Circulation Pump
Circulation Pump
Circulation Pump
Package 2
MANUFACTURER : FISCHER
AUTHOR : MURAD ABUBAKER
SUPPLIER : FISCHER
M-ANM-3A1DPW-CMEP-RPT-200047 Rev A
11 JANUARY 2024
CONTENTS
4. References -------------------------------------------------------------------------(11)
5. Material Specifications-----------------------------------------------------------(12)
6. Drawing Reference--------------------------------------------------------------- (14)
7. Calculations------------------------------------------------------------------------ (17)
The main purpose of this calculation document is concerned for Supports system
calculation from Fischer for services such as Piping, Ductwork with related drawing
in accordance with standard, project specifications and design requirement.
Reference Drawing
Calculation Notes
BS : British Standard
NA : Not Applicable
QC : Quality Control
FA : Fresh Air
EA : Exhaust Air
DW : Duct Work
GI : Galvanized Iron
4 REFERENCES
The materials to be used at site shall conform to the requirement of approved material Submittal.
DRAWING REFERENCE
4°
24
)
KK
AH LINE 2
SIDEWALK LEVEL (MA LINE 6
758.030 LINE 1 EAST DEPOT
LINE 5
LINE 3.
A A
WEST DEPOT
LINE 1
4°
H)
24
KKA
(MA
GENERAL NOTES
- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED .
753.800 - PLUMBING DRAWINGS SHALL BE READ WITH THE ARCHITECTURAL ,
STRUCTURAL ,ELECTRICAL ,A/C AND OTHER DRAWINGS FOR COORDINATION ,
VERIFICATION OF ADEQUATE SPACES AND EARLY DETERMINATION OF ANY
753.700 A A 753.790 CONTRADICTIONS OR INTERFERENCE PER THE PROVISIONS OF THE
A SPECIFICATION .
A A -THE DRAWINGS ARE ISSUED FOR PLUMBING WORKS ONLY AND SHALL NOT BE
A 753.360 USED FOR ARCHITECTURAL ,STRUCTURAL OR OTHER WORKS .
753.390 -THE ELEVATION ARE MEASURED FROM F.F.L LEVEL OF THE BASED FLOOR .
A A ← ←
-ALL PIPES SHOWN ARE RUNS INSIDE FALSE CEILING LEVEL OR EMBEDDED IN
THE WALLS EXCEPT OTHERWISE NOTED BY THE CONSULTANTS . .
-SIZES OF DRAIN ,VENT AND WATER PIPE CONNECTIONS TO INDIVIDUAL
PLUMBING FIXTURES SHALL BE IN ACCORDANCE WITH THE INDIVIDUAL FIXTURE
PIPE SIZE TABLE EXCEPT IF SHOWN OTHERWISE ON THE DRAWINGS.
-PLUMBING PIPES MATERIALS (SEWAGE ,FLOOR DRAINAGE AND VENT PIPE )ARE
ALL HDPE PIPES .WHICH WAS APPROVED BY THE CONSULTANTS .
-DISTANCE OF HANGER SUPPORT :DN "1=25BELOW 0.9 =M SPAN ;DN "1-1/4 1=32
ABOVE 1.2 =M SPAN SPACING
ROXPLUS 200 SUPPORT REFERENCE ARE FROM SBC -SAUDI BUILDING CODE 701AND HILTI
CALCULATIONS . .
- ALL MATERIALS ARE COMPLYING WITH SPECIFICATION AND APPROVED BY THE
CONSULTANTS .
- ELEVATION
- SCALE 1:100
S-02
-
PROJECT
T.G. M.A.
A.K. S.J.
DATE SCALES ORIGINAL SIZE A1
A1= 1:30
A3= 1:50
S-01 JANUARY 2024
0 2.5m 5m
-
SUBJECT TITLE
S-03
- WEST DEPOT
MEP
SEWAGE WASTE WATER RECYCLING TREATMENT
PLAN
MASTER PLAN S-02
- ANM SHOP DRAWING NUMBER REVISION SHEET
SCALE 1:100 1 of 4
M-ANM-3A1DPW-CUSE-SDR-200318 B
4°
24
NO DESCRIPTION BRAND SUBMITTAL REFERENCE NO. (MA
KK
AH
)
LINE 2
LINE 6
LINE 1 EAST DEPOT
1 WALL -- - LINE 5
01 02 N
4°
H)
24
KKA
03 (MA
GENERAL NOTES
- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED .
- PLUMBING DRAWINGS SHALL BE READ WITH THE ARCHITECTURAL ,
STRUCTURAL ,ELECTRICAL ,A/C AND OTHER DRAWINGS FOR COORDINATION ,
06 07 04
ABOVE 1.2 =M SPAN SPACING
SUPPORT REFERENCE ARE FROM SBC -SAUDI BUILDING CODE 701AND HILTI
CALCULATIONS . .
- ALL MATERIALS ARE COMPLYING WITH SPECIFICATION AND APPROVED BY THE
CONSULTANTS .
LAV.
WATER CLOSET
LAVATORY
SCALE : NTS H.D.P.E. HIGH-DENSITY POLYETHYLENE
SHOP DRAWING
PROJECT
T.G. M.A.
A.K. S.J.
DATE SCALES ORIGINAL SIZE A1
A1= NTS
A3= NTS
JANUARY 2024
0 2.5m 5m
SUBJECT TITLE
WEST DEPOT
MEP
SEWAGE WASTE WATER RECYCLING TREATMENT
DETAILS SHEET-1
M-ANM-3A1DPW-CUSE-SDR-200318 B 3 of 4
CALCULATIONS
Location : DEPOTS
Consultant : RMTC
Contractor : ANM
1. Calculation Note
f. Pipe 2 inch
Factor of Safety 2
Grade of Rod 4.8
Consider the own weight: Yes
Pipe Total Weight of Distance Factor Proposed Hanger Drop in Anchor Threaded Rod
Size pipe filled with between of Total Support
Point Load on
RESULT
water Supports Safety Weight Distance from
Utilization %
Utilization %
Utilization %
# hanger support
Wall to Center
(kN) Type Type Type
(KG) of Pipe (S)
(mm) (Kg/m) (mm)
1 15 0.74 900 2 0.007 0.01 150.00 FRSR 15-19 2% EA II M 10 0% TRS 10 1% SAFE
2 25 1.27 900 2 0.011 0.02 150.00 FRSR 26-30 4% EA II M 10 1% TRS 10 1% SAFE
3 32 1.93 1200 2 0.023 0.05 150.00 FRSR 32-36 7% EA II M 10 1% TRS 10 2% SAFE
4 40 2.33 1200 2 0.028 0.06 150.00 FRSR 38-43 9% EA II M 10 1% TRS 10 3% SAFE
5 50 3.66 1200 2 0.044 0.09 150.00 FRSR 53-58 14% EA II M 10 2% TRS 10 5% SAFE
6 65 5.70 1200 2 0.068 0.14 150.00 FRSR 68-72 21% EA II M 10 3% TRS 10 7% SAFE
7 80 8.00 1200 2 0.096 0.19 150.00 FRSR 75-80 30% EA II M 10 5% TRS 10 10% SAFE
8 100 13.85 1200 2 0.166 0.33 150.00 FRSR 99-105 28% EA II M 10 8% TRS 10 18% SAFE
9 150 27.90 1200 2 0.335 0.67 150.00 FRSR 99-105 56% EA II M 10 17% TRS 10 36% SAFE
Page 1 of 19
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 15 inch
weight of one pipe : 0.74 kg/m'
Support Distance: 900 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 0.67 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.01 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 15-19
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.01 kN.m
Allowable Force for FRSR 15-19 = 0.64 kN.m
Utalization Of fischer clamp FRSR 15-19 = 0.02 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 25 inch
weight of one pipe : 1.27 kg/m'
Support Distance: 900 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 1.14 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.02 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 26-30
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.02 kN.m
Allowable Force for FRSR 26-30 = 0.64 kN.m
Utalization Of fischer clamp FRSR 26-30 = 0.04 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 32 inch
weight of one pipe : 1.93 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 2.32 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.05 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 32-36
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.05 kN.m
Allowable Force for FRSR 32-36 = 0.64 kN.m
Utalization Of fischer clamp FRSR 32-36 = 0.07 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 40 inch
weight of one pipe : 2.33 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 2.80 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.06 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 38-43
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.06 kN.m
Allowable Force for FRSR 38-43 = 0.64 kN.m
Utalization Of fischer clamp FRSR 38-43 = 0.09 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 50 inch
weight of one pipe : 3.66 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 4.39 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.09 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 53-58
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.09 kN.m
Allowable Force for FRSR 53-58 = 0.64 kN.m
Utalization Of fischer clamp FRSR 53-58 = 0.14 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 65 inch
weight of one pipe : 5.70 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 6.84 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.14 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 68-72
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.14 kN.m
Allowable Force for FRSR 68-72 = 0.64 kN.m
Utalization Of fischer clamp FRSR 68-72 = 0.21 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 80 inch
weight of one pipe : 8.00 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 9.60 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.19 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 75-80
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.19 kN.m
Allowable Force for FRSR 75-80 = 0.64 kN.m
Utalization Of fischer clamp FRSR 75-80 = 0.30 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 100 inch
weight of one pipe : 13.85 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 16.62 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.33 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 99-105
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.33 kN.m
Allowable Force for FRSR 99-105 = 1.20 kN.m
Utalization Of fischer clamp FRSR 99-105 = 0.28 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe
Input Data:
Pipe Size 150 inch
weight of one pipe : 27.90 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 33.48 kg
Factorize load :
Safety Factor: 2
Factorize load: 0.67 kN
Proposed Sections:
Proposed Pipe Clamp: FRSR 99-105
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.67 kN.m
Allowable Force for FRSR 99-105 = 1.20 kN.m
Utalization Of fischer clamp FRSR 99-105 = 0.56 Ok, Safe
Mousa Hamayel
Area Technical Manager
fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
fischer Technical Submittal
Location : DEPOTS
Consultant : RMTC
Contractor : ANM
1. Calculation Note
f. Pipe 2 inch
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual application is with the customer
Calculation Note
Pipe 0.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.04 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.08 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1.25 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.12 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.14 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 2 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.22 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 2.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.34 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 3 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.48 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 4 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.83 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 6 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe
Input Data:
Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 1.67 kN
Following Please find fischer Software Output to design the fixing of the base plate
Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
fischer Technical Submittal
Location : DEPOTS
Consultant : RMTC
Contractor : ANM
1. Calculation Note
Factor of Safety 2
Safety Factofor
Distance Support Weight
Load Total
RESULT
Utilization %
Utilization %
Utilization %
between Span acting on
Pipe distance Weight
Supports (X) each
Size (S) (mm) (kG/m) Type Type Type
(mm) (mm) support
(mm)
(kN)
1 25 3000 125 125 2 0.70 0.02 FUS 21/2 1% FAZ II 10/10 5% RCWR 1" 1% SAFE
2 32 3000 132 132 2 1.15 0.03 FUS 21/2 2% FAZ II 10/10 5% RCWR 1 1/4" 2% SAFE
3 40 3000 140 140 2 1.78 0.05 FUS 21/2 4% FAZ II 10/10 5% RCWR 1 1/2" 3% SAFE
4 50 3000 150 150 2 2.77 0.08 FUS 21/2 6% FAZ II 10/10 5% RCWR 2" 4% SAFE
5 65 3000 165 165 2 4.41 0.13 FUS 21/2 11% FAZ II 10/10 5% RCWR 2 1/2" 5% SAFE
6 75 3000 175 175 2 6.24 0.19 FUS 21/2 16% FAZ II 10/10 5% RCWR 3" 5% SAFE
7 90 3000 190 190 2 8.97 0.27 FUS 21/2 25% FAZ II 10/10 5% RCWR 3" 8% SAFE
8 110 3000 210 210 2 13.40 0.40 FUS 21/2 40% FAZ II 10/10 5% RCWR 4" 8% SAFE
9 125 3000 225 225 2 17.28 0.52 FUS 21/2 55% FAZ II 10/10 5% RCWR 5" 5% SAFE
10 160 3000 260 260 2 28.27 0.85 FUS 41/2 38% FAZ II 10/10 5% RCWR 6" 8% SAFE
11 200 3000 300 300 2 44.20 1.33 FUS 41/2 67% FAZ II 10/10 5% RCWR 8" 8% SAFE
12 250 3000 350 350 2 69.09 2.07 FUS 62/2.5 57% FAZ II 10/10 5% RCWR 10" 20% SAFE
Mousa
fischer FZE
P.O. Box. 261738, Jebel Ali free Zone, Dubai, U.A.E.
Email. Fahmi@fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The
ultimate responsibility for selecting the product for the individual application is with the customer
Page 1 of 25
Pipe 25 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.01 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.02 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 32 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.02 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.03 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 40 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.04 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.05 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 50 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.06 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.08 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 65 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.09 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.13 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 75 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.12 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.19 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 90 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.18 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.27 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 110 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.27 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.40 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 125 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.35 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.52 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 160 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.57 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 0.85 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 200 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 0.88 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 1.33 kN
Following Please find fischer Software Output to design the fixing of the base plate
Pipe 250 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa
Safty Factor: 2
Factorize load: 1.38 kN/m'
Proposed Sections:
Proposed Horizontal Channel : FUS 62/2.5
Sections Check:
Vertical Load on each Cantilever = 2.07 kN
Following Please find fischer Software Output to design the fixing of the base plate
Technical Data for Used
Product
Bolt anchor FAZ II
BUILDING MATERIALS
Balcony railings
Approved for:
▪ Concrete C20/25toC50/60,
cracked and non-cracked
Also suitable for:
ADVANTAGES ▪ Concrete C12/15
▪ Natural stone with dense structure
▪ The optimised expansion clip allows for a high load-bearing capacity. Thus fewer fixing points and
smaller anchor plates are required.
▪ The international approvals guarantee maximum safety and the best performance.
▪ The bolt geometry allows for optimal load distribution and therefore enables use close to edges and
in thin components.
▪ Fewer hammer blows and the minimal torque slip page allow for a noticeably simpler installation.
▪ The drive-in pin protects the thread from damage and ensures a trouble-free dismantling of the fixture.
zinc-plated stainless highly corro- Drill hole Min. drill- Anchor Max. usable Thread Width Sales unit
steel steel sion resistant diameter hole depth length length across nut
Approval
TECHNICAL DATA
zinc-plated stainless highly corro- Drill hole Min. drill- Anchor Max. usable Thread Width Sales unit
steel steel sion resistant diameter hole depth length length across nut
Approval
steel for through hef,stand/
fixings hef,red
do h2 l t fix Ø x length SW
Art.-No. Art.-No. Art.-No. ETA ICC [mm] [mm] [mm] [mm] [mm] [mm] [pcs]
Item gvz A4 C
FAZ II 20/60 046633 1) — — ■ ▲ 20 185 202 60/— M 20 x 84 30 5
FAZ II 20/60 — 503183 1) — ■ ▲ 20 185 202 60/— M 20 x 84 30 4
FAZ II 20/160 503255 1) — — ■ ▲ 20 285 302 160/— M 20 x 100 30 5
FAZ II 24/30 046635 1) — — ■ ▲ 24 185 205 30/— M 24 x 58 36 5
FAZ II 24/30 — 501427 1) — ■ ▲ 24 185 205 30/— M 24 x 58 36 4
FAZ II 24/60 046636 1) — — ■ ▲ 24 215 235 60/— M 24 x 88 36 5
FAZ II 24/60 — 503184 1) — ■ ▲ 24 215 235 60/— M 24 x 88 36 4
TECHNICAL DATA
Bolt anchor FAZ II GS (with large washer) Bolt anchor FAZ II HBS (washer compliant to
wood construction standard DIN 1052)
zinc-plated stainless Drill hole Min. drill- Anchor Max. usable Thread Width Washer (ou- Sales unit
steel steel diameter hole depth length length across nut ter diameter
Approval
Diameter of thread M8 M 10 M 12 M 16 M 20 M 24
Nominal drill hole diameter do [mm] 8 10 12 16 20 24
Drill depth h1 [mm] 55 75 90 110 125 155
Effective anchorage depth hef [mm] 45 60 70 85 100 125
Drill hole depth for through fixing td [mm] td = h1+tfix
Clearance-hole in fixture to be attached df [mm] ≤9 ≤12 ≤14 ≤18 ≤22 ≤26
Wrench size SW [mm] 13 17 19 24 30 36
Required torque Tinst [Nm] 20 45 60 110 200 270
67
Bolt anchor FAZ II
Minimum member thickness and characteristic edge distance and spacing for design
Marking (A) (B) (C) (D) (E) (F) (G) (H) (I) (K) (L) (M) (N) (O) (P) (R) (S) (T) (U) (V) (W) (X) (Y) (Z)
max.tfix
for hef,sta M8 - M24 5 10 15 20 25 30 35 40 45 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400
max.tfix
M10 - M16 25 30 35 40 45 50 55 60 65 70 80 90 100 110 120 140 160 180 200 220 270 320 370 420
for hef,red
ACCESSORIES
TECHNICAL DATA
zinc-plated stainless Nominal Min. drill Anchor Reduced Thread Washer Sales unit
steel steel drill hole hole depth length embedment depth (outer
diameter for push- with respective diameter x
through usable length thickness)
installation
68
Bolt anchor FAZ II
LOADS
Bolt anchor FAZ II
69
Installation systems
Installation systems
Zinc plating Sendzimir zinc plated, approx. 20 µm
Material HDG Steel S235 JR (material no. 1.0045) acc. to EN 10027-2
Zinc plating Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material A2 Stainless steel of the corrosion resistance class II, e.g. A2
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
FUS 21 FUS 41 FUS 62
INSTALLATION
DESCRIPTION
▪ U-profiled channel for horizontal and vertical installation.
▪ Fast and streamlined fastening of pipe tracks and load-bearing constructions.
Advantages / Benefits
▪ High bending and tear-out strength due to optimized profile cross section.
▪ Serration in the rail for secure hold of channel nut FCN and FHS Clix S.
▪ Versatile options for wall, floor and ceiling installation.
▪ Simple cutting to size and installation due to the stamped grid dimension on the rail side.
▪ The fire inspection report in line with MLAR/EN 13501 guarantees independantly tested functional safety
TECHNICAL DATA
Type Art. No. Qty. per box Length Thickness Weight FUS 21 FUS 41
L S 30
pcs. [m] [mm] [kg/m] 30 S
14 50
FUS 21/2.0 – 2 m 40391 1 2 2.0 1.44 14 S 25
50
FUS 21/2.0 – 3 m 97660 1 3 2.0 1.44 L 25 L
FUS 21/2.5 – 2 m 92867 1 2 2.5 1.67 41
21
FUS 21/2.5 – 3 m 77349 1 3 2.5 1.67 22 22
FUS 21/2.5 – 6 m 77541 1 6 2.5 1.67 41 41
FUS 41/2.0 – 2 m 40390 1 2 2.0 2.06
FUS 41/2.0 – 3 m 97658 1 3 2.0 2.06 FUS 62 FUS 21D
FUS 41/2.0 – 6 m 97659 1 6 2.0 2.06
FUS 41/2.5 – 2 m 92295 1 2 2.5 2.45 30
FUS 41/2.5 – 3 m 77347 1 3 2.5 2.45 14 50
FUS 41/2.5 – 6 m 77537 1 6 2.5 2.45 25
FUS 62/2.5 – 6 m 504457 1 6 2.5 3.27 L
2.5
FUS 21D/2.0 – 3 m 504458 1 3 2.0 2.87 42
L 62
FUS 41D/2.5 – 6 m 504459 1 6 2.5 4.89 22
FUS 62D/2.5 – 6 m 504460 1 6 2.5 6.55
22 2 41
FUS 41/2,0 – 3 m hdg. 517426 1 3 2.0 2.05
FUS 62/2,5 – 3 m hdg. 517427 1 3 2.5 41
3.26
FUS 62/2,5 – 6 m hdg. 517428 1 6 2.5 3.26
FUS 21/2.0 A2 – 2m 504466 1 2 2.0 1.44 FUS 41D FUS 62D
FUS 41/2.0 A2 – 2m 504468 1 2 2.0 2.06
FUS 41/2.5 A2 – 2m 504470 1 2 2.5 2.45
FUS 21/2.0 A4 – 2m 504472 1 2 2.0 1.44
FUS 41/2.0 A4 – 2m 504474 1 2 2.2 2.06
FUS 41/2.5 A4 – 2m 504475 1 2 2.5 2.45
82
LOADS L
2.5 124
22
L
41
22
2.5 41
Item Weight Area Moment of Moment of Section Section Max. Recomended static load
inertia inertia modulus modulus Length = .5 M Length = 1 M Length = 1.5 M Length = 2 M Length = 3 M
W A Iy Iz Wy Wz Frec Frec Frec Frec Frec
[kg/m] [mm2] [mm4] [mm4] [mm3] [mm3] KN KN KN KN KN
FUS 21/2.0 1.44 172 9700 46600 890 2270 1.14 0.49 0.22 0.12 0.05
FUS 21/2.5 1.67 199 10300 52800 930 2580 1.19 0.52 0.23 0.13 0.06
FUS 41/2 2.06 252 53300 76900 2580 3750 3.30 1.65 1.10 0.67 0.30
FUS 41/2.5 2.45 300 60000 89900 2850 4380 3.65 1.82 1.22 0.76 0.34
FUS 62/2.5 3.27 405 177000 129000 5620 6290 7.19 3.60 2.40 1.80 0.99
FUS 21D/2 2.87 344 54900 93100 2610 4540 3.34 1.67 1.11 0.69 0.31
FUS 41D/2.5 4.89 600 10300 179000 8760 8780 2.08 0.52 0.23 0.13 0.06
FUS 62D/2.5 6.55 809 1110000 258000 17900 12580 22.91 11.46 7.64 5.73 3.82
* Maximum permissible deflection under load = L/200
149
Installation systems
Saddle flange SF L
OVER VIEW
Installation systems
Properties:
Material Base plate: DC01 (steel 1.0330) acc. DIN EN 10139
SF L41 SF L82 SF L124 Channel: S235JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating Electro zinc plated, min. 8 µm
Material Base plate: Steel DC01 (material no. 1.0330) acc. to DIN EN 10139
U profile: S235 JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating HDG Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
INSTALLATION
DESCRIPTION
▪ Connecting element for producing robust constructions in connection
with the fischer channels.
Advantages / Benefits
▪ Solid connecting element for load-bearing constructions.
▪ Simple installation by inserting the mounting rail in the saddle.
TECHNICAL DATA
SF L41 SF L82 SF L124
DESCRIPTION
FAF 3 FAF 4 ▪ For plane and frame installations with FUS channels.
151
Installation systems
DESCRIPTION
▪ Connecting elements for 3D frame installations with FUS Channels.
Advantages / Benefits
▪ Quick installation by using FCN Clix P.
TECHNICAL DATA
FUF 8T
FFF 4D FFF 3l
FFF 4T
DESCRIPTION
▪ For plane installations with FUS channels.
152
Installation systems
Installation systems
Material 1 Steel S235 JR (material no. 1.0037) acc. DIN EN 10025, plastic nylon PA6
FCN Clix P FCN Clix M Zinc plating Electro zinc plated, min. 5 µm
Material 2 HDG Steel S235 JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material 3 Stainless steel of the corrosion resistance class III, e.g. A4
Plastic Nylon PA 6
Properties:
FCN FCN-L Material ISO 898-1, DIN 975 & 976 (Steel: 4.8 & 8.8)
Finish Electro Galvanized (as per ASTM B633),
FCN-L Hot Dip Galvanized (as per ASTM A153)
Material SS316 DIN EN ISO 3506-1
DESCRIPTION INSTALLATION
▪ Insert in to the channel and rotate 90°.
▪ Fast connecting nut fitting to the FUS channel.
▪ FCN Clix P suitable for connecting channel and fittings.
▪ FCN Clix M suitable for connecting clamps with a threaded rod.
▪ To be used in connection with threaded rod G or GS,
see page 132.
▪ Threaded plate fitting to the FUS channels.
Advantages / Benefits
▪ Easy and precise positioning in the channel.
▪ Serration for secure hold in the FUS channel.
▪ Simple installation.
▪ Retrofitting in rails possible.
TECHNICAL DATA
Type Art. No. Qty. per box Thread Thickness Max.recommended Max.recommended Max.recommended Tightening torque for
tension load for FUS tension load for FUS shesr load screw grade≥ 4.6
2,0mm 2,0mm
S Nrec Nrec Vrec Tinst
pcs. M [mm] [kN] [kN] [kN] [kN]
FCN Clix P 6 504326 100 M6 6 3 3 1 10
FCN Clix P 8 504327 100 M8 6 4 4 2 20
FCN Clix P 10 504329 100 M 10 8 5 8 2.5 40
FCN Clix P 12 504331 100 M 12 9.5 5 8 3 50
FCN Clix M 6 504344 100 M6 6 3 3 1 10
FCN Clix M 8 504345 100 M8 6 4 4 2 20
FCN Clix M 10 504346 100 M 10 8 5 8 2.5 40
FCN Clix M 12 504347 100 M 12 9.5 5 8 2.5 30
FCN Clix P 12 HDG 517420 100 M 12 9.5 5 8 3 50
FCN Clix P 8 A4 504436 100 M8 6 4 4 2 -
FCN Clix P 10 A4 504437 100 M 10 8 5 8 2.5 -
FCN Clix P 12 A4 504439 100 M 12 9.5 5 8 3 -
FCN Clix M 8 A4 504440 100 M8 6 4 4 2 -
FCN Clix M 10 A4 504447 100 M 10 8 5 8 2.5 -
FCN 6 77405 100 M6 6 3 3 1 10
FCN 8 77407 100 M8 6 4 4 2 20
FCN 10 77409 100 M 10 8 5 8 2.5 40
FCN 12 77411 100 M 12 9 5 8 2.5 50
Type Art. No. Art. No. Art. No. Spring Thread Max.recommended Max.recommended Max.recommended Tightening torque for
Length tension load for FUS tension load for FUS shesr load screw grade≥ 4.6
2,0mm 2,5mm
Nrec Nrec Vrec Tinst
GI HDG SS316 mm D [kN] [kN] [kN] [kN]
FCN-L6 516750 516765 516774 6 M6 3 3 1 10
FCN-L8 516751 516766 516775 6 M8 4 4 2 20
FCN-L10 516752 516767 516776 8 M10 5 8 2.5 40
FCN-L12 516753 516768 -- 9 M12 5 8 2.5 50
FCN-L12 -- -- 516777 9.2 M12 5 8 2.5 50
FCN-L12 -- 516769 -- 12 M12 5 8 2.5 50
155
Installation systems
TECHNICAL DATA
Art. No. Qty. per box Length Thread Width across
L D nut
pcs. [mm] SW
TECHNICAL DATA
Art. No. Art. No. Art. No. Length Thread Type Art. No. Art. No. Art. No. Length Thread
L D L D
GI 8.8 HDG 8.8 SS 316 [mm] GI 8.8 HDG 8.8 SS 316 [mm]
164
Installation systems
Hexagonal nut MU
OVER VIEW
Installation systems
Properties:
Material acc. DIN EN 20898-2; min. strength category 04
MU Zinc plating Electro zinc plated, min. 5 µm
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
According: DIN 934
TECHNICAL DATA
Hexagonal nut HN
OVER VIEW
Properties:
Material DIN 934
HN Finish Electro Galvanized (as per ASTM B633),
Hot Dip Galvanized (as per ASTM A153)
TECHNICAL DATA
165
Installation systems
Washer U
OVER VIEW Properties:
Material Steel DD11 (material no.1.0139) acc. to DIN EN 10111
U Zinc plating Electro zinc plated, min. 3 µm
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
TECHNICAL DATA
Art. No. Qty. per box Thickness External Ø Hole Ø
S A
pcs. [mm] [mm] [mm]
Washer MW
OVER VIEW Properties:
Material DIN 125
MW Finish Electro Galvanized (as per ASTM B633),
Hot Dip Galvanized (as per ASTM A153)
TECHNICAL DATA
Art. No. Art. No. Art. No. Thread
D
GI HDG SS316 [mm]
166
Installation systems
APPROVALS
DESCRIPTION
▪ Designed to act as a rigid support for vertical pipes.
▪ Suitable for use with all types of pipes.
TECHNICAL DATA
Type Art. No. Qty. per box Bolt Size Width Bolt Diameter Max. Rec. Load T
A B
[in] pcs. [in] [mm] [in] [mm] [in] [mm] [IBS] [kg] [mm]
RCWR 1/2” 516673 35 3/8 M10 8 1/2 215 1 25 220 100 5
RCWR 3/4” 516674 30 3/8 M10 9 228.5 1 25 220 100 5
RCWR 1” 516675 25 3/8 M10 9 229.5 1 25 220 100 5
RCWR 1-1/4” 516676 25 3/8 M10 9 1/2 240.5 1 25 250 113 5
RCWR 1-1/2” 516677 25 3/8 M10 9 7/8 251 1 25 250 113 3
RCWR 2” 516678 25 3/8 M10 10 2/7 261.6 1 1/6 30 300 136 5
RCWR 2-1/2” 532380 25 3/8 M10 11 281.3 1 1/6 30 400 181 5
RCWR 3” 516679 20 3/8 M10 11 3/4 298.5 1 1/6 30 500 227 5
RCWR 4” 516680 12 1/2 M12 13 328.6 1 1/2 38 750 340 6
RCWR 5” 516681 12 1/2 M12 14 1/4 362 1 1/2 38 1500 680 6
RCWR 6” 516682 8 1/2 M12 15 1/2 393.7 2 50 1600 726 6
RCWR 8” 516683 4 5/8 M16 18 1/4 463.5 2 50 2500 1134 9.5
138