Module 2
Module 2
Classification of pumps
Pumps are classified into three different ways and must be considered in any discussion of fluid power equipment.
The two most common types of hydrodynamic pumps are the centrifugal and the axial flow propeller pumps.
1. Non-displacement pumps are not self-priming and hence they must be positioned below the fluid level.
2. Discharge is a function of output resistance.
3. Low volumetric efficiency.
(ii) Positive displacement pumps
Positive displacement pumps, in contrast, have very little slips, are self-priming and pump against very high
pressures, but their volumetric capacity is low. Positive displacement pumps have a very close clearance between
rotating and stationary parts and hence are self-priming. Positive displacement pumps eject a fixed amount of
fluid into the hydraulic system per revolution of the pump shaft. Such pumps are capable of overcoming the
pressure resulting from mechanical loads on the system as well as the resistance of flow due to friction. This
equipment must always be protected by relief valves to prevent damage to the pump or system. By far, a majority
of fluid power pumps fall in this category, including gear, vane and piston pumps. Performance curves for positive
and non-positive displacement pumps are shown in Fig. 1.
1. Type of motion of pumping element: Based on the type of motion of pumping element, positive displacement
pumps are classified as follows:
Rotary pumps, for example, gear pumps and vane pumps.
Reciprocating pumps, for example, piston pumps.
2. Displacement characteristics: Based on displacement characteristics, positive displacement pumps are
classified as follows:
Fixed displacement pumps.
Variable displacement pumps.
3. Type of pumping element.
The advantages of positive displacement pumps over non-positive displacement pumps are as follows:
1. They can operate at very high pressures of up to 800 bar (used for lifting oils from very deep oil wells).
2. They can achieve a high volumetric efficiency of up to 98%.
3. They are highly efficient and almost constant throughout the designed pressure range.
4. They are a compact unit, having a high power-to-weight ratio.
5. They can obtain a smooth and precisely controlled motion.
6. By proper application and control, they produce only the amount of flow required to move the load at the
desired velocity.
7. They have a great flexibility of performance. They can be made to operate over a wide range of pressures and
speeds.
All pumps operate by creating a partial vacuum at the intake, and a mechanical force at the outlet that induces
flow. This action can be best described by reference to a simple piston pump shown in Fig.2.
1. As the piston moves to the left, a partial vacuum is created in the pump chamber that holds the outlet valve
in place against its seat and induces flow from the reservoir that is at a higher (atmospheric) pressure. As this
flow is produced, the inlet valve is temporarily displaced by the force of fluid, permitting the flow into the
pump chamber (suction stroke).
2. When the piston moves to the right, the resistance at the valves causes an immediate increase in the pressure
that forces the inlet valve against its seat and opens the outlet valve thereby permitting the fluid to flow into
the system. If the outlet port opens directly to the atmosphere, the only pressure developed is the one required
to open the outlet valve (delivery stroke).
Figure 2 : Illustration of pumping theory
If the gear is specified by its module and number of teeth, then the theoretical discharge can be found by:
𝜋 2 cos 2 20
𝑄𝑇 = 2𝜋𝐿𝑚2 𝑁 [𝑧 + (1 + )] (𝑚3 /𝑚𝑖𝑛)
12
1. As the lobes come out of mesh, they create expanding volume on the inlet side of the pump. Liquid flows
into the cavity and is trapped by the lobes as they rotate.
2. Liquid travels around the interior of the casing in pockets between the lobes and the casing (it does not pass
between the lobes).
3. Finally, the meshing of the lobes forces the liquid through the outlet port under pressure.
Lobe pumps are frequently used in food applications because they are good at handling solids without
inflicting damage to the product. Solid particle size can be much larger in lobe pumps than in other positive
displacement types. Because lobes do not make contact, and clearances are not as close as in other positive
displacement pumps, this design handles low viscosity liquids with diminished performance. Loading
characteristics are not as good as other designs and suction ability is low. High-viscosity liquids require reduced
speeds to achieve satisfactory performance. Reductions of 25% of rated speed and lower are common with high-
viscosity liquids.
Advantages
The advantages of lobe pumps are as follows:
1. Lobe pumps can handle solids, slurries, pastes and many liquid.
2. No metal-to-metal contact.
3. Superior CIP (Cleaning in Place) /SIP (Sterilization in Place) capabilities.
4. Long-term dry run (with lubrication to seals).
5. Non-pulsating discharge.
Disadvantages
The disadvantages of lobe pumps are as follows:
Applications
Common rotary lobe pump applications include, but are not limited to, the following:
1. Polymers.
2. Paper coatings.
3. Soaps and surfactants.
4. Paints and dyes.
5. Rubber and adhesives.
6. Pharmaceuticals.
7. Food applications
2.5. GEROTOR PUMP
Gerotor pumps operate in the same manner as internal gear pumps. The inner gear rotor is called a gerotor element.
The gerotor element is driven by a prime mover and during the operation drives outer gear rotor around as they
mesh together. The gerotor has one tooth less than the outer internal idler gear. Each tooth of the gerotor is always
in sliding contact with the surface of the outer element. The teeth of the two elements engage at just one place to
seal the pumping chambers from each other. On the right-hand side of the pump, shown in Fig.7, pockets of
increasing size are formed, while on the opposite side, pockets decrease in size. The pockets of increasing size are
suction pockets and those of decreasing size are discharge pockets. Therefore, the intake side of the pump is on
the right and discharge side on the left. Pumping chambers are formed by the adjacent pair of teeth, which are
constantly in contact with the outer element, except for clearance. Refer to Fig 7, as the rotor is turned, its gear
tips are accurately machined so that they precisely follow the inner surface of the outer element. The expanding
chambers are created as the gear teeth withdraw. The chamber reaches its maximum size when the female tooth
of the outer rotor reaches the top dead center. During the second half of the revolution, the spaces collapse,
displacing the fluid to the outlet port formed at the side plate. The geometric volume of the gerotor pump is given
as
𝑉𝐷 = 𝑏 𝑍 (𝐴𝑚𝑎𝑥 − 𝐴𝑚𝑖𝑛 )
, where b is the tooth height, Z is the number of rotor teeth, A max is the maximum area between male and female
gears (unmeshed – occurs at inlet) and Amin is the minimum area between male and female gears (meshed – occurs
at outlet).
Ina screw pump, a chamber is formed between thread and housing as shown in Fig.9. The following expression
gives the volumetric displacement
𝜋 2 𝛼 sin 2𝛼
𝑉𝐷 = (𝐷 − 𝑑 2 )𝑠 − 𝐷2 { − }𝑠
4 2 2
Here, s is the stroke length and:
𝐷+𝑑
cos 𝛼 =
2𝐷
Figure 8 : Screw pump operation
e = eccentricity (in, m)
𝑄𝑇 = 𝑉𝐷 × 𝑁
1. Vane pumps are self-priming, robust and supply constant delivery at a given speed.
2. They provide uniform discharge with negligible pulsations.
3. Their vanes are self-compensating for wear and vanes can be replaced easily.
4. These pumps do not require check valves.
5. They are light in weight and compact.
6. They can handle liquids containing vapors and gases.
7. Volumetric and overall efficiencies are high.
8. Discharge is less sensitive to changes in viscosity and pressure variations.
1. Relief valves are required to protect the pump in case of sudden closure of delivery.
2. They are not suitable for abrasive liquids.
3. They require good seals.
4. They require good filtration systems and foreign particle can severely damage pump.
1. The balanced pump eliminates the bearing side loads and therefore high operating pressure can be used.
2. The service life is high compared to unbalanced type due to less wear and tear.
The volumetric displacement of the pump varies with the offset angle q, as shown in Figure 17. No flow
is produced when the cylinder block centerline is parallel to the drive shaft centerline. θ can vary from 0° to a
maximum of about 30°. Fixed displacement units are usually provided with 23° or 30° offset angles. Variable
displacement units are available with a yoke and some external control to change the offset angle such as a stroking
cylinder. Some designs have controls that move the yoke over the center position to reverse the direction of flow
through the pump. Figure 18 is a cutaway of a variable displacement piston pump in which an external handwheel
can be turned to establish the desired offset angle. Also shown is the hydraulic symbol used to represent variable
displacement pumps in hydraulic circuits
𝑆 = 𝐷 tan 𝜃
The total displacement volume equals the number of pistons multiplied by the displacement volume per piston:
𝑉𝐷 = 𝑌𝐴𝑆
Substituting, we have:
𝑉𝐷 = 𝑌𝐴𝐷 tan 𝜃
𝑄𝑇 = 𝑉𝐷 × 𝑁
Hence,
𝑄𝑇 = 𝐷𝐴𝑁𝑌 tan 𝜃
Comparison of Pumps
Pump design with a wide range of operating characteristics are available. A designer must select carefully to
achieve a circuit design that meets the functional objective while minimizing total cost which includes both
ownership cost and operating cost over the life of component. Pump selection is important decision in circuit
design. Designer must compare the various options available and then choose the optimum pump.
The major factor in adopting a pump to a particular system is the system’s overall needs. It would be wrong
to use a pump with high delivery in a system that requires only a low delivery rate. On the contrary, using a pump
that must produce at its peak continuously just to meet the minimum requirements of the system is equally wrong.
Making either of these mistakes produces a poor system due to excessive initial pump costs or maintenance cost.
One should use a pump that is suited to the system, whether a gear pump which has fewer moving precision parts
or a piston pump which has many parts fitted to close tolerance and is therefore more expensive.
Table 2 : Comparison of hydraulic pumps
Table. 2 compares various performance factors for hydraulic pumps. In general, gear pumps are the least expensive
but also provide the lowest level of performance. In addition, gear pump efficiency is rapidly reduced by wear,
which contributes to high maintenance costs. The volumetric efficiency of gear pumps is greatly affected by the
following leakage losses, which can rapidly accelerate due to wear:
Vane pump efficiencies and costs fall between those of gear and piston pumps. Vane pumps have good
efficiencies and last for a reasonably long time. However, continued satisfactory performance necessitates clean
oil with good lubricity. Excessive shaft speeds can cause operating problems. Leakage losses in vane pumps occur
across the faces of the rotor and between the bronze wear plates and the pressure ring.
Piston pumps are the most expensive and provide the highest level of overall performance. They can be
driven at high speeds (up to 5000 rpm) to provide a high horsepower-to-weight ratio. They produce essentially a
non-pulsating flow and can operate at the highest pressure levels. Due to very close-fitting pistons, they have the
highest efficiencies. Since no side loads occur to the pistons, the pump life expectancy is at least several years.
However, because of their complex design, piston pumps cannot normally be repaired in the field.
1. Volumetric efficiency (ηv):. Volumetric efficiency indicates the amount of leakage that takes place within the
pump. This involves considerations such as manufacturing tolerances and flexing of the pump casing under design
pressure operating conditions:
𝑎𝑐𝑡𝑢𝑎𝑙 𝑓𝑙𝑜𝑤 − 𝑟𝑎𝑡𝑒 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑 𝑏𝑦 𝑝𝑢𝑚𝑝 𝑄𝐴
η𝑣 = =
𝑡ℎ𝑒𝑜𝑟𝑒𝑡𝑖𝑐𝑎𝑙 𝑓𝑙𝑜𝑤 − 𝑟𝑎𝑡𝑒 𝑡ℎ𝑒 𝑝𝑢𝑚𝑝 𝑠ℎ𝑜𝑢𝑙𝑑 𝑝𝑟𝑜𝑑𝑢𝑐𝑒 𝑄𝑇
Volumetric efficiencies typically run from 80% to 90% for gear pumps, 82% to 92% for vane pumps, and 90% to
98% for piston pumps. Note that when substituting efficiency values into equations, decimal fraction values
should be used instead of percentage values. For example, an efficiency value of 90% would be represented by a
value of 0.90.
2. Mechanical efficiency (ηm): Mechanical efficiency indicates the amount of energy losses that occur for reasons
other than leakage. This includes friction in bearings and between other mating parts. It also includes energy losses
due to fluid turbulence. Mechanical efficiencies typically run from 90% to 95%.
𝑝𝑢𝑚𝑝 𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟 𝑎𝑠𝑠𝑢𝑚𝑖𝑛𝑔 𝑛𝑜 𝑙𝑒𝑎𝑘𝑎𝑔𝑒
η𝑚 =
𝑎𝑐𝑡𝑢𝑎𝑙 𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑 𝑡𝑜 𝑝𝑢𝑚𝑝
where,
Note that the theoretical torque required to operate a pump (TT) is the torque that would be required if there
were no leakage.
Equations for evaluating the theoretical torque and the actual torque are as follows:
where,
2𝜋
𝑁(𝑟𝑎𝑑/𝑠) = 𝑁 (𝑟𝑝𝑚)
60
3. Overall efficiency (ηo): The overall efficiency considers all energy losses and hence is defined as follows:
𝑎𝑐𝑡𝑢𝑎𝑙 𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑 𝑏𝑦 𝑝𝑢𝑚𝑝
η𝑜 =
𝑎𝑐𝑡𝑢𝑎𝑙 𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑 𝑡𝑜 𝑝𝑢𝑚𝑝
η𝑜 = η𝑣 × η𝑚
Thus,
𝑝𝑄𝐴
η𝑜 =
𝑇𝐴 𝑁
Note that the actual power delivered to a pump from a prime mover via a rotating shaft is called brake power
and the actual power delivered by a pump to the fluid is called hydraulic power.
Performance curves for the radial piston pump of Figure 24 are presented in Figure 26. This pump comes in three
different sizes:
Pump Noise
Noise is a significant parameter used to determine the performance of a pump. Any increase in the noise level
normally indicates increased wear and imminent pump failure. Pumps are good generators but poor radiators of
noise. As such, pumps are one of the main contributors to noise in a fluid power system. However, the noise we
hear is not just the sound coming directly from the pump. It includes the vibration and fluid pulsations produced
by the pump as well. Pumps are compact, and because of their relatively small size, they are poor radiators of
noise, especially at lower frequencies. Reservoirs, electric motors, and piping, being large, are better radiators.
Therefore, pump-induced vibrations or pulsations can cause them to radiate audible noise greater than that coming
from the pump. In general, fixed displacement pumps are less noisy than variable displacement units because they
have a more rigid construction. As illustrated in Figure 27, pump speed has a strong effect on noise, whereas
pressure and pump size have about equal but smaller effects. Since these three factors determine horsepower, they
provide a trade-off for noise. To achieve the lowest noise levels, use the lowest practical speed (1000 or 2000 rpm
where electric motors are used, a reducer gear for engine prime movers) and select the most advantageous
combination of size and pressure to provide the needed horsepower.
Figure 27 : Data showing effect of changing size, pressure, and speed on noise.
Pump Cavitation
Still another noise problem, called pump cavitation, can occur due to entrained air bubbles in the hydraulic fluid
or vaporization of the hydraulic fluid. This occurs when pump suction lift is excessive and the pump inlet pressure
falls below the vapor pressure of the fluid (usually about 5-psi suction).As a result, air or vapor bubbles, which
form in the low-pressure inlet region of the pump, are collapsed when they reach the high-pressure discharge
region. This produces high fluid velocity and impact forces, which can erode the metallic components and shorten
pump life.
1. Undersized plumbing.
2. Clogged lines or suction filters.
3. High fluid viscosity.
4. Too much elevation head between the reservoir and the pump inlet
The following rules will control or eliminate cavitation of a pump by keeping the suction pressure above the
saturation pressure of the fluid:
1. Keep suction line velocities below 4 ft/s (1.2 m/s).
2. Keep pump inlet lines as short as possible.
3. Minimize the number of fittings in the inlet line.
4. Mount the pump as close as possible to the reservoir.
5. Use low-pressure drop inlet filters or strainers. Use indicating-type filters and strainers so that they can be
replaced at proper intervals as they become dirty.
6. Use the proper oil as recommended by the pump manufacturer. The importance of temperature control lies in
the fact that increased temperatures tend to accelerate the liberation of air or vapor bubbles. Therefore,
operating oil temperatures should be kept in the range of 120°F to 150°F (50°C to 65°C) to provide an
optimum viscosity range and maximum resistance to liberation of air or vapor bubbles to reduce the
possibility of cavitation.
Pump noise is created as the internal rotating components abruptly increase the fluid pressure from inlet to outlet.
The abruptness of the pressure increases plays a big role in the intensity of the pump noise. Thus, the noise level
at which a pump operates depends greatly on the design of the pump. Gear and vane pumps generate a much
higher noise level than do screw pumps. Table.3 provides the approximate noise levels associated with various
pump designs
Table 3 : Noise levels for various pump designs
Pump Selection
Pumps are selected by taking into account a number of considerations for a complete hydraulic system involving
a particular application. Among these considerations are flow-rate requirements (gpm), operating speed (rpm),
pressure rating (psi), performance, reliability, maintenance, cost, and noise. The selection of a pump typically
entails the following sequence of operations:
1. Select the actuator (hydraulic cylinder or motor) that is appropriate based on the loads encountered.
2. Determine the flow-rate requirements. This involves the calculation of the flow rate necessary to drive the
actuator to move the load through a specified distance within a given time limit.
3. Select the system pressure. This ties in with the actuator size and the magnitude of the resistive force produced
by the external load on the system. Also involved here is the total amount of power to be delivered by the
pump.
4. Determine the pump speed and select the prime mover. This, together with the flow-rate calculation,
determines the pump size (volumetric displacement).
5. Select the pump type based on the application (gear, vane, or piston pump and fixed or variable displacement).
6. Select the reservoir and associated plumbing, including piping, valving, filters and strainers, and other
miscellaneous components such as accumulators.
7. Consider factors such as noise levels, horsepower loss, need for a heat exchanger due to generated heat, pump
wear, and scheduled maintenance service to provide a desired life of the total system.
8. Calculate the overall cost of the system.
Normally the sequence of operation is repeated several times with different sizes and types of components.
After the procedure is repeated for several alternative systems, the best overall system is selected for the given
application. This process is called optimization. It means determining the ultimate selection of a combination of
system components to produce the most efficient overall system at minimum cost commensurate with the
requirements of a particular application.
2.10 PRESSURE INTENSIFIERS
Introduction
Although a pump is the primary power source for a hydraulic system, auxiliary units are frequently employed for
special purposes. One such auxiliary unit is the pressure intensifier or booster.
A pressure intensifier is used to increase the pressure in a hydraulic system to a value above the pump discharge
pressure. It accepts a high-volume flow at relatively low pump pressure and converts a portion of this flow to high
pressure. Figure 28 shows a cutaway view of a Racine pressure intensifier. The internal construction consists of
an automatically reciprocating large piston that has two small rod ends (also see Figure 28).This piston has its
large area (total area of piston) exposed to pressure from a low-pressure pump. The force of the low-pressure oil
moves the piston and causes the small area of the piston rod to force the oil out at intensified high pressure. This
device is symmetrical about a vertical centerline. Thus, as the large piston reciprocates, the left- and right-hand
halves of the unit duplicate each other during each stroke of the large piston. The increase in pressure is in direct
proportion to the ratio of the large piston area and the rod area. The volume output is inversely proportional to
this same ratio.
ℎ𝑖𝑔ℎ 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑝𝑖𝑠𝑡𝑜𝑛 ℎ𝑖𝑔ℎ 𝑖𝑛𝑙𝑒𝑡 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒
= =
𝑙𝑜𝑤 𝑖𝑛𝑙𝑒𝑡 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑟𝑜𝑑 𝑙𝑜𝑤 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒
Racine pressure intensifiers are available with area ratios of 3:1, 5:1, and 7:1, developing pressures to 5000 psi
and flows to 7 gpm. There are many applications for pressure intensifiers, such as the elimination of a high-
pressure/low-flow pump used in conjunction with a low-pressure/high-flow pump. In an application such as a
punch press, it is necessary to extend a hydraulic cylinder rapidly using little pressure to get the ram near the sheet
metal strip as quickly as possible. Then the cylinder must exert a large force using only a small flow rate. The
large force is needed to punch the workpiece from the sheet metal strip. Since the strip is thin, only a small flow
rate is required to perform the punching operation in a short time. The use of the pressure intensifier results in a
significant cost savings in this application, because it replaces the expensive high-pressure pump that would
normally be required.
Single Acting Intensifier consists of a low-pressure chamber of a comparatively bigger area and a high-pressure
chamber of a smaller cross-sectional area. It has a piston with two active areas. The larger end of the on is in the
low-pressure chamber and the smaller end of the piston is in the high-pressure area.
The low-pressure fluid exerts a force on the piston equal to P p × A i.e. pump pressure into a bigger piston area.
The same force is transmitted to the smaller side piston. However, since the area in the high-pressure side is
smaller, higher pressure is developed in this chamber by the same force.
The double-acting intensifier consists of a large piston with a piston rod extending to both sides of the piston.
The larger area of the piston is exposed to the low-pressure fluid, and the piston rod is connected to the high-
pressure side, on both sides of the piston.
When low-pressure fluid enters either side of the big piston, it causes the movement of the piston. The
movement of the piston results in the movement of the piston rod, forcing the fluid out at intensified high
pressure. A double-acting intensifier is symmetrical, about the vertical center line. Thus, the movement of the on
in either direction results in an intensified fluid output from any of the two outlet ends.
Thus, a double-acting intensifier simulates the operation of the two single-acting intensifiers.
2.11 ACCUMULATORS
Definition of Accumulator
An accumulator is a device that stores potential energy by means of either gravity, mechanical springs, or
compressed gases. The stored potential energy in the accumulator is a quick secondary source of fluid power
capable of doing useful work as required by the system.
There are three basic types of accumulators used in hydraulic systems. They are identified as follows:
Spring-Loaded Accumulator
A spring-loaded accumulator is similar to the weight-loaded type except that the piston is preloaded with a spring,
as illustrated in Figure 36.The compressed spring is the source of energy that acts against the piston, forcing the
fluid into the hydraulic system to drive an actuator. The pressure generated by this type of accumulator depends
on the size and preloading of the spring. In addition, the pressure exerted on the fluid is not a constant. The spring-
loaded accumulator typically delivers a relatively small volume of oil at low pressures. Thus, they tend to be heavy
and large for high-pressure, large-volume systems. This type of accumulator should not be used for applications
requiring high cycle rates because the spring will fatigue, resulting in an inoperative accumulator.
Gas-Loaded Accumulators
Gas-loaded accumulators (frequently called hydropneumatic accumulators) have been found to be more practical
than the weight- and spring-loaded types. The gas-loaded type operates in accordance with Boyle’s law of gases,
which states that for a constant temperature process, the pressure of a gas varies inversely with its volume. Thus,
for example, the gas volume of the accumulator would be cut in half if the pressure were doubled. The
compressibility of gases accounts for the storage of potential energy. This energy forces the oil out of the
accumulator when the gas expands due to the reduction of system pressure when, for example, an actuator rapidly
moves a load. Nitrogen is the gas used in accumulators because (unlike air) it contains no moisture. In addition,
nitrogen is an inert gas and thus will not support combustion.
1. Non-separator type
2. Separator type
1. Piston type
2. Diaphragm type
3. Bladder type
Piston Accumulator: The piston type of accumulator consists of a cylinder containing a freely floating piston
with proper seals, as illustrated in Figure 38. The piston serves as the barrier between the gas and oil. A threaded
lock ring provides a safety feature, which prevents the operator from disassembling the unit while it is precharged.
The main disadvantages of the piston types of accumulator are that they are expensive to manufacture and have
practical size limitations. Piston and seal friction may also be a problem in low-pressure systems. Also, appreciable
leakage tends to occur over a long period, requiring frequent precharging. Piston accumulators should not be used
as pressure pulsation dampeners or shock absorbers because of the inertia of the piston and the friction of the
seals. The principal advantage of the piston accumulator is its ability to handle very high or low temperature
system fluids through the use of compatible O-ring seals.
Figure 38 : Piston-type gas-loaded accumulator
Diaphragm Accumulator: The diaphragm-type accumulator consists of a diaphragm, secured in the shell, which
serves as an elastic barrier between the oil and gas (see Figure 39). A shutoff button, which is secured at the base
of the diaphragm, covers the inlet of the line connection when the diaphragm is fully stretched. This prevents the
diaphragm from being pressed into the opening during the precharge period. On the gas side, the screw plug allows
control of the charge pressure and charging of the accumulator by means of a charging device. Figure 40 illustrates
the operation of a diaphragm-type accumulator. The hydraulic pump delivers oil into the accumulator and deforms
the diaphragm. As the pressure increases, the volume of gas decreases, thus storing energy. In the reverse case,
where additional oil is required in the circuit, it comes from the accumulator as the pressure drops in the system
by a corresponding amount. The primary advantage of this type of accumulator is its small weight-to-volume
ratio, which makes it suitable almost exclusively for airborne applications.
Bladder Accumulator: A bladder-type accumulator contains an elastic barrier (bladder) between the oil and gas,
as illustrated in Figure 41. The bladder is fitted in the accumulator by means of a vulcanized gas-valve element
and can be installed or removed through the shell opening at the poppet valve. The poppet valve closes the inlet
when the accumulator bladder is fully expanded. This prevents the bladder from being pressed into the opening.
The greatest advantage of this type of accumulator is the positive sealing between the gas and oil chambers. The
lightweight bladder provides quick response for pressure regulating, pump pulsation, and shock-dampening
applications. Figure 42 illustrates the operation of a bladder-type accumulator. The hydraulic pump delivers oil
into the accumulator and deforms the bladder. As the pressure increases, the volume of gas decreases, thus storing
energy. In the reverse case, where additional oil is required in the circuit, it comes from the accumulator as pressure
drops in the system by a corresponding amount.
Applications of Accumulator
Basic Applications
There are four basic applications where accumulators are used in hydraulic systems.