount 37
Rosemount 3144P May 2022
1.00 (25,4)
2.31 (58,7)
4.62 (117,2)
4.00 (101,5)
2.00 (51)
3/8-16 bolt
A
4.80 (121,9)
3/8-16 bolt
ØD
38 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Figure 8: HART/4-20 mA
Two-wire RTD and Three-wire RTD and Four-wire RTD and Thermocouples and RTD with compensation
Ohms Ohms(1) Ohms millivolts loop(2)
Rosemount 3144P dual-sensor connections
ΔT/Hot Backup/Dual ΔT/Hot Backup/Dual ΔT/Hot Backup/Dual ΔT/Hot Backup/Dual DT/Hot Backup/Dual
Sensor with two RTDs Sensor with two RTDs Sensor with RTDs/ Sensor with RTDs/ Sensor with two RTDs
Thermocouples(1) Thermocouples(1) with Compensation
Loop(1)
(1) Emerson provides four-wire sensors for all single-element RTDs. Use these RTDs in two-wire or three-wire configurations by leaving the unneeded
leads disconnected and insulated with electrical tape.
(2) Transmitter must be configured for a three-wire RTD in order to recognize an RTD with a compensation loop.
Two-wire RTD and Three-wire RTD and Four-wire RTD and Thermocouples and RTD with compensation
Ohms Ohms(1) Ohms millivolts loop(2)
Rosemount 3144P dual-sensor connections
ΔT/Hot Backup/dual ΔT/Hot Backup/dual ΔT/Hot Backup/dual ΔT/Hot Backup/dual ΔT/Hot Backup/dual
sensor with two RTDs sensor with two RTDs sensor with RTDs/ sensor with RTDs/ sensor with two RTDs
thermocouples(1) thermocouples(1) with compensation
loop(1)
(1) Emerson provides four-wire sensors for all single-element RTDs. Use these RTDs in two-wire or three-wire configurations by leaving the unneeded
leads disconnected and insulated with electrical tape.
(2) Transmitter must be configured for a three-wire RTD in order to recognize an RTD with a compensation loop.
Emerson.com/Rosemount 39
Rosemount 3144P May 2022
Standard configuration
4 mA value/lower range (HART®/4–20 mA) measurement point LO (FOUNDATION™ Fieldbus) 0 °C
20 mA value/upper range (HART/4–20 mA) measurement point HI (FOUNDATION Fieldbus) 100 °C
Damping 5 seconds
Output Linear with
temperature
Failure mode (HART/4–20 mA) High
Line voltage filter 60 Hz
Software tag See Software tag
Optional integral display Units and mA/
sensor 1 units
Single-sensor option
Sensor type 4-wire, Pt 100 a =
0.00385 RTD
Primary variable (HART/4–20 mA) analog input (AI) 1400 (FOUNDATION Fieldbus) Sensor 1
Secondary variable AI 1600 (FOUNDATION Fieldbus) Terminal
temperature
Tertiary variable Not used
Quaternary variable Not used
Dual-sensor option
Sensor type Two 3-wire, Pt 100 a
= 0.00385 RTD
Primary variable (HART/4–20 mA) AI 1400 (FOUNDATION Fieldbus) Sensor 1
Secondary variable AI 1500 (FOUNDATION Fieldbus) Sensor 2
Tertiary variable AI 1600 (FOUNDATION Fieldbus) Terminal
temperature
Quaternary variable Not used
40 Emerson.com/Rosemount
May 2022 Rosemount 3144P
To custom configure the Rosemount 3144P Transmitter with the dual-sensor option transmitter for one of the applications
described below, indicate the appropriate option code in the model number. If a sensor type is not specified, the transmitter will be
configured for two 3-wire Pt 100 (α = 0.00385) RTDs if any of the following option codes are selected.
Option code U2: average temperature with Hot Backup and sensor drift alert—warning mode
Primary usage Critical applications, such as safety interlocks and control loops. Outputs the average of
two measurements and sends a digital alert if temperature difference exceeds the set
maximum differential (Sensor Drift Alert – warning mode). If a sensor fails, an alert will
be sent digitally, and the primary variable will be reported as the remaining good sensor
value.
Emerson.com/Rosemount 41
Rosemount 3144P May 2022
Option code U3: average temperature with Hot Backup and sensor drift alert—alarm mode
Primary usage Critical applications, such as safety interlocks and control loops. Outputs the average of
two measurements and sets the analog output into alarm if temperature difference
exceeds the set maximum differential (sensor drift alert – alarm mode). If a sensor fails,
an alert will be sent digitally, and the primary variable will be reported as the remaining
good sensor value.
Primary variable Sensor average
Secondary variable Sensor 1
Tertiary variable Sensor 2
Quaternary variable Terminal temperature
42 Emerson.com/Rosemount
May 2022 Rosemount 3144P
Emerson.com/Rosemount 43
00813-0100-4021
Rev. TB
May 2022