Long-Start Motor Protection
Long-Start Motor Protection
Compact NSX Micrologic 5/6/7 > Protection Function > Motor-Feeder Application > Long-Start Motor Protection
Presentation
Long-start motor protection provides additional protection:
o For machines at risk of difficult starting:
o High inertia machines
o High resistive torque machines
o Machines with fluctuating load from steady state
Examples of machines with a significant risk of difficult starting: fans, compressors.
Description
Long-start motor protection is activated as soon as the average motor current Iavg exceeds 10% of the Ir setting value: the
protection tlong time delay is actuated. Long-start motor protection compares the value of the average motor current Iavg with
the setting value of the protection Ilong pickup.
By default, long-start motor protection is not active.
After function setting, long-start motor protection is:
o Active during startup
o Not active in steady state
1 Motor current
2 Activation of long-start motor protection tlong time delay
White: Protection not active. Green: Protection active
Diagram ΙΙΙ: The motor current has not fallen below 10% of the Ir setting value before the end of the tlong time delay: long-start
motor protection trips.
o A: Activation of protection time delay (10% of Ir pickup is exceeded)
o B: Protection tripped at the end of the time delay
If the motor current falls back below 10% of the Ir setting value before the end of the protection tlong time delay (for example
on contactor opening), long-start motor protection does not trip.
NOTE: The Micrologic trip unit measurement electronics filter the subtransient state (first current peak of approximately 20 ms
on contactor closing). This current peak is not therefore taken into account when assessing whether the Ilong pickup has been
crossed.