Important HVAC Formulas

The document provides important formulas for HVAC engineers related to sensible cooling load, chilled water flow, duct sizing, latent cooling load, total cooling load, exhaust air flow, sensible heat load of walls, and louver sizing. Key variables and their meanings are defined in the legend at the bottom.

Uploaded by

Parth Gandhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
280 views1 page

Important HVAC Formulas

The document provides important formulas for HVAC engineers related to sensible cooling load, chilled water flow, duct sizing, latent cooling load, total cooling load, exhaust air flow, sensible heat load of walls, and louver sizing. Key variables and their meanings are defined in the legend at the bottom.

Uploaded by

Parth Gandhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

IMPORTANT FORMULAS FOR HVAC ENGINEERS

SENSIBLE COOLING LOAD CHILLED WATER FLOW DUCT SIZING

a, (Kw) = 1.2 x m, (m'/s) x AT (°C) Q, (Kw) a (m/s) = A(m') xv (m/s)


m, (L/s)= 4.1855 x AT (°C)
, (Btu/hr) =1.075 x m, (cfm) xAT (°F)
Q (cfm) = A(ft) x v (fpm)
Q, (Ton) x 24
LATENT CoOLING LOAD rm, (GPM) =
AT (°F) Rectangular area:A =W x H
Q (Kw) =2963.6 x ma (m/s) xAx (Kg/Kg)
For AT = 16°F = 9°C Circular area :A 3.14 x R?
a (Btu/hr) =4770 x in,, (cfm) x Ax (Ib/lb) rm, (GPM) = Q, (Ton)x 1.5
TOTAL COOLING LOAD For 4T = 10 F = 5.5 °C LOUVERS SIZING
Q, (Kw) = 1.2 x ma (m'/s) x AH (Kj/Kg) m, (GPM) = 4, (Ton) x 2.4 Q
(m°/s) =F.A, xA (m') xv (m/s)
a, (Btu/hr) =4.5 x ma (cfm) x AH (Btu/lb) EXHAUST AIR FLOw Q(cfm) =FA, *A (ft')xv (fpm)
V(m³) x ACH ((hr) Recommended vma, for sand trap
m,(L/s) = louvers : Vmax =1 m/s or 200 fpm
SENSIBLE HEAT LOAD OF WALLS 3.6

a, (w)=A (m') x U
(w/m'°K)x&T (°C) m(cfm) =
V(itt) x ACH (/hr) Recommended vm, for exhaust
4,(Btu/hrl-A (ft'}xU (Btu/hr.ft'°F) xAT(°F) 60 louvers: Vmax =2.5 m/s or 500 fpm
Legend: Q,=Sensible cooling load ; Q,=Latent cooling load ; Q,=Total cooling load ; m=Volumetric flow; AT=Temperature difference ;
Ax=Humidity diference ; AH=Enthalpy difference ; A=Area ; U=Thermal transmittance; v=Velocity ; W=Width ; H=Height ; R=Radius ;
FA,-Free area rate ; =Air volumetric flow ;V=Volume ;ACH=Air change per hour