Model: SMX
The SMX model is designed keeping in mind the needs of today’s
performance conscious establishments. It is a range of compact
and feature-rich, modern-age panels that constitute together with
a suite of intelligent devices, highly reliable fire alarm systems.
The SMX panels meet the requirements of the latest codes and standards
and allow for quick and easy installation. Just fix the panel to the wall,
connect the field wiring devices, and power up the panel for a working fire
alarm system. The large touch display allows the panel to be programmed
easily by providing a clear menu structure, making the the entire setup
process extremely intuitive. Complex configuration is made easy by
using the mobile appl and the Bluetooth dongle connectivity.
SKU NO. DESCRIPTION NUMBER OF LOOP COLOR DEVICES DEVICES / LOOP ADDRESS RANGE DEVICES / PANEL
K E Y F E AT U R E S
• Multiple loop options – 1, 2, and 4 loops • Pluggable electrical connectors and • Ability to configure panels off-site
ergonomic design for easy installation and sync via USB pen drive
• Up to 198 devices per full loop
or Honeywell Bluetooth
• Large touch display for enhanced
• 160 fire zones
readability, context-awareness • Battery-backed, real-time clock (RTC)
• 10,000 events log and easy navigation resulting in
• 32-bit dual-core microprocessor
• Multiple output and input interfaces for exemplified user experience
• UL 864 10 th Edition Certified
a fully integrated fire alarm solution • Mobile and PC apps for
guided configuration
SMX Technical Specifications
INTERFACES
• 3 Output Relays with single pole changeover 24V DC 1 A: Fire Trouble & Programmable (Supervisory by default)
• 1 RS485 port for up to 8 repeaters or mimics or a combination of the two
• 1 RS232 ports: One for serial printer
• 2 USB ports: One for pen drive and Honeywell Bluetooth dongle and one reserved for future use
• 2 NAC circuit with max 150 mA each
• 2 on-board monitored inputs
MECHNICAL SPECIFICATIONS
MOUNTING HOLES 5
IP RATING 30
ELECTRICAL SPECIFICATIONS
Model: STX
The STX model is designed keeping in mind the needs of today’s
performance conscious establishments. It is a range of compact and
feature-rich, modern-age panels that constitute together with a suite of
intelligent devices, highly reliable fire alarm systems.
The STX panels meet the requirements of the latest codes and standards
and allow for quick and easy installation. Just fix the panel to the wall,
connect the field wiring devices, and power up the panel for a working
fire alarm system. The large touch display allows the panel to be
programmed easily by providing a clear menu structure, making the the
entire setup process extremely intuitive. Complex configuration is made
easy by using the mobile app and the Bluetooth dongle connectivity.
SKU NO. DESCRIPTION NUMBER OF LOOP COLOR DEVICES DEVICES / LOOP ADDRESS RANGE DEVICES / PANEL
K E Y F E AT U R E S
• Multiple loop options –half, 1 and 2 loops • Pluggable electrical connectors and • Ability to configure panels off-
ergonomic design for easy installation site and sync via USB pen drive
• Up to 198 devices per full loop
or Honeywell Bluetooth
• Large touch display for enhanced
• 160 fire zones
readability, context-awareness • Battery-backed, real-time clock (RTC)
• 5,000 events log and easy navigation resulting in
• 32-bit dual-core microprocessor
• Multiple output and input interfaces for exemplified user experience
• UL 864 10th Edition Certified
a fully integrated fire alarm solution • Mobile and PC apps for
guided configuration
STX Technical Specifications
INTERFACES
• 3 Output Relays with single pole changeover 24V DC 1 A: Fire Trouble & Programmable (Supervisory by default)
• 1 RS485 port for up to 4 repeaters or mimics or a combination of the two
• 1 RS232 ports: One for serial printer
• 2 USB ports: One for pen drive and Honeywell Bluetooth dongle and one reserved for future use
• 1 NAC circuit with max 150 mA
• 2 on-board monitored inputs
MECHNICAL SPECIFICATIONS
MOUNTING HOLES 3
IP RATING 30
ELECTRICAL SPECIFICATIONS
315-508
Honeywell Bluetooth USB Dongle is an elegant Bluetooth
Low Energy (BLE) product that is used for seamlessly
interfacing with the Morley STX and SMX fire panel models.
F E AT U R E S :
Following are the features of Honeywell wireless commissioning:
• Provides seamless wireless low power Bluetooth Connectivity to Morley STX and SMX fire panel models
• Eases the panel commissioning and maintenance operations through Honeywell SmartConfig™ Mobile app
• Enables productivity through a simple interface
• Eliminates the need to carry laptops, cables and so on to the site for configuration
How to connect the Honeywell Bluetooth USB Dongle to the fire panel?
1. Open the fire panel’s front door.
2. Look for the “USB 1” on the top
behind the display board.
3. Plug the USB dongle into
the “USB 1” port.
1 2 3 4
SMARTCONFIG
Launch the Honeywell Morley-IAS Establish a bluetooth connectivity Configure the Fire Alarm Control Voila! The Fire Alarm Control
SmartConfig™ mobile application. between mobile application and Panel using™ Quickwizard. Panel is configured.
Fire Alarm Control panel.
1. Ensure that the Honeywell Bluetooth USB Dongle is connected to the fire panel.
2. On the panel, tap Commissioning from the Main Menu.
3. Tap next to Configuration via Bluetooth.
4. On the mobile, switch-on the Bluetooth and discover, select the HONBLEKIT2 connection.
5. Enter the pass-code that appears on the panel screen into your mobile device.
6. The Bluetooth icon gets activated on the panel screen as soon as the panel is paired with the mobile device.
7. Now you can send the configuration from mobile to the panel or read from the panel, as required.
For more details on programing the fire panel via Bluetooth, refer to one or more of the following resources as required:
HM-D240CMO-UL
General
The HM-D240CMO-UL Addressable Relay Module provides
the system with a dry contact output for activating a variety of
auxilary devices, such as fans, door holders, dampers, control
equipment, etc. Addressability allows the dry contact to be
activated through panel programming, on a select basis.
Applications
The HM-D240CMO-UL may be programmed to operate
dry contacts for door holders, Air Handling Unit shutdown,
etc., and to reset four-wire smoke detector power.
Construction HM-D240CMO-UL
• The face plate is made of off-white, heat resistant plastic
F E AT U R E S & B E N E F I T S
• Built-in type identification • Integral LED “blinks” green each • Wide viewing angle of LED
automatically identifies these time a communication is received
• SEMS screws with clamping
devices to the control panel from the control panel and turns
plates for wiring ease
on in steady red when activated
• Internal circuitry and relay powered
• Direct-dial entry of address:
directly by two-wire SLC loop • High noise immunity (EMF/RFI)
61 -99 for models SMX and STX
HM-D240CMO-UL Technical Specifications
PARAMETER SPECIFICATION
Normal operating voltage 15 to 32 VDC
Maximum SLC current draw 6.5 mA (LED on)
Average operating current 230 μA direct poll (CLIP mode) with LED flashing
EOL resistance Not Used.
Temperature range 32°F to 120°F (0°C to 49°C)
Humidity range 10% to 93% non-condensing
4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm)
Dimensions
square x 2.215" (5.398 cm) deep box
Optional control module barrier, required by UL for separating power-limited and non-power-limited wiring in
CB500
the same junction box as HM-D240CMO-UL
NOTE: For installation instructions, see document CN-MN-0195 and refer to the SLC Wiring Manual.
HM-DCMO-UL
General
The HM-DCMO-UL Addressable Control Module provides a
circuit for Notification appliances like horns, strobes, and more.
Addressability allows the HM-DCMO-UL to be activated through
panel programming, on a select (zone or area of coverage) basis.
Construction
• The face plate is made of off-white, heat resistant plastic
Operation
Each HM-DCMO-UL uses one of the module addresses on a from the communication loop, so that a
SLC loop. It responds to regular polls from the control panel and trouble condition on the external power supply
reports its type and status, including the open/normal/ short status doesn’t interfere with the rest of the system.
of its Notification Appliance Circuit (NAC). The LED blinks with Rotary switches set a unique address for
each poll received. On command, it activates its internal relay. The each module. The address may be set
HM-DCMO-UL supervises Class B notification or control circuits. before or after mounting. The built-in TYPE
Upon code command from the panel, the HM-DCMO-UL will CODE (not settable) of the control panel will
disconnect the supervision and connect the external power supply in identify the module, so as to differentiate
the proper polarity across the load device. The disconnection of the between a module and a sensor address.
supervision provides a positive indication to the panel that the control
relay turned ON. The external power supply is always relay-isolated
F E AT U R E S & B E N E F I T S
• Built-in type identification • Integral green LED blinks each • Wide viewing angle of LED
automatically matches devices time a communication is received
• SEMS screws with clamping
to the control panel from the control panel and turns
plates for easy wiring
on steady red when activated
• Internal circuitry powered directly
• Direct-dial entry of address:
by a two-wire SLC loop The • High noise immunity (EMF/RFI)
61 -99 for models SMX and STX
HM-DCMO-UL module requires
• The HM-DCMO-UL may be used
power (for horns, strobes, etc.)
to switch 24-volt NAC power
HM-DCMO-UL Technical Specifications
PARAMETER SPECIFICATION
Average operating current 350 A direct poll (CLIP mode) with LED flashing
• 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep
Dimensions
• Mounts to a 4" (10.16 cm) square x 2.215" (5.398 cm) deep box
• ULC: S35595
Optional control module barrier, required by UL for separating power-limited and non-power-limited wiring in
CB500
the same junction box as HM-DCMO-UL
NOTE: For installation instructions, see document CN-MN-0194 and refer to the SLC Wiring Manual.
HM-DISO-UL
General
The HM-DISO-UL Fault Isolator Module is used with the fire alarm control
panels (FACPs) to protect the system against wire-to-wire short circuits
on the SLC loop. The HM-DISO-UL should be placed between each
device on the SLC loop to isolate a short circuit problem between the
modules. It is required for true Style 7 operation, so that other devices can
continue to operate normally in the event of a short circuit on the SLC.
Application
The Fault Isolator Modules should be spaced between groups of
sensors in a loop to protect the rest of the loop. The HM-DISO-
UL supports a maximum of 25 devices in between isolators.
HM-DISO-UL
F E AT U R E S & B E N E F I T S
Installation
• Mount on a standard junction box (4.0”/10.16 cm
square) which is at least 2.125”/5.398 cm deep
• Terminal screws are provided for “in and out” wiring
• Installation instructions are provided with each module
• Surface mount box available
HM-DMMI-UL Operation
HM-DMMI-UL Monitor Module Each HM-DMMI-UL uses one of the available
module addresses on an SLC loop. It responds to
regular polls from the control panel and reports
its type and the status (open/normal/short) of
its Initiating Device Circuit (IDC). A flashing LED
indicates that the module communicates with the
control panel. The LED steadily illuminates when an
alarm starts (subject to current loop limitations).
HM-DMMI-UL Specifications
Nominal operating voltage 15 to 32 VDC
HM-MM3E-UL Specifications
Nominal operating voltage 15 to 32 VDC
HM-MM3E-UL
350 A, 1 communication every 5 seconds, 47k
Average operating current
EOL; 600 A Max. (Communicating, IDC Shorted)
Maximum IDC wiring resistance 1500 Ohms
• Powered directly by two-wire SLC loop Maximum IDC Voltage 11 V
No additional power required Maximum IDC Current 450 A
• Tinned, stripped leads for easy wiring Temperature range 32°F to 120°F (0°C to 49°C)
Humidity range 10% to 93% non-condensing
• Direct-dial entry of address:
1.3” (3.302 cm) high x 2.75” (6.985 cm) wide x
61-99 for models SMX and STX Dimensions
0.65” (1.651 cm) deep
Wire length 6” (15.24 cm) minimum
HM-DCZRM-UL
The HM-MM3E-UL Min-Monitor Module can be • Supports compatible two-wire smoke detectors
installed in a single-gang junction directly behind the • Supervises IDC wiring and connection
monitored unit. Its small size and light weight allow it to of external power source
be installed without rigid mounting. The HM-MM3E-UL • High noise (EMF/RFI) immunity
is intended for use in intelligent, two-wire systems where • SEMS screws with clamping plates for ease of wiring
the individual address of each module is selected using • Direct-dial entry of address:
rotary switches. It provides a two-wire initiating device 61 -99 for models SMX and STX
circuit for normally open, contact fire alarm devices.
• LED flashes during normal operation
HM-MM3E-UL Applications • LED steadily illuminates to indicate an alarm
Use to monitor a single device or a zone of four-wire on command from the control panel
smoke detectors, manual fire alarm pull stations, The HM-DCZRM-UL Interface Module is intended
waterflow devices, or other normally open, dry contact for use in intelligent, addressable systems, where the
devices. Monitor normally-open supervisory devices individual address of each module is selected using
with special supervisory indication at the control built-in rotary switches. This module allows intelligent
panel. Monitored circuit/device is wired as an NFPA panels to interface and monitor two-wire conventional
Class B Initiating Device Circuit. A 47K Ohm end of smoke detectors. It transmits the status (normal, open,
line resistor (provided) terminates the circuit. or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being
monitored must be UL compatible with the module.
HM-DCZRM-Ul Applications Installation
Use the HM-DCZRM-UL to monitor a zone of two-wire HM-DMMI-UL, and HM-DCZRM-UL modules mount
smoke detectors. The monitored circuit may be wired as an directly to a standard 4” (10.16 cm) square, 2.125”
NFPA Class B Initiating Device Circuit. A 3.9 K Ohm end of (5.398 cm) deep, electrical box. They may also be
the line resistor (provided) terminates the end of the Class mounted to the SMB500 surface mount box. Mounting
B circuit (maximum IDC loop resistance is 25 Ohms). hardware and installation instructions are provided
with each module. All wiring must conform to applicable
HM-DCZRM-UL Operation
local codes, ordinances, and regulations. These
Each HM-DCZRM-UL uses one of the available
modules are intended for power-limited wiring only.
module addresses on an SLC loop. It responds to
regular polls from the control panel and reports The HM-MM3E-UL module is intended to be wired
its type and the status (open/normal/short) of and mounted without rigid connections, inside a
its Initiating Device Circuit (IDC). A flashing LED standard electrical box. All wiring must conform to
indicates that the module is in communicates with applicable local codes, ordinances, and regulations.
the control panel. The LED steadily illuminates when
an alarm is on (subject to current loop limitations).
Agency Listings and Approvals
HM-DCZRM-UL Specifications Listing and approval below apply to the modules specified
Nominal operating voltage 15 to 32 VDC in this. In some cases, certain modules may not be
Maximum current draw 5.1 mA (LED on) listed by certain approval agencies, or listing may be
Maximum IDC wiring resistance 25 Ohms in process. Consult factory for latest listing status.
270 A, 1 communication and 1 LED flash • UL: S35595
Average operating current
every 5 seconds, 3.9k eol
EOL resistance 3.9K Ohms Product Line Information
• DC voltage: 24 V power limited
External supply voltage
• Ripple voltage: 0.1 Vrms maximum HM-DMMI-UL Addressable Monitor Module
(between Terminals T10 and T11)
• Current: 90 mA per module maximum
HM-MM3E-UL Addressable Min-Monitor Module
Temperature range 32°F to 120°F (0°C to 49°C)
Humidity range 10% to 93% non-condensing HM-DCZRM-UL Addressable Interface Module
4.5” (11.43 cm) high x 4” (10.16 cm) wide NOTE: See installation instructions CN-MN-0196, CN-MN-0197
x 1.25” (3.175 cm) deep. Mounts to a 4”
Dimensions and CN-MN-0198 and refer to the SLC Wiring Manual.
(10.16 cm) square x 2.125” (5.398 cm)
deep box
Honeywell Building Technologies ASEAN Honeywell Building Technologies META
Level 25, UOA Corp Tower B, Avenue 10 Emaar Business Park, Building 2, 2nd Floor
The Vertical, Bangsar South City Sheikh Zayed Road
59200, Kuala Lumpur, Malaysia P.O.Box 232362, Dubai, U.A.E.
Email: [email protected] Phone: +971 4 4505 847
HM-FHSE-UL, HM-RHSE-UL
HM-HTSE-UL
General HM-RHSE-UL
HM-FHSE-UL
The HM-FHSE-UL, HM-RHSE-UL and HM-HTSE-UL Series
thermal detectors are addressable sensors that use a state-
of-the-art thermistor sensing circuit for fast response. These
sensors provide protection for open areas and can be used
use with addressable Fire Alarm Control Panels (FACPs).
Installation Operation
The HM-FHSE-UL Series of plug-in, intelligent Each HM-FHSE-UL Series detector uses one of 159
thermal detectors use a detachable base to simplify or 59 (Model: STX, 98 devices)possible addresses on a
installation, service, and maintenance. Installation control panel SLC loop. It responds to regular polls from
instructions are shipped with each detector. the control panel and reports type and status. If it receives
a test command from the panel (or a local magnet test),
Mount base on an electrical backbox which is at least 1.5” (3.81 cm) the detector stimulates its electronics and reports an
deep. For a chart of compatible junction boxes, see DF-60059. alarm. The LEDs blink when polled and the detector
turns the LEDs on when commanded by the panel. The
Application HM-FHSE-UL Series offer features and performance
Use thermal detectors for protection of property. that represent the latest in thermal detector technology.
F E AT U R E S & B E N E F I T S
SLC Loops: Operation: Mechanicals:
• Two-wire SLC loop connection • Factory preset at 135°F (57°C) for • Sealed against back pressure
• Unit uses base for wiring the HM-FHSE-UL and HM-RHSE-UL; • SEMS screws for wiring of
190°F (88°C) for the HM-HTSE-UL the separate base
Addressing:
• Rate-of-rise triggers at 15°F (8.3°C) • Designed for direct-surface or
• Addressable by device
per minute for the H355R(A) electrical-box mounting
• Rotary, decimal addressing:
• 360-degree viewing angle of the • Plugs into separate base for ease
1- 159 for models SMX and STX
visual alarm indicators. LEDs of installation and maintenance
Architecture: blink red in Normal condition and
Other system features:
• Sleek, low-profile, stylish design steadily illuminate red in Alarm
• Remote test feature from the panel
• State-of-the-art thermistor • Visible LEDs blink every time
• Walk test with address display
technology for fast response the unit is addressed
• Low standby current
• Integral communications and built-
• 94-5V plastic flammability rating
in device-type identification
• Built-in tamper resistant feature Options:
• Built-in functional test switch • Flanged surface mounting kit
activated by external magnet
HM-FHSE-UL, HM-RHSE-UL, HM-HTSE-UL Technical Specifications
PARAMETER SPECIFICATION
Agency Listings and Approvals
Listing and approval below apply to the modules specified
• 2.1" (5.3 cm) high; base determines diameter
Size in this. In some cases, certain modules may not be
• B501: 4.1” (10.4 cm) diameter
listed by certain approval agencies, or listing may be
Shipping weight 4.8 oz. (137 g)
in process. Consult factory for latest listing status.
• HM-FHSE-UL, HM-RHSE-UL: –4°F to 100°F
Installation temperature (–20°C to 38°C) • UL Listed: S36217
• HM-HTSE-UL: –4°F to 150°F (–20°C to 66°C)
Humidity range 10% to 93% relative humidity (non-condensing) PRODUCT LINE INFORMATION
Voltage range 15 to 32 VDC peak Intelligent thermal sensor; 135° F (57° C); B501
HM-FHSE-UL
base included
300 μA @ 24 VDC (one communication every five
Standby current Same as HM-FHSE-UL with rate of rise feature; B501
seconds with LED blink enabled) HM-RHSE-UL
base included
LED current 6.5 mA @ 24 VDC Intelligent, fixed, high-temperature thermal detector;
HM-HTSE-UL
190° F (88° C); B501 base included
135°F (57°C) for the HM-FHSE-UL and HM-RHSE-
Fixed-temperature setpoint
UL; 190°F (88°C) for the HM-HTSE-UL
ACCESSORIES
HM-MCP-GLASS-UL
General
The HM-MCP-GLASS-ULis an addressable manual break glass call
point which, as a simple rotary decade, switch at the rear of the unit
for addressing.
A specialist test key may be inserted into the bottom of the unit to lower
the glass and release the micro-switch – enabling a complete
functionality test.
LED Status
The LED status is controlled by the fire panel and shows blinking RED
each time the device is polled, or continuous RED to indicate
fire detection.
F E AT U R E S & B E N E F I T S
Mechnical Specifications
PARAMETER SPECIFICATION
IP Rating IP24D
Electrical Specifications
PARAMETER SPECIFICATION
Optional Accessories
PART CODE DESCRIPTION
• UL Listed: S36215
HM-PSE-UL
General
The HM-PSE-UL addressable, low-profile plug-in photoelectric
detectors use a state-of-the-art photoelectric sensing chamber
with communications to provide open area protection – used
exclusively with Fire Alarm Control Panels (FACPs). Since these
detectors are addressable, they will help emergency personnel
quickly locate a fire during its early stages, saving precious rescue
time while also reducing property damage. It comes with two LEDs
on each sensor light to provide a local, visible sensor indication.
Applications
The HM-PSE-UL uses photoelectric detectors in life safety applications
to provide a broad range of fire-sensing features, especially where
smoldering fires are anticipated. Ionization detectors are often
better than photoelectric detectors at sensing fast, flaming fires. HM-PSE-UL
Construction
These detectors are constructed of off-white, fire resistant plastic.
Operation
HM-PSE-UL plug-in, low-profile smoke detectors are designed
HM-PSE-UL has a unique unipolar chamber that
to commercial standards and have an appealing design.
responds quickly and uniformly to a broad range of
smoke conditions. It can withstand wind gusts up to
Installation
4,000 feet-per-minute (20 m/sec.) without sending
HM-PSE-UL plug-in detectors use a detachable mounting
an alarm level signal. Because of its unipolar
base to simplify installation, service, and maintenance.
chamber, the HM-PSE-UL is approximately two
Mount base (all base types) on an electrical backbox which is at least 1.5” times more responsive than most photoelectric
(3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059. sensor – offering enhanced stability.
F E AT U R E S & B E N E F I T S
ACCESSORIES
XR2B Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applications
XP-4 Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections
• UL Listed: S36216
HM-PTSE-UL
General
The HM-PTSE-UL detector is an intelligent, addressable, multi-sensing,
low-profile detector designed for Fire Alarm Control Panels.
F E AT U R E S & B E N E F I T S
ACCESSORIES
• UL Listed: S36216
315-040
LED Driver Module
General
The 315-040 is an LED driver module that can be used in a wide
variety of applications including as an interface with the Fire Alarm
Control Panel (FACP) to drive most customized graphic annunciators.
It comes in a plastic enclosure that may be mounted inside a custom
annunciator or accessory cabinet and can drive up to 40 LEDs.
K E Y F E AT U R E S
• 315-040 connects to the Repeater- • Compatible with Honeywell Morley • Up to eight Repeater-Bus
Bus terminal on the FACP and STX and SMX fire panel models devices may be connected to the
requires minimal programming Repeater-Bus of each FACP
• Can be remotely located up to 6,000
• Each 315-040 module feet (1,829 m) from the panel
drives up to 40 LEDs
• May be powered by 24 VDC from
• Programmable to indicate the host FACP or by remote power
activity for points or zones supply (requires 24 VDC)
315-040 Technical Specifications
Maximum Repeater-Bus Voltage 24 VDC
Maximum Current Alarm: 200 mA, Standby: 35 mA, Each LED: 10mA
External measurements 6.00” (15.2 cm.) high x 7.76” (19.7 cm.) wide x 1.46” (3.7 cm.) deep
The Repeater-Bus:
• Powering the devices on the repeater-bus from auxilIary power supply
Repeater-bus devices can be powered by an auxiliary power supply when
available panel power is exceeded. See facp manual for information.
ExitPoint™
Directional Sounder
with Voice Messaging
Audio/Visual Devices
General
The ExitPoint™ Directional Sounder has an integral audio ampli-
fier that produces a pulsating sound consisting of broadband
low, mid, and high range sounds. The broadband noise makes it
possible to determine the location of the sound. There are four
pulse patterns that can be used to create an egress pathway out
of a building and to mark perimeter exits. In addition to the
broadband noise, the sounder is capable of playing an alert
message in the form of a recorded voice message or other audi-
ble signals. These messages will instruct the occupants of what
action to take as they approach the directional sounder, and will
allow them to react quickly and confidently when the sounder is
activated. Fifteen different language combinations are available
to instruct occupants that they are nearing an exit, a stairway up,
a stairway down, or an area of refuge. The directional sounder
also incorporates an optional disable feature for use in conjunc-
tion with a control module or heat sensor.
The directional sounder features a number of field selectable
7044pho1.jpg
power settings including high, medium-high, medium-low, and
low. Installation ease and pleasing aesthetics are achieved by a
low profile compact design, and by the ability to flush mount in a
4” x 4” x 2¼” back-box.
ExitPoint directional sounders, fitted in addition to normal build-
ing evacuation sounders, draw people to evacuation routes in
both good and poor visibility. The directional sounder can be
Additional Tone Selection
used in a wide range of building applications. Trials consistently
Switch Switch
have shown an improvement of up to 75 percent in evacuation Position 5 Position 6 Sound Output
times in smoke and up to 35 percent without smoke. The 2007 Setting Setting
Edition of NFPA 72 now provides installation and maintenance
guidelines on directional sounders. On On Area of Refuge
On Off Upstairs
Features Off On Downstairs
• Listed to UL 464 (indoor applications only) Off Off Exit Here
• Five field-selectable power settings
• Four field-selectable routing evacuation patterns Enable/Disable Selection
• Constructed to be effective in unfamiliar surroundings or
poor visibility Switch
• Designed to work in open areas, corridors, or stairs
Position 4 Terminals 3 & 4 Sound Output
Setting
• Fifteen different language selections available
On Open Disabled
• Reduces evacuation times by as much as 75 percent
On Closed Enabled
• Optional disable feature for use in conjunction with a control
module or heat sensor Off Open Enabled
• Low profile, compact design Off Closed Disabled
315-080
80-Character Serial LCD Annunciator
General
The 315-080 annunciator is a compact, backlit, 80-character LCD fire
annunciator that mimics the Fire Alarm Control Panel (FACP) display.
It provides system status indicators for AC Power, Alarm, Trouble,
Supervisory, and Alarm Silenced conditions. The 315-080 and the FACP
communicate over a two-wire serial interface employing the Repeater-Bus
communication format. Connected devices are powered, via two additional
wires, by either the host FACP or a remote UL-listed, filtered power supply.
K E Y F E AT U R E S
• Listed to UL Standard 864, 9th Edition • Enclosure supervised for tamper • Surface mount directly to wall or to
single, double, or 4” square electrical box
• Backlit 80-character LCD display • System status LEDs for AC Power,
(20 characters x 4 lines) Alarm, Trouble, Supervisory, • Semi-flush mount to single, double,
and Alarm Silence or 4” square electrical box. Use ANN-
• Mimics all display information
SB80KIT for angled view mounting
from the host panel • Local sounder can be enabled
or disabled at the FACP • Can be remotely located up to 6,000
• Control switches for System
feet (1,800 m) from the panel
Acknowledge, Signal Silence, and Reset • 315-080 connects to the Repeater-
Bus terminal on the FACP and requires • Backlight turns off during AC loss to
• Control switches can be independently
minimal panel programming conserve battery power but will turn
enabled or disabled at the FACP
back on if an alarm condition occurs
• Displays device type identifiers,
• Keyswitch enables/disables
individual point alarm, • May be powered by 24 VDC from
control switches and mechanically
trouble, supervisory, zone, the host FACP or by remote power
locks annunciator enclosure
and custom alpha labels supply (requires 24 VDC)
• Keyswitch can be enabled
• Time and date display field • Up to eight 315-080 repeaters can be
or disabled at the FACP
connected on the RS485 Repeater-Bus
315-080 Technical Specifications
Operating voltage range 18 VDC to 28 VDC
Dimention 5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375” (3.49 cm.) deep