0% found this document useful (0 votes)
521 views46 pages

Notifier DVC Mass Notification Systems Manual

The document provides an overview and limitations of mass notification systems and fire alarm systems. It discusses components of these systems and how they function but cannot guarantee protection from fires. It also outlines important installation and maintenance considerations to ensure proper operation.

Uploaded by

Hunter Cullen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
521 views46 pages

Notifier DVC Mass Notification Systems Manual

The document provides an overview and limitations of mass notification systems and fire alarm systems. It discusses components of these systems and how they function but cannot guarantee protection from fires. It also outlines important installation and maintenance considerations to ensure proper operation.

Uploaded by

Hunter Cullen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Configuration, Programming and Operation Manual for

Mass Notification Systems

Document LS10063-000NF-E Rev: E


06/26/2019 ECN: 18-0305
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke Heat detectors do not sense particles of combustion and alarm
detectors, heat detectors, manual pull stations, audible warning only when heat on their sensors increases at a predetermined rate
devices, and a fire alarm control panel (FACP) with remote notifica- or reaches a predetermined level. Rate-of-rise heat detectors may
tion capability—can provide early warning of a developing fire. Such be subject to reduced sensitivity over time. For this reason, the rate-
a system, however, does not assure protection against property of-rise feature of each detector should be tested at least once per
damage or loss of life resulting from a fire. year by a qualified fire protection specialist. Heat detectors are
An emergency communication system—typically made up of an designed to protect property, not life.
automatic fire alarm system (as described above) and a life safety IMPORTANT! Smoke detectors must be installed in the same
communication system that may include an autonomous control room as the control panel and in rooms used by the system for the
unit (ACU), local operating console (LOC), voice communication, connection of alarm transmission wiring, communications, signal-
and other various interoperable communication methods—can ing, and/or power. If detectors are not so located, a developing fire
broadcast a mass notification message. Such a system, however, may damage the alarm system, compromising its ability to report a
does not assure protection against property damage or loss of life fire.
resulting from a fire or life safety event. Audible warning devices such as bells, horns, strobes, speak-
The Manufacturer recommends that smoke and/or heat detectors ers and displays may not alert people if these devices are located
be located throughout a protected premises following the on the other side of closed or partly open doors or are located on
recommendations of the current edition of the National Fire another floor of a building. Any warning device may fail to alert peo-
Protection Association Standard 72 (NFPA 72), manufacturer's ple with a disability or those who have recently consumed drugs,
recommendations, State and local codes, and the alcohol, or medication. Please note that:
recommendations contained in the Guide for Proper Use of System • An emergency communication system may take priority over a
Smoke Detectors, which is made available at no charge to all fire alarm system in the event of a life safety emergency.
installing dealers. This document can be found at http:// • Voice messaging systems must be designed to meet intelligibility
www.systemsensor.com/appguides/. A study by the Federal requirements as defined by NFPA, local codes, and Authorities
Emergency Management Agency (an agency of the United States Having Jurisdiction (AHJ).
government) indicated that smoke detectors may not go off in as
many as 35% of all fires. While fire alarm systems are designed to • Language and instructional requirements must be clearly dis-
provide early warning against fire, they do not guarantee warning or seminated on any local displays.
protection against fire. A fire alarm system may not provide timely or • Strobes can, under certain circumstances, cause seizures in
adequate warning, or simply may not function, for a variety of people with conditions such as epilepsy.
reasons: • Studies have shown that certain people, even when they hear a
Smoke detectors may not sense fire where smoke cannot reach fire alarm signal, do not respond to or comprehend the meaning
the detectors such as in chimneys, in or behind walls, on roofs, or of the signal. Audible devices, such as horns and bells, can have
on the other side of closed doors. Smoke detectors also may not different tonal patterns and frequencies. It is the property
sense a fire on another level or floor of a building. A second-floor owner's responsibility to conduct fire drills and other training
detector, for example, may not sense a first-floor or basement fire. exercises to make people aware of fire alarm signals and
Particles of combustion or “smoke” from a developing fire may instruct them on the proper reaction to alarm signals.
not reach the sensing chambers of smoke detectors because: • In rare instances, the sounding of a warning device can cause
• Barriers such as closed or partially closed doors, walls, chim- temporary or permanent hearing loss.
neys, even wet or humid areas may inhibit particle or smoke A life safety system will not operate without any electrical power. If
flow. AC power fails, the system will operate from standby batteries only
• Smoke particles may become “cold,” stratify, and not reach the for a specified time and only if the batteries have been properly
ceiling or upper walls where detectors are located. maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air out- Equipment used in the system may not be technically compatible
lets, such as air conditioning vents. with the control panel. It is essential to use only equipment listed for
service with your control panel.
• Smoke particles may be drawn into air returns before reaching
the detector. Telephone lines needed to transmit alarm signals from a premises
to a central monitoring station may be out of service or temporarily
The amount of “smoke” present may be insufficient to alarm smoke disabled. For added protection against telephone line failure,
detectors. Smoke detectors are designed to alarm at various levels backup radio transmission systems are recommended.
of smoke density. If such density levels are not created by a devel-
oping fire at the location of detectors, the detectors will not go into The most common cause of life safety system malfunction is inad-
alarm. equate maintenance. To keep the entire life safety system in excel-
lent working order, ongoing maintenance is required per the
Smoke detectors, even when working properly, have sensing limita- manufacturer's recommendations, and UL and NFPA standards. At
tions. Detectors that have photoelectronic sensing chambers tend a minimum, the requirements of NFPA 72 shall be followed. Envi-
to detect smoldering fires better than flaming fires, which have little ronments with large amounts of dust, dirt, or high air velocity require
visible smoke. Detectors that have ionizing-type sensing chambers more frequent maintenance. A maintenance agreement should be
tend to detect fast-flaming fires better than smoldering fires. arranged through the local manufacturer's representative. Mainte-
Because fires develop in different ways and are often unpredictable nance should be scheduled as required by National and/or local fire
in their growth, neither type of detector is necessarily best and a codes and should be performed by authorized professional life
given type of detector may not provide adequate warning of a fire. safety system installers only. Adequate written records of all inspec-
Smoke detectors cannot be expected to provide adequate warning tions should be kept.
of fires caused by arson, children playing with matches (especially Limit-D2-2016
in bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).

2 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may operate
nected to the fire alarm control panel. Disconnect all sources of erratically or can be damaged when subjected to lightning induced
power before servicing. Control unit and associated equipment may transients. Although no system is completely immune from lightning
be damaged by removing and/or inserting cards, modules, or inter- transients and interference, proper grounding will reduce suscepti-
connecting cables while the unit is energized. Do not attempt to bility. Overhead or outside aerial wiring is not recommended, due to
install, service, or operate this unit until manuals are read and an increased susceptibility to nearby lightning strikes. Consult with
understood. the Technical Services Department if any problems are anticipated
CAUTION - System Re-acceptance Test after Software or encountered.
Changes: To ensure proper system operation, this product must be Disconnect AC power and batteries prior to removing or inserting
tested in accordance with NFPA 72 after any programming opera- circuit boards. Failure to do so can damage circuits.
tion or change in site-specific software. Re-acceptance testing is Remove all electronic assemblies prior to any drilling, filing,
required after any change, addition or deletion of system compo- reaming, or punching of the enclosure. When possible, make all
nents, or after any modification, repair or adjustment to system cable entries from the sides or rear. Before making modifications,
hardware or wiring. All components, circuits, system operations, or verify that they will not interfere with battery, transformer, or printed
software functions known to be affected by a change must be 100% circuit board location.
tested. In addition, to ensure that other operations are not inadver-
tently affected, at least 10% of initiating devices that are not directly Do not tighten screw terminals more than 9 in-lbs. Over-tighten-
affected by the change, up to a maximum of 50 devices, must also ing may damage threads, resulting in reduced terminal contact
be tested and proper system operation verified. pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017

FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.

HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 3


Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we
strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Contact Technical Support with any questions about software and the appropriate version for a specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.

4 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Table of Contents
Section 1: Introduction ..................................................................................................................................................... 6
1.1: Overview............................................................................................................................................................................................................6
1.2: Mass Notification Features ................................................................................................................................................................................7
1.3: Supplemental Documentation............................................................................................................................................................................8
1.4: Cautions and Warnings ......................................................................................................................................................................................8
Section 2: Configurations................................................................................................................................................. 9
2.1: Autonomous Control Unit (ACU) .....................................................................................................................................................................9
2.1.1: Description..............................................................................................................................................................................................9
2.1.2: Configurations ........................................................................................................................................................................................9
2.2: Local Operating Console (LOC) .....................................................................................................................................................................10
2.2.1: Description............................................................................................................................................................................................10
2.2.2: Configurations ......................................................................................................................................................................................10
2.3: Central Control Station (CCS).........................................................................................................................................................................11
2.3.1: Description............................................................................................................................................................................................11
2.3.2: Configurations ......................................................................................................................................................................................11
2.4: MN Alarm Indicator ........................................................................................................................................................................................13
2.5: Inputs ...............................................................................................................................................................................................................13
2.5.1: Monitor Module and Initiating Device .................................................................................................................................................13
2.5.2: Microphone Activations for MN ..........................................................................................................................................................14
2.5.3: ACS and DVC-KD Activations............................................................................................................................................................14
2.6: Outputs.............................................................................................................................................................................................................14
2.6.1: Strobes and Horns.................................................................................................................................................................................14
2.6.2: Speakers................................................................................................................................................................................................14
2.6.3: CAP Gateway .......................................................................................................................................................................................14
2.7: Supplemental Equipment.................................................................................................................................................................................14
Section 3: Programming ................................................................................................................................................. 15
3.1: Overview..........................................................................................................................................................................................................15
3.2: Programming Steps..........................................................................................................................................................................................15
3.2.1: ACU......................................................................................................................................................................................................15
3.2.2: LOC ......................................................................................................................................................................................................16
3.2.3: CCS.......................................................................................................................................................................................................16
3.2.4: Subsidiary Equipment...........................................................................................................................................................................17
3.3: Programming ...................................................................................................................................................................................................18
3.3.1: DCC Participation.................................................................................................................................................................................18
3.3.2: Mass Notification Control Settings for the DVC .................................................................................................................................19
3.3.3: Set the Priority .....................................................................................................................................................................................19
3.3.4: MN Mapping ........................................................................................................................................................................................23
3.3.5: Type IDs ...............................................................................................................................................................................................24
3.3.6: Special Function Zones.........................................................................................................................................................................25
3.3.7: MN Active Tone ...................................................................................................................................................................................25
3.3.8: Fire Active Tone ...................................................................................................................................................................................29
3.3.9: DVC-RPU.............................................................................................................................................................................................33
3.3.10: LCD-160 .............................................................................................................................................................................................33
3.3.11: MN Annunciator Programming ..........................................................................................................................................................34
3.3.12: DVC General Zones ...........................................................................................................................................................................34
3.3.13: MN Control Label...............................................................................................................................................................................35
Section 4: Operation ....................................................................................................................................................... 36
4.1: Mass Notification Events.................................................................................................................................................................................36
4.1.1: MN Alarm.............................................................................................................................................................................................36
4.1.2: MN Supervisory....................................................................................................................................................................................37
4.1.3: MN Trouble ..........................................................................................................................................................................................38
4.2: Performing a System Reset..............................................................................................................................................................................39
4.3: Output Event Suppression ...............................................................................................................................................................................40
4.4: Mass Notification Control Operation ..............................................................................................................................................................41
4.5: Paging ..............................................................................................................................................................................................................42
4.6: Drill Operation.................................................................................................................................................................................................42
Index ................................................................................................................................................................................. 43

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 5


Section 1: Introduction
1.1 Overview
A Notifier system is capable of providing both fire and mass notification protection. Based on risk assessment, installers can configure
and program a system so that mass notification (MN) system events will always have either a higher or lower priority than fire events.
When MN is programmed as the highest priority:
• Fire events will be suppressed by MN alarm events until the MN alarms are cleared.
• MN events will display ahead of fire events in each event category.
Notifier systems provide this capability beginning with the software releases in Table 1.1.

Software
Product Release
Number
NFS2-3030 FACP 20.00
NCA-2 Network Annunciator 20.00
NFS2-640 FACP 20.00
NFS-320/SYS FACP 20.00
NCM Network Communication Module, PCA 3.60
Version
NCM Network Communication Module, PCB 10.02
Version
HS-NCM Hi-speed Network Control Module 20.3
DVC Digital Voice Command 7.00
ONYXWorks-WS with NOTIFY-IP 3.20
VeriFire® Tools* 7.00
*This manual describes programming with VeriFire Tools version
8.00 and higher. Earlier versions of VeriFire Tools will differ in
options and appearance.
Table 1.1 MN Software First Releases

This manual describes how to use Notifier products to configure, program, and operate a system with mass notification capabilities. It
covers assembling the following key components of a mass notification system:
• Autonomous Control Units (ACU)
• Local Operating Consoles (LOC)
• Central Control Stations (CCS)
It also details the programming required to assign mass notification (MN) event priority, and describes the system’s operation when MN
is part of its function.
The configurations and functions covered in this manual comply with the following standard:
UL 2572 Mass Notification Systems Standard.
Data and Security: Communication Level 1. Stored Data Level: 0. Access Control Level: 1. (Access Control Level: 2 for
ONYXWorks Workstation). Physical Security Level: 1.

6 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Mass Notification Features Introduction

LOC LOC

(DVC-RPU and (DVC-RPU and


ACU LCD-160) LCD-160)
NFS-320/SYS (NFS2-3030 and
DVC) Noti•Fire•Net

LOC

ACU (DVC-RPU and


LCD-160)
(NCA-2 and
NFS2-640 DVC)
LOC

(DVC-RPU and
LCD-160)

CCS
LOC LOC
(NCA-2 and DVC,
or ONYXWorks) NCA-2 (NCA-2 or NFS2- (DVC-RPU and
3030 and DVC) LCD-160)

Notes:
• MN System works on Standard and Hi-speed Noti•Fire•Net
• A total of 15 ONYXWorks workstations may participate in paging on a mass notification system.
Figure 1.1 Block Diagram Example of an MN System

1.2 Mass Notification Features


• MN events can be programmed as higher or lower than fire events, based on risk analysis.
• MN alarms suppress fire alarm events when MN is the highest priority.
• MN alarms are generated locally
– by an ACU, LOC, or CCS page.
– by manual activation of a UL-approved switch or button device installed for initiating MN alarms. A Listed UL2017 initiating
switch/device is required.
• MN events generate messages over Noti•Fire•Net to MN-mapped nodes.
• Programmable using VeriFire Tools.
• Automatic activation of Special Function Zone ZF20 to signal MN alarm.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 7


Introduction Supplemental Documentation

1.3 Supplemental Documentation


The table below provides a list of documents referenced in this manual.

Product Part Number


NFS2-3030 Listing Document LS10006-051NF-E
NFS2-640 Listing Document 52741LD
NFS-320/SYS Listing Document 52745LD
NCA-2 Installation, Programming and Operations Manual 52482
ONYXWorks Workstation Manual 52342
ONYXWorks NOTIFY-IP Manual 53620
CAP Gateway Listing Document LS10021-051NF-E
ACS Series Annunciator Control System Manual 15842
LCD-160 Manual 51850
LCD2-80 Listing Document 54089LD
DVC Digital Voice Command Manual 52411
DAA2 and DAX Amplifiers Manual 53265
DS-DB Digital Series Distribution Board and Amplifiers Manual 53622
DVC-RPU Listing Document 50107524-001
AMPS-24 Manual 51907
ACPS-610 Manual 53018
FMM-1 Monitor Module Installation Document 156-1171/156/3056
FMM-101 Mini Monitor Module Installation Document 156-1173
FDM-1 Dual Monitor Module Installation Document 156-1463/156-3531
XP10-M Installation Document 156-1803
SLC Wiring Manual 51253

Table 1.2 Related Documentation Table

1.4 Cautions and Warnings


This manual may contain cautions and warnings to alert the reader as follows:

CAUTION: SUMMARY OF CAUTION INFORMATION


! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR
EQUIPMENT DAMAGE.

WARNING: SUMMARY OF WARNING INFORMATION


! INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE
CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR PERSONAL INJURY.

8 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Section 2: Configurations
Notifier equipment can be combined to meet the UL 2572 requirements for ACU, LOC, and CCS command centers. This section
describes the product combinations that can be used to create these MN features, as well as their MN inputs and outputs.

NOTE: Product combinations must be in the same cabinet, or in cabinets next to each other with connections in conduit.

2.1 Autonomous Control Unit (ACU)


2.1.1 Description
An Autonomous Control Unit (ACU) is the primary local control unit for a mass notification system. It monitors and controls notifica-
tion appliances for a building or other protected premise. The ACU provides the ability to acknowledge, silence, and reset any events
(fire or MN) that are mapped to the ACU. MN events can be acknowledged, silenced or reset only by an active MN command center.
Alarm, supervisory and trouble events are acknowledged and reset using the same acknowledge and reset buttons. In the event both an
MN and fire event are active, only the highest priority type will change state with a reset. A second reset is required to clear the lower
priority events.
The ACU displays MN alarms differently from fire alarms. Fire alarms are indicated by the “Fire Alarm” LED, and will be counted with
the Fire Alarm counter. MN alarms are indicated by the “Other” LED on the display, and indicated on an annunciator with a dedicated
LED and counted with an OTHER counter. MN supervisory events and fire supervisory events share the Supervisory LED, piezo sound-
ing pattern, and supervisory counter. MN points in trouble and fire points in trouble will share the same trouble LED, piezo sounding pat-
tern and trouble counter in the display.
The DVC (in ACU mode) provides the audio functions of the ACU. It provides three paging levels - Level 1, Level 2 and Level 3 -
which may be assigned to MN, fire, or general paging for prioritization based on site-specific requirements. A page at the MN level will
create a latching MN alarm condition that requires acknowledgment and reset. Multiple ACU locations can be prioritized in hierarchical
levels by adjusting the priority level of the local microphone input. The ACU supports All Call when priority allows. MN pages from an
ACU must be ALL CALL pages.
When an ACU gains control of acknowledge, silence and reset functions in an MN system, control is indicated by a lit Controls Active
LED at the ACU. All other Controls Active LEDs in the system are extinguished, red lockout icons appear in ONYXWorks Workstation
paging zones and on the acknowledge, silence, and reset control buttons; acknowledge, silence and reset functions are blocked until the
MN alarm is cleared.

2.1.2 Configurations
The following two equipment combinations will meet the requirements for ACU functionality when combined with MN priority pro-
gramming.
• An NCA-2 combined with a DVC (in ACU mode) and its local microphone.
• An NFS2-3030 (in network display mode), combined with a DVC (in ACU mode) and its local microphone.
A DVC-KD, ACM-24AT, or AEM-24AT LED point must be programmed as a dedicated visual indicator of an MN alarm for each of
these configurations.

OTHER LED Required LED


for MN alarm OTHER LED annunciator or
annunciation for MN alarm DVC-KD point
annunciation programmed to
illuminate when an
MN alarm
activates
NFS2-3030
and DVC NCA-2 and
DVC

Required LED
annunciator or
DVC-KD point
programmed to
illuminate when an
MN alarm activates

Power Power
Supply Supply
AMPS-24 AMPS-24

ACU Configuration 2 ACU Configuration 1

Figure 2.1 ACU Configurations


Refer to page 15 for programming.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 9


Configurations Local Operating Console (LOC)

2.2 Local Operating Console (LOC)


2.2.1 Description
A Local Operating Console (LOC) is used by authorized personnel to initiate messages and signaling for mass-notification applications.
It provides three paging levels - Level 1, Level 2 and Level 3 - which may be assigned to MN, fire, or general paging for prioritization
based on site-specific requirements. A page at the MN level will create a latching MN alarm condition that requires acknowledgment and
reset. The LOC supports All Call when priority allows. LOC pages must be ALL CALL pages.
MN events can be acknowledged, silenced or reset only by an active MN command center. When an LOC gains control of acknowledge,
silence and reset functions in an MN system, control is indicated by a lit Controls Active LED at the LOC. All other Controls Active
LEDs in the system are extinguished, red lockout icons appear in ONYXWorks Workstations paging zones and on the acknowledge,
silence, and reset control buttons; acknowledge, silence and reset functions are blocked until the MN alarm is cleared.
Multiple LOC stations can be used in a single system: control is granted on a first-come, first-served basis.
Each LOC requires a point to be mapped in programming, which should be visible when required at the ACU.
2.2.2 Configurations
Either of the following two equipment combinations can meet the requirements for LOC functionality in an MN system when combined
with MN priority programming:
• A DVC-RPU combined with an LCD-160 that is connected to an NCA-2 or NFS2-3030 (in network display mode).
– The NCA-2 or NFS2-3030 (in network display mode) must be associated through programming with the DVC-RPU’s DVC.
– The DVC-RPU must have the same address on the DAL (Digital Audio Loop) as the LCD-160 has on its RDP bus. Addressing
is critical - refer to page 33 for more information.
• A DVC operated in LOC mode combined with an NFS2-3030 (in network display mode), or NCA-2.
OR

DAL to DVC DAL to DVC

DVC-RPU DVC-RPU

RDP bus to NCA-2 or NFS2- RDP bus to NCA-2 or NFS2-3030


3030 associated through associated through programming to the
programming to the DVC- DVC-RPU’s DVC.
RPU’s DVC.

LCD-160 LCD-160
Caution!
Addressing is critical to command operations.
The DVC-RPU address on the digital audio loop must equal the LCD-160 address on the RDP bus.
LOC Configuration 1
OTHER EVENT LED
for MN alarm
annunciation

NCA-2 or NFS2-
3030, and DVC

Required LED
annunciator or DVC-KD
point programmed to
illuminate when an MN
alarm activates.

LOC Configuration 2
Figure 2.2 LOC Configurations
Refer to Section 3 on page 15 for programming.

10 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Central Control Station (CCS) Configurations

2.3 Central Control Station (CCS)


2.3.1 Description
A Central Control Station (CCS) is a system component with emergency communication and control that is used in conjunction with one
or more ACUs in a mass notification system. The priority of a CCS will be lower than that of an ACU or LOC in the MN/fire system.
ONYXWorks Workstation
The ONYXWorks workstation (in FCC mode, with the NOTIFY-IP option) displays events and status of the MN and fire systems from
any ACU located on Noti•Fire•Net. It provides three paging levels - Level 1, Level 2 and Level 3 - which may be assigned to MN, fire,
or general paging for prioritization based on site-specific requirements. A page at the MN level will create a latching MN alarm condi-
tion that requires acknowledgment and reset. The workstation supports All Call paging when priority allows. An MN page from a CCS
must be an ALL CALL page.
The ONYXWorks workstation has the capability to acknowledge, silence, and reset events (MN and fire) in the system. MN events can
be acknowledged, silenced or reset only by an active MN command center. Control of acknowledge, silence and reset functions is indi-
cated for an active ONYXWorks Workstation by the absence of red lockout icons in paging zones and control buttons. All other Controls
Active LEDs in the system are extinguished, and red lockout icons appear in paging zones and control buttons of non-active ONYX-
Works Workstation; acknowledge, silence and reset functions are blocked until the MN alarm is cleared.
In the event both MN and fire are active in the system, the reset control will reset only the highest priority type event. A second reset is
required to reset lower-priority type events. The acknowledge control acknowledges all troubles and supervisories for MN and fire. Fire
alarms and MN alarms are acknowledged one-by-one, based on highest priority events.
A total of 15 ONYXWorks workstations may participate in paging on a mass notification system.
NCA-2 with DVC
The NCA-2 displays and annunciates fire and MN events and status for the monitored points in each of the ACUs and LOCs in the sys-
tem. It also provides acknowledge, silence, and reset capabilities. Alarm, supervisory and trouble events are acknowledged and reset
using the same acknowledge and reset buttons. The reset control resets only the highest priority active event type in the system. A second
reset is required to reset lower-priority type events. The acknowledge control block acknowledges all troubles and supervisories for MN
and fire. Fire alarms and MN alarms are acknowledged one-by-one, based on highest priority events.
The DVC (in CCS mode) provides the audio functions of the CCS. It provides three paging levels - Level 1, Level 2 and Level 3 - which
may be assigned to MN, fire, or general paging for prioritization based on site-specific requirements. A page at the MN level will create
a latching MN alarm condition that requires acknowledgment and reset. Multiple CCS locations can be prioritized in hierarchical levels
by adjusting the priority level of the local microphone input. The CCS supports All Call paging when priority allows. MN pages from a
CCS must be All Call pages.
MN events can be acknowledged, silenced or reset only by an active MN command center. When the CCS gains control of acknowledge,
silence and reset functions in an MN system, control is indicated by a lit Controls Active LED at the CCS. All other Controls Active
LEDs in the system are extinguished, red lockout icons appear in ONYXWorks Workstation paging zones and the acknowledge, silence,
and reset control buttons; acknowledge, silence and reset functions are blocked until the MN alarm is cleared.

2.3.2 Configurations
The following two equipment combinations can meet the requirements for CCS functionality in an MN system when combined with MN
priority programming:
• An ONYXWorks workstation.
• An NFS2-3030 (in network display mode) or NCA-2 combined with a DVC and its local microphone. For this combination, a
DVC-KD, ACM-24AT, or AEM-24AT LED point must be programmed as a dedicated visual indicator of an MN alarm.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 11


Configurations Central Control Station (CCS)

OTHER EVENT LED


for MN alarm
annunciation

MN alarm icon
display for MN NCA-2 or NFS2-
alarm 3030, and DVC
annunciation

Required LED
annunciator or DVC-
KD point programmed
to illuminate when an
ONYXWorks MN alarm activates.
workstation

CCS Configuration 1

CCS Configuration 2
Figure 2.3 CCS Configurations
Refer to Section 3 on page 15 for programming.

12 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


MN Alarm Indicator Configurations

2.4 MN Alarm Indicator


One of the following must be programmed as a dedicated MN alarm indicator for the NFS-320/SYS, NFS2-640, NFS2-3030, and NCA-
2. The indicator is not required if a panel is acting as a displayless node.
• An ACM-24AT or AEM-24AT LED annunciator point.
• A DVC-KD point.
An ONYXWorks workstation does not require an additional annunciator point, as it has a dedicated icon to indicate when an MN alarm
is active. This icon is displayed constantly during an MN alarm.
LED annunciator point
programmed to
NFS2-640 or NFS- illuminate when an MN
320/SYS alarm activates.

Refer to Section 3.3.11 on


page 34 for programming.

Figure 2.4 NFS2-640 or NFS-320/SYS MN Alarm Annunciation

OTHER EVENT
LED for MN alarm
annunciation

NCA-2 or NFS2-3030

Required LED annunciator


or DVC-KD point
programmed to illuminate
when an MN alarm
activates. Refer to Section 3.3.11 on
page 34 for programming.

Figure 2.5 NFS2-3030, or NCA-2 MN Alarm Annunciation

2.5 Inputs
2.5.1 Monitor Module and Initiating Device
An FMM-1 Monitor Module, FMM-101 Mini Monitor Module, FDM-1 SL
Dual Monitor Module, or XP10-M Monitor Module can be installed to _ +
monitor a UL-approved switch or button device installed for initiating
MN alarms. A Listed UL2017 initiating switch/device is required. It will _
generate an MN alarm, MN supervisory, or MN trouble message when it _ SL
+ +
is programmed with an MN/ECS type code. (Refer to “Type IDs” on
_
page 24). +
Optional
UL 2017 Listed Class A
Monitor module
manual input
device
Figure 2.6 Monitor Module and Input Device

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 13


Configurations Outputs

2.5.2 Microphone Activations for MN


MN Microphone activations are initiated at ACU, LOC and CCS stations. Programming determines which button is assigned to mass
notification.
ACU, LOC, and Non-ONYXWorks CCS Activations
MN ALL CALL paging is activated by pressing one of the top two paging buttons in the second column of DVC-KD buttons, then using
the microphone to page. Programming determines which button it is. MN paging will be the top button if MN is programmed as the
highest priority in the system. It will be the second paging button down if Fire is programmed as the highest priority in the system. (Fire
paging will be the top button.) MN paging activates an MN alarm.
ONYXWorks Activations
MN paging is activated by clicking the audio button for the desired MN paging group. MN paging groups are listed on the right side of
the workstation graphic area. The Live Microphone dialog box will open and the Start Paging bar will be available to click and use the
microphone to page.

2.5.3 ACS and DVC-KD Activations


Annunciator buttons, and the buttons in the two right columns of a DVC-KD, can be programmed to initiate MN alarms for vectored
paging or for playing pre-recorded MN messages. Refer to “Programming” on page 15, and to the DVC manual for more information.

2.6 Outputs
2.6.1 Strobes and Horns
Notification Appliance Circuits (NACs) for driving strobes and horns can be shared between fire and mass notification, or they can be
dedicated to a single application. When dedicated, releasing zone operation will not be affected by the state of MN in the system. For fire
and MN, only the highest priority active event will cause activations.
Strobe circuits that are associated with MN or an MN/Fire combination must be programmed as non-silenceable.

2.6.2 Speakers
All speakers on a DAL (Digital Audio Loop) will play live and pre-recorded MN messages according to their programming. They can be
shared between fire, mass notification, and releasing applications.

2.6.3 CAP Gateway


The CAP Gateway is a primary output for an MN System.

2.7 Supplemental Equipment


The following equipment is listed for UL2572 supplemental use.
• NFN-GW-EM3
• NWS-3
• BACNET-GW-3
• MODBUS-GW

14 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Section 3: Programming
3.1 Overview
When a system is configured for both fire and MN protection, programming determines which events always have the highest priority -
MN or fire. If MN is programmed as the highest priority at the fire panels and network annunciators, fire events are suppressed when
MN alarms are active. For the DVC, PAM programming for the MN Active Tone will suppress the activation of fire sequences and
pages.
Special Function Zones and Type Codes separate MN alarm, supervisory and trouble messages from fire messages, so that each can be
correctly prioritized and displayed by the system. Mapping links nodes that will communicate with each other regarding MN events.
This chapter describes the special MN programming (needed in addition to fire programming) for an MN system.

NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same mass notification priority settings.
The established priorities must be consistent throughout a system.

NOTE: All fire panel and display nodes must be programmed with DCC disabled. DVC nodes must be programmed as described in this
chapter.

3.2 Programming Steps


This section lists the MN programming steps required, and provides reference to the appropriate programming, detailed in Section 3.3,
for each station, panel, or network annunciator. These steps must be followed if the system is set up for MN and fire, or MN only.
Refer also to Section 4.3, “Output Event Suppression”, on page 40. This section presents basic principles for suppression.

3.2.1 ACU
An ACU is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC

ACU Programming Steps

NFS2-3030*/NCA-2

Field Refer to:

1 Set the mass notification priority. page 19

2 Set the DCC field. page 18


3 Set the MN Control Field to ACU. page 35

4 Map to MN nodes. page 23, page 23

5 Program with MN type IDs. page 24


6 Program with MN Special Function Zones. page 25

* NFS2-3030 must be in network display mode to function as part of an ACU.

DVC

1 Set the MN mode, enable paging levels. page 21

2 Enter associated NFS2-3030/NCA-2 node number. page 19

3 Program input categories and priorities. page 21,page 22

4 Create and program an MN Active Tone. page 25

5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 15


Programming Programming Steps

3.2.2 LOC
An LOC is comprised of a DVC in LOC mode, (with an NCA-2 or NFS2-3030 in network display mode) or a DVC-RPU combined with
an LCD-160. The LCD-160 must be associated with the NCA-2 or NFS2-3030 (in network display mode) that is being used for the
ACU. The DVC-RPU must be associated with the DVC used for the ACU.

LOC Programming Steps

DVC

Field Refer to:

1 Set the MN mode, enable paging levels. page 21

2 Enter associated NFS2-3030*/NCA-2 node number. page 19

3 Program input categories and priorities page 21, page 22

4 Create and program an MN Active Tone page 25

5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29

DVC-RPU

1 Enable Paging Levels for which All Call functionality is required. page 33

2 Program the DAL address - critical to LOC operation page 33

LCD-160

1 Program RDP address - critical to LOC operation. page 33

NFS2-3030*/NCA-2
1 Set the MN Control Field to LOC. page 35

* NFS2-3030 must be in network display mode to function as part of an LOC.

3.2.3 CCS
A CCS is comprised of an NFS2-3030 and a DVC, or an NCA-2 and a DVC, or an ONYXWorks Workstation.

CCS Programming Steps

NFS2-3030*/NCA-2

Field Refer to:

1 Set the mass notification priority. page 19

2 Set the DCC field. page 18

3 Set the MN Control Field to CCS. page 35


4 Map to MN nodes. page 23, page 23

5 Program with MN type IDs. page 24

6 Program with MN Special Function Zones. page 25

* NFS2-3030 must be in network display mode to function as part of a CCS.

DVC

1 Set the MN mode, enable paging levels. page 21

2 Enter associated NFS2-3030/NCA-2 node number. page 19

3 Program input categories and priorities. page 21, page 22


4 Create and program an MN Active Tone. page 25

5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29

ONYXWorks Workstation

1 Set the workstation to FCC Mode. manual

2 Set the DCC field to disabled manual

3 Configure the Notify-IP feature. manual

16 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Steps Programming

CCS Programming Steps

4 Create MN audio paging group(s). manual

5 Set up the workstation priorities for an MN CCS station. manual

3.2.4 Subsidiary Equipment


The panels and network annunciators in this section may be present on an MN network without being part of an ACU, LOC or CCS.
They do not have local control when an MN alarm is active in the system unless fire is the highest priority and there is a fire alarm on the
panel or on a mapped node on the NCA-2. They are capable of initiating and annunciating an MN alarm, but can not perform acknowl-
edge, silence, or reset functions while an MN alarm is active in the system.

Subsidiary Equipment Programming Steps

NFS2-3030*/NCA-2

1 Set the mass notification priority. page 19

2 Set the DCC field. page 18

3 Map to MN nodes. page 23, page 23

4 Program with MN type IDs. page 24

5 Set the MN Control Field to Subsidiary. page 35


6 Program with MN Special Function Zones. page 25

*NFS2-3030 may be in standard or network display mode.

NFS2-640/NFS-320/SYS
1 Set the mass notification priority page 21

2 Set the DCC field. page 18

3 Map to MN nodes. page 24

4 Program with MN type IDs. page 24

5 Program with MN Special Function Zones. page 25

DVC
1 Set the MN Mode.* page 21

2 Set the Associated Node Number field. page 21

3 Program input categories and priorities. page 21, page 22

4 Create and program an MN Active Tone. page 25

5 Create and program a Fire Active Tone (when Fire is the highest priority). page 29

*MN paging levels are not installed when the DVC acts as a subsidiary device.

DVC-RPU
MN Paging Levels are not installed when the DVC-RPU acts as a subsidiary device.
Program the DVC-RPU label. Refer to “DVC-RPU” on page 33.
MN Annunciator Programming
Program an annunciator as a dedicated MN alarm annunciator (See page 34). Set an LCD2-80 to terminal mode (See page 34). Use DVC
General Zones Z501 - Z533 to annunciate LOC and ACU paging. Refer to “DVC General Zones” on page 34.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 17


Programming Programming

3.3 Programming
3.3.1 DCC Participation
In a system with both MN and Fire, DCC must always be disabled for all NFS-320/SYSs, NFS2-640s, NFS2-3030s, NCA-2s and
ONYXWorks Workstation.
NFS2-3030/NCA-2
Panel: In the Panel Settings Menu, set DCC Participation to NO PANEL SETTINGS
to disable DCC Participation. LCM LOCAL MODE: YES REGIONAL SETTINGS

POWER MANAGEMENT MODE:OFF

DCC PARTICIPATION: NO MORE

RAPID ALL CALL: NO ACCEPT

DEFAULT SETTINGS BACK

Figure 3.1 Panel Settings Screen (2), NFS2-3030

VeriFire Tools: Leave the Display and Control Center box unchecked in the NFS2-3030 and NCA-2. Do not enable DCC.
NFS2-3030 General Settings Branch, “General
Settings 1” column

NCA-2 General Settings Branch, “General


Settings 2” column
Leave
unchecked.

Figure 3.2 VeriFire Tools, NFS2-3030/NCA-2

NFS2-640/NFS-320/SYS
Panel: In the Utility Program Menu, set “DCC-mode” to “N” (no) to REGION=0 TBL.REMIND=2 ALA.SCROLL=N
disable DCC participation. LOCAL CONTROL=0 IP-ACCESS=0 DCC-mode:N

Figure 3.3 Utility Program, NFS2-640/NFS-320/SYS

18 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

VeriFire Tools: Leave the Display and Control Center box unchecked NFS2-640/NFS-320/SYS General Settings
in the NFS2-640 and NFS-320/SYS service. Branch, “General Settings 2” column

Leave
unchecked.

Figure 3.4 VeriFire Tools, NFS2-640/NFS-320/SYS

3.3.2 Mass Notification Control Settings for the DVC


Open the General Settings branch of the DVC System Programming Service in VeriFire Tools.
In the General Settings 3 column, set the MN Mode to LOC, ACU, or CCS. The Associated Node Number becomes available in the
Mass Notification Control Settings section.
Enter the node number of the NCA-2 or NFS2-3030 that is associated with the DVC. VeriFire Tools will set this to 0 (zero) if the DVC is
acting as a subsidiary device (i.e., it is not part of an ACU, LOC or CCS).
DVC General Settings Branch,
“General Settings 2” and “General Settings 3” columns

Enter node # of associated NCA-2 or NFS2-3030. If the DVC is acting as a


subsidiary device, 0 (zero) will be entered automatically.

Figure 3.5 DVC MN Mode Setting

3.3.3 Set the Priority


NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same priority settings. The established
priorities must be consistent throughout a system.
DVC will use the priority of the node with which it is associated.

NFS2-3030/NCA-2
This field allows the programmer to define the panel’s relative fire and MN priority. The priority may be set at the panel (See Figure 3.6)
or in VeriFire Tools. (See Figure 3.7).

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 19


Programming Programming

Panel: Navigate through the Panel Settings menu, pressing the


“More” softkey until “MN PRIORITY OVER FIRE” appears.
Press the softkey next to this selection until the appropriate PANEL SETTINGS
setting appears, then press “ACCEPT”. SILENCEABLE WATERFLOW: YES

Settings:
MN PRIORITY OVER FIRE: YES
• YES: MN is the highest priority.
• NO: Fire is the highest priority. SOUNDER BASE STANDBY POWER MON:OFF
• MNS NOT USED: The system is for fire protection only.
(Default) ACCEPT

BACK

Figure 3.6 Priority Setting - Panel

VeriFire Tools: On the VeriFire Tools General Settings NFS2-3030 General Settings Branch, “General
branch for NFS2-3030/NCA-2, select the appropriate setting Settings 3” column
from the pull-down menu for the “Mass Notification Priority”
field.
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than Fire
• Fire is a higher priority than Mass Notification

Mass NCA-2 General Settings Branch, “General


Notification Settings 2” column
Priority Field

Figure 3.7 Priority Setting - VeriFire Tools, NFS2-


3030/NCA-2

20 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

NFS2-640/NFS-320/SYS
This field allows the programmer to define the panel’s fire and MN NFS2-640/NFS-320/SYS General Settings Branch,
priority. “General Settings 2” column
On the VeriFire Tools General Settings branch for NFS2-640 or NFS-
320/SYS, select the appropriate setting from the pull-down menu for
the “Mass Notification Priority” field.
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than fire
• Fire is a higher priority than Mass Notification

Mass Notification Priority Field


Figure 3.8 Priority Setting - VeriFire Tools,
NFS2-640/NFS-320/SYS

DVC
 Set the Mode and Paging Level
On the VeriFire Tools General Settings branch for DVC,
select ACU, LOC, CCS, or Subsidiary from the MN
Mode pull-down menu in the DVC MN Mode box. DVC MN
Mode Field
A DVC that is not an ACU, LOC or CCS on an MN net-
work must be programmed as Subsidiary, and its Associ-
ated Node Number must be 0 (zero).
Select the Paging Levels to enable the ALL CALL but-
tons in the second column of the DVC-KD.
 Set the Input Category
Following are the Programmable Audio Matrix (PAM) Select the
Input Numbers, Default Priorities and Categories that paging levels
appear for a DVC when ACU, LOC, CCS, or Subsidiary to be used on
the DVC-KD.
is selected as the DVC MN Mode. The default priorities
for the first 12 inputs comply with the priorities specified
in UL2572 in that at each level ACU is the highest prior-
ity and CCS is the lowest.
DVC-KD Level buttons in the second column page as
follows:
Figure 3.9 Setting DVC MN Mode & Paging Level
• Top button (Level 1) - always pages Inputs 1, 3, or
5, depending on whether the DVC is an ACU, LOC
or CCS.
• Second button (Level 2) - always pages Inputs 7, 9, or 11, depending on whether the DVC is an ACU, LOC or CCS.
• Third button (Level 3) - always pages Input 13.
Input Categories are Fire, MN, General, and MN Active Tone:
• When ACU, LOC, CCS, or Subsidiary is selected as a mode, Level 1 inputs default to the MN category, and Level 2 inputs default
to the Fire category.
• “MN Active Tone” is a category (it is assigned to a sequence, there is no default), and it must be assigned only to the MN Active
Tone message sequence (See pages 25–28).

Input Number Input Source Default Priority Category


1 ACU Local Paging Level 1 1 MN
2 ACU Network Paging Level 1 2 MN
3 LOC Local Paging Level 1 3 MN
4 LOC Network Paging Level 1 4 MN
5 CCS Local Paging Level 1 5 MN
6 CCS Network Paging Level 1 6 MN

Table 3.1 Default Input Priorities, MN Mode Selected

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 21


Programming Programming

Input Number Input Source Default Priority Category


7 ACU Local Paging Level 2 7 Fire
8 ACU Network Paging Level 2 8 Fire
9 LOC Local Paging Level 2 9 Fire
10 LOC Network Paging Level 2 10 Fire
11 CCS Local Paging Level 2 11 Fire
12 CCS Network Paging Level 2 12 Fire
13 Local General Paging 13 General
14 Network General Paging 14 General

Table 3.1 Default Input Priorities, MN Mode Selected

If an input categorized as MN goes active, ZF20 activates and can suppress fire signals for all nodes in the MN mapping when MN is the
highest priority in the system.
Open the DVC Inputs branch. Because the DVC is set to ACU, LOC, CCS or Subsidiary mode, the first 14 Input lines will show MN
default input priorities. Assign the MN category to mass notification inputs, the Fire category to fire inputs, the MN Active Tone cate-
gory to the MN Active Tone input, and the General category to inputs that are neither MN, Fire, or MN Active Tone.

Select Category from the Use the Up & Down buttons to reassign
drop-down choices. the priority of an input.

Assign categories to all


Inputs as appropriate.

If MN is the highest priority


in the system, select the
MN category for all Level 1
Inputs and the Fire
category for all Level 2
Inputs.
Level 1
If Fire is the highest priority Inputs
in the system, select the
Fire category for all Level 1
Inputs and the MN
category for all Level 2
Inputs.
Level 2
Assign the MN Active Tone Inputs
category to the MN Active
Tone input.

If a Fire Active Tone input


is required, assign it to the
Fire category

Note: Inputs 31-1000 represent


Audio Message Sequences, created
and labeled on the DVC’s Audio
Settings branch as described in the
DVC Manual.

Figure 3.10 DVC Input Priority and Category Settings

 Set the Input Priority


The priority for input sources can be modified from the default priority. The priority of the inputs should be modified to group inputs of
similar categories together. That is, in a system that has prioritized MN events over fire, all inputs associated with MN should be
assigned to the “MN” category and re-prioritized to be higher than fire inputs. “Fire” category inputs should be prioritized above “Gen-
eral” category inputs. Figure 3.15 on page 27 illustrates inputs grouped and prioritized by category.
The priority of the input is also used to prioritize network audio. In a system that utilizes multiple DVCs, the default configuration
assigns priority to the local microphone input over the microphone input from a network source. To prioritize a network DVC over the
local DVC, reassign the priority for the Network Paging rows to a lower number (and therefore a higher priority) than that of the Local
Paging rows.

22 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

In systems that implement multiple network audio sources, the priority of the network sources will be determined by the priority
assigned to the active input on the network source. For example, a DVC that is sending an ACU Local Paging Level 1 of priority 1 to a
network DVC will take priority over a DVC that is sending an ACU Local Paging level 2 of priority 7 to the same DVC. In the event of
the priority levels being identical for multiple network audio sources, the first source to activate will be granted priority.
ONYXWorks Workstation
1. Set the workstation to FCC Mode.
2. Create MN audio paging group(s).
3. Set up the workstation priorities for an MN CCS station. In Figure 3.10, Inputs are shown in their fixed order, which comply with
UL2572. CCS Inputs are:
• 5 (CCS Local Paging Level 1)
• 11 (CCS Local Paging Level 2)
• 13 (Local General Paging)
3.3.4 MN Mapping
MN Mapping determines if a ZF20 MN alarm will suppress fire events at the panel if there is an active MN alarm at another node and
MN is the highest priority.
NFS2-3030 in Network Display Mode
NETWORK MAPPING
MN network mapping may be done at the panel or in Veri-
Fire Tools. SCREEN 1 of 15
001:OFFLINE / 002:OFFLINE /
Panel: Navigate to the Panel Program Menu 1 screen. Press 003:ONLINE /MAPPED 004:OFFLINE /
005:OFFLINE / 006:OFFLINE /
the softkey next to NETWORK MAPPING to bring up the 007:OFFLINE / 008:OFFLINE /
009:ONLINE /MAPPED 010:OFFLINE /
screen shown in Figure 3.11. The panel will monitor the 012:OFFLINE / 012:OFFLINE /
nodes mapped here for MN alarm messages in order to sup- 013:OFFLINE / 014:OFFLINE /
015:OFFLINE / 016:OFFLINE /
press fire.
AUTO PROGRAM ACCEPT

NEXT BACK

Figure 3.11 Network Mapping Screen, NFS2-3030

VeriFire Tools: In the Network Mapping branch of VeriFire Tools, select the nodes in the Mass Notification column that the panel will
monitor for MN alarm messages in order to suppress fire.

Check boxes for


the nodes to be
monitored for MN
events (a
maximum of four
DVCs and one fire
panel). The
NFS2-3030 node
being
programmed is
grayed out and
unavailable.

Figure 3.12 MN Mapping, NFS2-3030

NCA-2
NCA-2 Network event mapping defines its MN mapping; there is no unique MN mapping for the NCA-2.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 23


Programming Programming

NFS2-640, NFS-320/SYS Mass Notification Mapping Column


MN network mapping allows the programmer to
select the Noti•Fire•Net nodes from which the
NFS2-640 or NFS-320/SYS will accept an MN
alarm message to initiate fire suppression.
On the NFS2-640 or NFS-320/SYS Network Map-
ping branch of VeriFire Tools, check the appropriate
boxes in the Mass Notification mapping column.

Figure 3.13 MN Mapping, NFS2-640/NFS-320/SYS

DVC
DVC MN mapping consists of:
• Creating a logic equation for the MN Active Tone that will activate if a ZF20 MN alarm comes in from any MN-mapped node.
Refer to Section 3.3.7 on page 25 for this programming.
• All Call mapping in VeriFire Tools. MN pages will go out to the nodes in this map. Refer to the programming section of the DVC
manual for VeriFire Tools programming.

3.3.5 Type IDs


Program inputs and outputs dedicated to mass notification with MN Type IDs. Outputs with combined functions may use other type IDs.
Table 3.1 lists and describes MN monitor module Type IDs.

Point Characteristics

Type Code Point Type Latching


Activates
(Y=yes Device Function
CBE
N=no)

ECS/MN MONITOR MN Alarm Y Y Mass Notification alarm monitoring device.

ECS/MN SUPT MN N Y Indicates tracking supervisory condition.


Supervisory

ECS/MN SUPL MN Y Y Indicates latching supervisory condition.


Supervisory

ECS/MN TROUBLE Trouble N N Generates a trouble for both short and open
MON circuit conditions.

Table 3.1 MN Monitor Type IDs


Monitor module activations with these Type IDs will generate mass notification events locally and over a network. Trouble conditions at
these points will generate an MN trouble.

24 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

Table 3.2 lists and describes MN control module and panel bell circuit Type IDs.

Point Characteristics
Point
Type Code Switch Walk
Type Silenceable Device Function
Inhibit Test

MNS NAC N N N Mass notification supervised output.


GENERAL

MNS NAC N N N Mass notification supervised NAC.


CONTROL

MNS NAC N N N Mass notification supervised NAC.


STROBE
MNS NAC N N N Mass notification supervised NAC for speaker
SPEAKER circuits.

MNS RELAY Relay N N N Mass notification relay output.

Table 3.2 MN Control Type IDs


Activations will generate mass notification events locally and over a network. Trouble conditions at these points will generate MN trou-
bles.

3.3.6 Special Function Zones


The MN Special Function Zones in Table 3.3 below activate when an MN alarm, supervisory, or trouble event occurs.

NOTE: Use ZF20 in the map of an LED annunciator programmed with a “monitor” mode as a dedicated MN alarm indicator.

Special
Function Name Description
Code

ZF20 MN Alarm Zone Activates for local events and network ZF20 activations when an MN alarm is present in the system. It
suppresses fire protection when MN is prioritized as higher than fire (see “Output Event Suppression” on
page 40). It is sent out to the network, and each networked panel will check the ZF20’s source against its
table of mapped MN nodes. If the source has a match in the table, fire protection will be suppressed in the
panel that made the match. Logic equations will be activated.

ZF21 MN Supervisory Activates for local events when there is an MN supervisory in the system.
Zone

ZF22 MN Trouble Activates for local events when an MN trouble occurs.


Zone

Table 3.3 MN Special Function Zones


The MN Special Function Zones are available as indicated in Table 3.4.

ZF20 ZF21 ZF22

NFS2-3030   
NCA-2

NFS2-640/NFS-320/SYS   
DVC 
ONYXWorks Workstation 

Table 3.4 MN Special Function Zone Availability

3.3.7 MN Active Tone


When MN has the highest priority in a network and the DVC is operating in Mass Notification mode, it must be programmed in VeriFire
Tools to generate an “MN Active Tone”. This programming is required for two reasons:
• It generates an audible reminder every 30 seconds that MN has control of the system and that fire signals may be suppressed if MN
is the highest priority.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 25


Programming Programming

• It suppresses fire sequences and pages that come below it in priority, until an MN reset clears the “MN Active Tone”.
NOTE: Fire or OTHER sequences and pages will not be suppressed for MN alarms without the MN Active Tone, properly prioritized in the
PAM.

Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the MN Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 27.)
3. Create MN Logic Zones. (See page 28.)
4. Add MN Active Tone Logic to PAM Programming. (See page 28.)
Detailed Procedures
 Build the MN Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the MN Active Tone audio sequence on the Message
Sequences tab.
1. Select and expand a sequence in the
Message Sequences Number column.
This example uses Sequence 1. Assign
the sequence an Evac message type.
2. Type “MN Active Tone” in the Label
field.
3. Select Command File for “Play
Forever” for Sequence Step 1.
4. Select Wave File for “Active Tone” for
Sequence Step 2.
5. Select Command File for “End Play” for
Sequence Step 3.
6. Press Play Sequence to listen to and
review the sequence as a test. The
Play Forever command will play 200
times as a test, will play forever in a
non-test situation. Use the audio-player
buttons to pause and restart playback.
7. Press Save.

Figure 3.14 Creating an MN Active Tone Sequence

26 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

 Assign Message Priorities


Open the DVC Inputs branch of VeriFire Tools DVC programming, scroll down to the MN Active Tone Sequence. Assign the MN
Active Tone Category to the MN Active Tone sequence, and give it the priority just below the MN Category inputs. When MN is the
highest priority in the system, the MN Active Tone input will be the priority just above the Fire category of pages. When Fire is the high-
est priority in the system, the MN Active Tone input will be at the priority just above the General category of pages and sequences.

Example: MN has the highest Input number is display and sort only.
priority, and the MN Active Tone
Category has been assigned to Input Change priority of inputs with the Up and Down buttons.
31, the MN Active Tone (Message
Sequence 1 from Figure 3.14). It has
been assigned a priority of 8, just
below the MN Category inputs and
above the Fire Category inputs.

Priorities 1 - 7,
MN Message
Category

Priority 8, MN Active
Tone Category,
Sequence 2 (the MN
Active Tone)

Priorities 9 - 16,
Fire Message
Category

Figure 3.15 Assign Priority to the MN Active Tone Sequence

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 27


Programming Programming

 Create MN Logic Zones


Create a logic zone that will activate if a ZF20 MN alarm comes in from any MN-mapped node.

1. Select “OR” as the function.


2. Select “Special Function” ZF20 as the point,
and link it to each MN-mapped node on the
system.
3. Close the equation with a parenthesis, and
save changes.
4. Add label “MN Active Tone” (optional.)
5. In this example, ZL1 is the Logic Zone
programmed to activate when a ZF20 MN
alarm comes in from any MN-mapped node.
All MN-mapped nodes must be included in
the logic equation. In this example, there are
three in the system, so all three are in the
equation.

Figure 3.16 Create a Logic Sequence for the MN Active Tone

 Add MN Active Tone Logic to PAM Programming


On the PAM Settings branch, add the Logic Zone created in Figure 3.16 above to the entire MN Active Tone Input row (Input 31,
Sequence 1 in this example).

Add the MN Active Tone logic


equation to the entire Input row
for the MN Active Tone
Sequence.
In this example, Logic Zone 1 is
being added to all the cells in
Input row 31.

Figure 3.17 Map the MN Active Tone Sequence to a Logic Zone

28 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

3.3.8 Fire Active Tone


When Fire is the highest priority in a system, a DVC must be programmed in VeriFire Tools to generate a “Fire Active Tone”. This pro-
gramming is required for two reasons:
• It generates an audible reminder every 30 seconds that Fire has control of the system and that MN signals may be suppressed.
• It suppresses MN sequences and pages that come below it in priority, until a fire reset clears the “Fire Active Tone”.
NOTE: MN or OTHER sequences and pages will not be suppressed for fire alarms without the Fire Active Tone, properly prioritized in the
PAM.

Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the Fire Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 30.)
3. Create Fire Logic Zones. (See page 31.)
4. Add Fire Logic Zones to PAM Programming. (See page 31.)
Detailed Procedures
 Build the Fire Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the Fire Active Tone audio sequence on the Message
Sequences tab.
1. Select and expand a sequence in the
Message Sequences Number column.
This example uses Sequence 6 Assign
the sequence an Evac message type.
2. Type “Fire Active Tone” in the Label
field.
3. Select Command File for “Play
Forever” for Sequence Step 1.
4. Select Wave File for “Active Tone” for
Sequence Step 2.
5. Select Command File for “End Play” for
Sequence Step 3.
6. Press Play Sequence to listen to and
review the sequence as a test. The
Play Forever command will play 200
times as a test, will play forever in a
non-test situation. Use the audio-player
buttons to pause and restart playback.
7. Press Save.

Figure 3.18 Creating a Fire Active Tone Sequence

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 29


Programming Programming

 Assign Message Priorities


Open the DVC Inputs branch of VeriFire Tools DVC programming, scroll down to the Fire Active Tone Sequence. Assign the Fire Cate-
gory to the Fire Active Tone sequence, and give it the priority just below the Fire Category inputs. When MN is the highest priority in the
system, the MN Active Tone input will be the priority just above the Fire category of pages. When Fire is the highest priority in the sys-
tem, the MN Active Tone input will be at the priority just above the General category of pages and sequences.

Example: Fire has the highest Input number is display and sort only.
priority, and the Fire Category has
been assigned to Input 36, the Fire Change priority of inputs with the Up and Down buttons.
Active Tone (Message Sequence 6
from Figure 3.18). It has been
assigned a priority of 8, just below
the Fire Category inputs and above
the MN Category inputs.

Priorities 1 - 7,
Fire Message
Category

Priority 8, Fire
Category, Sequence 6
(the Fire Active Tone)

Priorities 9 - 16,
MN Message
Category

Figure 3.19 Assign Priority to the Fire Active Tone Sequence

30 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

 Create Fire Logic Zones


The logic equation for the Fire Active Tone sequence must reference all DVC, panel, and NCA-2 nodes on the network. Write an OR
logic equation that includes the local DVC’s general zone, the general zones on the other networked DVCs, and the general alarm zones
on the networked fire panels. The example in Figure 3.20 assumes a network with two DVCs, three fire alarm control panels, and one
network control annunciator.

1. Select “OR” as the function.


2. Select Zone Z1.
3. Select Zone Z1 on networked DVC nodes.
4. Select Zone Z0 on networked FACP nodes
and network control annunciators.
5. Close the equation with a parenthesis, and
save changes.
6. Add label “Fire Active Tone” (optional).
7. In this example, In this example, ZL3 is the
Logic Zone programmed for activation of the
Fire Active Tone.

Figure 3.20 Create a Logic Equation to Activate Fire Active Tone

 Add Fire Logic Zones to PAM Programming


On the PAM Settings branch:
1. Map a common general zone (for example, Z1) to all the PAM points designated as the Fire category. Select PAM View “All CBEs”
for quick data-entry.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 31


Programming Programming

2. Add the Logic Zone created in Figure 3.21 to all PAM Points in the row for Fire Active Tone. Select PAM View “Logic Equations”
for quick data-entry.

Add the common general zone to


all PAM points designated as “Fire”.

This example uses General Zone


Z1 created in Figure 3.21.

Add the Fire Active Tone logic


equation to all PAM points in the
row for the Fire Active Tone input.

This example uses Logic Zone ZL3


created in Figure 3.21.

Figure 3.21 Map the Fire Active Tone Sequence to a Logic Zone

32 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

3.3.9 DVC-RPU
On the DAL Mapping branch, install a DVC-RPU by selecting Device Type RPU-PCC at the appropriate address. Click on the address’s
row and edit the device-specific information where it displays at the bottom of the screen.

1. Addressing: The DVC-RPU’s


DAL address on its node must be
set to be the same as the RDP
bus address for the LCD-160 on
its node. See 3.3.10, "LCD-160"
section, below.
2. On the device’s General Settings
tab, select the Paging Levels to
enable the ALL CALL buttons in
the second column of the DVC-
KD.
3. RPU Label. Type a free-form
label description to identify it as
source of an MN page, which
generates an MN alarm
condition.

Figure 3.22 DVC-RPU Paging Levels and Labeling

3.3.10 LCD-160
To act as an LOC, the DVC-RPU requires an LCD-160 that is
wired to the DVC’s NCA-2, or NFS2-3030 (in network display
mode). The LCD-160’s Remote Display (RDP) bus address must
be the same address as the DVC-RPU’s Digital Audio Loop
(DAL) address.
In this example, the LCD-160 is at Node 3 Address 10
(Figure 3.23), and the DVC-RPU is at Node 16 DAL Address 10
(Figure 3.22).

Figure 3.23 LCD-160 Address

CAUTION: THE DVC-RPU ADDRESS MUST EQUAL THE LCD-160 ADDRESS ON THE RDP BUS
! ADDRESSING IS CRITICAL TO COMMAND OPERATIONS. THE DVC-RPU ADDRESS ON THE DIGITAL AUDIO LOOP
MUST EQUAL THE LCD-160 ADDRESS ON THE RDP BUS.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 33


Programming Programming

Linked through DVC Mass


Notification Control Settings,
“Associated Node Number” setting
NCA-2 or in Veri-Fire Tools DVC
NFS2-3030

LCD-160 DVC-RPU
RDP Bus DAL
Address 5 Address 5
on RPD Bus on DAL

LCD-160 and DVC-RPU


have same address
number

Figure 3.24 Block Diagram Illustrating Address Link

3.3.11 MN Annunciator Programming


Dedicated MN Alarm Annunciator
An ACM-24AT, AEM-24AT, or DVC-KD LED annunciator, programmed as a dedicated MN alarm annunciator, is required for each
NFS2-640, NFS-320/SYS, NFS2-3030 and NCA-2 on an MN network.
 NFS2-3030 and NCA-2
A dedicated annunciator may be programmed to light when a ZF20 MN Special Function Zone activates, indicating an MN alarm.
• Programming special function zone ZF20 in an LED annunciator map will cause the annunciator to light when a local MN alarm is
activated.
• To annunciate an MN alarm for a specific network node, map an annunciator point to that specific network node and ZF20 (e.g.
N3ZF20).
 NFS2-640 and NFS-320/SYS
A dedicated annunciator must be programmed to light when a ZF20 MN Special Function Zone activates, indicating an MN alarm. Use
custom annunciator mapping in VeriFire Tools to map ZF20 to an LED annunciator.
• Select a custom annunciator group user map.
• Program the desired annunciator point with ZF20.
 DVC-KD
A DVC-KD user-defined point may be programmed to light when an MN alarm activates. In VeriFire Tools DVC-KD programming,
select “Monitor” as the Function. Map to light when a local MN alarm event (mapping = ZF20) or an MN alarm event from network
nodes (Mapping = a logic equation that includes ZF20 on desired network nodes).
LCD2-80
When an LCD2-80 is connected to an NCA-2, NFS2-3030, NFS2-640, or NFS-320/SYS, it must be set to Terminal Mode. The panel it
is connected to must be subsidiary.

NOTE: The LCD2-80, as well as the LCD-160, may not be used as a primary display for mass notification events.

NOTE: A dedicated alarm annunciator is not required if a panel is a displayless node.

3.3.12 DVC General Zones


General Zones 501-533 activate whenever microphone paging is active from a DVC, RPU or ONYXWorks Workstation. Zones 501-532
activate with paging from DVC-RPU addresses 1-32, and zone 533 activates with paging from the DVC or ONYXWorks Workstation.
These zones may be monitored anywhere in the system to annunciate active paging from a location. They must be used in logic equa-
tions to achieve further granularity of the type of page being performed.

34 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Programming Programming

3.3.13 MN Control Label


This field provides values of Subsidiary, ACU, LOC and CCS.
Select the MN function provided by the NFS2-3030 or NCA-2. This
field can be set at the panel or in VeriFire Tools.
PANEL
Subsidiary: Make this selection when the NFS2-3030 or NCA-2 is SETTINGS
present on the network, but not acting as an ACU, LOC or CCS.
ACU, LOC or CCS: Make the appropriate entry. The NFS2-3030 or SILENCEABLE WATERFLOW:_NO
NCA-2 entry should match the DVC’s MN status.

MN PRIORITY OVER

Select the applicable MN configuration type, or select


Subsidiary if the NFS2-3030 or NCA-2 is not an ACU,
LOC or CCS.

Figure 3.25 MN Control, Panel

NFS2-3030 General Settings Branch, “General Settings NCA-2 General Settings Branch, “General Settings 2”
1” column column

Select the applicable MN configuration type, or select Subsidiary if


the NFS2-3030 or NCA-2 is not an ACU, LOC or CCS.

Figure 3.26 MN Control, VeriFire Tools, NFS2-3030/NCA-2

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 35


Section 4: Operation
4.1 Mass Notification Events
Special zones ZF20 (MN alarm), ZF21 (MN supervisory), and ZF22 (MN trouble) are used to signal mass notification events locally and
over Noti•Fire•Net. If MN has the highest priority in the system, a ZF20 (MN alarm) will suppress fire locally and for every node in the
initiating node’s MN map.

4.1.1 MN Alarm
Activating an MN Alarm
An MN alarm can be activated by any of the following events:
1. Paging at the MN level.
2. Activation of an MN Alarm Type Code on an ONYX panel.
3. Pressing an annunciator or DVC-KD control point programmed to activate an MN alarm message.
NFS2-3030, NCA-2 MN Activations
 Local Activation
When an MN alarm activates locally, it:
• Produces a steady audible tone if the piezo is enabled.
• Flashes the “OTHER” LED for NFS2-3030/NCA-2.
• Does not activate the alarm relays.
• Displays MN ALARM in the upper left corner of the display of NFS2-3030, NCA-2, and LCD-160, as well as other information
specific to the alarm. Displays as MN ALM on LCD2-80/LCD-80 in terminal mode.
• Activates Special Function Zone ZF20 (MN alarm zone).
• Suppresses fire alarms if MN has the highest priority (refer to “Output Event Suppression” on page 40)
• Activates “General Pending” type code at the NFS2-3030.
• Does not activate “General Alarm” or “Alarm Pending” type codes.
• Is acknowledged individually.
• Scrolls using “Other Event/Scroll Display” key.
• Any device programmed for “Resound by Fire” will not resound.
• Increments the OTHER counter in the event counts display.
• Sends an MN alarm message to the history buffer and installed printer and annunciators.
• Appears as “MNA” in the Multiple Events list screen, grouped under “MN Alarm”.
• Latches the control panel in alarm. The control panel will not return to normal operation until the alarm condition is corrected and
the control panel is reset. Resets require two presses of the reset button if both MN and Fire events are present in the system. The
first press will reset the MN events, the second will reset the rest.
• Initiates any Control-By-Event (CBE) actions. If the node goes off-line, active logic equations with ZF20 in them will stay active
until MN reset.
• Sends an MN alarm message (ZF20) out to the network.
 Network Activation
When an MN alarm is sent out to the network from the initiating node, each node on Noti•Fire•Net will check its MN map to determine
if it should react to the MN alarm. If a node has been programmed with the initiating node in its MN map, it will accept the MN alarm
from Noti•Fire•Net and react according to its programming.
• Logic equations with Special Function Zone ZF20 (MN alarm zone) in them will be evaluated.
• Fire alarms are suppressed if MN has the highest priority (Refer to “Output Event Suppression” on page 40).
• If the system is “ALL SYSTEMS NORMAL”, NETWORK MN ACTIVE will display.
NFS2-640, NFS-320/SYS MN Activation
 Local Activation
When an MN alarm activates locally, it:
• Produces a steady audible tone if the piezo is enabled.
• Illuminates the ACS LED dedicated to MN alarms (required for the NFS2-640 and NFS-320/SYS). No LED on the panel lights for
an MN alarm.
• Does not activate the alarm relays.
• Displays ALARM:ECS/MN MON in the upper left corner of the display, as well as other information specific to the alarm.
Displays MN ALM on LCD2-80/LCD-80 in terminal mode.
• Activates Special Function Zone ZF20 (MN alarm zone).
• Suppresses fire alarms if MN has the highest priority (refer to “Output Event Suppression” on page 40).
• Does not activate “General Alarm” or “Alarm Pending” type codes.
• Is block acknowledged in scrolling mode, acknowledged one-by-one in non-scrolling mode.

36 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Mass Notification Events Operation

• Any device programmed for “Resound by Fire” will not resound.


• Sends an MN alarm message to the history buffer and installed printer and annunciators.
• Latches the control panel in alarm. The control panel will not return to normal operation until the alarm condition is corrected and
the control panel is reset. Resets require two presses of the reset button if both MN and Fire events are present in the system. The
first press will reset the MN events, the second will reset the rest.
• Initiates any Control-By-Event (CBE) actions. If the node goes off-line, active logic equations with ZF20 in them will stay active
until MN reset.
• Sends an MN alarm message (ZF20) out to the network.
 Network Activation
• Logic equations with Special Function Zone ZF20 (MN alarm zone) in them will be evaluated.
• Fire alarms are suppressed if MN has the highest priority (Refer to “Output Event Suppression” on page 40).
• If the system is “ALL SYSTEMS NORMAL”, MN ALARM will display.
DVC
 Local Activation
When an MN alarm message or page activates on the DVC or DVC-RPU the alarm is sent out to the network.
 Network Activation
• Logic equations with ZF20 in them will be evaluated.

4.1.2 MN Supervisory
MN Supervisory Activation
An MN supervisory message can be activated by an MN Supervisory Type Code on an ONYX panel.

NOTE: MN supervisories are block acknowledged.

NFS2-3030, NCA-2 MN Activations


 Local Activation
When an MN supervisory activates locally, it:
• Produces a warbling audible tone if the piezo is enabled.
• Activates the panel’s supervisory relay.
• Flashes the SUPERVISORY yellow LED.
• Activates Special Function Zone ZF21 (MN supervisory zone).
• Does not suppress Fire or any other activations.
• Increments the supervisory counter on the Events Code screen.
• Is acknowledged with a block acknowledgement.
• Uses the “Supervisory Scroll” key for scrolling.
• Activates “General Pending” type code at the NFS2-3030.
• Activates “General Supervisory” type code at the NFS2-3030.
• Any device programmed for “Resound by Supervisory” will not resound.
• Displays MN SUPERVISORY in the upper left corner of the display, as well as other information specific to the supervisory
message, for the NFS2-3030, NCA-2, LCD-160. Displays MN SUP on the LCD2-80.
• Is a latching or tracking event based on Type ID (see Table 3.2 on page 25). The control panel will not return to normal operation
until the supervisory condition is corrected and the control panel is reset. Resets require two presses of the reset button if both MN
and Fire events are present in the system. The first press will reset the MN events, the second will reset the rest.
• Sends an MN Supervisory message to the history buffer and installed printer and annunciators.
• Appears as “MNS” in the Multiple Events list screen, grouped under “SUPERVISORY”.
• Sends an MN supervisory message (ZF21) out to the network.
• Resets require two presses of the reset button if both MN and fire evetns are present in the system. The first press will reset the MN
events, the second will reset the rest.
 Network Activation
• Logic Zones with ZF21 (MN supervisory zone) will be evaluated.

NFS2-640, NFS-320/SYS MN Activation


 Local Activation
When an MN supervisory activates locally, it:
• Produces a warbling audible tone if the piezo is enabled.
• Activates the panel’s supervisory relay.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 37


Operation Mass Notification Events

• Flashes the SUPERVISORY yellow LED.


• Activates Special Function Zone ZF21 (MN supervisory zone).
• Does not suppress Fire or any other activations.
• Does not activate “General Supervisory” type ID.
• Any device programmed for “Resound by Supervisory” will not resound.
• Displays ACTIVE:ECS/MN SUPT or ACTIVE:ECS-MN SUPL in the display, as well as other information specific to the
supervisory message.
• Sends an MN Supervisory message to the history buffer and installed printer and annunciators.
• Sends an MN supervisory message (ZF21) out to the network.
 Network Activation
• Logic Zones with ZF21 (MN supervisory zone) will be evaluated.

4.1.3 MN Trouble
MN Trouble Activation

NOTE: MN troubles are block acknowledged.

NFS2-3030, NCA-2 MN Activations


 Local Activation
When an MN trouble activates locally, it:
• Produces a pulsed audible tone if the piezo is enabled.
• Activates the panel’s trouble relay.
• Flashes the TROUBLE yellow LED.
• Activates Special Function Zone ZF22 (MN trouble zone).
• Does not suppress Fire or any other activations.
• Is acknowledged with a block acknowledgement.
• Uses the TROUBLE/SCROLL DISPLAY key for scrolling.
• Increments the trouble counter on the Events Code screen.
• Activates “General Pending” type code at the NFS2-3030
• Activates “General Trouble” and “Trouble Pending” type codes at the NFS2-3030.
• Any device programmed for “Resound by Trouble” will not resound.
• Displays MN TROUBLE in the upper left corner of the display, as well as other information specific to the supervisory message.
• Sends an MN trouble message to the history buffer and installed printer and annunciators.
• Appears as “MNT” in the Multiple Events list screen, grouped under “TROUBLE”.
• Sends an MN trouble message (ZF22) out to the network.
 Network Activation
• NETWORK MN ACTIVE will display if all systems are normal.
• Logic Zones with ZF22 (MN trouble zone) will be evaluated.
NFS2-640, NFS-320/SYS MN Activation
 Local Activation
When an MN trouble activates locally, it:
• Produces a pulsed audible tone if the piezo is enabled.
• Activates the panel’s trouble relay.
• Flashes the TROUBLE yellow LED.
• Activates Special Function Zone ZF22 (MN trouble zone).
• Does not suppress Fire or any other activations.
• Does not activate “General Supervisory” type ID.
• Any device programmed for “Resound by Trouble” will not resound.
• Activates “General Trouble” or “Trouble Pending” type code.
• Sends an MN Trouble message to the history buffer and installed printer and annunciators.
• Sends an MN trouble message (ZF22) out to the network.
 Network Activation
• Logic Zones with ZF22 (MN trouble zone) will be evaluated.

38 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Performing a System Reset Operation

4.2 Performing a System Reset


If both fire and MN events are present in the system, two button presses are required to reset the system. The first button press resets the
highest priority events, the second press resets the lowest priority events. When the first button press resets the highest priority events,
the lower priority events will resound, if necessary.
For example, when MN has the highest priority in a system, resetting a panel after an MN event has concluded requires two button
presses if there are fire events in the system. The first button press clears the MN alarms and supervisories, the second will reset the other
system events.
The NCA-2, NFS2-3030 and LCD-160 display the following text at the reset softkey, to indicate the type of reset being performed.
• FIRE SYSTEM RESET - indicates the reset is for fire events.
• MN SYSTEM RESET - indicates the reset is for mass notification events.
ONYXWorks Workstation displays different buttons for the different reset types.

A “U-turn” arrow indicates the reset is for fire events.

A “U-turn” arrow with a speaker indicates the reset


if for mass notification events.

Figure 4.1 ONYXWorks Workstation Resets


An MN system reset is sent out over Noti•Fire•Net and picked up by participating MN nodes and the MN event will automatically clear
from their local systems.
MN and Fire Events Present in System
MN is the highest priority: When both MN and fire events are present in the system, and MN events have the highest priority, press the
panel’s reset button to:
• Reset MN alarms and supervisories only (ZF20 and ZF21 activations, refer to “Special Function Zones” on page 25), clearing them
from the display and counters.
• Display an MN system reset message on the panel display, as well as on an LCD-160 if one is present.
• Turn off the “Other” LED if no active “other” events are in the system (NFS2-3030, NCA-2 only).
• Output processing:
– Turn back ON suppressed outputs (silenceable fire outputs, strobes).
– Clear general zones mapped to the MN events being cleared.
– Run logic equations.
– Re-evaluate outputs.
• Add an MN system reset entry to printer and history to indicate the MN events were reset.
• Send reset message for MN alarms and supervisories out to Noti•Fire•Net.
All network nodes will go through a 10 second decouple time.
Pressing Reset a second time will reset remaining system events.
Fire is the highest priority: When fire is the highest priority, press the panel’s reset button to:
• Reset all events except MN events.
Pressing Reset a second time will reset MN events, and send a reset message for MN alarms and supervisories out to Noti•Fire•Net.
MN Events Only Present in System
When MN events have the highest priority and no other types of events are present in the system, pressing the panel’s Reset button once
will:
• Reset MN alarms and supervisories only (ZF20 and ZF21 activations), clearing them from the display and counters.
• Display an MN network reset on the panel display, as well as on an LCD-160 if one is present.
• Turn off the “Other” LED if no active “other” events are in the system (NFS2-3030, NCA-2 only).
• Output processing:
– Clear general zones mapped to the MN events being cleared.
– Run logic equations.
– Re-evaluate outputs.
• Add an MN system reset entry to printer and history to indicate the MN events were reset.
• Send reset message for MN alarms and supervisories out to Noti•Fire•Net.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 39


Operation Output Event Suppression

All network nodes will go through a 10 second decouple time. An MN reset may require up to 60 seconds of decouple time depending on
the complexity of logic equation evaluations.
Fire Events Only Present in System
When MN events have the highest priority and only fire events are present in the system, pressing the panel’s Reset button will reset the
system.

4.3 Output Event Suppression


Event suppression results from automatic panel suppression as well as programming. Following is a list of factors to keep in mind during
system setup to achieve the desired event suppression.
 General Considerations for MN and Fire:
• General zones and logic zones are not suppressed by an MN or Fire event. Output device and zone map programming determine
whether an output will be suppressed, not the state of the zone.
• A general zone tracks the type of event (i.e. MN or Fire) that initiates its activation, and its outputs will be suppressed or resounded
automatically by panel programming. Suppression of outputs activated by general zones is dependent upon the event type that
initiated its activation.
• Each general zone must be dedicated to a single event type. If a general zone is used for MN, that zone can not also be used for fire,
security, etc..
• An output device, such as a horn or strobe, can be mapped to multiple zones. The zones can be general zones, special function
zones, logic zones, or releasing zones. These zones do not need to be the same event type: for example, a general zone used for MN
and a general zone used for Fire can be mapped to the same strobe.
• A logic zone does not automatically track the type of event that initiates its activation. Logic zones must be written to ensure
suppression. See examples below.
 MN is the Highest Priority
Zones:
• It is crucial that logic zones be written conditionally to ensure suppression. The following examples illustrate two ways to achieve
suppression using logic equations.
Example 1:
Output suppression using Logic Zone Programming and Special Function Zone ZF20
Logic equation ZL1 = AND(OR(Z10,Z11,Z12),NOT(ZF20)), mapped to an output that is used for fire and suppressed during MN.
Z10, Z11, and Z12 are dedicated fire zones.
ZF20 is the MN alarm zone.
If Z10, Z11, or Z12 is active, and ZF20 is not, ZL1 will go active.
If any MN alarm occurs, ZL1 will go inactive, and any outputs mapped to it may be suppressed.

Example 2:
Output suppression using Logic Zone Programming and MN-dedicated General Zones
Logic equation ZL2 = AND(OR(Z10,Z11,Z12),NOT(Z2)), mapped to an output that is used for fire and suppressed during MN.
Z10, Z11, and Z12 are dedicated fire zones.
Z2 is an MN alarm zone.
If Z10, Z11, or Z12 is active, and Z2 is not, ZL2 will go active.
If Z10, Z11, or Z12, and Z2 are active, ZL2 will go inactive, and any outputs mapped to it may be suppressed.
Outputs:
• All outputs used for MN must be programmed as non-silenceable. This includes those outputs that are shared between MN and
other events, such as Fire.
• Dedicated Fire outputs can be programmed as silenceable or non-silenceable.
• All silenceable outputs will be suppressed at the start of an MN event.*
• All devices programmed with strobe Type IDs, as well as all intelligent sounder bases, will be suppressed regardless of silenceable
programming at the start of an MN event.*
*Zone map programming will then be re-evaluated, and if a device contains ZF20, or any general zone dedicated to MN that is
active, in its zone map, it will be re-activated.
• An output programmed with a releasing Type ID, or programmed with an active releasing zone in its zone map, will not be
suppressed.
Audio:
• Fire sequences playing on a DAL (digital audio loop) will be silenced, and the DVC will sound the MN Active Tone while fire is
suppressed.
• Fire sequences on a DVC will not sound, and the DVC will sound the MN Active Tone while fire is suppressed.
Drill and custom drill operation is blocked while fire activations are suppressed. This prevents activation of fire outputs while a Mass
Notification is in progress.
When an MN alarm is cleared, suppressed outputs will reactivate, even if they were silenced prior to being suppressed

40 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Mass Notification Control Operation Operation

 Fire is the Highest Priority


Zones:
• It is crucial that logic zones be written conditionally to ensure suppression.
Example 1:
Output suppression using Logic Zone Programming and Special Function Zone ZF20
Logic equation ZL1 = AND(ZF20,NOT(OR(Z1,Z2,Z3))), mapped to an output that is used for both fire and MN.
Z1, Z2, and Z3 are dedicated fire zones.
ZF20 is the MN alarm zone.
IIf ZF20 is active, an Z1, Z2, or Z3 are not, ZL1 will go active.
If Z1, Z2, or Z3 subsequently goes active, ZL1 will go inactive, and any outputs mapped to it may be suppressed.

Example 2:
Output suppression using Logic Zone Programming and Fire-dedicated General Zones.
Logic equation ZL2 = AND(Z11,NOT(OR(Z1,Z2,Z3))).
Z1, Z2, and Z3 are dedicated fire zones.
Z11 is an MN alarm zone.
If Z11 is active, and Z1, Z2, or Z3 are not, ZL2 will go active.
If Z1, Z2, or Z3 subsequently go active, ZL2 will go inactive, and any outputs mapped to it may be suppressed.
• Special Function Zone ZF20 (MN alarm) must not be mapped to Fire outputs, as outputs mapped to ZF20 will not be suppressed.
WARNING: IF FIRE IS THE HIGHEST PRIORITY, DO NOT USE ZF20 FOR MASS NOTIFICATION
! DO NOT USE ZF20 TO TURN ON MASS NOTIFICATION-DEDICATED OUTPUTS WHEN FIRE IS THE HIGHEST
PRIORITY.

Outputs:
• All outputs used for MN must be programmed as non-silenceable. This includes those outputs that are shared between MN and
other events, such as Fire.
• Dedicated Fire outputs can be programmed as silenceable or non-silenceable.
• Outputs mapped to Special Function Zone ZF20 will not be suppressed. See Warning above.
Audio:
• MN sequences playing on a DVC will be silenced, and the DVC will sound the Fire Active Tone while MN is suppressed.
• MN sequences on a DVC will not sound, and the DVC will sound the Fire Active Tone while MN is suppressed.

4.4 Mass Notification Control Operation


For all panels and network annunciators except ONYXWorks Workstation, the “Controls Active” LED indicates if control functions are
enabled. Figure 4.2 shows the ONYXWorks Workstation control indications. If the controls active LED is off, or the ONYXWorks
Workstation control lockout icon is present, Acknowledge, Signal Silence, System Reset or Drill can not be performed. When the control
functions are blocked, the NCA-2, NFS2-3030 and LCD-160 display “Local Control Disabled” when an Acknowledge, Signal Silence,
System Reset or Drill is attempted.
Silence Reset
Acknowledge

If this red control lockout


icon is present on a
control button, the control
button will not work.
Figure 4.2 ONYXWorks Workstation Local Control Lockout Indication
Control will be given to an NFS2-3030 (in network display mode), NCA-2, LCD-160, or ONYXWorks Workstation only during an MN
page from that control unit. When no MN page is in progress, local control is active at each panel that does not have it disabled.
On panels that are not part of an ACU, LOC or CCS (subsidiaries), local control will be removed when a local MN alarm is active unless
fire is the highest priority and an active fire alarm is present on the panel or a mapped node on the NCA-2. A local MN alarm is one that
has initiated at the local panel, or one that has activated on a remote node that is MN mapped to the local panel. An LCD-160 will follow
the NFS2-3030 it is wired to, removing control when the panel does.
An MN page at a DVC will:
• Give control to its assigned NCA-2 or NFS2-3030, which will maintain its Controls Active LED on and maintain control functions
as unblocked.
• Turn off Control Active LEDs and block control functions at all other panels and annunciators.

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 41


Operation Paging

An MN page at a DVC-RPU will:


• Give control to its assigned LCD-160, which will maintain its Controls Active LED on and maintain control functions as
unblocked.
• Turn off Control Active LEDs and block control functions at all other panels and annunciators.
An MN alarm that is not activated by an MN page:
• NCA-2’s and NFS2-3030’s (in network display mode) will remain in control: their Controls Active LEDs will remain on and their
control functions will remain unblocked.
• NFS2-3030s not in network display mode, NFS2-640’s, and NFS-320/SYS’s will extinguish their Controls Active LEDs and their
control functions will be blocked.

4.5 Paging
When a system has MN capabilities, the second column on a MN Paging Button
(In the example shown, the system has MN as the highest priority.)
DVC or DVC-RPU keypad has three functional buttons repre-
senting three priority levels of paging. If MN is the highest
priority in the system, pressing the highest button will create POWER PAGE
LAMP TEST
an MN page locally and to all MN mapped nodes, initiating an TROUBLE
FRONT
PAGE 2nd
MN alarm and suppressing fire activations. If Fire is the high- DVC OFF-LINE MN FLOOR
MUSIC to
est priority, pressing the highest button in column two will MICROPHONE
PAGE
AUDITORIUM
TROUBLE
create a Fire page to all mapped nodes. Pressing the Level 3 PHONE REMOTE MIC
(GENERAL PAGE) button will create a general ALL CALL TROUBLE
FFT
BUSY / WAIT
page that will not suppress any fire activations. PAGE FIRE
CAFETERIA
PAGE FFT
INHIBITED
Buttons in the two right columns of the keypad can also create PRE-
EAST WING
ANNOUNCE
an MN alarm if programmed to do so.
ACU’s take priority over LOC’s, and LOC’s take priority over GENERAL
CCS’s. PAGE

Level 1
Level 2
Level 3
Figure 4.3 DVC-KD Keypad

4.6 Drill Operation


Drill operation is blocked while fire activations are suppressed. So if MN is the highest priority in the system, an MN Alarm on the local
panel or on a network panel that is MN Mapped, drill operation, including custom drill operation, will be blocked. This is to prevent the
user from activating fire outputs while a mass notification is in progress.

42 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Index
A M Special function zones, MN 15, 25
ACM-24AT 9, 11, 13 Mass notification events 36 Subsidiary Equipment 17
ACU (Autonomous Control Unit) 7, 9 MN Active Tone 15, 16, 17
configurations 9 programming 25 T
function description 9 MN alarm activations 36 Type IDs 15
programming 15 MN alarm annunciator programming 34
AEM-24AT 9, 11, 13 MN alarm indicator 13, 25 U
MN annunciator programming 17
UL2572 Mass Notification Systems Standard 6
B MN Control Field 35
Block diagram, MN system 7 MN reset 39
MN Supervisory activations 37 V
MN system block diagram 7 VeriFire Tools software release 6
C MN Trouble activations 38
CCS (Central Control Station) 7 Z
configurations 11
N ZF20 7, 22, 23, 24, 25, 28, 34, 36, 39
function description 11
NCA-2 ZF21 25, 36, 37, 38, 39
programming 16
in ACU configuration 9 ZF22 25, 36, 38
in CCS configuration 11
D MN alarm activations 36
Data and Security Levels 6 MN supervisory activations 37
Default input priorities, MN 21 MN trouble activations 38
Drill operation 42 programming 19, 20, 34
DVC 19 software release 6
in ACU configuration 9 NCM
in CCS configuration 11 software release 6
in LOC configuration 10 NFS2-3030
MN alarm activations 37 in ACU configuration 9
programming 21, 24 MN alarm activations 36
software release 6 MN supervisory activations 37
DVC-KD 9, 11, 34 MN trouble activations 38
DVC-RPU programming 19, 20, 23, 34
in LOC configuration 10 software release 6
label programming 17, 33 NFS2-640
MN alarm activations 36
F MN supervisory activations 37
Fire Active Tone 15, 16, 17, 29 programming 34
programming 29 software release 6
Fire suppression 40 NFS-320/SYS
MN alarm activations 36
G MN supervisory activations 37, 38
programming 24, 34
General Zones, DVC 34
software release 6

H O
HS-NCM
ONYXWorks
software release 6
in CCS configuration 11
MN network limitations 7
I programming 23
Input Category 21 software release 6
settings 22
P
L Priority programming for MN, fire 19
Levels, Data and Security 6
LOC (Local Operating Console) 7
R
configurations 10
Reset, MN, fire 39
function description 10
Risk assessment 6
programming 16

S
Software release numbers 6

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 43


Index

44 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019


Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer
warrants that the Products manufactured by it in its Northford, Connecticut facility
and sold by it to its authorized Distributors shall be free, under normal use and
service, from defects in material and workmanship for a period of thirty six months
(36) months from the date of manufacture (effective Jan. 1, 2009). The Products
manufactured and sold by Manufacturer are date stamped at the time of production.
Manufacturer does not warrant Products that are not manufactured by it in its
Northford, Connecticut facility but assigns to its Distributor, to the extent possible,
any warranty offered by the manufacturer of such product. This warranty shall be
void if a Product is altered, serviced or repaired by anyone other than Manufacturer
or its authorized Distributors. This warranty shall also be void if there is a failure to
maintain the Products and the systems in which they operate in proper working
conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY
AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH
RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES
RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS
A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS
PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to
its products and replaces all previous warranties and is the only warranty made by
Manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized. Manufacturer does not represent that its products will
prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion,
each part returned by its authorized Distributor and acknowledged by Manufacturer
to be defective, provided that such part shall have been returned to Manufacturer
with all charges prepaid and the authorized Distributor has completed Manufacturer's
Return Material Authorization form. The replacement part shall come from
Manufacturer's stock and may be new or refurbished. THE FOREGOING IS
DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A
WARRANTY CLAIM.

Warn-HL-08-2009.fm

Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 45


NOTIFIER
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
www.notifier.com

You might also like