Notifier DVC Mass Notification Systems Manual
Notifier DVC Mass Notification Systems Manual
This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
Software
Product Release
Number
NFS2-3030 FACP 20.00
NCA-2 Network Annunciator 20.00
NFS2-640 FACP 20.00
NFS-320/SYS FACP 20.00
NCM Network Communication Module, PCA 3.60
Version
NCM Network Communication Module, PCB 10.02
Version
HS-NCM Hi-speed Network Control Module 20.3
DVC Digital Voice Command 7.00
ONYXWorks-WS with NOTIFY-IP 3.20
VeriFire® Tools* 7.00
*This manual describes programming with VeriFire Tools version
8.00 and higher. Earlier versions of VeriFire Tools will differ in
options and appearance.
Table 1.1 MN Software First Releases
This manual describes how to use Notifier products to configure, program, and operate a system with mass notification capabilities. It
covers assembling the following key components of a mass notification system:
• Autonomous Control Units (ACU)
• Local Operating Consoles (LOC)
• Central Control Stations (CCS)
It also details the programming required to assign mass notification (MN) event priority, and describes the system’s operation when MN
is part of its function.
The configurations and functions covered in this manual comply with the following standard:
UL 2572 Mass Notification Systems Standard.
Data and Security: Communication Level 1. Stored Data Level: 0. Access Control Level: 1. (Access Control Level: 2 for
ONYXWorks Workstation). Physical Security Level: 1.
LOC LOC
LOC
(DVC-RPU and
LCD-160)
CCS
LOC LOC
(NCA-2 and DVC,
or ONYXWorks) NCA-2 (NCA-2 or NFS2- (DVC-RPU and
3030 and DVC) LCD-160)
Notes:
• MN System works on Standard and Hi-speed Noti•Fire•Net
• A total of 15 ONYXWorks workstations may participate in paging on a mass notification system.
Figure 1.1 Block Diagram Example of an MN System
NOTE: Product combinations must be in the same cabinet, or in cabinets next to each other with connections in conduit.
2.1.2 Configurations
The following two equipment combinations will meet the requirements for ACU functionality when combined with MN priority pro-
gramming.
• An NCA-2 combined with a DVC (in ACU mode) and its local microphone.
• An NFS2-3030 (in network display mode), combined with a DVC (in ACU mode) and its local microphone.
A DVC-KD, ACM-24AT, or AEM-24AT LED point must be programmed as a dedicated visual indicator of an MN alarm for each of
these configurations.
Required LED
annunciator or
DVC-KD point
programmed to
illuminate when an
MN alarm activates
Power Power
Supply Supply
AMPS-24 AMPS-24
DVC-RPU DVC-RPU
LCD-160 LCD-160
Caution!
Addressing is critical to command operations.
The DVC-RPU address on the digital audio loop must equal the LCD-160 address on the RDP bus.
LOC Configuration 1
OTHER EVENT LED
for MN alarm
annunciation
NCA-2 or NFS2-
3030, and DVC
Required LED
annunciator or DVC-KD
point programmed to
illuminate when an MN
alarm activates.
LOC Configuration 2
Figure 2.2 LOC Configurations
Refer to Section 3 on page 15 for programming.
2.3.2 Configurations
The following two equipment combinations can meet the requirements for CCS functionality in an MN system when combined with MN
priority programming:
• An ONYXWorks workstation.
• An NFS2-3030 (in network display mode) or NCA-2 combined with a DVC and its local microphone. For this combination, a
DVC-KD, ACM-24AT, or AEM-24AT LED point must be programmed as a dedicated visual indicator of an MN alarm.
MN alarm icon
display for MN NCA-2 or NFS2-
alarm 3030, and DVC
annunciation
Required LED
annunciator or DVC-
KD point programmed
to illuminate when an
ONYXWorks MN alarm activates.
workstation
CCS Configuration 1
CCS Configuration 2
Figure 2.3 CCS Configurations
Refer to Section 3 on page 15 for programming.
OTHER EVENT
LED for MN alarm
annunciation
NCA-2 or NFS2-3030
2.5 Inputs
2.5.1 Monitor Module and Initiating Device
An FMM-1 Monitor Module, FMM-101 Mini Monitor Module, FDM-1 SL
Dual Monitor Module, or XP10-M Monitor Module can be installed to _ +
monitor a UL-approved switch or button device installed for initiating
MN alarms. A Listed UL2017 initiating switch/device is required. It will _
generate an MN alarm, MN supervisory, or MN trouble message when it _ SL
+ +
is programmed with an MN/ECS type code. (Refer to “Type IDs” on
_
page 24). +
Optional
UL 2017 Listed Class A
Monitor module
manual input
device
Figure 2.6 Monitor Module and Input Device
2.6 Outputs
2.6.1 Strobes and Horns
Notification Appliance Circuits (NACs) for driving strobes and horns can be shared between fire and mass notification, or they can be
dedicated to a single application. When dedicated, releasing zone operation will not be affected by the state of MN in the system. For fire
and MN, only the highest priority active event will cause activations.
Strobe circuits that are associated with MN or an MN/Fire combination must be programmed as non-silenceable.
2.6.2 Speakers
All speakers on a DAL (Digital Audio Loop) will play live and pre-recorded MN messages according to their programming. They can be
shared between fire, mass notification, and releasing applications.
NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same mass notification priority settings.
The established priorities must be consistent throughout a system.
NOTE: All fire panel and display nodes must be programmed with DCC disabled. DVC nodes must be programmed as described in this
chapter.
3.2.1 ACU
An ACU is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC
NFS2-3030*/NCA-2
DVC
5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29
3.2.2 LOC
An LOC is comprised of a DVC in LOC mode, (with an NCA-2 or NFS2-3030 in network display mode) or a DVC-RPU combined with
an LCD-160. The LCD-160 must be associated with the NCA-2 or NFS2-3030 (in network display mode) that is being used for the
ACU. The DVC-RPU must be associated with the DVC used for the ACU.
DVC
5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29
DVC-RPU
1 Enable Paging Levels for which All Call functionality is required. page 33
LCD-160
NFS2-3030*/NCA-2
1 Set the MN Control Field to LOC. page 35
3.2.3 CCS
A CCS is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC, or an ONYXWorks Workstation.
NFS2-3030*/NCA-2
DVC
5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29
ONYXWorks Workstation
NFS2-3030*/NCA-2
NFS2-640/NFS-320/SYS
1 Set the mass notification priority page 21
DVC
1 Set the MN Mode.* page 21
5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29
*MN paging levels are not installed when the DVC acts as a subsidiary device.
DVC-RPU
MN Paging Levels are not installed when the DVC-RPU acts as a subsidiary device.
Program the DVC-RPU label. Refer to “DVC-RPU” on page 33.
MN Annunciator Programming
Program an annunciator as a dedicated MN alarm annunciator (See page 34). Set an LCD2-80 to terminal mode (See page 34). Use DVC
General Zones Z501 - Z533 to annunciate LOC and ACU paging. Refer to “DVC General Zones” on page 34.
3.3 Programming
3.3.1 DCC Participation
In a system with both MN and Fire, DCC must always be disabled for all NFS-320/SYSs, NFS2-640s, NFS2-3030s, NCA-2s and
ONYXWorks Workstation.
NFS2-3030/NCA-2
Panel: In the Panel Settings Menu, set DCC Participation to NO PANEL SETTINGS
to disable DCC Participation. LCM LOCAL MODE: YES REGIONAL SETTINGS
VeriFire Tools: Leave the Display and Control Center box unchecked in the NFS2-3030 and NCA-2. Do not enable DCC.
NFS2-3030 General Settings Branch, “General
Settings 1” column
NFS2-640/NFS-320/SYS
Panel: In the Utility Program Menu, set “DCC-mode” to “N” (no) to REGION=0 TBL.REMIND=2 ALA.SCROLL=N
disable DCC participation. LOCAL CONTROL=0 IP-ACCESS=0 DCC-mode:N
VeriFire Tools: Leave the Display and Control Center box unchecked NFS2-640/NFS-320/SYS General Settings
in the NFS2-640 and NFS-320/SYS service. Branch, “General Settings 2” column
Leave
unchecked.
NFS2-3030/NCA-2
This field allows the programmer to define the panel’s relative fire and MN priority. The priority may be set at the panel (See Figure 3.6)
or in VeriFire Tools. (See Figure 3.7).
Settings:
MN PRIORITY OVER FIRE: YES
• YES: MN is the highest priority.
• NO: Fire is the highest priority. SOUNDER BASE STANDBY POWER MON:OFF
• MNS NOT USED: The system is for fire protection only.
(Default) ACCEPT
BACK
VeriFire Tools: On the VeriFire Tools General Settings NFS2-3030 General Settings Branch, “General
branch for NFS2-3030/NCA-2, select the appropriate setting Settings 3” column
from the pull-down menu for the “Mass Notification Priority”
field.
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than Fire
• Fire is a higher priority than Mass Notification
NFS2-640/NFS-320/SYS
This field allows the programmer to define the panel’s fire and MN NFS2-640/NFS-320/SYS General Settings Branch,
priority. “General Settings 2” column
On the VeriFire Tools General Settings branch for NFS2-640 or NFS-
320/SYS, select the appropriate setting from the pull-down menu for
the “Mass Notification Priority” field.
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than fire
• Fire is a higher priority than Mass Notification
DVC
Set the Mode and Paging Level
On the VeriFire Tools General Settings branch for DVC,
select ACU, LOC, CCS, or Subsidiary from the MN
Mode pull-down menu in the DVC MN Mode box. DVC MN
Mode Field
A DVC that is not an ACU, LOC or CCS on an MN net-
work must be programmed as Subsidiary, and its Associ-
ated Node Number must be 0 (zero).
Select the Paging Levels to enable the ALL CALL but-
tons in the second column of the DVC-KD.
Set the Input Category
Following are the Programmable Audio Matrix (PAM) Select the
Input Numbers, Default Priorities and Categories that paging levels
appear for a DVC when ACU, LOC, CCS, or Subsidiary to be used on
the DVC-KD.
is selected as the DVC MN Mode. The default priorities
for the first 12 inputs comply with the priorities specified
in UL2572 in that at each level ACU is the highest prior-
ity and CCS is the lowest.
DVC-KD Level buttons in the second column page as
follows:
Figure 3.9 Setting DVC MN Mode & Paging Level
• Top button (Level 1) - always pages Inputs 1, 3, or
5, depending on whether the DVC is an ACU, LOC
or CCS.
• Second button (Level 2) - always pages Inputs 7, 9, or 11, depending on whether the DVC is an ACU, LOC or CCS.
• Third button (Level 3) - always pages Input 13.
Input Categories are Fire, MN, General, and MN Active Tone:
• When ACU, LOC, CCS, or Subsidiary is selected as a mode, Level 1 inputs default to the MN category, and Level 2 inputs default
to the Fire category.
• “MN Active Tone” is a category (it is assigned to a sequence, there is no default), and it must be assigned only to the MN Active
Tone message sequence (See pages 25–28).
If an input categorized as MN goes active, ZF20 activates and can suppress fire signals for all nodes in the MN mapping when MN is the
highest priority in the system.
Open the DVC Inputs branch. Because the DVC is set to ACU, LOC, CCS or Subsidiary mode, the first 14 Input lines will show MN
default input priorities. Assign the MN category to mass notification inputs, the Fire category to fire inputs, the MN Active Tone cate-
gory to the MN Active Tone input, and the General category to inputs that are neither MN, Fire, or MN Active Tone.
Select Category from the Use the Up & Down buttons to reassign
drop-down choices. the priority of an input.
In systems that implement multiple network audio sources, the priority of the network sources will be determined by the priority
assigned to the active input on the network source. For example, a DVC that is sending an ACU Local Paging Level 1 of priority 1 to a
network DVC will take priority over a DVC that is sending an ACU Local Paging level 2 of priority 7 to the same DVC. In the event of
the priority levels being identical for multiple network audio sources, the first source to activate will be granted priority.
ONYXWorks Workstation
1. Set the workstation to FCC Mode.
2. Create MN audio paging group(s).
3. Set up the workstation priorities for an MN CCS station. In Figure 3.10, Inputs are shown in their fixed order, which comply with
UL2572. CCS Inputs are:
• 5 (CCS Local Paging Level 1)
• 11 (CCS Local Paging Level 2)
• 13 (Local General Paging)
3.3.4 MN Mapping
MN Mapping determines if a ZF20 MN alarm will suppress fire events at the panel if there is an active MN alarm at another node and
MN is the highest priority.
NFS2-3030 in Network Display Mode
NETWORK MAPPING
MN network mapping may be done at the panel or in Veri-
Fire Tools. SCREEN 1 of 15
001:OFFLINE / 002:OFFLINE /
Panel: Navigate to the Panel Program Menu 1 screen. Press 003:ONLINE /MAPPED 004:OFFLINE /
005:OFFLINE / 006:OFFLINE /
the softkey next to NETWORK MAPPING to bring up the 007:OFFLINE / 008:OFFLINE /
009:ONLINE /MAPPED 010:OFFLINE /
screen shown in Figure 3.11. The panel will monitor the 012:OFFLINE / 012:OFFLINE /
nodes mapped here for MN alarm messages in order to sup- 013:OFFLINE / 014:OFFLINE /
015:OFFLINE / 016:OFFLINE /
press fire.
AUTO PROGRAM ACCEPT
NEXT BACK
VeriFire Tools: In the Network Mapping branch of VeriFire Tools, select the nodes in the Mass Notification column that the panel will
monitor for MN alarm messages in order to suppress fire.
NCA-2
NCA-2 Network event mapping defines its MN mapping; there is no unique MN mapping for the NCA-2.
DVC
DVC MN mapping consists of:
• Creating a logic equation for the MN Active Tone that will activate if a ZF20 MN alarm comes in from any MN-mapped node.
Refer to Section 3.3.7 on page 25 for this programming.
• All Call mapping in VeriFire Tools. MN pages will go out to the nodes in this map. Refer to the programming section of the DVC
manual for VeriFire Tools programming.
Point Characteristics
ECS/MN TROUBLE Trouble N N Generates a trouble for both short and open
MON circuit conditions.
Table 3.2 lists and describes MN control module and panel bell circuit Type IDs.
Point Characteristics
Point
Type Code Switch Walk
Type Silenceable Device Function
Inhibit Test
NOTE: Use ZF20 in the map of an LED annunciator programmed with a “monitor” mode as a dedicated MN alarm indicator.
Special
Function Name Description
Code
ZF20 MN Alarm Zone Activates for local events and network ZF20 activations when an MN alarm is present in the system. It
suppresses fire protection when MN is prioritized as higher than fire (see “Output Event Suppression” on
page 40). It is sent out to the network, and each networked panel will check the ZF20’s source against its
table of mapped MN nodes. If the source has a match in the table, fire protection will be suppressed in the
panel that made the match. Logic equations will be activated.
ZF21 MN Supervisory Activates for local events when there is an MN supervisory in the system.
Zone
NFS2-3030
NCA-2
NFS2-640/NFS-320/SYS
DVC
ONYXWorks Workstation
• It suppresses fire sequences and pages that come below it in priority, until an MN reset clears the “MN Active Tone”.
NOTE: Fire or OTHER sequences and pages will not be suppressed for MN alarms without the MN Active Tone, properly prioritized in the
PAM.
Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the MN Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 27.)
3. Create MN Logic Zones. (See page 28.)
4. Add MN Active Tone Logic to PAM Programming. (See page 28.)
Detailed Procedures
Build the MN Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the MN Active Tone audio sequence on the Message
Sequences tab.
1. Select and expand a sequence in the
Message Sequences Number column.
This example uses Sequence 1. Assign
the sequence an Evac message type.
2. Type “MN Active Tone” in the Label
field.
3. Select Command File for “Play
Forever” for Sequence Step 1.
4. Select Wave File for “Active Tone” for
Sequence Step 2.
5. Select Command File for “End Play” for
Sequence Step 3.
6. Press Play Sequence to listen to and
review the sequence as a test. The
Play Forever command will play 200
times as a test, will play forever in a
non-test situation. Use the audio-player
buttons to pause and restart playback.
7. Press Save.
Example: MN has the highest Input number is display and sort only.
priority, and the MN Active Tone
Category has been assigned to Input Change priority of inputs with the Up and Down buttons.
31, the MN Active Tone (Message
Sequence 1 from Figure 3.14). It has
been assigned a priority of 8, just
below the MN Category inputs and
above the Fire Category inputs.
Priorities 1 - 7,
MN Message
Category
Priority 8, MN Active
Tone Category,
Sequence 2 (the MN
Active Tone)
Priorities 9 - 16,
Fire Message
Category
Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the Fire Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 30.)
3. Create Fire Logic Zones. (See page 31.)
4. Add Fire Logic Zones to PAM Programming. (See page 31.)
Detailed Procedures
Build the Fire Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the Fire Active Tone audio sequence on the Message
Sequences tab.
1. Select and expand a sequence in the
Message Sequences Number column.
This example uses Sequence 6 Assign
the sequence an Evac message type.
2. Type “Fire Active Tone” in the Label
field.
3. Select Command File for “Play
Forever” for Sequence Step 1.
4. Select Wave File for “Active Tone” for
Sequence Step 2.
5. Select Command File for “End Play” for
Sequence Step 3.
6. Press Play Sequence to listen to and
review the sequence as a test. The
Play Forever command will play 200
times as a test, will play forever in a
non-test situation. Use the audio-player
buttons to pause and restart playback.
7. Press Save.
Example: Fire has the highest Input number is display and sort only.
priority, and the Fire Category has
been assigned to Input 36, the Fire Change priority of inputs with the Up and Down buttons.
Active Tone (Message Sequence 6
from Figure 3.18). It has been
assigned a priority of 8, just below
the Fire Category inputs and above
the MN Category inputs.
Priorities 1 - 7,
Fire Message
Category
Priority 8, Fire
Category, Sequence 6
(the Fire Active Tone)
Priorities 9 - 16,
MN Message
Category
2. Add the Logic Zone created in Figure 3.21 to all PAM Points in the row for Fire Active Tone. Select PAM View “Logic Equations”
for quick data-entry.
Figure 3.21 Map the Fire Active Tone Sequence to a Logic Zone
3.3.9 DVC-RPU
On the DAL Mapping branch, install a DVC-RPU by selecting Device Type RPU-PCC at the appropriate address. Click on the address’s
row and edit the device-specific information where it displays at the bottom of the screen.
3.3.10 LCD-160
To act as an LOC, the DVC-RPU requires an LCD-160 that is
wired to the DVC’s NCA-2, or NFS2-3030 (in network display
mode). The LCD-160’s Remote Display (RDP) bus address must
be the same address as the DVC-RPU’s Digital Audio Loop
(DAL) address.
In this example, the LCD-160 is at Node 3 Address 10
(Figure 3.23), and the DVC-RPU is at Node 16 DAL Address 10
(Figure 3.22).
CAUTION: THE DVC-RPU ADDRESS MUST EQUAL THE LCD-160 ADDRESS ON THE RDP BUS
! ADDRESSING IS CRITICAL TO COMMAND OPERATIONS. THE DVC-RPU ADDRESS ON THE DIGITAL AUDIO LOOP
MUST EQUAL THE LCD-160 ADDRESS ON THE RDP BUS.
LCD-160 DVC-RPU
RDP Bus DAL
Address 5 Address 5
on RPD Bus on DAL
NOTE: The LCD2-80, as well as the LCD-160, may not be used as a primary display for mass notification events.
MN PRIORITY OVER
NFS2-3030 General Settings Branch, “General Settings NCA-2 General Settings Branch, “General Settings 2”
1” column column
4.1.1 MN Alarm
Activating an MN Alarm
An MN alarm can be activated by any of the following events:
1. Paging at the MN level.
2. Activation of an MN Alarm Type Code on an ONYX panel.
3. Pressing an annunciator or DVC-KD control point programmed to activate an MN alarm message.
NFS2-3030, NCA-2 MN Activations
Local Activation
When an MN alarm activates locally, it:
• Produces a steady audible tone if the piezo is enabled.
• Flashes the “OTHER” LED for NFS2-3030/NCA-2.
• Does not activate the alarm relays.
• Displays MN ALARM in the upper left corner of the display of NFS2-3030, NCA-2, and LCD-160, as well as other information
specific to the alarm. Displays as MN ALM on LCD2-80/LCD-80 in terminal mode.
• Activates Special Function Zone ZF20 (MN alarm zone).
• Suppresses fire alarms if MN has the highest priority (refer to “Output Event Suppression” on page 40)
• Activates “General Pending” type code at the NFS2-3030.
• Does not activate “General Alarm” or “Alarm Pending” type codes.
• Is acknowledged individually.
• Scrolls using “Other Event/Scroll Display” key.
• Any device programmed for “Resound by Fire” will not resound.
• Increments the OTHER counter in the event counts display.
• Sends an MN alarm message to the history buffer and installed printer and annunciators.
• Appears as “MNA” in the Multiple Events list screen, grouped under “MN Alarm”.
• Latches the control panel in alarm. The control panel will not return to normal operation until the alarm condition is corrected and
the control panel is reset. Resets require two presses of the reset button if both MN and Fire events are present in the system. The
first press will reset the MN events, the second will reset the rest.
• Initiates any Control-By-Event (CBE) actions. If the node goes off-line, active logic equations with ZF20 in them will stay active
until MN reset.
• Sends an MN alarm message (ZF20) out to the network.
Network Activation
When an MN alarm is sent out to the network from the initiating node, each node on Noti•Fire•Net will check its MN map to determine
if it should react to the MN alarm. If a node has been programmed with the initiating node in its MN map, it will accept the MN alarm
from Noti•Fire•Net and react according to its programming.
• Logic equations with Special Function Zone ZF20 (MN alarm zone) in them will be evaluated.
• Fire alarms are suppressed if MN has the highest priority (Refer to “Output Event Suppression” on page 40).
• If the system is “ALL SYSTEMS NORMAL”, NETWORK MN ACTIVE will display.
NFS2-640, NFS-320/SYS MN Activation
Local Activation
When an MN alarm activates locally, it:
• Produces a steady audible tone if the piezo is enabled.
• Illuminates the ACS LED dedicated to MN alarms (required for the NFS2-640 and NFS-320/SYS). No LED on the panel lights for
an MN alarm.
• Does not activate the alarm relays.
• Displays ALARM:ECS/MN MON in the upper left corner of the display, as well as other information specific to the alarm.
Displays MN ALM on LCD2-80/LCD-80 in terminal mode.
• Activates Special Function Zone ZF20 (MN alarm zone).
• Suppresses fire alarms if MN has the highest priority (refer to “Output Event Suppression” on page 40).
• Does not activate “General Alarm” or “Alarm Pending” type codes.
• Is block acknowledged in scrolling mode, acknowledged one-by-one in non-scrolling mode.
4.1.2 MN Supervisory
MN Supervisory Activation
An MN supervisory message can be activated by an MN Supervisory Type Code on an ONYX panel.
4.1.3 MN Trouble
MN Trouble Activation
All network nodes will go through a 10 second decouple time. An MN reset may require up to 60 seconds of decouple time depending on
the complexity of logic equation evaluations.
Fire Events Only Present in System
When MN events have the highest priority and only fire events are present in the system, pressing the panel’s Reset button will reset the
system.
Example 2:
Output suppression using Logic Zone Programming and MN-dedicated General Zones
Logic equation ZL2 = AND(OR(Z10,Z11,Z12),NOT(Z2)), mapped to an output that is used for fire and suppressed during MN.
Z10, Z11, and Z12 are dedicated fire zones.
Z2 is an MN alarm zone.
If Z10, Z11, or Z12 is active, and Z2 is not, ZL2 will go active.
If Z10, Z11, or Z12, and Z2 are active, ZL2 will go inactive, and any outputs mapped to it may be suppressed.
Outputs:
• All outputs used for MN must be programmed as non-silenceable. This includes those outputs that are shared between MN and
other events, such as Fire.
• Dedicated Fire outputs can be programmed as silenceable or non-silenceable.
• All silenceable outputs will be suppressed at the start of an MN event.*
• All devices programmed with strobe Type IDs, as well as all intelligent sounder bases, will be suppressed regardless of silenceable
programming at the start of an MN event.*
*Zone map programming will then be re-evaluated, and if a device contains ZF20, or any general zone dedicated to MN that is
active, in its zone map, it will be re-activated.
• An output programmed with a releasing Type ID, or programmed with an active releasing zone in its zone map, will not be
suppressed.
Audio:
• Fire sequences playing on a DAL (digital audio loop) will be silenced, and the DVC will sound the MN Active Tone while fire is
suppressed.
• Fire sequences on a DVC will not sound, and the DVC will sound the MN Active Tone while fire is suppressed.
Drill and custom drill operation is blocked while fire activations are suppressed. This prevents activation of fire outputs while a Mass
Notification is in progress.
When an MN alarm is cleared, suppressed outputs will reactivate, even if they were silenced prior to being suppressed
Example 2:
Output suppression using Logic Zone Programming and Fire-dedicated General Zones.
Logic equation ZL2 = AND(Z11,NOT(OR(Z1,Z2,Z3))).
Z1, Z2, and Z3 are dedicated fire zones.
Z11 is an MN alarm zone.
If Z11 is active, and Z1, Z2, or Z3 are not, ZL2 will go active.
If Z1, Z2, or Z3 subsequently go active, ZL2 will go inactive, and any outputs mapped to it may be suppressed.
• Special Function Zone ZF20 (MN alarm) must not be mapped to Fire outputs, as outputs mapped to ZF20 will not be suppressed.
WARNING: IF FIRE IS THE HIGHEST PRIORITY, DO NOT USE ZF20 FOR MASS NOTIFICATION
! DO NOT USE ZF20 TO TURN ON MASS NOTIFICATION-DEDICATED OUTPUTS WHEN FIRE IS THE HIGHEST
PRIORITY.
Outputs:
• All outputs used for MN must be programmed as non-silenceable. This includes those outputs that are shared between MN and
other events, such as Fire.
• Dedicated Fire outputs can be programmed as silenceable or non-silenceable.
• Outputs mapped to Special Function Zone ZF20 will not be suppressed. See Warning above.
Audio:
• MN sequences playing on a DVC will be silenced, and the DVC will sound the Fire Active Tone while MN is suppressed.
• MN sequences on a DVC will not sound, and the DVC will sound the Fire Active Tone while MN is suppressed.
4.5 Paging
When a system has MN capabilities, the second column on a MN Paging Button
(In the example shown, the system has MN as the highest priority.)
DVC or DVC-RPU keypad has three functional buttons repre-
senting three priority levels of paging. If MN is the highest
priority in the system, pressing the highest button will create POWER PAGE
LAMP TEST
an MN page locally and to all MN mapped nodes, initiating an TROUBLE
FRONT
PAGE 2nd
MN alarm and suppressing fire activations. If Fire is the high- DVC OFF-LINE MN FLOOR
MUSIC to
est priority, pressing the highest button in column two will MICROPHONE
PAGE
AUDITORIUM
TROUBLE
create a Fire page to all mapped nodes. Pressing the Level 3 PHONE REMOTE MIC
(GENERAL PAGE) button will create a general ALL CALL TROUBLE
FFT
BUSY / WAIT
page that will not suppress any fire activations. PAGE FIRE
CAFETERIA
PAGE FFT
INHIBITED
Buttons in the two right columns of the keypad can also create PRE-
EAST WING
ANNOUNCE
an MN alarm if programmed to do so.
ACU’s take priority over LOC’s, and LOC’s take priority over GENERAL
CCS’s. PAGE
Level 1
Level 2
Level 3
Figure 4.3 DVC-KD Keypad
H O
HS-NCM
ONYXWorks
software release 6
in CCS configuration 11
MN network limitations 7
I programming 23
Input Category 21 software release 6
settings 22
P
L Priority programming for MN, fire 19
Levels, Data and Security 6
LOC (Local Operating Console) 7
R
configurations 10
Reset, MN, fire 39
function description 10
Risk assessment 6
programming 16
S
Software release numbers 6
Warn-HL-08-2009.fm