Circulation Pump

Download as pdf or txt
Download as pdf or txt
You are on page 1of 134

RIYADH METRO PROJECT

Package 2

WEST DEPOT – MEP


SEWAGE TREATMENT PLANT
PIPING SUPPORTS CALCULATION

MANUFACTURER : FISCHER
AUTHOR : MURAD ABUBAKER
SUPPLIER : FISCHER

M-ANM-3A1DPW-CMEP-RPT-200047 Rev A
11 JANUARY 2024

Page 1 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

“This Page Left Intentionally Blank”

Page 2 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION
PROJECT TITLE: Riyadh Metro

DOCUMENT TITLE: MEP WATER SUPPLY SYSTEM PIPING SUPPORTS CALCULATION


PUMP STATION & STORAGE TANKS

RIYADH METRO - M-ANM-3A1DPW-CMEP-RPT-200047 REV.A

REV DESCRIPTION ORIG REVIEW APPROVAL DATE ENGINEER DATE


APPROVAL

P1 Issued for Engineer Review 10/01/2024


Murad Tamer G. Matteo A. Name
Abubaker

A Issued for Internal Review 11/01/2024


Samiyudeen Tamer G. Matteo A. Name

A Issued for Engineer Approval


A Hertel Ross Hazelwood P Bganati. Name

Page 3 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

“This Page Left Intentionally Blank”

Page 4 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

CONTENTS

1. Purpose of the document ------------------------------------------------------(07)


2. Location of Work ------------------------------------------------------------------(08)

3. Definitions & Abbreviations-----------------------------------------------------(09)

4. References -------------------------------------------------------------------------(11)

5. Material Specifications-----------------------------------------------------------(12)
6. Drawing Reference--------------------------------------------------------------- (14)

7. Calculations------------------------------------------------------------------------ (17)

8. Technical Data of used products--------------------------------------------- (44)

Page 5 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

“This Page Left Intentionally Blank”

Page 6 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


1 PURPOSE OF THE DOCUMENT

The main purpose of this calculation document is concerned for Supports system
calculation from Fischer for services such as Piping, Ductwork with related drawing
in accordance with standard, project specifications and design requirement.

The Riyadh Metro System comprises varieties of Depots, Underground, Deep


Underground, Elevated Stations and Tunnels along Line 3 package.

The calculation report is including the following sections:

 Reference Drawing

 Calculation Notes

 Product Data Sheet

 Fischer material Approval

Page 7 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


2 LOCATION OF WORK
Calculation in this document will be carried out for the West Depot of the Riyadh Metro Project,
Line 3.

Figure 1 – Location of West Depot Line-3 of Riyadh Metro


Project

Page 8 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

3 DEFINITIONS AND ABBREVIATIONS

ANM : ArRiyadh New Mobility Consortium (CWG / EWG).

ASHRAE : American Society for Heating, Refrigeration and Air Conditioning


Engineer

BS : British Standard

DCP : Design Control Point

HSS : Health and Safety Standard

ITP : Inspection & Test Plan

NCR : Non-Conformity Report

PPE : Personal Protection


Equipment ACY: Air Chiller Yard
SA : Sound Attenuator

NA : Not Applicable

SEM : Structural Requirements for Electrical & Mechanical


services PPE : Personal Protective Equipment
QA : Quality Assurance

QC : Quality Control

FA : Fresh Air

EA : Exhaust Air

DW : Duct Work

GI : Galvanized Iron

SMACNA : Sheet Metal & Air Conditioning Contractor’s National


Association

DW-144 : Specification for Sheet Metal Ductwork

Page 9 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

CWS/R : Cold Water Supply/Return pipe

HWS/R : Hot Water Supply/Return pipe

MFF : Manual Firefighting pipe

BSP : Black Steel Pipe

RMP : Riyadh Metro Project

MOL : Ministry of Labor

CWG : Civil Works Group

EWG : Electromechanical Working Group Joint (ANM)

Page 10 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

4 REFERENCES

4.1 GENERAL REFERENCES

Employer’s Requirements set out – WPS 2.02 –


Civil and Infrastructure Construction Specifications

Employer’s Requirements – WPS 3.02 –


Stations and Buildings Construction Specifications

Project Management Plan M-ANM-300000-GA00-MPL-000001

Site Health & Safety Plan M-ANM-300000-GH00-MPL-000001

Environment Management Plan M-ANM-300000-GV00-MPL-000001

Construction Organization Plan M-ANM-300000-GC00-MPL-000001

Project Schedule Control Plan M-ANM-300000-GB00-MPL-000002

Quality Assurance Plan M-ANM-300000-GQQA-MPL-000001

Quality Control Plan M-ANM-300000-GQQC-MPL-000001

Risk Management Plan M-ANM-300000-GK00-MPL-000001

Testing and Commissioning Organization Plan M-ANM-300000-GSTC-MPL-000001

Page 11 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION
5 MATERIAL / SPECIFICATION

The materials to be used at site shall conform to the requirement of approved material Submittal.

DESCRIPTION OF MATERIALS MSS REFERENCE NUMBER

Fischer Support Systems (Fixation cable


Trays, Mechanical pipe support, HVAC M-ANM-P2-SBM-003731
supports in Stations & Depots)

Page 12 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

“This Page Left Intentionally Blank”

Page 13 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

DRAWING REFERENCE

Page 14 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


METRO PROJECT
N
LINE 6 LINE 2
LINE 4


24
)
KK
AH LINE 2
SIDEWALK LEVEL (MA LINE 6
758.030 LINE 1 EAST DEPOT

LINE 5

LINE 3.
A A

WEST DEPOT
LINE 1

WEST DEPOT KEY PLAN


H)

24
KKA
(MA

GENERAL NOTES
- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED .
753.800 - PLUMBING DRAWINGS SHALL BE READ WITH THE ARCHITECTURAL ,
STRUCTURAL ,ELECTRICAL ,A/C AND OTHER DRAWINGS FOR COORDINATION ,
VERIFICATION OF ADEQUATE SPACES AND EARLY DETERMINATION OF ANY
753.700 A A 753.790 CONTRADICTIONS OR INTERFERENCE PER THE PROVISIONS OF THE
A SPECIFICATION .
A A -THE DRAWINGS ARE ISSUED FOR PLUMBING WORKS ONLY AND SHALL NOT BE
A 753.360 USED FOR ARCHITECTURAL ,STRUCTURAL OR OTHER WORKS .
753.390 -THE ELEVATION ARE MEASURED FROM F.F.L LEVEL OF THE BASED FLOOR .
A A ← ←
-ALL PIPES SHOWN ARE RUNS INSIDE FALSE CEILING LEVEL OR EMBEDDED IN
THE WALLS EXCEPT OTHERWISE NOTED BY THE CONSULTANTS . .
-SIZES OF DRAIN ,VENT AND WATER PIPE CONNECTIONS TO INDIVIDUAL
PLUMBING FIXTURES SHALL BE IN ACCORDANCE WITH THE INDIVIDUAL FIXTURE
PIPE SIZE TABLE EXCEPT IF SHOWN OTHERWISE ON THE DRAWINGS.
-PLUMBING PIPES MATERIALS (SEWAGE ,FLOOR DRAINAGE AND VENT PIPE )ARE
ALL HDPE PIPES .WHICH WAS APPROVED BY THE CONSULTANTS .
-DISTANCE OF HANGER SUPPORT :DN "1=25BELOW 0.9 =M SPAN ;DN "1-1/4 1=32
ABOVE 1.2 =M SPAN SPACING
ROXPLUS 200 SUPPORT REFERENCE ARE FROM SBC -SAUDI BUILDING CODE 701AND HILTI
CALCULATIONS . .
- ALL MATERIALS ARE COMPLYING WITH SPECIFICATION AND APPROVED BY THE
CONSULTANTS .

LEGEND AND SYMBOLS:


F.D. FLOOR DRAIN
751.480 751.520
W.C. WATER CLOSET
751.230
LAV. LAVATORY

750.970 H.D.P.E. HIGH-DENSITY POLYETHYLENE

B.O.P. BOTTOM OF PIPE

F.F.L. FINISH FLOOR LEVEL

SEWAGE (S.W.) - HDPE

SEWAGE UNDERGROUND (S.W.) - HDPE

VENTILATION PIPE (V.P.) - HDPE

FLOOR DRAIN (F.D.)

- ELEVATION
- SCALE 1:100

S-02
-

S-03 S-01 SHOP DRAWING


- -

B 10/01/2024 ISSUED FOR APPROVAL (IFA) M.A.

A 06/10/2022 ISSUED FOR REVIEW (IFR) L.M.

REV. DATE DESCRIPTION APP.

PROJECT

RIYADH METRO PROJECT


PACKAGE 2. LINE 3

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

T.G. M.A.
A.K. S.J.
DATE SCALES ORIGINAL SIZE A1
A1= 1:30
A3= 1:50
S-01 JANUARY 2024
0 2.5m 5m
-

SUBJECT TITLE
S-03
- WEST DEPOT
MEP
SEWAGE WASTE WATER RECYCLING TREATMENT
PLAN
MASTER PLAN S-02
- ANM SHOP DRAWING NUMBER REVISION SHEET
SCALE 1:100 1 of 4
M-ANM-3A1DPW-CUSE-SDR-200318 B

ANM REFERENCE DETAILED DESIGN DRAWING NUMBER REVISION SHEET


See RGR For Design Reference & Details B 1 of 1
METRO PROJECT
N
LINE 6 LINE 2
LINE 4


24
NO DESCRIPTION BRAND SUBMITTAL REFERENCE NO. (MA
KK
AH
)
LINE 2
LINE 6
LINE 1 EAST DEPOT

1 WALL -- - LINE 5

2 U-BOLT FISCHER M-ANM-P2-SBM-003731-A1


3 BLACK STEEL PIPE SCHD. 40 INTER PIPE M-ANM-P2-SBM-004414-C1 LINE 3.

4 WALL BRACKET FISCHER M-ANM-P2-SBM-003731-A1


WEST DEPOT
5 CHANNEL END CAP FISCHER M-ANM-P2-SBM-003731-A1 LINE 1

6 FLUSH ANCHOR FISCHER M-ANM-P2-SBM-003731-A1


7 HEXAGON NUT & WASHER FISCHER M-ANM-P2-SBM-003731-A1 WEST DEPOT KEY PLAN

01 02 N


H)

24
KKA

03 (MA

GENERAL NOTES
- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED .
- PLUMBING DRAWINGS SHALL BE READ WITH THE ARCHITECTURAL ,
STRUCTURAL ,ELECTRICAL ,A/C AND OTHER DRAWINGS FOR COORDINATION ,

05 VERIFICATION OF ADEQUATE SPACES AND EARLY DETERMINATION OF ANY


CONTRADICTIONS OR INTERFERENCE PER THE PROVISIONS OF THE
SPECIFICATION .
-THE DRAWINGS ARE ISSUED FOR PLUMBING WORKS ONLY AND SHALL NOT BE
USED FOR ARCHITECTURAL ,STRUCTURAL OR OTHER WORKS .
-THE ELEVATION ARE MEASURED FROM F.F.L LEVEL OF THE BASED FLOOR .
-ALL PIPES SHOWN ARE RUNS INSIDE FALSE CEILING LEVEL OR EMBEDDED IN
THE WALLS EXCEPT OTHERWISE NOTED BY THE CONSULTANTS . .
-SIZES OF DRAIN ,VENT AND WATER PIPE CONNECTIONS TO INDIVIDUAL
PLUMBING FIXTURES SHALL BE IN ACCORDANCE WITH THE INDIVIDUAL FIXTURE
PIPE SIZE TABLE EXCEPT IF SHOWN OTHERWISE ON THE DRAWINGS.
-PLUMBING PIPES MATERIALS (SEWAGE ,FLOOR DRAINAGE AND VENT PIPE )ARE
ALL HDPE PIPES .WHICH WAS APPROVED BY THE CONSULTANTS .
-DISTANCE OF HANGER SUPPORT :DN "1=25BELOW 0.9 =M SPAN ;DN "1-1/4 1=32

06 07 04
ABOVE 1.2 =M SPAN SPACING
SUPPORT REFERENCE ARE FROM SBC -SAUDI BUILDING CODE 701AND HILTI
CALCULATIONS . .
- ALL MATERIALS ARE COMPLYING WITH SPECIFICATION AND APPROVED BY THE
CONSULTANTS .

LEGEND AND SYMBOLS:


F.D. FLOOR DRAIN

PIPE SUPPORT DETAIL (TYPE - A) W.C.

LAV.
WATER CLOSET

LAVATORY
SCALE : NTS H.D.P.E. HIGH-DENSITY POLYETHYLENE

B.O.P. BOTTOM OF PIPE

F.F.L. FINISH FLOOR LEVEL

SEWAGE (S.W.) - HDPE

SEWAGE UNDERGROUND (S.W.) - HDPE

VENTILATION PIPE (V.P.) - HDPE

MATERIAL SCHEDULE - WASTE WATER TREATMENT PLANT FLOOR DRAIN (F.D.)

NO. SYMBOL BRAND MSS STATUS SUBMITTAL REF. NO.


DESCRIPTION MANUFACTURER

SHOP DRAWING

B 10/01/2024 ISSUED FOR APPROVAL (IFA) M.A.

A 06/10/2022 ISSUED FOR REVIEW (IFR) L.M.

REV. DATE DESCRIPTION APP.

PROJECT

RIYADH METRO PROJECT


PACKAGE 2. LINE 3

ARRIYADH NEW MOBILITY

ORIGINATOR CHECK REVIEW APPROVAL

T.G. M.A.
A.K. S.J.
DATE SCALES ORIGINAL SIZE A1
A1= NTS
A3= NTS
JANUARY 2024
0 2.5m 5m

SUBJECT TITLE
WEST DEPOT
MEP
SEWAGE WASTE WATER RECYCLING TREATMENT
DETAILS SHEET-1

ANM SHOP DRAWING NUMBER REVISION SHEET

M-ANM-3A1DPW-CUSE-SDR-200318 B 3 of 4

ANM REFERENCE DETAILED DESIGN DRAWING NUMBER REVISION SHEET


See RGR For Design Reference & Details B 1 of 1
SEWAGE TREATMENT PLANT PIPING SUPPORTS CALCULATION

CALCULATIONS

Page 15 M-ANM-3A1DPW-CMEP-RPT-200047 Rev A


fischer Technical Submittal

PVC Pipe- Wall Mounted Support

Project : Riyadh Metro Project, Package (2), Line (3)

Location : DEPOTS

Consultant : RMTC

Contractor : ANM

Originator : Mousa Hamayel (Fischer)

Manufacturer : fischerwerke GmbH Co. KG


Supplier : BROOQ ALAMMAN TRAING
Index

1. Calculation Note

a. Design Cases Summary h. Pipe 3 inch

b. Pipe 0.5 inch i. Pipe 4 inch

c. Pipe 1 inch j. Pipe 6 inch

d. Pipe 1.25 inch k. Anchor Calculation

e. Pipe 1.5 inch

f. Pipe 2 inch

g. Pipe 2.5 inch

1. Technical Data for Used Product


fischer Summary Sheet
TITLE CPVC Pipe - Single Pipe - Wall Mounted

CONSULTANT RMTC CONTRACTOR ANM Riyadh DATE 12/3/2017 REV 1

Factor of Safety 2
Grade of Rod 4.8
Consider the own weight: Yes

Pipe Total Weight of Distance Factor Proposed Hanger Drop in Anchor Threaded Rod
Size pipe filled with between of Total Support
Point Load on

RESULT
water Supports Safety Weight Distance from

Utilization %

Utilization %

Utilization %
# hanger support
Wall to Center
(kN) Type Type Type
(KG) of Pipe (S)
(mm) (Kg/m) (mm)
1 15 0.74 900 2 0.007 0.01 150.00 FRSR 15-19 2% EA II M 10 0% TRS 10 1% SAFE
2 25 1.27 900 2 0.011 0.02 150.00 FRSR 26-30 4% EA II M 10 1% TRS 10 1% SAFE
3 32 1.93 1200 2 0.023 0.05 150.00 FRSR 32-36 7% EA II M 10 1% TRS 10 2% SAFE
4 40 2.33 1200 2 0.028 0.06 150.00 FRSR 38-43 9% EA II M 10 1% TRS 10 3% SAFE
5 50 3.66 1200 2 0.044 0.09 150.00 FRSR 53-58 14% EA II M 10 2% TRS 10 5% SAFE
6 65 5.70 1200 2 0.068 0.14 150.00 FRSR 68-72 21% EA II M 10 3% TRS 10 7% SAFE
7 80 8.00 1200 2 0.096 0.19 150.00 FRSR 75-80 30% EA II M 10 5% TRS 10 10% SAFE
8 100 13.85 1200 2 0.166 0.33 150.00 FRSR 99-105 28% EA II M 10 8% TRS 10 18% SAFE
9 150 27.90 1200 2 0.335 0.67 150.00 FRSR 99-105 56% EA II M 10 17% TRS 10 36% SAFE

Page 1 of 19
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 15 inch
weight of one pipe : 0.74 kg/m'
Support Distance: 900 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 0.67 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.01 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 15-19
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.01 kN.m
Allowable Force for FRSR 15-19 = 0.64 kN.m
Utalization Of fischer clamp FRSR 15-19 = 0.02 Ok, Safe

Maximum moment in the threaded rod = 0.00 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.01 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.01 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.00 Ok, Safe

Proof: Total Utalization = 2.09 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 25 inch
weight of one pipe : 1.27 kg/m'
Support Distance: 900 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 1.14 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.02 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 26-30
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.02 kN.m
Allowable Force for FRSR 26-30 = 0.64 kN.m
Utalization Of fischer clamp FRSR 26-30 = 0.04 Ok, Safe

Maximum moment in the threaded rod = 0.00 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.01 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.02 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.01 Ok, Safe

Proof: Total Utalization = 3.59 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 32 inch
weight of one pipe : 1.93 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 2.32 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.05 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 32-36
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.05 kN.m
Allowable Force for FRSR 32-36 = 0.64 kN.m
Utalization Of fischer clamp FRSR 32-36 = 0.07 Ok, Safe

Maximum moment in the threaded rod = 0.01 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.02 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.05 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.01 Ok, Safe

Proof: Total Utalization = 7.27 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 40 inch
weight of one pipe : 2.33 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 2.80 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.06 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 38-43
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.06 kN.m
Allowable Force for FRSR 38-43 = 0.64 kN.m
Utalization Of fischer clamp FRSR 38-43 = 0.09 Ok, Safe

Maximum moment in the threaded rod = 0.01 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.03 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.06 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.01 Ok, Safe

Proof: Total Utalization = 8.77 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 50 inch
weight of one pipe : 3.66 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 4.39 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.09 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 53-58
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.09 kN.m
Allowable Force for FRSR 53-58 = 0.64 kN.m
Utalization Of fischer clamp FRSR 53-58 = 0.14 Ok, Safe

Maximum moment in the threaded rod = 0.01 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.05 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.09 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.02 Ok, Safe

Proof: Total Utalization = 13.78 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 65 inch
weight of one pipe : 5.70 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 6.84 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.14 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 68-72
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.14 kN.m
Allowable Force for FRSR 68-72 = 0.64 kN.m
Utalization Of fischer clamp FRSR 68-72 = 0.21 Ok, Safe

Maximum moment in the threaded rod = 0.02 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.07 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.14 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.03 Ok, Safe

Proof: Total Utalization = 21.46 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 80 inch
weight of one pipe : 8.00 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 9.60 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.19 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 75-80
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.19 kN.m
Allowable Force for FRSR 75-80 = 0.64 kN.m
Utalization Of fischer clamp FRSR 75-80 = 0.30 Ok, Safe

Maximum moment in the threaded rod = 0.03 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.10 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.19 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.05 Ok, Safe

Proof: Total Utalization = 30.12 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 100 inch
weight of one pipe : 13.85 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 16.62 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.33 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 99-105
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.33 kN.m
Allowable Force for FRSR 99-105 = 1.20 kN.m
Utalization Of fischer clamp FRSR 99-105 = 0.28 Ok, Safe

Maximum moment in the threaded rod = 0.05 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.18 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.33 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.08 Ok, Safe

Proof: Total Utalization = 27.70 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
Project : Riyadh Metro
Customer : ANM
Application : CPVC Pipe

Input Data:
Pipe Size 150 inch
weight of one pipe : 27.90 kg/m'
Support Distance: 1200 mm
Distance From Wall to Center of Pipe (S): 150 mm
Total weight of each support: 33.48 kg

Factorize load :

Safety Factor: 2
Factorize load: 0.67 kN

Proposed Sections:
Proposed Pipe Clamp: FRSR 99-105
Proposed Threaded rod: TRS 10
Proposed Anchor bolt: EA II M 10
Sections Check:
Maximum Load on a support = 0.67 kN.m
Allowable Force for FRSR 99-105 = 1.20 kN.m
Utalization Of fischer clamp FRSR 99-105 = 0.56 Ok, Safe

Maximum moment in the threaded rod = 0.10 kN


Allowable Tension Force For TRS 10 = 0.28 kN
Utalization Of fischer Threaded rod TRS 10 = 0.36 Ok, Safe

Maximum Tension force in the Anchor bolt = 0.67 kN


Concrete strength factor "fb,N" 1.00
Allowable Tension Force For EA II M 10 = 4.00 kN
Utalization Of fischer Anchor EA II M 10 = 0.17 Ok, Safe

Proof: Total Utalization = 55.80 %


Ok, The Support is Safe

Mousa Hamayel
Area Technical Manager

fischer FZE
Mobile : +966 544 510 338
Email : mousa.hamayel@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product
for the individual application is with the customer
fischer Technical Submittal

PVC Pipe Hanger & Support System- Wall Mounted

Project : Riyadh Metro Project, Package (2), Line (3)

Location : DEPOTS

Consultant : RMTC

Contractor : ANM

Originator : Mousa Hamayel (Fischer)

Manufacturer : fischerwerke GmbH Co. KG


Supplier : BROOQ ALAMMAN TRAING
Index

1. Calculation Note

a. Design Cases Summary h. Pipe 3 inch

b. Pipe 0.5 inch i. Pipe 4 inch

c. Pipe 1 inch j. Pipe 6 inch

d. Pipe 1.25 inch k. Anchor Calculation

e. Pipe 1.5 inch

f. Pipe 2 inch

g. Pipe 2.5 inch

1. Technical Data for Used Product


Design Cases Summary
PVC Pipe
No. Pipe Size in inch Pipe Weight (Kg/m) support distance mm Proposed C- Channel Proposed Anchor Bolt
1 0.5 0.74 1500 FUS 21/2 FAZ II M 10/10
2 1 1.27 1500 FUS 21/2 FAZ II M 10/10
3 1.25 1.93 1500 FUS 21/2 FAZ II M 10/10
4 1.5 2.33 1500 FUS 21/2 FAZ II M 10/10
5 2 3.66 1500 FUS 21/2 FAZ II M 10/10
6 2.5 5.7 1500 FUS 21/2 FAZ II M 10/10
7 3 8 1500 FUS 21/2 FAZ II M 10/10
8 4 13.85 1500 FUS 21/2 FAZ II M 10/10
9 6 27.9 1500 FUS 41/2 FAZ II M 10/10

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual application is with the customer
Calculation Note
Pipe 0.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 0.5 inch

Pipe Weight 0.74 kg/m'


Safety Factor 4

Factorize load: 0.03 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 212.5 mm
Load Distance (S): 106.25 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.04 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.00 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.04 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.00 mm


Allowable Defliction on Channel (L/200) = 0.53 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Proof: Total Utalization = 2.12 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.00 kN.m


Maximum Shear Force in "Z" Direction 0.04 kN

Maximum Tension Forces in one bolt: 0.12 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 0.25 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.00 kN.m


Maximum Shear Force in "Z" Direction 0.04 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 1 inch

Pipe Weight 1.27 kg/m'


Safety Factor 4

Factorize load: 0.05 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 225 mm
Load Distance (S): 112.5 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.08 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.01 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.04 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.08 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.00 mm


Allowable Defliction on Channel (L/200) = 0.56 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Proof: Total Utalization = 3.85 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.01 kN.m


Maximum Shear Force in "Z" Direction 0.08 kN

Maximum Tension Forces in one bolt: 0.21 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 0.45 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.01 kN.m


Maximum Shear Force in "Z" Direction 0.08 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1.25 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 1.25 inch

Pipe Weight 1.93 kg/m'


Safety Factor 4

Factorize load: 0.08 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 231.25 mm
Load Distance (S): 115.625 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.12 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.01 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.06 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.12 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.01 mm


Allowable Defliction on Channel (L/200) = 0.58 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Proof: Total Utalization = 6.02 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.01 kN.m


Maximum Shear Force in "Z" Direction 0.12 kN

Maximum Tension Forces in one bolt: 0.33 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 0.69 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.01 kN.m


Maximum Shear Force in "Z" Direction 0.12 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 1.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 1.5 inch

Pipe Weight 2.33 kg/m'


Safety Factor 4

Factorize load: 0.09 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 237.5 mm
Load Distance (S): 118.75 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.14 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.02 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.07 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.14 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.01 mm


Allowable Defliction on Channel (L/200) = 0.59 kN
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Proof: Total Utalization = 7.46 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.02 kN.m


Maximum Shear Force in "Z" Direction 0.14 kN

Maximum Tension Forces in one bolt: 0.40 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 0.86 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.02 kN.m


Maximum Shear Force in "Z" Direction 0.14 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 2 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 2 inch

Pipe Weight 3.66 kg/m'


Safety Factor 4

Factorize load: 0.15 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 250 mm
Load Distance (S): 125 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.22 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.03 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.12 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.22 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.02 mm


Allowable Defliction on Channel (L/200) = 0.63 kN
Utalization Of fischer C Channel FUS 21/2 = 0.03 Ok, Safe

Proof: Total Utalization = 12.34 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.03 kN.m


Maximum Shear Force in "Z" Direction 0.22 kN

Maximum Tension Forces in one bolt: 0.66 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 1.40 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.03 kN.m


Maximum Shear Force in "Z" Direction 0.22 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 2.5 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 2.5 inch

Pipe Weight 5.7 kg/m'


Safety Factor 4

Factorize load: 0.23 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 262.5 mm
Load Distance (S): 131.25 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.34 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.04 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.20 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.34 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.03 mm


Allowable Defliction on Channel (L/200) = 0.66 kN
Utalization Of fischer C Channel FUS 21/2 = 0.05 Ok, Safe

Proof: Total Utalization = 20.17 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.04 kN.m


Maximum Shear Force in "Z" Direction 0.34 kN

Maximum Tension Forces in one bolt: 1.07 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 2.28 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.04 kN.m


Maximum Shear Force in "Z" Direction 0.34 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 3 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 3 inch

Pipe Weight 8 kg/m'


Safety Factor 4

Factorize load: 0.32 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 275 mm
Load Distance (S): 137.5 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.48 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.07 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.30 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.48 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.03 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.05 mm


Allowable Defliction on Channel (L/200) = 0.69 kN
Utalization Of fischer C Channel FUS 21/2 = 0.08 Ok, Safe

Proof: Total Utalization = 29.66 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.07 kN.m


Maximum Shear Force in "Z" Direction 0.48 kN

Maximum Tension Forces in one bolt: 1.56 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 3.32 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.07 kN.m


Maximum Shear Force in "Z" Direction 0.48 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 4 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 4 inch

Pipe Weight 13.85 kg/m'


Safety Factor 4

Factorize load: 0.55 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 300 mm
Load Distance (S): 150 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.83 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.12 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.56 Ok, Safe

Maximum Shear Force in "Z" Direction = 0.83 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.05 Ok, Safe

Maximum Deflection in "Z" Direction FUS 21/2 = 0.12 mm


Allowable Defliction on Channel (L/200) = 0.75 kN
Utalization Of fischer C Channel FUS 21/2 = 0.16 Ok, Safe

Proof: Total Utalization = 56.02 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.12 kN.m


Maximum Shear Force in "Z" Direction 0.83 kN

Maximum Tension Forces in one bolt: 2.91 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 6.19 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.12 kN.m


Maximum Shear Force in "Z" Direction 0.83 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
Pipe 6 inch
Project : Riyadh Metro Project
Customer : ANM
Application : PVC Pipe

Input Data:

Service Type: Pipe

Pipe Size: 6 inch

Pipe Weight 27.9 kg/m'


Safety Factor 4

Factorize load: 1.12 kN/m'

Supports Distance: 1500 mm


Cantilever length (X): 350 mm
Load Distance (S): 175 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 1.67 kN

Check Of Horizontal Channel:

Maximum Bending Moment around "Y" Axis = 0.29 kN.m


Allowable bending moment for FUS 41/2 = 0.65 kN.m
Utalization Of fischer C Channel FUS 41/2 = 0.45 Ok, Safe

Maximum Shear Force in "Z" Direction = 1.67 kN


Allowable Shear Force for Channel FUS 41/2 = 25.20 kN
Utalization Of fischer C Channel FUS 41/2 = 0.07 Ok, Safe

Maximum Deflection in "Z" Direction FUS 41/2 = 0.07 mm


Allowable Defliction on Channel (L/200) = 0.88 kN
Utalization Of fischer C Channel FUS 41/2 = 0.08 Ok, Safe

Proof: Total Utalization = 45.42 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: SKS 10 x 30

Maximum Bending Moment around "Y" Axis 0.29 kN.m


Maximum Shear Force in "Z" Direction 1.67 kN

Maximum Tension Forces in one bolt: 6.70 kN


Maximum Shear Forces in one bolt: 0.00 kN

Allowable tension force for SKS 10 x 30 = 46.95 kN


Allowable Shear force for SKS 10 x 30 = 27.6 kN

Proof: Total Utalization = 14.26 %


Ok, The Vertical beam is Safe

Saddle Flange to wall connection:

Maximum Bending Moment around "Y" Axis 0.29 kN.m


Maximum Shear Force in "Z" Direction 1.67 kN

Following Please find fischer Software Output to design the fixing of the base plate

Mousa Hamayel
Technical Team Leader – Saudi Arabia
fischer FZE
Mobile : +966 544 510 338
Email : mousa@fischer.ae
Website: www.fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The ultimate responsibility for selecting the product for the individual
application is with the customer
fischer Technical Submittal

PVC Pipe Riser Support

Project : Riyadh Metro Project, Package (2), Line (3)

Location : DEPOTS

Consultant : RMTC

Contractor : ANM

Originator : Mousa Hamayel (Fischer)

Manufacturer : fischerwerke GmbH Co. KG


Supplier : BROOQ ALAMMAN TRAING
Index

1. Calculation Note

Riser Support System

a. Design Cases Summary h. Pipe 90 mm

b. Pipe 25 mm i. Pipe 110 mm

c. Pipe 32 mm j. Pipe 125 mm

d. Pipe 40 mm k. Pipe 160 mm

e. Pipe 50 mm l. Pipe 200 mm

f. Pipe 65 mm m.Pipe 250 mm

g. Pipe 75 mm n. Pipe 300 mm

1. Technical Data for Used Product


Calculation Note
Riser Support System
Design Cases Summary
Summary Sheet - Pipes
TITLE Riser Support - PVC Pipe

CONSULTANT RMTC CONTRACTOR ANM Riyadh REV 0

Factor of Safety 2

Total Horizontal Channel Anchor Riser Clamp

Safety Factofor
Distance Support Weight
Load Total

RESULT
Utilization %

Utilization %

Utilization %
between Span acting on
Pipe distance Weight
Supports (X) each
Size (S) (mm) (kG/m) Type Type Type
(mm) (mm) support
(mm)
(kN)
1 25 3000 125 125 2 0.70 0.02 FUS 21/2 1% FAZ II 10/10 5% RCWR 1" 1% SAFE
2 32 3000 132 132 2 1.15 0.03 FUS 21/2 2% FAZ II 10/10 5% RCWR 1 1/4" 2% SAFE
3 40 3000 140 140 2 1.78 0.05 FUS 21/2 4% FAZ II 10/10 5% RCWR 1 1/2" 3% SAFE
4 50 3000 150 150 2 2.77 0.08 FUS 21/2 6% FAZ II 10/10 5% RCWR 2" 4% SAFE
5 65 3000 165 165 2 4.41 0.13 FUS 21/2 11% FAZ II 10/10 5% RCWR 2 1/2" 5% SAFE
6 75 3000 175 175 2 6.24 0.19 FUS 21/2 16% FAZ II 10/10 5% RCWR 3" 5% SAFE
7 90 3000 190 190 2 8.97 0.27 FUS 21/2 25% FAZ II 10/10 5% RCWR 3" 8% SAFE
8 110 3000 210 210 2 13.40 0.40 FUS 21/2 40% FAZ II 10/10 5% RCWR 4" 8% SAFE
9 125 3000 225 225 2 17.28 0.52 FUS 21/2 55% FAZ II 10/10 5% RCWR 5" 5% SAFE
10 160 3000 260 260 2 28.27 0.85 FUS 41/2 38% FAZ II 10/10 5% RCWR 6" 8% SAFE
11 200 3000 300 300 2 44.20 1.33 FUS 41/2 67% FAZ II 10/10 5% RCWR 8" 8% SAFE
12 250 3000 350 350 2 69.09 2.07 FUS 62/2.5 57% FAZ II 10/10 5% RCWR 10" 20% SAFE

Mousa
fischer FZE
P.O. Box. 261738, Jebel Ali free Zone, Dubai, U.A.E.
Email. Fahmi@fischer.ae
The user has the responsibility to check whether the present conditions on site and the anchors, setting tools etc. intended to use comply with the conditions given. The
ultimate responsibility for selecting the product for the individual application is with the customer

Page 1 of 25
Pipe 25 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 25 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 0.70 kg/m'

Safty Factor: 2
Factorize load: 0.01 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 125 mm
Load distance (S): 125 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.02 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.00 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Shear Force = 0.02 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection FUS 21/2 = 0.00 mm


Allowable Defliction on Channel (L/200) = 0.63 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Proof: Total Utalization = 1.30 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.02 kN


Maximum Moment on the horizontal beam: 0.00 kN

Maximum Tension Forces in one bolt: 0.06 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 0.84 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.00 kN
Maximum Shear Forces : 0.02 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 32 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 32 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 1.15 kg/m'

Safty Factor: 2
Factorize load: 0.02 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 132 mm
Load distance (S): 132 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.03 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.00 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Maximum Shear Force = 0.03 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection FUS 21/2 = 0.01 mm


Allowable Defliction on Channel (L/200) = 0.66 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Proof: Total Utalization = 2.25 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.03 kN


Maximum Moment on the horizontal beam: 0.00 kN

Maximum Tension Forces in one bolt: 0.11 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 1.44 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.00 kN
Maximum Shear Forces : 0.03 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 40 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 40 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 1.78 kg/m'

Safty Factor: 2
Factorize load: 0.04 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 140 mm
Load distance (S): 140 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.05 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.01 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.03 Ok, Safe

Maximum Shear Force = 0.05 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection FUS 21/2 = 0.01 mm


Allowable Defliction on Channel (L/200) = 0.70 kN
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Proof: Total Utalization = 3.67 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.05 kN


Maximum Moment on the horizontal beam: 0.01 kN

Maximum Tension Forces in one bolt: 0.18 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 2.35 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.01 kN
Maximum Shear Forces : 0.05 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 50 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 50 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 2.77 kg/m'

Safty Factor: 2
Factorize load: 0.06 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 150 mm
Load distance (S): 150 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.08 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.01 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.06 Ok, Safe

Maximum Shear Force = 0.08 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.00 Ok, Safe

Maximum Deflection FUS 21/2 = 0.02 mm


Allowable Defliction on Channel (L/200) = 0.75 kN
Utalization Of fischer C Channel FUS 21/2 = 0.03 Ok, Safe

Proof: Total Utalization = 6.09 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.08 kN


Maximum Moment on the horizontal beam: 0.01 kN

Maximum Tension Forces in one bolt: 0.29 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 3.88 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.01 kN
Maximum Shear Forces : 0.08 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 65 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 65 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 4.41 kg/m'

Safty Factor: 2
Factorize load: 0.09 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 165 mm
Load distance (S): 165 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.13 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.02 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.10 Ok, Safe

Maximum Shear Force = 0.13 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Deflection FUS 21/2 = 0.05 mm


Allowable Defliction on Channel (L/200) = 0.83 kN
Utalization Of fischer C Channel FUS 21/2 = 0.06 Ok, Safe

Proof: Total Utalization = 10.58 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.13 kN


Maximum Moment on the horizontal beam: 0.02 kN

Maximum Tension Forces in one bolt: 0.50 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 6.70 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.02 kN
Maximum Shear Forces : 0.13 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 75 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 75 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 6.24 kg/m'

Safty Factor: 2
Factorize load: 0.12 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 175 mm
Load distance (S): 175 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.19 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.03 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.15 Ok, Safe

Maximum Shear Force = 0.19 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.01 Ok, Safe

Maximum Deflection FUS 21/2 = 0.09 mm


Allowable Defliction on Channel (L/200) = 0.88 kN
Utalization Of fischer C Channel FUS 21/2 = 0.10 Ok, Safe

Proof: Total Utalization = 15.81 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.19 kN


Maximum Moment on the horizontal beam: 0.03 kN

Maximum Tension Forces in one bolt: 0.75 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 9.98 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.03 kN
Maximum Shear Forces : 0.19 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 90 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 90 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 8.97 kg/m'

Safty Factor: 2
Factorize load: 0.18 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 190 mm
Load distance (S): 190 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.27 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.05 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.23 Ok, Safe

Maximum Shear Force = 0.27 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Maximum Deflection FUS 21/2 = 0.16 mm


Allowable Defliction on Channel (L/200) = 0.95 kN
Utalization Of fischer C Channel FUS 21/2 = 0.17 Ok, Safe

Proof: Total Utalization = 24.54 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.27 kN


Maximum Moment on the horizontal beam: 0.05 kN

Maximum Tension Forces in one bolt: 1.16 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 15.43 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.05 kN
Maximum Shear Forces : 0.27 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 110 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 110 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 13.40 kg/m'

Safty Factor: 2
Factorize load: 0.27 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 210 mm
Load distance (S): 210 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.40 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.08 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.38 Ok, Safe

Maximum Shear Force = 0.40 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.02 Ok, Safe

Maximum Deflection FUS 21/2 = 0.32 mm


Allowable Defliction on Channel (L/200) = 1.05 kN
Utalization Of fischer C Channel FUS 21/2 = 0.30 Ok, Safe

Proof: Total Utalization = 40.28 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.40 kN


Maximum Moment on the horizontal beam: 0.08 kN

Maximum Tension Forces in one bolt: 1.89 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 25.19 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.08 kN
Maximum Shear Forces : 0.40 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 125 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 125 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 17.28 kg/m'

Safty Factor: 2
Factorize load: 0.35 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 225 mm
Load distance (S): 225 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 21/2
Sections Check:
Vertical Load on each Cantilever = 0.52 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.12 kN.m


Allowable bending moment for FUS 21/2 = 0.22 kN.m
Utalization Of fischer C Channel FUS 21/2 = 0.52 Ok, Safe

Maximum Shear Force = 0.52 kN


Allowable Shear Force for Channel FUS 21/2 = 17.20 kN
Utalization Of fischer C Channel FUS 21/2 = 0.03 Ok, Safe

Maximum Deflection FUS 21/2 = 0.51 mm


Allowable Defliction on Channel (L/200) = 1.13 kN
Utalization Of fischer C Channel FUS 21/2 = 0.45 Ok, Safe

Proof: Total Utalization = 55.44 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.52 kN


Maximum Moment on the horizontal beam: 0.12 kN

Maximum Tension Forces in one bolt: 2.59 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 34.56 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.12 kN
Maximum Shear Forces : 0.52 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 160 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 160 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 28.27 kg/m'

Safty Factor: 2
Factorize load: 0.57 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 260 mm
Load distance (S): 260 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 0.85 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.22 kN.m


Allowable bending moment for FUS 41/2 = 0.65 kN.m
Utalization Of fischer C Channel FUS 41/2 = 0.34 Ok, Safe

Maximum Shear Force = 0.85 kN


Allowable Shear Force for Channel FUS 41/2 = 25.20 kN
Utalization Of fischer C Channel FUS 41/2 = 0.03 Ok, Safe

Maximum Deflection FUS 41/2 = 0.23 mm


Allowable Defliction on Channel (L/200) = 1.30 kN
Utalization Of fischer C Channel FUS 41/2 = 0.18 Ok, Safe

Proof: Total Utalization = 37.55 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 0.85 kN


Maximum Moment on the horizontal beam: 0.22 kN

Maximum Tension Forces in one bolt: 4.83 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 64.46 %


Ok, The Vertical beam is Safe
Saddle Flange to wall connection:
Maximum Moment : 0.22 kN
Maximum Shear Forces : 0.85 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 200 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 200 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 44.20 kg/m'

Safty Factor: 2
Factorize load: 0.88 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 300 mm
Load distance (S): 300 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 41/2
Sections Check:
Vertical Load on each Cantilever = 1.33 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.40 kN.m


Allowable bending moment for FUS 41/2 = 0.65 kN.m
Utalization Of fischer C Channel FUS 41/2 = 0.62 Ok, Safe

Maximum Shear Force = 1.33 kN


Allowable Shear Force for Channel FUS 41/2 = 25.20 kN
Utalization Of fischer C Channel FUS 41/2 = 0.05 Ok, Safe

Maximum Deflection FUS 41/2 = 0.56 mm


Allowable Defliction on Channel (L/200) = 1.50 kN
Utalization Of fischer C Channel FUS 41/2 = 0.37 Ok, Safe

Proof: Total Utalization = 66.94 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 1.33 kN


Maximum Moment on the horizontal beam: 0.40 kN

Maximum Tension Forces in one bolt: 8.62 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 114.92 %


The Vertical beam is Un Safe
Saddle Flange to wall connection:
Maximum Moment : 0.40 kN
Maximum Shear Forces : 1.33 kN

Following Please find fischer Software Output to design the fixing of the base plate
Pipe 250 mm
Riser Support - PVC Pipe
PROJECT Riyadh Metro Project
CONS RMTC DATE 4/19/2017
CONT ANM REV 0
BY Mousa

Service Type: Pipe

Pipe Size: 250 mm Each Pipe Support contains two cantilevers

Total weight of Pipe : 69.09 kg/m'

Safty Factor: 2
Factorize load: 1.38 kN/m'

Distance between Supports: 3000 mm


Cantilever length (X): 350 mm
Load distance (S): 350 mm

Proposed Sections:
Proposed Horizontal Channel : FUS 62/2.5
Sections Check:
Vertical Load on each Cantilever = 2.07 kN

Check Of Horizontal Channel:

Maximum Bending Moment = 0.73 kN.m


Allowable bending moment for FUS 62/2.5 = 1.41 kN.m
Utalization Of fischer C Channel FUS 62/2.5 = 0.52 Ok, Safe

Maximum Shear Force = 2.07 kN


Allowable Shear Force for Channel FUS 62/2.5 = 40.50 kN
Utalization Of fischer C Channel FUS 62/2.5 = 0.05 Ok, Safe

Maximum Deflection FUS 62/2.5 = 0.42 mm


Allowable Defliction on Channel (L/200) = 1.75 kN
Utalization Of fischer C Channel FUS 62/2.5 = 0.24 Ok, Safe

Proof: Total Utalization = 56.75 %


Ok, The Horizontal beam is Safe
Check Of Horizontal Channel to Saddle Flange Connections:
Proposed Suddle Flange: SF L 41
Proposed Hexagonal Bolt: FCN 12

Maximum Shear Forces on the horizontal beam: 2.07 kN


Maximum Moment on the horizontal beam: 0.73 kN

Maximum Tension Forces in one bolt: 15.55 kN

Allowable Shear force for FCN 12 = 4.5 kN


Allowable tension force for FCN 12 = 7.5 kN

Proof: Total Utalization = 207.27 %


The Vertical beam is Un Safe
Saddle Flange to wall connection:
Maximum Moment : 0.73 kN
Maximum Shear Forces : 2.07 kN

Following Please find fischer Software Output to design the fixing of the base plate
Technical Data for Used
Product
Bolt anchor FAZ II

Efficient fixing for cracked concrete


VERSIONS APPROVALS
▪ zinc-plated steel
▪ stainless steel
▪ highly corrosion-resistant steel

BUILDING MATERIALS
Balcony railings
Approved for:
▪ Concrete C20/25toC50/60,
cracked and non-cracked
Also suitable for:
ADVANTAGES ▪ Concrete C12/15
▪ Natural stone with dense structure
▪ The optimised expansion clip allows for a high load-bearing capacity. Thus fewer fixing points and
smaller anchor plates are required.
▪ The international approvals guarantee maximum safety and the best performance.
▪ The bolt geometry allows for optimal load distribution and therefore enables use close to edges and
in thin components.
▪ Fewer hammer blows and the minimal torque slip page allow for a noticeably simpler installation.
▪ The drive-in pin protects the thread from damage and ensures a trouble-free dismantling of the fixture.

INSTALLATION TECHNICAL DATA

Bolt anchor FAZ II

zinc-plated stainless highly corro- Drill hole Min. drill- Anchor Max. usable Thread Width Sales unit
steel steel sion resistant diameter hole depth length length across nut
Approval

steel for through hef,stand/


fixings hef,red
do h2 l t fix Ø x length  SW
Art.-No. Art.-No. Art.-No. ETA ICC [mm] [mm] [mm] [mm] [mm] [mm] [pcs]
Item gvz A4 C
FAZ II 8/10 094871 1) 501396 1) — ■ ▲ 8 65 75 10/- M 8 x 38 13 50
FAZ II 8/10 — — 501428 1) ■ ▲ 8 65 75 10/- M 8 x 38 13 10
FAZ II 8/30 094877 1) 501399 1) — ■ ▲ 8 85 95 30/- M 8 x 58 13 50
FAZ II 8/30 — — 501429 1) ■ ▲ 8 85 95 30/- M 8 x 58 13 10
FAZ II 8/50 094878 1) 501401 1) — ■ ▲ 8 105 115 50/- M 8 x 78 13 50
FAZ II 8/100 094879 1) — — ■ ▲ 8 155 165 100/- M 8 x 128 13 25
FAZ II 8/160 503251 — — ■ ▲ 8 215 225 160/- M 8 x 100 13 20
FAZ II 10/10 094981 1) 501403 1) — ■ ▲ 10 85 95 10/30 M 10 x 53 17 50
FAZ II 10/10 — — 501430 1) ■ ▲ 10 85 95 10/30 M 10 x 53 17 10
FAZ II 10/20 094982 1) — — ■ ▲ 10 95 105 20/40 M 10 x 63 17 25
FAZ II 10/20 — 501406 1) — ■ ▲ 10 95 105 20/40 M 10 x 63 17 50
FAZ II 10/30 094983 1) — — ■ ▲ 10 105 115 30/50 M 10 x 73 17 25
FAZ II 10/30 — 501407 1) — ■ ▲ 10 105 115 30/50 M 10 x 73 17 50
FAZ II 10/30 — — 503185 1) ■ ▲ 10 105 115 30/50 M 10 x 73 17 10
FAZ II 10/50 094984 1) 501409 1) — ■ ▲ 10 125 135 50/70 M 10 x 93 17 20
FAZ II 10/70 — 501410 1) — ■ ▲ 10 145 155 70/90 M 10 x 113 17 20
FAZ II 10/80 094985 1) — — ■ ▲ 10 155 165 80/100 M 10 x 123 17 20
FAZ II 10/100 094986 1) — — ■ ▲ 10 175 185 100/120 M 10 x 143 17 20
FAZ II 10/160 503252 501412 — ■ ▲ 10 235 245 160/180 M 10 x 193 17 20
FAZ II 12/10 095419 1) 501413 1) — ■ ▲ 12 100 110 10/30 M 12 x 61 19 20
FAZ II 12/10 — — 503186 1) ■ ▲ 12 100 110 10/30 M 12 x 61 19 10
FAZ II 12/20 095420 1) 501415 1) — ■ ▲ 12 110 120 20/40 M 12 x 71 19 20
FAZ II 12/30 095421 1) 501416 1) — ■ ▲ 12 120 130 30/50 M 12 x 81 19 20
FAZ II 12/30 — — 501431 1) ■ ▲ 12 120 130 30/50 M 12 x 81 19 10
FAZ II 12/50 095446 1) 501419 1) — ■ ▲ 12 140 150 50/70 M 12 x 101 19 20
FAZ II 12/60 — 501420 1) — ■ ▲ 12 150 160 60/80 M 12 x 111 19 20
FAZ II 12/80 095454 1) — — ■ ▲ 12 170 180 80/100 M 12 x 131 19 20
FAZ II 12/100 095470 1) 501421 1) — ■ ▲ 12 190 200 100/120 M 12 x 151 19 20
FAZ II 12/160 503253 — — ■ ▲ 12 250 260 160/180 M 12 x 186 19 10
FAZ II 12/160 — 503180 — ■ ▲ 12 250 260 160/180 M 12 x 186 19 20
FAZ II 12/200 095605 — — ■ ▲ 12 290 300 200/220 M 12 x 186 19 10
FAZ II 16/5 522125 — ■ ▲ 16 115 128 5/25 M 16 x 64 — 10
FAZ II 16/5 522124 1) — — ■ ▲ 16 115 128 5/25 M 16 x 64 — 20
FAZ II 16/25 095836 1) — 501432 1) ■ ▲ 16 135 148 25/45 M 16 x 84 24 10
FAZ II 16/25 — 501423 1) — ■ ▲ 16 135 148 25/45 M 16 x 84 24 20
FAZ II 16/50 095864 1) — 503187 1) ■ ▲ 16 160 173 50/70 M 16 x 109 24 10
FAZ II 16/50 — 501424 1) — ■ ▲ 16 160 173 50/70 M 16 x 109 24 20
FAZ II 16/100 095865 1) 501425 1) — ■ ▲ 16 210 223 100/120 M 16 x 159 24 10
FAZ II 16/160 503254 — — ■ ▲ 16 270 283 160/180 M 16 x 189 24 10
FAZ II 16/200 095967 — — ■ ▲ 16 310 323 200/220 M 16 x 189 24 10
FAZ II 16/250 095968 — — ■ ▲ 16 360 373 250/270 M 16 x 100 24 10
FAZ II 16/300 096188 — — ■ ▲ 16 410 423 300/320 M 16 x 100 24 10
FAZ II 20/30 046632 1) — — ■ ▲ 20 155 172 30/- M 20 x 54 30 5
FAZ II 20/30 — 501426 1) — ■ ▲ 20 155 172 30/- M 20 x 54 30 4
1)
Only one of both requirements has to be fullfilled.
2)
Intermediate values by linear interpolation.
66
Bolt anchor FAZ II

TECHNICAL DATA

High performance steel anchors


Bolt anchor FAZ II

zinc-plated stainless highly corro- Drill hole Min. drill- Anchor Max. usable Thread Width Sales unit
steel steel sion resistant diameter hole depth length length across nut

Approval
steel for through hef,stand/
fixings hef,red
do h2 l t fix Ø x length  SW
Art.-No. Art.-No. Art.-No. ETA ICC [mm] [mm] [mm] [mm] [mm] [mm] [pcs]
Item gvz A4 C
FAZ II 20/60 046633 1) — — ■ ▲ 20 185 202 60/— M 20 x 84 30 5
FAZ II 20/60 — 503183 1) — ■ ▲ 20 185 202 60/— M 20 x 84 30 4
FAZ II 20/160 503255 1) — — ■ ▲ 20 285 302 160/— M 20 x 100 30 5
FAZ II 24/30 046635 1) — — ■ ▲ 24 185 205 30/— M 24 x 58 36 5
FAZ II 24/30 — 501427 1) — ■ ▲ 24 185 205 30/— M 24 x 58 36 4
FAZ II 24/60 046636 1) — — ■ ▲ 24 215 235 60/— M 24 x 88 36 5
FAZ II 24/60 — 503184 1) — ■ ▲ 24 215 235 60/— M 24 x 88 36 4

TECHNICAL DATA

Bolt anchor FAZ II GS (with large washer) Bolt anchor FAZ II HBS (washer compliant to
wood construction standard DIN 1052)

zinc-plated stainless Drill hole Min. drill- Anchor Max. usable Thread Width Washer (ou- Sales unit
steel steel diameter hole depth length length across nut ter diameter
Approval

for through hef,stand/ x thickness)


fixings hef,red
do h2 l tfix Ø x length  SW
Art.-No. Art.-No. ETA [mm] [mm] [mm] [mm] [mm] [mm] [mm] [pcs]
Item gvz A4
FAZ II 8/10 GS 094872 1) 501398 ■ 8 65 75 10/- M 8 x 38 13 22 x 2,5 50
FAZ II 8/30 GS 096189 1) 501400 1) ■ 8 85 95 30/- M 8 x 58 13 22 x 2,5 50
FAZ II 10/10 GS 096291 1) 501405 1) ■ 10 85 95 10/30 M 10 x 53 17 25 x 3 50
FAZ II 10/30 GS 096297 1) — ■ 10 105 115 30/50 M 10 x 73 17 25 x 3 25
FAZ II 10/30 GS — 501408 1) ■ 10 105 115 30/50 M 10 x 73 17 25 x 3 50
FAZ II 12/10 GS 096303 1) 501414 1) ■ 12 100 110 10/30 M 12 x 61 19 30 x 3 20
FAZ II 12/20 GS 502530 1) — ■ 12 110 120 20/40 M 12 x 71 19 30 x 3 20
FAZ II 12/30 GS 096340 1) 501418 1) ■ 12 120 130 30/50 M 12 x 81 19 30 x 3 20
FAZ II 12/50 GS 502531 1) — ■ 12 140 150 50/70 M 12 x 101 19 30 x 3 20
FAZ II 12/100 GS 502532 1) — ■ 12 190 200 100/120 M 12 x 151 19 30 x 3 20
FAZ II 12/120 GS 096367 1) — ■ 12 210 220 120/140 M 12 x 151 19 30 x 3 20
FAZ II 12/160 GS — 503181 ■ 12 250 260 160/180 M 12 x 186 19 44 x 4 20
FAZ II 16/160 GS 503261 1) — ■ 16 270 283 160/180 M 16 x 189 24 56 x 5 10
FAZ II 16/160 GS — 503182 1) ■ 16 270 283 160/180 M 16 x 100 24 56 x 5 4
FAZ II 16/200 GS 096370 — ■ 16 310 323 200/220 M 16 x 189 24 56 x 5 10
FAZ II 12/100 HBS 522951 1) — ■ 12 190 205 100/120 M 12 x 151 19 58 x 6 20
FAZ II 12/120 HBS 522952 1) — ■ 12 210 225 120/140 M 12 x 171 19 58 x 6 20
FAZ II 16/160 HBS 522953 1) — ■ 16 270 278 160/180 M 16 x 189 24 68 x 6 10
FAZ II 16/200 HBS 522954 — ■ 16 310 328 200/220 M 16 x 189 24 68 x 6 10
1)
Approved for seismic performance category C1 according to ETA0069/05- with standard embedment depth

ANCHOR INSTALLATION DATA

Anchor type FAZ II 8 FAZ II 10 FAZ II 12 FAZ II 16 FAZ II 20 FAZ II 24

Diameter of thread M8 M 10 M 12 M 16 M 20 M 24
Nominal drill hole diameter do [mm] 8 10 12 16 20 24
Drill depth h1 [mm] 55 75 90 110 125 155
Effective anchorage depth hef [mm] 45 60 70 85 100 125
Drill hole depth for through fixing td [mm] td = h1+tfix
Clearance-hole in fixture to be attached df [mm] ≤9 ≤12 ≤14 ≤18 ≤22 ≤26
Wrench size SW [mm] 13 17 19 24 30 36
Required torque Tinst [Nm] 20 45 60 110 200 270

67
Bolt anchor FAZ II

Minimum member thickness and characteristic edge distance and spacing for design

Anchor type FAZ II 8 FAZ II 10 FAZ II 12 FAZ II 16 FAZ II 20 FAZ II 24


hef 45 60 70 85 100 125
Minimum thickness of concrete member hmin [mm] 100 120 140 170 200 250
Cracked concrete
smin [mm] 35 40 45 60 95 100
for c≧ [mm] 50 55 70 95 140 170
cmin [mm] 40 45 55 65 85 100
for s ≧ [mm] 70 80 110 150 190 220
Application with concrete member thicknes h ≧ 2 · hef Non-cracked concrete
smin [mm] 40 40 50 60 95 100
for c ≧ [mm] 50 60 70 95 180 200
cmin [mm] 40 45 55 65 95 135
for s≧ [mm] 100 80 110 150 190 235
Minimum thickness of concrete member hmin [mm] 80 100 120 140 160 200
Cracked and Non-cracked concrete
smin [mm] 35 40 50 80 125 150
Application with concrete member thicknes h < 2 · hef for c ≧ [mm] 70 100 90 130 220 230
cmin [mm] 40 60 60 65 125 135
for s ≧ [mm] 100 90 120 180 230 235
1)
Intermediate values by linear interpolation.

Letter code on marking area 1 and maximum thickness of fixture tfix:

Marking (A) (B) (C) (D) (E) (F) (G) (H) (I) (K) (L) (M) (N) (O) (P) (R) (S) (T) (U) (V) (W) (X) (Y) (Z)
max.tfix
for hef,sta M8 - M24 5 10 15 20 25 30 35 40 45 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400
max.tfix
M10 - M16 25 30 35 40 45 50 55 60 65 70 80 90 100 110 120 140 160 180 200 220 270 320 370 420
for hef,red

ACCESSORIES

fischer Anchor bolt setting tool FABS

Fits anchor Sales unit


Item Art.-No. [pcs]
FABS 077937 FAZ II, FBN II, EXA for diameter from M6 - M12 1

TECHNICAL DATA

Bolt anchor FAZ II K/FAZ II K GS (short version)


Approval

zinc-plated stainless Nominal Min. drill Anchor Reduced Thread Washer Sales unit
steel steel drill hole hole depth length embedment depth (outer
diameter for push- with respective diameter x
through usable length thickness)
installation

h2 l hef, red. tfix dia x length


Art.-No. Art.-No.
Article description gvz A4 ETA [mm] [mm] [mm] [mm] [mm] [mm] [mm] [pcs]
FAZ II 10/10 K 522108 522116 ■ 10 65 75 40 10 M 10 x 33 19 x 1.8 50
FAZ II 10/20 K 522110 522117 ■ 10 75 85 40 20 M 10 x 43 29x 1.8 25
FAZ II 12/10 K 522118 522122 ■ 12 80 90 50 10 M 12 x 41 23 x 2.3 20
FAZ II 12/20 K 522119 522123 ■ 12 90 100 50 20 M 12 x 51 23 x 2.3 20
FAZ II 10/10 K GS 522115 - ■ 10 65 75 40 10 M 10 x 33 25 x 3.0 50
FAZ II 12/10 K GS 522121 - ■ 12 80 90 50 10 M 12 x 41 30 x 3.0 20

Letter code on marking area 1 and maximum thickness of fixture tfix:


Marking (a) (b) (c) (d)
max.tfix
for hef,red M10 - M16 5 10 15 20

68
Bolt anchor FAZ II

LOADS
Bolt anchor FAZ II

High performance steel anchors


Highest permissible loads for a single anchor1) in concrete C20/254)
For the design the complete approval ETA - 05/0069 has to be considered.
Cracked concrete Non-cracked concrete
Type minimum maximum minimum torque permissible permissible min. min. permissible permissible min. min.
effective effective member moment tensile load shear load spacing edge tensile load shear load spacing edge
anchorage anchorage thickness5) distance distance
depth depth
hef,min hef,max hmin Tinst Nperm3) Vperm3) smin2) cmin2) Nperm3) Vperm3) smin2) cmin2)
[mm] [mm] [mm] [Nm] [kN] [kN] [mm] [mm] [kN] [kN] [mm] [mm]
FAZ II 8 45 100 20,0 2,4 6,9 35 40 4,3 6,9 40 40
40 80 45,0 4,3 8,7 40 45 6,1 11,4 40 45
FAZ II 10
60 120 45,0 4,3 11,4 40 45 7,6 11,4 40 45
50 100 60,0 6,1 13,9 50 55 8,5 16,9 50 55
FAZ II 12
70 140 60,0 7,6 16,9 50 55 11,9 16,9 50 55
65 140 110,0 9,0 20,7 65 65 12,6 29,0 65 65
FAZ II 16
85 170 110,0 13,4 31,4 65 65 18,8 31,4 65 65
FAZ II 20 100 200 200,0 17,1 40,0 95 85 24,0 40,0 95 95
FAZ II 24 125 250 270,0 24,0 49,1 100 100 33,6 49,1 100 135

gerissener Beton ungerissener Beton


Type minimum maximum minimum torque permissible permissible min. min. permissible permissible min. min.
effective effective member moment tensile load shear load spacing edge tensile load shear load spacing edge
anchorage anchorage thickness5) distance distance
depth depth
hef,min hef,max hmin Tinst Nperm3) Vperm3) smin2) cmin2) Nperm3) Vperm3) smin2) cmin2)
[mm] [mm] [mm] [Nm] [kN] [kN] [mm] [mm] [kN] [kN] [mm] [mm]
FAZ II 8 A4 45 100 20,0 2,4 6,9 35 40 4,3 6,9 40 40
40 80 45,0 4,3 8,7 40 45 6,1 11,4 40 45
FAZ II 10 A4
60 120 45,0 4,3 11,4 40 45 7,6 11,4 40 45
50 100 60,0 6,1 13,9 50 55 8,5 16,9 50 55
FAZ II 12 A4
70 140 60,0 7,6 16,9 50 55 11,9 16,9 50 55
65 140 110,0 9,0 20,7 65 65 12,6 29,0 65 65
FAZ II 16 A4
85 170 110,0 13,4 31,4 65 65 18,8 31,4 65 65
FAZ II 20 A4 100 200 200,0 17,1 40,0 95 85 24,0 40,0 95 95
FAZ II 24 A4 125 250 270,0 24,0 49,1 100 100 33,6 49,1 100 135

Cracked concrete Non-cracked concrete


Type minimum maximum minimum torque permissible permissible min. min. permissible permissible min. min.
effective effective member moment tensile load shear load spacing edge tensile load shear load spacing edge
anchorage anchorage thickness5) distance distance
depth depth
hef,min hef,max hmin Tinst Nperm3) Vperm3) smin2) cmin2) Nperm3) Vperm3) smin2) cmin2)
[mm] [mm] [mm] [Nm] [kN] [kN] [mm] [mm] [kN] [kN] [mm] [mm]
FAZ II 8 C 45 100 20,0 2,4 6,9 35 40 4,3 6,9 40 40
40 80 45,0 4,3 8,7 40 45 6,1 11,4 40 45
FAZ II 10 C
60 120 45,0 4,3 11,4 40 45 7,6 11,4 40 45
50 100 60,0 6,1 13,9 50 55 8,5 16,9 50 55
FAZ II 12 C
70 140 60,0 7,6 16,9 50 55 11,9 16,9 50 55
65 140 110,0 9,0 20,7 65 65 12,6 29,0 65 65
FAZ II 16 C
85 170 110,0 13,4 31,4 65 65 18,8 31,4 65 65
FAZ II 20 C 100 200 200,0 17,1 40,0 95 85 24,0 40,0 95 95
FAZ II 24 C 125 250 270,0 24,0 49,1 100 100 33,6 49,1 100 135
1) 3)
The partial safety factors for material resistance as regulated in the approval as well as a partial For combination of tensile loads, shear loads, bending moments as well as reduced edge
safety factor for load actions of L = 1,4 are considered. As an single anchor counts e.g. an an- distances or spacings (anchor groups) see approval.
4)
chor with a spacing s ≥ 3 x hef and an edge distance c ≥ 1,5 x hef. Accurate data see approval. For higher concrete strength classes up to C50/60 higher permissible loads may be possible.
2) 5)
Minimum possible axial spacings resp. edge distance while reducing the permissible load for the According approval the minimum member thickness (h min ≧ 2 x hef) can be reduced under
minimum member thickness (h min ≧ 2 x hef). The combination of the given min. spacing and specific conditions.
min. edge distance is not possible. One of them has to be increased according approval.

69
Installation systems

Channel FUS Properties:


OVER VIEW Material Steel S250 GD-C (material no. 1.0242+Z) acc. to DIN EN 1.0346

Installation systems
Zinc plating Sendzimir zinc plated, approx. 20 µm
Material HDG Steel S235 JR (material no. 1.0045) acc. to EN 10027-2
Zinc plating Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material A2 Stainless steel of the corrosion resistance class II, e.g. A2
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
FUS 21 FUS 41 FUS 62

INSTALLATION

FUS 21D FUS 41D FUS 62D

DESCRIPTION
▪ U-profiled channel for horizontal and vertical installation.
▪ Fast and streamlined fastening of pipe tracks and load-bearing constructions.
Advantages / Benefits
▪ High bending and tear-out strength due to optimized profile cross section.
▪ Serration in the rail for secure hold of channel nut FCN and FHS Clix S.
▪ Versatile options for wall, floor and ceiling installation.
▪ Simple cutting to size and installation due to the stamped grid dimension on the rail side.
▪ The fire inspection report in line with MLAR/EN 13501 guarantees independantly tested functional safety

TECHNICAL DATA
Type Art. No. Qty. per box Length Thickness Weight FUS 21 FUS 41
L S 30
pcs. [m] [mm] [kg/m] 30 S
14 50
FUS 21/2.0 – 2 m 40391 1 2 2.0 1.44 14 S 25
50
FUS 21/2.0 – 3 m 97660 1 3 2.0 1.44 L 25 L
FUS 21/2.5 – 2 m 92867 1 2 2.5 1.67 41
21
FUS 21/2.5 – 3 m 77349 1 3 2.5 1.67 22 22
FUS 21/2.5 – 6 m 77541 1 6 2.5 1.67 41 41
FUS 41/2.0 – 2 m 40390 1 2 2.0 2.06
FUS 41/2.0 – 3 m 97658 1 3 2.0 2.06 FUS 62 FUS 21D
FUS 41/2.0 – 6 m 97659 1 6 2.0 2.06
FUS 41/2.5 – 2 m 92295 1 2 2.5 2.45 30
FUS 41/2.5 – 3 m 77347 1 3 2.5 2.45 14 50
FUS 41/2.5 – 6 m 77537 1 6 2.5 2.45 25
FUS 62/2.5 – 6 m 504457 1 6 2.5 3.27 L
2.5
FUS 21D/2.0 – 3 m 504458 1 3 2.0 2.87 42
L 62
FUS 41D/2.5 – 6 m 504459 1 6 2.5 4.89 22
FUS 62D/2.5 – 6 m 504460 1 6 2.5 6.55
22 2 41
FUS 41/2,0 – 3 m hdg. 517426 1 3 2.0 2.05
FUS 62/2,5 – 3 m hdg. 517427 1 3 2.5 41
3.26
FUS 62/2,5 – 6 m hdg. 517428 1 6 2.5 3.26
FUS 21/2.0 A2 – 2m 504466 1 2 2.0 1.44 FUS 41D FUS 62D
FUS 41/2.0 A2 – 2m 504468 1 2 2.0 2.06
FUS 41/2.5 A2 – 2m 504470 1 2 2.5 2.45
FUS 21/2.0 A4 – 2m 504472 1 2 2.0 1.44
FUS 41/2.0 A4 – 2m 504474 1 2 2.2 2.06
FUS 41/2.5 A4 – 2m 504475 1 2 2.5 2.45

82
LOADS L
2.5 124

22
L
41

22
2.5 41

Item Weight Area Moment of Moment of Section Section Max. Recomended static load
inertia inertia modulus modulus Length = .5 M Length = 1 M Length = 1.5 M Length = 2 M Length = 3 M
W A Iy Iz Wy Wz Frec Frec Frec Frec Frec
[kg/m] [mm2] [mm4] [mm4] [mm3] [mm3] KN KN KN KN KN
FUS 21/2.0 1.44 172 9700 46600 890 2270 1.14 0.49 0.22 0.12 0.05
FUS 21/2.5 1.67 199 10300 52800 930 2580 1.19 0.52 0.23 0.13 0.06
FUS 41/2 2.06 252 53300 76900 2580 3750 3.30 1.65 1.10 0.67 0.30
FUS 41/2.5 2.45 300 60000 89900 2850 4380 3.65 1.82 1.22 0.76 0.34
FUS 62/2.5 3.27 405 177000 129000 5620 6290 7.19 3.60 2.40 1.80 0.99
FUS 21D/2 2.87 344 54900 93100 2610 4540 3.34 1.67 1.11 0.69 0.31
FUS 41D/2.5 4.89 600 10300 179000 8760 8780 2.08 0.52 0.23 0.13 0.06
FUS 62D/2.5 6.55 809 1110000 258000 17900 12580 22.91 11.46 7.64 5.73 3.82
* Maximum permissible deflection under load = L/200

149
Installation systems

Saddle flange SF L
OVER VIEW

Installation systems
Properties:
Material Base plate: DC01 (steel 1.0330) acc. DIN EN 10139
SF L41 SF L82 SF L124 Channel: S235JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating Electro zinc plated, min. 8 µm
Material Base plate: Steel DC01 (material no. 1.0330) acc. to DIN EN 10139
U profile: S235 JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating HDG Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4

INSTALLATION
DESCRIPTION
▪ Connecting element for producing robust constructions in connection
with the fischer channels.
Advantages / Benefits
▪ Solid connecting element for load-bearing constructions.
▪ Simple installation by inserting the mounting rail in the saddle.
TECHNICAL DATA
SF L41 SF L82 SF L124

Type Art. No. Qty. per box For Profile FUS


pcs.
SF L 41 504355 10 21; 41; 21D; 62
SF L 82 504357 5 41D
SF L 124 504358 5 62D
SF L 41 hdg. 517421 10 21; 41; 21D; 62
SF L 41 A4 504522 10 FUS 21 + FUS 41

Angle fittings FAF


OVER VIEW
Properties:
Material Steel DD11 (material no. 1.0332) acc. to DIN EN 10111
FAF 2 FAF 2/135°
Zinc plating Elecro zinc plated min. 5 µm
Material A4: Stainless steel of the corrosion resistance class III, e.g. A4

DESCRIPTION
FAF 3 FAF 4 ▪ For plane and frame installations with FUS channels.

TECHNICAL DATA FAF 3 FAF 4

FAF 2 FAF 2/135°

Type Art. No. Qty. per box


pcs.
FAF 2 - angle fittings 504501 25
FAF 3 - angle fittings 504506 25
FAF 4 - angle fittings 504509 25
FAF 2/135° - angle fittings 504369 25
FAF 2 A4 504519 25
FAF 4 A4 504520 25
FAF 2/135° A4 504521 25

151
Installation systems

FUS 3D flanges FZF, FUF


OVER VIEW
Properties:
FZF 21 FZF 41 FUF 21 Material Steel DD11 (material no. 1.0332) acc. to DIN EN 10111
Zinc plating Electro zinc plated min. 5 µm

FUF 41 FUF 180°R FUF 180°L FUF 4Y FUF 8T

DESCRIPTION
▪ Connecting elements for 3D frame installations with FUS Channels.
Advantages / Benefits
▪ Quick installation by using FCN Clix P.

TECHNICAL DATA

FZF 21 FZF 41 FUF 21 FUF 41

Type Art. No. Qty. per box


pcs.
FZF 21 504375 25
FZF 41 504515 25
FUF 21 504376 25
FUF 41 504377 25
FUF 4Y
FUF 180°R FUF 180°L

FUF 8T

Type Art. No. Qty. per box


pcs.
FUF 4Y 504378 20
FUF 180°L 504379 20
FUF 180°R 504383 20
FUF 8T 504387 10

Flat fittings FFF


OVER VIEW
Properties:
Material Steel DD11 (material no. 1.0332) acc. to DIN EN 10111
FFF 1 FFF 4
Zinc plating Electro zinc plated min. 5 µm

FFF 4D FFF 3l

FFF 4T

DESCRIPTION
▪ For plane installations with FUS channels.

152
Installation systems

Channel nut FCN Clix Properties:


OVER VIEW

Installation systems
Material 1 Steel S235 JR (material no. 1.0037) acc. DIN EN 10025, plastic nylon PA6
FCN Clix P FCN Clix M Zinc plating Electro zinc plated, min. 5 µm
Material 2 HDG Steel S235 JR (material no. 1.0037) acc. to DIN EN 10025
Zinc plating Hot-dip galvanized, approx. 40 µm acc. to DIN EN ISO 1461
Material 3 Stainless steel of the corrosion resistance class III, e.g. A4
Plastic Nylon PA 6

Properties:
FCN FCN-L Material ISO 898-1, DIN 975 & 976 (Steel: 4.8 & 8.8)
Finish Electro Galvanized (as per ASTM B633),
FCN-L Hot Dip Galvanized (as per ASTM A153)
Material SS316 DIN EN ISO 3506-1

DESCRIPTION INSTALLATION
▪ Insert in to the channel and rotate 90°.
▪ Fast connecting nut fitting to the FUS channel.
▪ FCN Clix P suitable for connecting channel and fittings.
▪ FCN Clix M suitable for connecting clamps with a threaded rod.
▪ To be used in connection with threaded rod G or GS,
see page 132.
▪ Threaded plate fitting to the FUS channels.
Advantages / Benefits
▪ Easy and precise positioning in the channel.
▪ Serration for secure hold in the FUS channel.
▪ Simple installation.
▪ Retrofitting in rails possible.

FCN Clix P FCN Clix M

Spring nut tensile resistance Spring nut sliding resistance

TECHNICAL DATA
Type Art. No. Qty. per box Thread Thickness Max.recommended Max.recommended Max.recommended Tightening torque for
tension load for FUS tension load for FUS shesr load screw grade≥ 4.6
2,0mm 2,0mm
S Nrec Nrec Vrec Tinst
pcs. M [mm] [kN] [kN] [kN] [kN]
FCN Clix P 6 504326 100 M6 6 3 3 1 10
FCN Clix P 8 504327 100 M8 6 4 4 2 20
FCN Clix P 10 504329 100 M 10 8 5 8 2.5 40
FCN Clix P 12 504331 100 M 12 9.5 5 8 3 50
FCN Clix M 6 504344 100 M6 6 3 3 1 10
FCN Clix M 8 504345 100 M8 6 4 4 2 20
FCN Clix M 10 504346 100 M 10 8 5 8 2.5 40
FCN Clix M 12 504347 100 M 12 9.5 5 8 2.5 30
FCN Clix P 12 HDG 517420 100 M 12 9.5 5 8 3 50
FCN Clix P 8 A4 504436 100 M8 6 4 4 2 -
FCN Clix P 10 A4 504437 100 M 10 8 5 8 2.5 -
FCN Clix P 12 A4 504439 100 M 12 9.5 5 8 3 -
FCN Clix M 8 A4 504440 100 M8 6 4 4 2 -
FCN Clix M 10 A4 504447 100 M 10 8 5 8 2.5 -
FCN 6 77405 100 M6 6 3 3 1 10
FCN 8 77407 100 M8 6 4 4 2 20
FCN 10 77409 100 M 10 8 5 8 2.5 40
FCN 12 77411 100 M 12 9 5 8 2.5 50

Type Art. No. Art. No. Art. No. Spring Thread Max.recommended Max.recommended Max.recommended Tightening torque for
Length tension load for FUS tension load for FUS shesr load screw grade≥ 4.6
2,0mm 2,5mm
Nrec Nrec Vrec Tinst
GI HDG SS316 mm D [kN] [kN] [kN] [kN]
FCN-L6 516750 516765 516774 6 M6 3 3 1 10
FCN-L8 516751 516766 516775 6 M8 4 4 2 20
FCN-L10 516752 516767 516776 8 M10 5 8 2.5 40
FCN-L12 516753 516768 -- 9 M12 5 8 2.5 50
FCN-L12 -- -- 516777 9.2 M12 5 8 2.5 50
FCN-L12 -- 516769 -- 12 M12 5 8 2.5 50

155
Installation systems

Hexagonal screw SKS


OVER VIEW
Properties:
Zinc plating Electro zinc plated, 3 – 8 µm
SKS
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
acc. DIN-EN-ISO 4017, steel 8.8

TECHNICAL DATA
Art. No. Qty. per box Length Thread Width across
L D nut
pcs. [mm] SW

SKS 6 x 20 079711 100 20 M6 10


SKS 8 x 16 079415 100 16 M8 13
SKS 8 x 30 079713 100 30 M8 13
SKS 8 x 45 079714 100 45 M8 13
SKS 8 x 55 079715 100 55 M8 13
SKS 8 x 100 079827 100 100 M8 13
SKS 10 x 20 079416 100 20 M 10 17
SKS 10 x 30 079417 100 30 M 10 17
SKS 10 x 55 079721 100 55 M 10 17
SKS 10 x 85 505552 100 85 M 10 17
SKS 12 x 20 077610 100 20 M 12 19
SKS 12 x 55 077611 100 55 M 12 19
SKS 12 x 85 505553 100 85 M 12 19
Stainless steel A4
SKS M 10 x 30 A4 505547 100 - M 10 17
SKS M 12 x 30 A4 505548 100 - M 12 19

Hexagonal screw SKSL


OVER VIEW
Properties:
Material DIN 933 (Steel: 8.8)
SKSL
Finish Electro Galvanized (as per ASTM B633),
Hot Dip Galvanized (as per ASTM A153)
Material SS316 DIN EN ISO 3506-1

TECHNICAL DATA
Art. No. Art. No. Art. No. Length Thread Type Art. No. Art. No. Art. No. Length Thread
L D L D
GI 8.8 HDG 8.8 SS 316 [mm] GI 8.8 HDG 8.8 SS 316 [mm]

SKSL M 6x16 516755 - - 16 M6 SKSL M 12x25 516786 - - 25 M12


SKSL M 6x20 - 516797 - 20 M6 SKSL M 12x30 - 516595 - 30 M12
SKSL M 6x25 516756 516798 516606 25 M6 SKSL M 12x35 516787 - - 35 M12
SKSL M 6x40 516757 - - 40 M6 SKSL M 12x40 516788 - 516615 40 M12
SKSL M 6x50 - - 516607 50 M6 SKSL M 12x50 516789 - 516616 50 M12
SKSL M 8x16 516758 - - 16 M8 SKSL M 12x55 - 516596 516617 55 M12
SKSL M 8x20 516759 516799 - 20 M8 SKSL M 12x60 516790 - 516618 60 M12
SKSL M 8x25 516761 - - 25 M8 SKSL M12X75 - - 516619 75 M12
SKSL M 8x30 516763 - - 35 M8 SKSL M12X100 - - 516620 100 M12
SKSL M 8x35 516762 516800 - 30 M8 SKSL M12X110 - - 516621 110 M12
SKSL M 8x45 516764 - - 45 M8 SKSL M12x120 - - 516622 120 M12
SKSL M 8x55 516778 - - 55 M8 SKSL M 16x30 516791 - - 30 M16
SKSL M 8x80 - 516552 - 80 M8 SKSL M 16x35 516792 - - 35 M16
SKSL M 10x16 516779 - - 16 M10 SKSL M 16x40 516793 - - 40 M16
SKSL M 10x20 516780 516553 - 20 M10 SKSL M 16x50 516794 - - 50 M16
SKSL M 10x25 516781 516554 516608 25 M10 SKSL M 16x55 516597 - 55 M16
SKSL M 10x30 516782 516555 - 30 M10 SKSL M 16x70 516795 - - 70 M16
SKSL M 10x35 516783 - - 35 M10 SKSL M 16x80 - 516598 516623 80 M16
SKSL M 10x40 - 516556 - 40 M10 SKSL M 16x100 - 516599 516624 100 M16
SKSL M 10x50 - 516592 516609 50 M10 SKSL M 20x40 516796 - - 40 M20
SKSL M 10x55 516784 - - 55 M10 SKSL M 20X90 - 516600 - 90 M20
SKSL M 10x60 - 516593 516610 60 M10 SKSL M 20X125 - 516601 516625 125 M20
SKSL M 10x70 - - 516611 70 M10 SKSL M 20X130 - 516602 - 130 M20
SKSL M 10x90 - - 516612 90 M10 SKSL M 22X80 - - 516626 80 M22
SKSL M 10x100 - 516594 - 100 M10 SKSL M 22X100 - 516603 - 100 M22
SKSL M 10x110 - - 516613 110 M10 SKSL M 24X150 - 516604 516627 150 M24
SKSL M 10x120 - - 516614 120 M10 SKSL M 24X180 - 516605 - 180 M24
SKSL M 12x20 516785 - - 20 M12

164
Installation systems

Hexagonal nut MU
OVER VIEW

Installation systems
Properties:
Material acc. DIN EN 20898-2; min. strength category 04
MU Zinc plating Electro zinc plated, min. 5 µm
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4
According: DIN 934

TECHNICAL DATA

Type Art. No. Qty. per box Thread Width across


D nut
pcs. SW
[mm]
MU M 6 079733 100 M6 10
MU M 8 079734 100 M8 13
MU M 10 079735 100 M 10 17
MU M 12 024650 100 M 12 19
MU M 16 55727 50 M 16 24
Stainless steel A4
MU M 8 A4 77642 100 M8 13
MU M 10 A4 77641 100 M 10 17

Hexagonal nut HN
OVER VIEW
Properties:
Material DIN 934
HN Finish Electro Galvanized (as per ASTM B633),
Hot Dip Galvanized (as per ASTM A153)

TECHNICAL DATA

Type Art. No. Art. No. Art. No. Thread


D
GI HDG SS316 [mm]
HN M6 516801 516806 516811 M6
HN M8 516802 516807 516812 M8
HN M10 516803 516808 516813 M10
HN M12 516804 516809 516814 M12
HN M16 516805 516810 516815 M16
HN M20 516739 516741 516743 M20
HN M24 516740 516742 516744 M24

165
Installation systems

Washer U
OVER VIEW Properties:
Material Steel DD11 (material no.1.0139) acc. to DIN EN 10111
U Zinc plating Electro zinc plated, min. 3 µm
Material A4 Stainless steel of the corrosion resistance class III, e.g. A4

TECHNICAL DATA
Art. No. Qty. per box Thickness External Ø Hole Ø
S A
pcs. [mm] [mm] [mm]

U 6 x 24 020939 200 2 24 6.4


U 8 x 17 091477 100 1.6 17 8.4
U 8 x 28 079725 100 2 28 8.4
U 8 x 40 079729 100 3 40 8.4
U 10 x 21 091478 100 2 21 10.5
U 10 x 28 079726 100 2 28 10.5
U 10 x 40 079730 100 3 40 13
U 12 x 24 557301 100 2,5 24 13
U 12 x 40 024649 100 3 40 16.5
U 16 x 30 557303 50 3 30 16.5
U 8 x 28 A4 505542 100 2 28 8.4
U 8 x 40 A4 505543 100 3 40 8.4
U 10 x 28 A4 505544 100 2 30 10.5
U 10 x 40 A4 505545 100 3 40 10.5
U 12 x 24 A4 505546 100 2 24 12.5

Washer MW
OVER VIEW Properties:
Material DIN 125
MW Finish Electro Galvanized (as per ASTM B633),
Hot Dip Galvanized (as per ASTM A153)

TECHNICAL DATA
Art. No. Art. No. Art. No. Thread
D
GI HDG SS316 [mm]

MW M6X12 516816 516832 516824 M6


MW M8X16 516817 516833 516825 M8
MW M8X30 516818 516834 516826 M8
MW M8X40 516819 516835 516827 M8
MW M10x20 516820 516836 516828 M10
MW M10x30 516821 516837 516829 M10
MW M10x40 516822 516838 516830 M10
MW M12x24 516823 516839 516831 M12
MW M16x30 516770 516745 516748 M16
MW M16x40 516771 - - M16
MW M20x37 516772 516746 516749 M20
MW M24x44 516773 516747 516760 M24

166
Installation systems

Riser Clamp RCWR Properties:


OVER VIEW Material Carbon Steel Q 235
Micron ≥ 5 µM
Finish Electro galvanized, Epoxy coated & other finish
RCWR available upon request

APPROVALS

DESCRIPTION
▪ Designed to act as a rigid support for vertical pipes.
▪ Suitable for use with all types of pipes.

TECHNICAL DATA

Type Art. No. Qty. per box Bolt Size Width Bolt Diameter Max. Rec. Load T

A B

[in] pcs. [in] [mm] [in] [mm] [in] [mm] [IBS] [kg] [mm]
RCWR 1/2” 516673 35 3/8 M10 8 1/2 215 1 25 220 100 5
RCWR 3/4” 516674 30 3/8 M10 9 228.5 1 25 220 100 5
RCWR 1” 516675 25 3/8 M10 9 229.5 1 25 220 100 5
RCWR 1-1/4” 516676 25 3/8 M10 9 1/2 240.5 1 25 250 113 5
RCWR 1-1/2” 516677 25 3/8 M10 9 7/8 251 1 25 250 113 3
RCWR 2” 516678 25 3/8 M10 10 2/7 261.6 1 1/6 30 300 136 5
RCWR 2-1/2” 532380 25 3/8 M10 11 281.3 1 1/6 30 400 181 5
RCWR 3” 516679 20 3/8 M10 11 3/4 298.5 1 1/6 30 500 227 5
RCWR 4” 516680 12 1/2 M12 13 328.6 1 1/2 38 750 340 6
RCWR 5” 516681 12 1/2 M12 14 1/4 362 1 1/2 38 1500 680 6
RCWR 6” 516682 8 1/2 M12 15 1/2 393.7 2 50 1600 726 6
RCWR 8” 516683 4 5/8 M16 18 1/4 463.5 2 50 2500 1134 9.5

138

You might also like