Environment
Ambient temperature -15 to + 60°C (5 to 140°F) (operating and storage)
Relative humidity 80%, without condensation
* F.S. = Full scale (10 m/s)
1)
Under reference conditions i.e. measuring fluid = water, ambient and water temperature = 20°C (68°F), applying the
minimum inlet and outlet pipe straights, matched inside pipe dimensions.
www.burkert.com p. 1/5
8030
Electrical data
Operating voltage 12 - 36 V DC filtered and regulated (via Bürkert transmitter
the device is connected for “Low Power” version)
Current consumption with sensor
Hall version 30 mA
Hall “Low power” version 0.8 mA
Output: Frequency
Hall version 2 transistors NPN and PNP, open collector, max. 100 mA,
frequency: 0... 300 Hz; duty cycle 1/2 ±10%
NPN output: 0,2-36 VDC
PNP output: supply voltage
Hall “Low Power” version 1 transistor NPN, open collector, max. 10 mA,
frequency: 0... 300 Hz; duty cycle 1/2 ±10%
Dielectric strengh 2300 V AC
Reversed polarity of DC Protected * For the 97/23/CE pressure directive, the device can
only be used under following conditions (dependent on
Standards and approvals max. pressure, pipe diameter and fluid).
Protection class IP65 with connector plugged-in and tightened Type of fluid Conditions
Standard and directives Fluid group 1, §1.3.a DN 25 only
EMC EN 61000-6-2, 61000-6-3 Fluid group 2, §1.3.a DN 32 or
Pressure Complying with article 3 of §3 from 97/23/CE directive.* DN > 32 and PN*DN 1000
Vibration EN 60068-2-6 Fluid group 1, §1.3.b PN*DN 2000
Shock EN 60068-2-27 Fluid group 2, §1.3.b DN 200
Pressure/temperature chart
0ÖBAR !
-ETAL
06$&
06#Ö Ö00 06$&Ö0.
06#Ö0.
00Ö0.
4ÖÊ#
p. 2/5
8030
The flowmeter 8030 is built up with an electronic module SE30 associated to a fitting S030 with integrated measurement paddle wheel. This connec-
tion is made by means of a Quarter-Turn.
In a 3-wire system, the signal can be displayed or processed directly. The output signal is provided via cable plug according to EN 175301-803.
When liquid flows through the pipe, the paddle-wheel is set in rotation. The non-wetted permanent magnets inserted in the paddle wheel generate a
measuring signal which frequency is proportional to the flow velocity. A conversion coefficient (K-factor, available in the instruction manual of the fitting), specific
to each pipe (size and material) enables the conversion of this frequency into flow rate.
- with two transistor outputs NPN and PNP. - with one NPN transistor “Low Power” output.
An external power supply of 12 - 36 V DC is required. It is designed for An external power supply of 12 - 36 V DC is required. Can only be con-
connection to any system with open collector NPN or PNP frequency nected to remote versions of flow transmitters Type 8025/8032.
input.
Installation
The 8030 flowmeter can easily be installed into any Bürkert INLINE fitting system Type S030, by means of a Quarter-
Turn. Minimum straight upstream and downstream distances must be observed. According to the pipe’s design, neces-
sary distances can be bigger or use a flow conditioner to obtain the best accuracy. For more information, please refer to
EN ISO 5167-1.
EN ISO 5167-1 prescribes the straight inlet and outlet distances that must be complied with when installing fittings in
pipe lines in order to achieve calm flow conditions. The most important layouts that could lead to turbulence in the flow are
shown below, together with the associated prescribed minimum inlet and outlet distances. These ensure calm, problem-free
measurement conditions at the measurement point.
Pipe diameter
Control valve 2 x 90° elbow joint
expansion
Correct Incorrect
FLOW
Correct
Incorrect
Correct FLOW
Pressure and temperature ratings must be respected according to the selected fitting material. The suitable pipe size is selected using the diagram
Flow/Velocity/DN. The measuring device is not designed for gas flow measurement.
p. 3/5
8030
• Flow: 10 m3/h
• Ideal flow velocity: 2...3 m/s
For these specifications, the diagram indicates a pipe size of DN40 [or DN50 for (*) men-
tioned fittings]
Flow rate of fluid
Not recommended
gpm m3/h
1000 l/min
3000 200
500 2000 DN65
100
DN50 (DN65)*
1000
200 50 DN40 (DN50)*
500 DN32 (DN40)*
100
20 DN25 (DN32)*
50 200 DN20 (DN25)*
10
(
50
10
2 DN08
5 20
1 DN06
10
2 0.5
DN H
5 [mm] [mm]
1
0.2 06 95.5
0.5 2 08 95.5
0.1
15 100.5
1
0.2 0.05 20 98.0
0.5 25 98.0
0.1
0.02 32 102.0
0.05 0.2 40 105.5
0.01
50 112.0
0.1 0.3 0.5 1 3 5 10m/s Flow
0.3 0.5 1 3 5 10 30 fps velocity
65 112.0
p. 4/5
8030
Description
connection
Electrical
Item no.
Voltage
Output
supply
Hall version flowmeter (pluggable to Types 12 - 36 V DC Frequency, 2 transistors NPN and Cable plug EN 175301-803 423 913
8025 Universal transmitter, batch controller or PNP
konti-Dos; 8032; 8619; PLC)
Hall “Low Power” version flowmeter from associated Frequency, 1 transistor NPN Cable plug EN 175301-803 423 914
(pluggable to Types 8025, 8032 transmitter) transmitter
Specifica-
Item no.
tions
Cable plug EN 175301-803 with cable gland (Type 2508) 438 811
Cable plug EN 175301-803 with NPT1/2 “ reduction without cable gland (Type 2509) 162 673