AIOM-2 Instruction Manual, Rev C-9500700990
AIOM-2 Instruction Manual, Rev C-9500700990
www.basler.com AIOM-2
+1 618.654.2341 (USA) Description
[email protected]
Analog I/O Module
INTRODUCTION
The AIOM-2 Analog I/O Module provides an additional four analog inputs, two resistance temperature detector
(RTD) inputs, and eight analog outputs to an ECS2100 or DECS-2100 digital excitation control system. AIOM-2
analog inputs and outputs interface with external devices such as meters, RTDs, transducers, chart recorders,
distributed control systems (DCS) and programmable logic controllers (PLC). An ECM/SIM or ECM-2 excitation
control module polls each AIOM-2 for input status and controls AIOM-2 outputs through a fiber optic link. Up to
two AIOM-2 modules can be connected in daisy chain configuration to provide a total of eight analog inputs, four
RTD inputs, and sixteen analog outputs.
The metal enclosure of the AIOM-2 offers electric shock protection from incidental contact. An identical footprint
and functional compatibility makes for simple replacement of an AIOM with the AIOM-2.
SPECIFICATIONS
Analog Inputs
Inputs: 4
Range: ±10 Vdc or 4 to 20 mAdc (switch selectable, see Voltage/Current Input Mode Switch)
Pin Assignments
CH1: 1 (V+), 2 (–), 3 (I+)
CH2: 4 (V+), 5 (–), 6 (I+)
CH3: 7 (V+), 8 (–), 9 (I+)
CH4: 10 (V+), 11 (–), 12 (I+)
Analog Outputs
Outputs: 8
Range: ±10 Vdc or 4 to 20 mAdc
Pin Assignments
OUT1: 33 (+), 34 (–)
OUT2: 31 (+), 32 (–)
OUT3: 29 (+), 30 (–)
OUT4: 27 (+), 28 (–)
OUT5: 44 (+), 45 (–)
OUT6: 42 (+), 43 (–)
Instructions
Publication Revision Date Copyright
Communication Interface
Type: Fiber optic link
Connectors:
Main: F1 (TX), F2 (RX), F3 (CLK)
Redundant: F4 (TX), F5 (RX), F6 (CLK)
AIOM: F8 (TX), F7 (RX), F9 (CLK)
Environment
Temperature
Operating: –40 to 60°C (–40 to 140°F)
Storage: –40 to 65°C (–40 to 149°F)
Ingress Protection Class: IP20
Altitude: Up to 1,000 meters (3,300 feet)
Humidity: 0 to 95%, non-condensing
Physical
Weight: 1.6 lb (0.7 kg)
Size (WxHxD): 5.82 x 6.81 x 2.82 inches (147.9 x 173 x 71.6 mm)
INSTALLATION
The AIOM-2 is typically preinstalled in the excitation control system. If replacement is necessary, carefully label
and document each of the connections to the AIOM-2 in order to properly reconnect the new module. AIOM-2
connectors and indicators are illustrated in Figure 1. Locator letters in Figure 1 correspond to the lettered
descriptions in Table 1. The AIOM-2 must be monitored and adjusted to fit the specific application at initial startup,
whether it is a new unit or a replacement.
AIOM-2 Connections
AIOM-2 connections consist of screw terminal connectors and fiber optic connectors.
Screw Terminal Connectors
Connectors with screw-down compression terminals are used for the analog inputs, analog outputs, channel
selection input, RTD inputs, and operating power inputs. The connectors, and the headers that they plug into,
have a dovetailed edge that ensures proper connector orientation. Similar-sized connectors and headers are
uniquely keyed to ensure that a connector mates only with the correct header to prevent damage to the AIOM-2.
However, care must still be taken to ensure that the proper connector is inserted into the appropriate header.
Connector screw terminals accept a maximum wire size of 12 AWG. The maximum screw torque is 5.3 in-lb or
0.6 N•m.
Fiber Optic Connectors
Fiber optic connectors exchange an isolated, digital signal with the ECM-2 or ECM/SIM.
Instructions
Publication Revision Date Page
Instructions
Publication Revision Date Page
Analog Outputs
Eight individually configurable analog outputs are provided on each module. Each output is isolated at 500 Vac
from the other outputs, the power supply, the analog inputs, and the RTD inputs. The analog outputs may be
configured to supply either ±10 Vdc or 4-20 mAdc with 16-bit resolution. The voltage mode of operation requires a
Instructions
Publication Revision Date Page
Operating Power
AIOM-2 operating power is provided through the redundant +24 Vdc PS1 and PS2 connectors. The power supply
is isolated at 500 Vac from the analog inputs, RTD inputs, and analog outputs.
MONITORING
AIOM-2 monitoring consists of two LED indicators located on the front panel. The green Power LED lights to
indicate the presence of AIOM-2 operating power at either of the power supply inputs (PS1 or PS2). The green
Active Status LED lights to indicate proper communication is established with an ECM/SIM or ECM-2.
VERIFICATION
There are no user adjustments on the AIOM-2. Using a precision voltage source, multimeter, an ECM or ECM-2
and BESTCOMSPro, the accuracy of the inputs across the full range may be verified by plotting the analog input
versus the digital values displayed in BESTCOMSPro. Likewise, the accuracy of the outputs may be verified by
plotting the digital output value shown in BESTCOMSPro versus the measured analog output. The RTD input may
be verified by connecting a variable resistor to the input and plotting the measured resistance to the digital
temperature (or resistance) value displayed in BESTCOMSPro.
MAINTENANCE
This module contains solid-state components which require no preventive maintenance.
SPARE PARTS
A reasonable stock of spare parts minimizes downtime in the event of malfunction. When ordering spare parts,
care should be taken to specify the style numbers (or other identification) which are printed on the nameplate.
Careful documentation of the original connections is essential any time the AIOM-2 is removed. It is
recommended that at least one AIOM 2 is stocked.
Warning!
Instructions
Publication Revision Date Page
GLOSSARY
AIOM-2, AIOM
Analog I/O Module. Provides additional analog inputs, RTD inputs, and analog outputs to an ECS2100 or DECS-
2100 digital excitation control system.
BCM-2
Bridge Control Module. The BCM-2 generates the gating pulses for the SCRs in a power bridge.
BESTCOMS™Pro
A Windows®-based PC application which connects to an ECM-2, FCIM, or BCM-2 for user programming and
monitoring of excitation system functions. This software presents table and block diagram representations of the
controller logic configuration.
ECM
Exciter Control Module. This contains the excitation control, limiting, protection, and communication software. The
ECM is used with the ECS2100 system.
ECM-2
Excitation Control Module. This contains the excitation control, firing control, limiting, protection, and
communication software. The ECM-2 is used with the DECS-2100 system.
FCIM
Firing Control Interface Module, used only in ECS2100 excitation systems. Determines when to fire power bridge
SCRs based on the ac source waveforms and firing angle commands from the ECM.
SIM
Sensor Input Module, used only in ECS2100 excitation systems. Provides isolated signals from the PT, CT,
AIOM-2, and DIOM-2 to the ECM.
Instructions
Publication Revision Date Page