Cables and Accessories
Cables and Accessories
Telephone: 6 17-926-4900
FAX: 61 7-926-0528
RBCA -6960
Part # 500-344M2A-1976-Rev A
TABLE OF CONTENTS
SECTION PACE
3.00 SAFETY
Sec. 4-1
PREFACE
It is the intent of this guide to assemble and place in the hands of operating personnel information cover-
ing the inspection and testing of cables and accessories, usually found on powi: systems, and the location of
faults therein. An extensive Bibliography is included for those who require more detailed information.
In some cases in the guide. the names of manufacturers of test equipment, devices, and instruments have
been included for the convenience of Clients. Such inclusion is for the purpose of giving examples and does
not imply that the particular devices listed are recommended or that other devices are not suitable. It is
apparent that there may be numerous other manufacturers of equal, lesser, or superior devices.
This guide is a project of the Doble Client Committee on Arresters, Capacitors, Cables and Accessories,
but it does not offer any recommendation of either the Committee or the Doble Engineering Company.
REFERENCE BOOK ON CABLES AND ACCESSORlES
SECTION 1 . 0 0
GENERAL
SCOPE
This guide covers field t e s t s and inspection of power cable circuits of all types
that a r e insulated with plastic, rubber and rubber-like materials, varnished-cambric
and paper insulation of the solid type and all types of a c c e s s o r i e s used in these circuits.
Although much of this information is applicable to gas and oil p r e s s u r e , and pipe-type
cables, it is the intent of the guide to cover only electrical t e s t s on circuits of these
types of cable. * This guide a l s o covers field test and inspection of commrtnication and
control cables of all types with all types of insulation.
SECTION 3.00
SAFETY
Revised 1996
REFERENCE BOOK ON CABLES AND ACCESSORIES M7.b
-b
3.01 GENERAL
Safety procedures should be followed for checking that electrical devices being prepared for tests are de-
energized. disconnected, and will not be energized by any personnel except those responsible for the tests.
Procedures vary between organizations and are usually different for communication and control cable than
for power cable operating at higher voltages. This section of the Reference Book on Cables and Accessories
highlights the cable safety practices of contributing Committee Member organizations and the recommenda-
tions noted within various sources of manufacturers' literature.
Prior to beginning field tests, most organizational procedures recommend that all personnel involved in
performing the tests should have a discussion concerning the safety and procedural steps involved in complet-
ing the task. Topics for discussion should include:
clearance coordination with the Load Dispatcher or Systems Operations
decision hierarchy when more than one department is involved
switching. tagging, and lockout responsibilities
informing others of your presence and purpose
potential hazards
stationing of safety personnel, protective barriers, warning signs, flags. etc.
special permits for compliance with regulations
required safety clothing and devices
identification 'of the device to be tested
isolation of the test specimen
tests to determine that the device is de-energized
apparatus grounding requirements
exposed cable ends insulation and isolation requirements
preparation of the test specimen
the influence of nearby energized apparatus
test voltages and test sequence
Electrical equipment and cables must always be considered energized unless positively proven to be
de-energized. Before beginning work, a preliminary inspection and tests should be conducted in order to
prove that the electrical equipment and cables are de-energized. Tests for potentialshould be made with a
hot line tool. switch stick, or other approved device. This precaution applies to both normally energized and
normally grounded conductors.
Field tests on cables and accessories often require work adjacent to energized circuits and devices. Definite
safety measures musr be taken to prevent test personnel from contacting energized equipment.
m
e
- REFERENCE BOOK O N CABLES A N D ACCESSORIES
When a cable circuit is switched out of service, restrikes across a breaker or switch may result in the cable's
being charged to a voltage greater than the normal crest voltage. Using a simple single phase model, it can be
shown that an unfaulted cable may charge to an odd multiple of the normal crest voltage (1.3.5 ...). The
ungrounded surfaces of a cable circuit with good insulation can maintain charge for a long period of time. The
capacitance and surface resistivity control the rate at which an ungrounded cable circuit will discharge.
The application of a ground for a short period of time, then removing it. does not render a cable circuit safe
to personnel. Residual charge may exist; therefore, a dangerous voltage may still be present. It is essential to
ground the cable whenever personnel may contact it. Additionally, after completing a high voltage test and
prior to handling, some organizations recommend applying a ground for a minimum of four times the period
that the cable was energized.
A11 phases of all isolated cables not under test should be grounded at the conductor and shield.
Dangerous charges may be induced by the tested cable in de-energized circuits and devices. Precautions
should be taken to protect personnel and prevent damage to the de-energized circuits and devices.
High voltage tests on a cable circuit connected to one side of an open disconnect switch require careful
consideration when the opposite side of the disconnect switch is energized with system operating voltage. A
flashover may occur across the open disconnect switch or to ground. A flashover across the open disconnect
will energize the high voltage test equipment circuit with the system operating voltage. which could result in a
system phase to ground fault. The test equipment operator would then be exposed to shock, arc flash, and
explosive hazards. Similarly, a flashover to ground may spread across the open disconnect switch with the
same consequences.
The possibility of a flashover in liquid-filled switches is greater. The electrostatic field may align moisnue
and other contaminants such that a path is established across the switch or to ground. A system fault from
phase to ground within a liquid-filled switch may result in an explosion, fire. or both.
REFERENCE BOOK ON CABLES AND ACCESSORIES
-.
e n
3.05 GROUNDING DE-ENERGIZED CONDUCTORS
Electrical equipment and cables must not be worked on until all exposed ungrounded conductors have been
de-energized, tested for potential, and properly grounded with suitable devices. When installing the
grounding devices. they should first be solidly connected to a ground before the connections are made at the
de-energized conductors. When removing the grounding devices, they must first be disconnected from the
de-energized conductors before disconnecting from the system ground.
Damaged and defective apparatus may fail violendy during high voltage tests. Possible safety hazards, such
as an exploding porcelain rain-shed cable terminal due to an internal failure, should be considered.
As stated earlier, particular attention should be given to non-shielded cable with non-metallic sheaths. A
dangerous potential may exist from the sheath to ground. Ungrounded cable sheaths and shields present a
similar hazard.
Doble power factor tests are performed with the apparatus to be tested completely de-energized and iso-
lated. The apparatus to be tested should be visually inspected prior to applying the test voltage. High voltage
cable shields, sheaths, and non-energized isolated conductors should be grounded; furthermore. safety
grounds should be applied to all apparatus terminals before doing any work on them and before connecting
and disconnecting leads.
The Doble test set should be located where the operator will have an unobstructed view of both the appara-
tus under test and personnel. If both ends of a cable specimen are not visible because of the remote location of
one end, appropriate barriers or observers must be posted. Proper clearance between the test set and appara-
tus should be maintained.
The following steps should be conducted prior to making any test set to apparatus connections. Pint. ensure
that the test set is properly grounded. Second, all test leads should be connected to the test set. Third, the
operation of the safety switches should be verified. The safety switch function must not be defeated, and the
switches must be operated manually at all times.
Although the High Voltage Test Cable is double shielded. it must not be handled while it is energized.
After tests are completed, all of the test leads should be removed from the apparatus and brought to the
ground before they are disconnected from the test set. The heavy duty ground cable is the last lead removed
from the test set.
SECTION 4.00
INSPECI'ION
SECTION 4 . 0 0
INSPECTION
2. Deteriorated c o v e r i n g o n t h e c a b l e and s p l i c e s .
4. Oil leaks.
6. S w o l t e n o r collapsed l e a d splice s l e e v e s .
1. Excessive c a b l e movement.
A. Puncture
B. Coring and Tracking
C. T h e r m a l Instability
D. Corona
5.011 TYPE A
5.012 TYPE B
5.013 TYPE C
e. Hxcesrive s h e a t h c u r r e n t s i n t h e c a s e of a single-
conductor c a b l e .
a. Lightning
b. Switching o r other s u r g e s during n o r m a l operation
c. Switching surges during a-c or d-c t e s t s
d. Impulse t e s t s
e. A failure in cable or an a c c e s s o r y , o r a t e r m i n a l
flashpver during operation o r any type of high-
voltage t e s t
5.014 TYPE D
1. S t r e s s concentration
2. Tangential and r a d i a l s t r e s s e s
3. Insufficient f l a s h o r leakage distance over the e x t e r i o r
s u r f a c e of t e r m i n a l s
4. Faulty workmanship
5 . 0 5 BIBLIOGRAPHY
SECX'ION 6.00
..
TEST METHODS
-
SECTON 6.00
TEST METHODS
6.01 GENERAL
The three general methoda that may be used in the field for testing the
insulation of cables and a c c e s s o r i e s are:
Of these t e s t s , the high-voltage d-c t e s t i s the most popular f o r power cable. High-
voltage a - c t e s t s a r e r a r e l y used when high-voltage d-c t e s t equipment is available.
A-c loss characteristic m e a s u r e m e n t s , e. g., Doble t e s t s , a r e often used for short
lengths of power cable and f o r potheads. D-c l o s s c h a r a c t e r i s t i c measurements,
e. g., insulation resistance t e s t s , a r e popular f o r all types of cable. A-c corona t e s t s
a r e seldom used in the iield; however, they should r e c e i v e f a r m o r e attention, partic-
ularly in the c a s e of rubber-~nsulatedcable.
-
In considering t e s t methods that may be used for cable c i r c u i t s , i t i s well to
consider just how a defect that may be indicated by a t e s t may be located. It is evident
that a defect, indicated by a-c o r d-c loss c h a r a c t e r i s t i c m e a s u t e m e n t s , such a s the
entrance of moisture into paper insulation through a hole in the cable sheath can not be
located until t h e r e is e i t h e r a s e r v i c e failure o r a failure during a high-voltage t e s t
(Section 8.00). This a l s o applies t o defects indicated by a-c c o r o n a t e s t s .
6 . 0 2 DEFINITIONS
A-C T e s t
FIELD TESTS
Proof T e s t
Acceptance T e s t
Periodic T e s t
KVA = 0 . 3 1 1 ~ ~ ~
Wirere: C = Capacitance in m i c r o f a r a d s
E = T e s t kilovolts
If a n a-c t e s t voltage in e x c e s s of approximately 40 kilovolts i s t o be applied t o
a cable, the cable m u s t be terminated in potheads o r t e r m i n a l s that will withstand t h e
Sec. 6-2
t e s t voltage. This i s due to the f a c t that the s t r e s s concentration a t the end of the
metallic sheath o r shielding will result in failures at that point. The minimum
voltage a t which such failures a r e probable is dependent upon the d i a m e t e r of the cable
conductor, the insulation thickness and the dielectric constant (SIC)of the insulation.
This paragraph does not apply to d - c tests.
The high-voltage d-c withstand t e s t is the most widely used f i e l d t e s t for power
cables. This test, unlike the high-voltage a-C withstand t e s t s , will not r e s u l t in damage
to cable insulation due to d i e l e c t r i c heating and corona cutting. The power supply
requirements a r e f a r l e s s and the equipment i s lighter and l e s s bulky.
The maximum d-c t e s t voltages given in the Standard Cable Specifications and
the maximum time of application will be found in Section 7. 06. The initially applied
voltage should not exceed the rated voltage of the cable. The rate of r i s e of test voltage
should be uniform and such that t e s t voltage i s not reached in l e s s than thirty seconds.
Slower r a t e s of r i s e a r e permissible and may be advantageous for minimizing charging
cur rent, particularly on long circuits having high capacitance. Usually , high v o l b g e
d-c t e s t s e t s have extremely poor regulation, and when the charging c u r r e n t i s high
c a r e should be taken to insure that when the desired t e s t voltage i s reached, the decay
of charging c u r r e n t will not result in overshooting the t e s t voltage.
The A-C L o s s C h a r a c t e r i s t i c M e a s u r e m e n t s , e . g.
in the field on power c a b l e and a c c e s s o r i e s a r e :
. Doble t e s t s , that a r e made
1. Power-factor m e a s u r e m e n t s usually on r e l a t i v e l y s h o r t lengths
of cable.
K V = T e s t kilovolts
L = Length of c a b l e in f e e t
V A = Required v o l t - a m p e r e s
The power factor of the conductor t o conductor and the conductor t o ground
insulation of a non- shielded, multi-conductor belted cable with a metallic sheath or
metallic covering directly over the belt of insulation may be determined f r o m the
following t t s t s and calculations:
1 A
2 A
3 B
4 B
5 C
6 C C
7 ABC ABC*
CALCULATED RESULTS
I
ABC*
-
PHASE TO PHASE
Test I -2
Test 3 -4
Test 5 -6
*NOTE: The measured and t a l t u l a t e d values of charging c u r r e n t s
and watts l o s s should be equal.
The power f a c t o r of the insulation between any two conductors, of this type of
cable, may be measured directly using the ungrarnded specimen teat (UST) technique,
with all other conductor a grounded.
~ When the rneta\lk base of a pothead can be isolated f r o m grarlrd, the cable
shielding and the metallic sheath and coverings d the cable, the power factor d the
insulation, above the s t r e s s cone and metallic cable sheath and between the metallic
pothead base and the cable conductor, can be measured b y grounding the c onductor
and energizing the pothead base, provided the t e s t set has sufficient capacity. It is
also possible t o make an ungrounded specimen t e s t by connecting the isolated pothead
base to the UST lead and energizing the conductor. This i s seldom practical except in
the c a s e of non-shielded cable without a metallic sheath or covering. It h a s been
suggested that a pothead can be isolated from c a b l e shielding and the metallic cable
sheath and/or coverings by removing a short section of the jnielding and/or metallic
sheath and/or covering from the cable below the pothead. Unless extreme c a r e i s taken
in the removal and replacement of this material. t h e r e will probably be a subsequent
failure at this pdint. Particular c a r e m u s t be taken not to damage the cable insulation
and t o insure that in making the r e p a i r s a f t e r t h e t e s t neither rough metallic edges nor
sharp metallic points a r e left in contact with the cable insulation and there a r e no
voids between the insulation and the shielding o r c a b l e sheath. Experienced cable
engineers d o not approve of this practice. The r e s u l t s of such t e s t s can be evaluated
by comparison with the r e s u l t s of t e s t s on identical potheads.
D-C CURRENT R EOUIR EM ENTS FOR HIGH VOLTAGE D-C TESTS O N TY PlCAL CABLES
Single Conductor,
Shielded Rubbc r 5 400 15 1
Single and T h r e e
Conductor Belted
L e a d Covered* Paper 5 10,000 20 1
Single and T h r e e
C o d u c t o r Shielded
Lead Covered* Pa pe r 15 12,000 60 I
Single and T h r e e
Conductor Shielded,
Lead Covered Paper 23 15,500 90 1
Pipe-Type, High-
P r e s s u r e Oil Paper 115 25,400 320 2
Varnished-Cambric
Shielded and/or Lead Sheathed Impregnated-Paper
Rated 8 KV o r More Solid-Type
Power F a c t o r
Temperaturr Single-Conductor Multi-Conductor Temperature
Degrees and Shielded Belted Degree8 Power
C Cable Cable C - Factor
Temperature Temperature
Power Degrees Power
Factor C Factor
NOTES:
1. The temperature. shall be'uniform throughout the cable.
The values of power factor for temperatures between those
listed shall be obtained by linear interpolation.
RESULTS OF
HOT COLLAR TEST
FIGURE 6-2
6 . 0 6 D-C LOSS CHARACTERISTIC TESTS
1. G e o m e t r i c a l capacitance charging c u r r e n t :
2. Reversible absorption current:
4. Conduction current:
Where: E=2.718
C = Geometric capacitance of the dielectric
s y s t e m . (The capacitance measured at
60 cycles i s c l o r e enough for this purpose. )
i l = C u r r e n t at t = 60.
R e = Leakage rcsist8ncc.
V = Applied voltage.
The c u r v e s in Figure 6-3 give the charging current and i t s various
components, from 0.0 1 t o 1000 seconds after applying t e s t voltage
t o a cable c i r c u i t having the following characteristics:
P = 2 . 2 9 = Polarization Index
5
R, = 10 Ohms
4
V = 10 Volts
2. Reversible absorption c u r r e n t :
8
2. The values of ia, ic, i and i. at any instant t, i a dependent upon
B 1
the t e s t voltage V; t h e r e f o r e , any variation in V will r e s u l t in
wide variation in the charging current. Furthermore, t h e
g r e a t e r V is, the g r e a t e r the initial value of i,, i and ii
g
and the value of ic.
Sec. 6-17
tion at all other points and the resistance over the outer s u r f ace of
the potheads, the measured value of the insulation resistance of the
cable circuit will be l e s s than the resistance of the path consisting
of r e s i s t o r s "D," "E,*' and "G. Therefore, insulation contamination
o r deterioration that reduces the insulation resistance f r o m cable
conductor t o another eonductor o r ground a t any point in a cable
circuit can be detected f r o m the results of d-c resistance measurements.
1 Voids in insulation.
R1 = Resistance at t l
R Z = Resistance at t2
t l = Higher t e m p e r a t u r e in C 0
t2 = Lower t e m p e r a t u r e
2. A d e c r e a s e in insulation r t r i s t u r c e o r an i n c r e a s e in leakage
c u r r e n t with time.
6.09 BIBLIOGRAPHY
FIGURE 6-3
TIME IN SECONDS
FIGURE 6-4
EQUIVALENT CIRCUIT OF THE 0-C
RESl9TArUcE OF THE MISUUTION
OF A CIRCUIT OF S1NOl.e COlYWCTOR CABLE
FIGURE 6-5
REFERENCE BOOK -ONCABLES AND ACCESSORIES
SECITC V 7.00
TEST VOLTAGES
Revised 1991
I
REFERENCE BOOK ON CABLES AND ACCESSORIES e
m-b
The personnel of the Doble Client Committee on Cables and Accessories at the time this revision was
published consisted of:
W. E. Sjpe, Chairman
J. E. Skog, Vice Chainnan
Raka Levi, Secretary
R. W. Allison J. Lacroix
J. F. Barresi K . Marcks
D A. Basile R. M. Millikin
R. Bell W. 0. Momson
K. Buttke S. Mustaro
G. S. Dolchak L. Oms
B. J . Goodman E. Roussel
F. W. Hanley L. 1. Sauter
C. C. Heniey J. E. Stewart
G. L. Hubbard C. F. Todd
REFEREXCE BOOK ON CABLES AND ACCESSORIES
SECTION 7.00
TEST VOLTAGES
1990 Revision
7.01 INTRODUCTION
This section deals with the selection of cable test voltages in the field. It will sen :: as a guide to personnel in
the development of their own cable test programs. While the manufacturer usually performs a comprehensive
set of tests on length; of the cable prior to shipment. the cable may have sustained damage or been improperly
handled or protected during shipment, installation. assembiy, and operauon. Consequently, a continuing test
program is desirable to prove that a cable system is suitable for service, or to determine its reliability and
quality.
When choosing a voltage level to test s cable, one must remember that some insulation defects ate extreme-
ly difficult to identify and consequently may not have been detected by prior factory or installation tests.
While there are several schools of thought as to a proper test voltage, it is generally agreed that the test voltage
must be related to the circuit Basic Impulse Insulation Level (BIL). This approach, to test the different
insulation thicknesses, types, and ages rn a practical manner. provides a consistent guideline for test person-
nel. and accommodates the common operating fact that users have a mixture of cable types in circuits,
It is understood that some users may apply different or established test programs according to their various
specific applicattons of cables. and that some may wish to retain the old Section 7.00 of 1956 for its technical
information and references with respect to older cable types.
7.02 DEFINITIONS AND TERhlINOLOCY
Absorption Current
Current resulting from charge absorbed In the dielectric as a result of polarization.
AC High-Potential Test (Hi-pot)
A test that places a high alternating voltage across cable insulation; condition is determined by the insula-
tion power factor, leakage current, and watt losses of the insulation. [See Section 6.03j.
Acceptance Test
~ e s t performed
s after installation but before the cable is placed in service to detect any shipping or installa-
tion damage, gross defect. or error In workmanship. [See Section 6.02).
Capacitance Current
Current which charges the capacitor formed. by the capacitance of the cable under test.
Leakage Current
Current that flows through the cable insulation or over the surfaces of the terminators.
Proof Test
A test performed at any time during installation or during the manufacturer's guarantee period, at reduced
voltage levels as defined by the appropriate AEIC specification or the tenns of the warranty. Also. a tea on
repaired cable or component to determine if they are ready to be placed back in service.
The set-up procedures for the above tests are similar. All established safety procedures mwt be followed,
including de-tnergizing and grounding of all components before testing. Where practical. cable accessories
should be isolated from the cable under t e a and tested separately. Accessories that are not isolated from the
cable should be cleaned with a dry cloth; application of silicone grease on some types of accessories help to
reduce leakage current and prevent flashover.
REFERENCE BOOK ON CABLES AND ACCESSORIES
6-rn
During both ac and dc high-potential testing. breakdown or terminal flashover may generate abnormal
surges; therefore, installation of suitable spark gaps at each cable-end or termmation must be considered.
These gaps should include a 50 ohm non-inductive series resistor to dissipate the energy of the discharge and
limit overvoltages.
7.04 TEST DURATION
For either a 60 hertz ac or a dc high-potential test, the maximum test voltage should be maintained for at
least one minute. with duration up to fifteen minutes being acceptable. For longer duration tests, the current
magnitudes should be recorded at both the one-minute mark and just prior to shutdown. At the end of the
period the current should be stable or decreasing in value for a cable in good condition.
For a power-factor test. the test duration is not important. since the voltage should be relatively low and
non-destructive.
7.05 TYPICAL TEST VOLTAGES
A test voltage is determined by the system voltage or the BIL rating of the cable system. and is independent
of the cable designs and insulation materials. It may be desirable to select other test voltages for specific
situations, but routine voltages applied by some clients are tabulated as a guide in Table I.
TABLE I
Typical Test Voltages
Nominal System Cable System Acceptance Test Periodic Test
Voltage kV kV kV
Phase-to-Phase BIL kV DC A~RMS DC ACMS
60 35 21 25 15
8 95 40 24 30 18
15 110 55 33 40 24
25 150 80 48 60 36
35 200 100 60 75 45
46 250 120 72 90 54
69 350 170 102 125 75
115 550 325 195 270 162
138 650 380 228 285 171
both of these should decay during a period of time leaving a leakage current component only. The time
required to reach a final steady-state current value can be a number of hours for oil-impregnated lamlnated
insulation.
For both ac and dc high-potential tests. the final test current should be stable or decreasing for cable
insulation in good condition. If the current value begins to increase for a constant voltage, dielectric break-
down is indicated to be in progress. Insulation failure is indicated by trip-off of the test set, and is confirmed
by an inability to reach final test voltage during a second test.
Acceptable results for tests performed at the voltages suggested in Section 6.05 and Section 7.05 are given
in Table 11.
TABLE 11
Acceptable Test Results
Class of Test DC Current A C Hi-pot A C Power Factor
' XLPE . . . . 0.2%
Acceptance 10 pA EPR . . . . . . 1.0%
All other .. 2.0%
'An acceptable ac test should have an insignificant increase in corona level during the test period, or above
the level measured in a previous test at the same' voltage.
SECTION 8.00
CABLE-FAULT LOCATION
SECTION 8.00
CABLE-FAULT LOCATION
8 . 0 1 GENERAL
8 . 0 2 TYPE OF FAULT
Sec. 8-1
whether there is an open circuit. F o r this purpose a test lamp and source of d-c
potential, a battery and buzzer, o r an ohmmeter may be satisfactory. A "Megger" or
megohm bridge would be better. For power cable, a source of high d-c voltage is ideal.
since for some faults it i s necessary to use voltages ranging from the ope rating voltage
of the cable to the maximcim permissible test voltage for the cable, to determine the
type of fault and the conductors involved.
8 . 0 3 INSULATION DEFECTS
Where defective insulation can not be broken down with the maximum a-c or d-c
voltage that can safely be applied to thc cable circuit, and the fault can not be located by
inseection, it i s necessary to either r e s o r t to the Cut-and-Try method o r return the
circuit to the service until i t s insulation has deteriorated sufficiently s o that it can be
broken dowa with a reasonable a - c o r d-c voltage. The objection to this procedure i s
that t h e r e i s no practical method of determining o r even estimating the r a t e of
deterioration of defective insulation when the nature of a defect is unknown.
No matter what method is used for locating faults in any type of cable, fault
resistance will be a consideration. Many engineers consider "fault resistance" a
misnomer. This i s no doubt due to the fact that any fault, which has very high r e s i s t a n c e
when measured with a low voltage, will have low resistance when measured with a high
voltage. There i s certainly no mystery about this. When f a u l t resistance is measured
with a very low voltage, the actual resistance of the insulation and other matter between
the faulted conductor and ground o r between the faulted conductors is obtained. When
fault resistance is r n t a s w e d with very high voltage, the r e s u l t obtained i s the r e s i s t a n c e
of the insulation and other m a t t e r between the faulted conductors in parallel with the
resistance of the a r c a c r o s s the fault. The value of fault r e s i s t a n c e c a n not be
determined with sufficient a c c u r a c y to be of any use in any procedure for the exact
location ot faults. Therefore, the T e s t Engineers' problem with fault resistance i s in
reducing i t t o a value at which available fault location device8 will function.
8 . 0 5 FAULT R EDUCTION
Sec. 8-3
4. Faults in any type of cable where the conductor resistance from the
cable terminal to the fault i s so high that sufficient c u r r e n t to
carbonize the insulation at the fault cannot be circulated without the
application of excessive voltage o r exceeding the thermal limit of
the insulation.
When sufficient voltage i s applied to the f i r s t two types of faults listed above, the
fault will flash over, the applied voltage will drop and the compound, petrolatum or
oil quickly extinguishes the arc. If the applied voltage is raised t o and maintained at
a value that r e s u l t s in flashovers in rapid succession. sufficient m a t e r i a l adjacent to
the fault will in time be carbonized to result in a stable low-resistance fault. Under
some conditions this will take hours. F a u l t s under water behave i n a s i m i l a r manner,
except that water a f t e r extinguishing the a r c washes away carbonized cable insulation,
thus preventing the formation of a low-resistance carbonized path a c r o s s fault. It
has been suggested that adding salt to the water in which faults c a n not be reduced would
solve the problem. Possibly it would help in fault location. but it certainly would
result in serious lead-sheath corrosion.
When the resistance of a fault can not be reduced t o a constant low value, i t may
be possible t o locate the fault by using one of the methods covered in Section 8.06 with
high-voltage equipment. Measurements will be difficult if the fault resistance i s
variable, because instruments seldom function properly with fluctuating voltage and
current. The Tracer-Current method i s generally the most satisfactory f o r this
purpose.
The theory underlyiag the methods of cable-fault location i s very rimple. However,
the actual selection of procedure and the execution af t e s t s required f o r quick. accurate
cable-fault location r e q u i r e s skill and judgment that c a n be obtained only by actual
experience.
Cable-fault location methods can be divided into eight general types, i:e. ,
1. Inspection (Section 8 . 0 7 )
2. Cut-and-Try (Gction 8 . 0 8 )
3. Smoke (Section 8 . 0 9 )
4. Audible Discharge (Section 8 . 1 0 )
5. T r a c e r Current (Section 8. 11)
a. Interrupted A-C (8. 1 12)
b. Interrupted D-C (8. 11 3 )
C. Audio Frequency (8. 114)
d. Impulse(8.llS)
e . D-C Sheath Potential Drop (8. 116)
6. Reflection (Section 8 . 1 2 )
a . Pulse Echo (8. 121)
b. Quarter Wave Resonance (8. 122)
7. D-C Resistance M e a s u r e m e n t s (Section 8.13)
8. A-C Capacitance M e a s u r e m e n t s (Section 8. 14)
Of all of the various methods that have been used, the T r a c e r C u r r e n t method i s
the most a c c u r a t e and s a t i s f a c t o r y f o r pinpointing the majority of the f a u l t s encountered
on utility s y s t e m s . It i s often advantageous t o d e t e r m i n e the approximate fault location
with M u r r a y Loop t e s t s on power c a b l e c i r c u i t s and Varley Loop t e s t s on c o n t r o l and
communication c i r c u i t s p r i o r t o applying t r a c e r c u r r e n t . The Reflection method i s
a l s o useful f o r this purpose. The Reflection method and a-c capacitance m e a s u r e m e n t s
a r e useful in determining the approximate Location of open c i r c u i t s .
8 . 0 7 INSPECTION METHODS
8 . 0 8 CUT-AND-TRY METHOD
d. Buried cable.
8 . 1 0 AUDIBLE DISCHARGE
The limitations given above f o r the Smoke method a l s o apply t o the Audible
Discharge method. F o r such conditions d e v i c e s b a r e d on t h e stethoscope p r i n c i p l e , and
using a contact microphone, a m p l i f i e r , phones o r o t h e r indicator, have been used to
advantage.
8 . 1 1 TRACER-CURRENT METHOD
T h e s p l i t - c u r r e n t t r a n s f o r m e r type of d e t e c t o r c o n s i s t s of a s p l i t - c o r e
c u r r e n t t r a n s f o r m e r that can be clamped around the c a b l e and a n indicating
i n s t r u m e n t with o r without an amplifier. T h i s type of d e t e c t o r i s used only
with Interrupted A-C t r a c e r c u r r e n t s . I t h a s the s a m e disadvantagrs and
limitations a s the magnetic pickup coil type of d e t e c t o r .
KVA = 0 . 3 7 7 ~ ~ ~
Where: C = Capacitance i n m i c r o f a r a d s
E = Kilovolts
T h i s r e s u l t s in heavy, bulky equipment t h a t r e q u i r e s a r a t h e r high kva power
s o u r c e . I t h a s no advantage over the Interrupted D-C method and i s used only
when equipment i s not available f o r m o r e suitable methods.
T e s t s e t s f o r applying a - c t r a c e r c u r r e n t a r e not c o m m e r c i a l l y a v a i l a b l e ,
but have been a s s e m b l e d by utilities. T h e s e s e t s v a r y f r o m 5 t o 500 kva i n
capacity at output voltages u p t o 7200 volts. One type c o n s i s t s of a n i n t e r r u p t e r ,
a d i s t z i b u t b n t r a n s f o r m e r , a c u r r e n t limiting r e s i s t o r , o r r e a c t o r , and
i n s t r u m e n t s t o indicate the output voltage and c u r r e n t . T h i s a r r a n g e m e n t
c a n be improved by adding a variable a u t o t r a a s f o r m e r o r voltage r e g u l a t o r
t o c o n t r o l the output voltage. Another type c o n s i s t s of a constant c u r r e n t
s t r e e t lighting t r a n s f o r m e r , a shorting s w i t c h and i n s t r u m e n t s t o indicate the
output voltage.
Sec. 8-10
8.11 3 IXTERRUPTED D-C METHOD
T e s t s e t s of t h i s type c o n s i s t of a variable a u t o t r a n s f o r m e r or
regulator, s t e p - u p t r a n s f o r m e r , r e c t i f i e r , c o n d e n s e r d i s c h a r g e gap, and in
some c a s e s a n instrument t o indicate the output voltage, F i g u r e 8 - 1.
In operation the rectifier c h a r g e s the condenser t o a voltage a t which the gap
will f i r e and d i s c h a r g e the condenser sufficiently to reduce the voltage to a
level at which the gap will no longer f i r e , whereupon the condenser s t a r t s
charging again and the cycle repeats. This continues a t a constant rate that
i s dependent on the output voltage of the r e c t i f i e r , the regulation of the
rectifier and the gap spacing. The output voltage is controlled by the gap
setting. F o r low voltage cable the discharge gap i s replaced with a
contactor since discharge gaps a r e not practical a t low voltages.
The accuracy of this method i s dependent upon the a c c u r a c y t o which the length
of the circuit i s known and o t h e r f a c t o r s (Section 8. 121 and 8. 122).
Of these the Pulse Echo method h a s been used with all types and s i z e s of cable. The
Quarter Wave Resonance method h a s not been used a s wisely as the other method: how-
e v e r , i t h a s the advantage t h a t variations in conductor s i z e a r e l e s s troublesome.
C = Condenser, coatinuously v a r i a b l e ,
50 to 1000 m i c r o f a r a d s
C = Oscillator, continuously v a r i a b l e ,
50 t o 1000 kilocycles with maximum output
of 10 to 50 volts into a n impedance of 25
ohms or more
F r = Resonant f r e q u e n c y , in m e g a c y c l e s , of the
faulted cable c i r c u i t .
L = D i s t a n c e t o the f a u l t in feet.
Ll = Length of t h e c a b l r c i r c u i t in feet.
N = Number of odd q u a r t e r wave lengths
1 , 3, 5, 7, e t c . , o r even q u a r t e r
wave lengths 2 , 4, 6, 8, e t c , , t o the
fault.
In c a s e s where the faulted conductor and the good conductor making up the loop
under t e s t a r e neither in the s a m e c a b l e , conduit n o r duct, it may be difficult, and in
some c a s e s impossible, to make d-c r e s i s t a n c e measuremmits because of induced
voltages in the loop under t e s t due t o n o r m a l and s t r a y c u r r e n t s in adjacent e l e c t r i c a l
conductors. T h i s difficulty i n c r e a s e s with i n c r e a s e d spacing of the two conductors in
the loop and with increasing cable concentration. The difficulties due to induced
voltage c a n in some c a s e s b e m a t e r i a l l y reduced by adding a condenser o r r e a c t o r a t
the proper point in the measuring c i r c u i t .
L ~
Leg, L l ,L 2 , L 3 may be in any units of length,
~ l
provided the s a m e units a r e used
throughout.
Bridges having a consistent a c c u r a c y better than plus o r minus one tenth of one
percent, a r e seldom used in cable fault location. The many o t h e r e r r o r s in fault .
location prevent the utilization of g r e a t e r accuracy t o a n advantage. Other r e s i s t a n c e
measuring devices used for cable fault location d o not have the a c c u r a c y of bridges.
Sac. 8-17
a circuit. Under some conditions, the effects of e r r o r s in conductor Lengths can be
reduced and the a c c u r a c y of fault location can be improved by making m e a s u r e m e n t s
from both ends of the circuit.
Of the many possible methods of locating cable faults with d-c resrstance m e a s u r e -
ments, the M u r r a y Loop and the Varley Loop methods a r e the m o s t practical and most
used. The Varley Loop method i s most suitable for communication and other c i r c u i t s
where small conductors having relatively high conductor r e s i s t a n c e are used. The
Murray Loop method i s ideal for power and other c i r c u i t s where l a r g e conductors
having comparatively low r e s i s t a n c e a r e used. While not a s satisfactory a s the Varley
Loop, the M u r r a y Loop t e s t s may be used f o r communication and other c i r c u i t s where
small conductors having relatively high conductor r esistance a r e used. E i t h e r of these
loop methods completely eliminates fault r e s i s t a n c e f r o m the m e a s u r e m e n t s . The M u r r a y
-
Loop t e s t is shown in F i g u r e 8- 1 1 and the Varley Loop t e s t in F i g u r e 8 12. In calculating
a fault location f r o m M u r r a y Loop test. c o r r e c t i o n s must be made f o r the t e s t leads if
the total r e s i s t a n c e of the leads i s equal to the r e s i s t a n c e of a n appreciable leagth of cable.
Such corrections can be made by the use of the f o r m u l a for loop r e s i s t a n c e aad the f o r m u l a
for equivalent r e s i s t a n c e of conductor of various s i z e s . T h i s i s not n e c e s s a r y with the
type of Varley Loop t e s t shown in F i g u r e 6-12.
Sec. 8-19
I This method c o n s i s t s of measuring the a-c capacitance f r o m the faulted conductor
to ground o r t o another conductor and c o m p a r i n g i t with the capacitance of a good con-
ductor. The capacitance of the conductor may be calculated o r preferably obtained by
measuring the capacitance of a good conductor in the c i r c u i t using the s a m e techniques
a s used in m e a s u r i n g the capacitance of the faulted conductor. When t h e r e a r e c a b l e s
In the c i r c u i t , of different types o r having different conductor s i z e s , different t y p e s
of insulation o r different thicknesses of insulation, the length and capacitance of e a c h
different type of c a b l e m u s t be known. B r a n c h e s in the c i r c u i t complicate the d e t e r m i a -
ation ox the approximate location of f a u l t s with this method even when the length and
capacitance of e a c h cable in the circuit a r e a c c u r a t e l y known. This is due t o the f a c t
that a m e a s u r e m e n t may indicate that the fault is either i n the m a i n cable o r in a branch.
The Western E l e c t r i c Company's No. lO2OC and ll2OC T e s t Sets, available thrnugh
the Graybar Eiectric Company, a r e quite satisfactory for the Audio Frequency T r a c e r
C u r r e n t method. Sectlon 8.114. These small, light, inexpensive, battery operated t e s t
s e t s consist of a v i b r a t o r , electro-magnetic interrupter and a c a e s s o r i e s for generating
a continuous o r an inter rupted audio frequency. An electro-magnetic pickup c o i l and
headphones a r e suppl;ed with the t e s t set. A No. 107A a m p l i f i e r is available f o r u s e where
g r e a t e r sensitivity is desired. T h i s s e t is suitable f o r locating c r o s s e s , grounds, opens,
shorts, w e t rpots and split p a i r s in communication cable. It is a l s o useful f o r locating
faults in control cable, but it is not recommended for power cable.
FIGURE 8-2
FIGURE 8 - 3
0 - C POTENTIAL DROP
METHOD OF FAULT LOCATION
6 VOLT
aATTLW
FIGURE 8-4
FIGURE 8-5
QUARTER WIWE RESONANCE METHOD
OF C4BLE FAULT LOCATION
NOTES
I. V t nust 8K C O ~ C n t ODIIICCTU TO TNC
TERYUIAL w me r r u L t g o COIDUCTOR.
t. ALL IUST1UUKlltS WOULD @L ¶ W I L D L O AND
CWWCCTSO WITH CO&XlAL C A 8 U .
FIGURE 8-6
FIGURE 8-7
STANDING WAVES IN A CABLE
WITH AN OPEN CIRCUIT
FIGURE 8-8
Wn€mmwEU R f O e
mTn WOE WIW RAW Am8
PORYUL.:
rG
R*r%R
FIGURE 8 - 9
FIGURE 8- 10
MURRAY TEST LuOO VARLBY LOOP
.* R d w ) -Ra
*wm
tnlb FOmULI IO N L I1
' 10 ~
mw€sWCTn A aLl# WIRE GALJIRATLD
In 1000 aau rnvmma
FIGURE 8-11
FIGURE 8- 12
FIGURE 8-14
FIGURE 8- 13
FIGURE 8- 16
FIGURE 8-15
FIGURE 8- 17
FIGURE 8-18
8 . 1 6 BIBLIOGRAPHY
8. 1616 -
" F a u l t L o c a t i o n o n Non-Metallic S h e a t h C a b l e G r o u p IU M i s c e l l a n e o u s
M e t h o d s , " H. M. Ekvall, E l e c t r i c a l q o r l d , Vol. 121, pp. 1990,
May 27, 1944.
8. 1617 "Cable Field Testing and F a u l t Location. " W. D. Fenn and L. A. Gray.
E l e c t r i c a l World, Vol. 122, pp. 97, Aug. 19, 1944.
8.1630 -
"The tLinascope' An Echo-Ranging Type Fault Locator for High-Voltage
L i n e s , " G. R . L e s l i e , K. H. Kidd, AIEE Transactions, Vol. 67, Part 2,
pp. 1162, 1948.
Sec. 8-32
8.1633 "Cable F a u l t Location, J. C. P a r k e r , Minutes of the 1949 Doble Client
Conference, 1949.
8.1636 "Three Units Used t o Locate Cable Faulta, " E l e c t r i c a l World, Vol. 133,
pp. 114. J u n e 19, 1950.