Metrosil Design Calculation and Selection 1715763923
Metrosil Design Calculation and Selection 1715763923
Selection procedure
Design Calculation
Prepared By,
MOHAMED JABIR
Protection Engineer
How to select the correct Metrosil device for your relay:-
5.Maximum Allowable Current Through the Relay Metrosil at the Setting Voltage
During normal operation, the relay Metrosil leaks a small amount of current. As the Metrosil is in parallel with the relay, it is important to account for the
leakage so the relay operates at the correct voltage/current.
TABLE-1: For 1A CTs Relay Metrosils with Maximum Internal Secondary Fault Current of 50Arms.
•600A reference to the disc diameter •I discs electrically insulated •P discs connected in parallel
•S1- single Metrosil disc units •S2 - 2 Metrosil disc units •S3 - 3 Metrosil disc units
TABLE-2 : For 5A CTs Relay Metrosils with maximum internal secondary fault currents of up to 150Arms.
NOTE: The distinction between 1A and 5A devices is based on typical fault current requirements. It is acceptable to use a 1A Metrosil device with a 5A CT
or vice versa, so long as the rated secondary fault current is not exceeded and all other parameters are appropriate. All properties quoted in this table
are typical values and do not constitute a specification.
Step 2 - Identify the Metrosil type
a) Identify the recommended Metrosil Type from either Table 1 or Table 2 using columns 2 and 5 ( ’Typical Relay Setting Voltage’ range and ‘Rated
Maximum Current’).
b) Find a relay setting voltage that is close to what you require. If your setting voltage is lower than the example voltages given, the corresponding
leakage current will be lower through that device.
NOTE: If required, these values can be more accurately determined in steps 3 and 4. For a 1A CT, decide if a single pole or a triple pole (3-phase) Metrosil
type is required.
At the relay setting voltage, check that the maximum leakage current for the identified Metrosil type is within the permissible limits of the relay system.
Or
For a maximum secondary internal fault current condition, check that the identified Metrosil type will limit the voltage to a level that does not exceed
the maximum allowable voltage of the relay system.
This can be done either:-
Or
If the fault duration is longer than 0.5s, use tables 1 or 2, columns 7, 8 and 9, to check that the fault time of the system is within the short time current
rating for the specified Metrosil type.
Energy and Power Ratings
Below table displays the rated energy absorption for each device (or each phase of a three phase device), along with the short time Power rating. Finally
the power dissipation represents the cooling rate of a Metrosil device after a surge event, provided it is installed with adequate space and airflow.