Operation Manual Asea AC15-3L 15-3H 18-3L 18-3H 603051-10 - 1
Operation Manual Asea AC15-3L 15-3H 18-3L 18-3H 603051-10 - 1
Operation Manual Asea AC15-3L 15-3H 18-3L 18-3H 603051-10 - 1
P/N 603051
Revised 1/7/08
AC15-3 and AC18-3 Operations Manual....2
CERTIFICATION
ASEA Power Systems certifies that this product was thoroughly tested and inspected and found to
meet or exceed its published specifications when shipped from the factory.
WARRANTY
ASEA Power Systems warrants each unit to be free from defects in material and workmanship. For
a period of 18 months after purchase or 12 months after installation (whichever is shorter), ASEA
Power Systems will repair or replace any defective module provided the unit has been installed and
operated in a manner according to this manual. A thorough inventory of spare parts & modules is
maintained at our factory. Our world-wide sales/support facilities also inventory a complement of
spare parts and modules.
ASEA Power Systems is not responsible for consequential damage arising from the use of its
equipment. It does not apply to extensively modified or non-standard systems. Debit memos for
returned units are not accepted, and will cause return of the system without repair.
ASEA Power Systems does not authorize the use of any of its products or systems for use an AC
voltage supply (source) for life support systems. Life support systems are devices which support or
sustain life, and whose failure to perform, when properly used in accordance with this Operations
Manual, can be reasonably expected to result in significant injury to the user.
AC15-3 and AC18-3 Operations Manual....3
It is important that the operator reads this manual prior to installing and operating the AC15-3 or
AC18-3. A thorough understanding of the information covered in this manual is required for proper
installation and operation.
If any questions arise while reading this manual, the user is encouraged to call ASEA Power
Systems. ASEA Power Systems is located at:
TABLE OF CONTENTS
CERTIFICATION........................................................................................................................... 2
WARRANTY.................................................................................................................................. 2
2 SAFETY NOTICES............................................................................................................ 6
4 SPECIFICATIONS ........................................................................................................... 10
4.1 ELECTRICAL SPECIFICATIONS...................................................................... 10
4.1.1 Input Service ............................................................................................. 10
4.1.2 Output Service........................................................................................... 10
4.1.3 Control, Metering, and Status ................................................................... 11
4.2 PHYSICAL SPECIFICATIONS........................................................................... 11
4.2.1 Mechanical ........................................................................................... 11
4.2.2 Environmental ........................................................................................... 11
5 INSTALLATION.............................................................................................................. 12
5.1 MECHANICAL INSTALLATION ...................................................................... 13
5.2 ELECTRICAL INSTALLATION ........................................................................ 16
5.2.1 Input Power Connections .......................................................................... 17
5.2.2 Output Power Connections ....................................................................... 18
5.2.3 Grounding and isolation considerations in IT electrical installations....... 19
AC15-3 and AC18-3 Operations Manual....5
6 OPERATION .................................................................................................................... 20
6.1 POWER TURN-ON PROCEDURE ..................................................................... 20
6.2 AUTO-RESTART FEATURE.............................................................................. 23
6.2.1 Operation................................................................................................... 24
6.3 TURN-OFF PROCEDURE................................................................................... 24
6.5 REMOTE COMMUNICATIONS ........................................................................ 25
7 DIAGNOSTICS ................................................................................................................ 32
7.1 STATUS WORD BIT DEFINITION.................................................................... 33
8 MAINTENANCE.............................................................................................................. 35
FIGURES
1 SYSTEM BLOCK DIAGRAM .......................................................................................... 8
2 CONTROLS........................................................................................................................ 9
2 SAFETY NOTICES
The AC15-3 and AC18-3 are capable of transferring very large amounts of electrical energy very
quickly. This quality is fundamental to a high performance power converter. International symbols
are used throughout this manual to stress important information. Read the text below each symbol
carefully and use professional skills and prudent care when performing the actions described by the
text.
Dual-conversion technology is the preferred technique for AC power conversion, and was chosen for
the AC15-3 and AC18-3. In this technology, the three-phase input service is isolated by
transformers then converted to DC power by a Power Factor Correction (PFC) power supply. The
output inverters then convert the DC power back to the required AC form (both voltage and
frequency) required by the yacht.
Being a unit designed from the ground up specifically for the yachting industry, all efforts have been
made to produce a system capable of sustaining the marine environment. All system components are
packaged in one drip-proof, dust-resistant stainless steel enclosure. Major components are internally
modular, allowing a simple exchange in the unlikely event of failure. Complete maintenance and
service can be provided with only front access to the system.
System operation is managed through three basic operators. A safety disconnect at the bottom of the
enclosure is used for securing input service during maintenance and service. Two membrane switch
groups in the control console, SHORE POWER and SHIPS POWER, provide normal operation of
the system. Each switch group contains an ON and OFF switch with associated LED indicators.
In addition to the basic function of power conversion, the AC15-3 and AC18-3 provide the user with
a sophisticated power analysis and monitoring capacity. All parameters for input and output power,
along with operations and status information, are available on the front panel display console.
Various displays are selected through a long life, sealed membrane switch panel. All front panel
information is available through the serial port for remote display, status and diagnostics.
FIGURE 2 CONTROLS
AC15-3 and AC18-3 Operations Manual....10
4 SPECIFICATIONS
4.1 ELECTRICAL SPECIFICATIONS
4.2.2 Environmental
Ambient Temperature Range 0-45 C non-condensing 0-45 C non-condensing
Air Exchange Rate 400CFM 400CFM
AC15-3 and AC18-3 Operations Manual....12
5 INSTALLATION
The installation section will be divided into two parts. The first will cover mechanical installation,
the second, electrical installation.
Read this manual thoroughly prior to attempting the installation. Improper installation is the most
significant cause of system start-up problems and service issues over the products life. Upon receipt
of the equipment, perform an external visual inspection. Verify that nameplate information is
consistent with the ship’s power requirements (required form, voltage, and frequency).
Proper planning will speed up installation, location, and connection of the equipment. Follow the
suggested minimum clearances provided in Table 1. Ensure the room/compartment has adequate
ventilation and cooling. The thermal load presented by the AC15-3 will be substantial,
approximately 5,936BTU/Hr at maximum continuous load. The thermal load presented by the
AC18-3 will be substantial, approximately 6,456BTU/Hr at maximum continuous load.
The mounting surface should be flat and dimensionally stable to within 1/16" (1.5mm) to prevent
torsional stresses being applied to the structure of the AC15-3 or AC18-3. Spacers (shim stock) may
be added between the mounting surface and the converter mounting ears to adjust the mounting
plane. Resilient mounts must not be used directly between the converter and the mounting surface.
If the converter is to be mounted in a high vibration/shock environment, then the factory must be
consulted concerning the application. Drawings for approved shock mounting panels will be
supplied.
The AC15-3 or AC18-3 may be mounted horizontally with the correct preparations to the mounting
surface. The factory must be contacted concerning the application prior to order/delivery of the
system to allow the required internal modifications to be included, and for concurrence on the
application and installation.
TABLE 1
FOR PROPER
Operation Service
Front 6” (Airflow) 24” min
Bottom 12” (Airflow) N/A
Sides 8” (Airflow) 6”
Top 0” 6”
AC15-3 and AC18-3 Operations Manual....14
All power wiring requires the removal of the lower front cover. This cover is secured with 18 ea. 6-
32 x 1/4” stainless steel screws. Do not remove the upper front cover, or the disconnect
switch/bracket assembly. Place the disconnect switch in the OFF position.
Remove the input service panel from the bottom of the system. This panel is secured with 10 ea 10-
32 x ½” stainless steel screws. The input service panel is supplied with two pilot holes for power
wiring strain reliefs. Drill or punch the appropriate holes for the selected strain reliefs. Re-install
the input service panel using the removed hardware.
Prepare the power cable by removing the outer cable insulation approximately 6”. Strip the
insulation back exposing 1/2” of bare conductor on all three wires. Insert the prepared cable and
strain relief assembly into the rearmost hole in the input service panel. Follow the wire table in the
illustration below for correct termination.
The input to the AC15-3 or AC18-3 is fully isolated with no phase orientation requirements to the
input power service.
AC15-3 and AC18-3 Operations Manual....18
THE AC15-3 AND AC18-3 ISOLATE THE OUTPUT POWER FROM THE
INPUT POWER AND EQUIPMENT (SAFETY) GROUND SIMILAR TO AN
ISOLATION TRANSFORMER. THE INSTALLER MUST RE-ESTABLISH
THE GROUND REFERENCE FOR THE EQUIPMENT AT TIME OF
INSTALLATION. NEUTRAL AND EQUIPMENT (SAFETY) GROUND TO
BE CONNECTED PER ABYC OR APPLICABLE STANDARD. (NOTE
THAT THE INPUT TRANSFORMERS HAVE FAULT SHIELDS, AND THAT
THESE GROUNDS ARE CONNECTED TO THE EQUIPMENT SAFTEY
GROUND.)
Prepare the power cable by removing the outer cable insulation approximately 6”. Strip the
insulation back exposing 1/2” of bare conductor on all three conductors. Insert the prepared cable
and strain relief assembly into the forward hole in the input service panel. Insert the wire ends into
the output terminal block and tighten.
6 OPERATION
6.1 POWER TURN-ON PROCEDURE
Close the input (shore power) circuit breaker to the AC15-3/AC18-3. Turn the disconnect switch
(10) to the ON position. After 1-3 seconds the fans will be heard and the display will illuminate and
become active. Allow the opening message to complete.
At this time both of the red LED indicators next to the OFF buttons (3 & 4) should be illuminated.
Press the SHORE POWER (5) display button. The display will indicate basic input power
information; voltage, current, and kVA. Verify the displayed voltage indicates that which is
expected. If not, do not proceed until contacting factory personnel.
Press the CONVERTER POWER (6) button and the screen will now change. Output voltage(s) and
current(s) should indicate zero.
To start the system, press the SHORE POWER - ON (1) button. The system will begin a soft-start
procedure which requires approximately 2 seconds to complete. At the conclusion of this process
the indicator LED in the SHORE POWER control area of the display should change from red to
green. View the display information for CONVERTER POWER (6) and verify the displayed
voltage is at the desired potential, frequency, and form.
NOTE: It is normal under no load conditions for the currents to indicate 2-4 Amps flowing. This
level of current is due to the internal filters and will not degrade the system’s power rating.
When ready to place the yacht’s convenience distribution bus load on the AC15-3/AC18-3, press the
CONVERTER POWER ON (2) button on the control panel. This will place voltage at the output
terminals of the AC15-3/AC18-3. The green ON indicator LED should now be lighted.
When load has been applied to the AC15-3/AC18-3, monitor the load currents and voltages. Ensure
the load is within the system ratings. Monitor the input power voltage and current levels with load
applied. Refer to published rating curves for maximum current, kVA, and kW levels.
AC15-3 and AC18-3 Operations Manual....23
Next press the SHORE POWER OFF (3) button. This will initiate the inverter shutdown process.
The system will complete the shutdown process within 10 seconds.
The baud rate can be increased by pressing the F1 (8) button, and decreased by pressing the F2 (9)
button. Pressing SYSTEM STATUS (7) saves the setting. Standard baud rates are 1200, 2400,
4800, 9600, 19200, and 38400 where 19200 is the default and standard for communication with all
ASEA Power Systems Touch Screens. No other parameters are user selectable.
The RS-232C serial port is a DE9S (female, 9-pin D-subminiature connector). The pin-out the
connector is standard for an RS-232C DCE (Data Communication Device). Figure 8 on page 35
demonstrates connection from a DCE to a DTE (Data Terminal Device as standard PC’s are
configured) or from a DCE to a DCE. Use of a shielded, jacketed, four-wire (two twisted pairs),
color-coded cable for each converter in the system is required.
The RS-232C serial port is located in the upper right-hand corner of the converter’s right side.
The TxD signal originating in the converter is approximately +15V when “High” and -15V when
“Low.”
AC15-3 and AC18-3 Operations Manual....26
What follows is a listing of the available commands through standard serial protocol. The
commands are given in the form that they should be sent: the colons and upper-case characters are
mandatory, the question marks and lower-case letters are optional. The commands may be sent in
either lower-case or upper-case characters with a carriage return [Enter] following each command
(except for the “Immediate Commands” which execute instantly after the two characters have been
typed). Contact the factory for questions regarding the use of commands listed herein.
AC15-3 and AC18-3 Operations Manual....28
7 DIAGNOSTICS
As an aid to system diagnostics, a Status Word has been provided at the bottom of the SUMMARY
DISPLAY screen. This Status Word is comprised of 16 digits, each indicating a separate internal logic term.
It can also be found along with other useful system data on the STATUS DISPLAY screen accessed by
pressing the SYSTEM STATUS (7) and F2 (9) buttons simultaneously.
If a problem has been encountered by the system, carefully record the Status Word before removing power to
the system (Diagnostic data may be deleted or reset with power cycling). When calling the factory for
assistance, please have the Status Word handy along with the system model, serial number, and software
version number.
Pressing the SYSTEM STATUS (7) and F1 (8) buttons simultaneously opens a system data screen containing
the converter software version as well as run-hours.
This screen will alternatively contain plain-language failure data if the SUMMARY DISPLAY or STATUS
DISPLAY is currently flashing WARNING or FAILURE. The example below is displayed when internal
converter temperatures exceed sensor limits. After a WARNING or FAILURE condition subsides, the
message can be cleared by pressing the F1 (8) and F2 (9) buttons simultaneously.
DIAGNOSTIC:XXX_X_OT * * FAILURE * *
OVER-TEMPERATURE CONDITION.
CHECK INTAKE AND AMBIENT TEMPERATURE.
CONVERTER SHUTDOWN.
AC15-3 and AC18-3 Operations Manual....33
LVDC OK All low voltage (housekeeping) supplies are valid. Should always be “1.”
HVDC >120 Both high voltage supplies (+/- 185VDC) are above the minimum threshold
for PFC operation. Should be a “0” when the inverter is off, a “1” when the
inverter has been started and the Shore Power LED is green.
HVDC>210 One or both of the high voltage power supplies has failed in an over-voltage
state. Should always be a “0.”
INV ENABLE The inverter is enabled. A “0” when the system is off, turns to a “1” when
the inverter is on.
INV TST OK Inverter tests OK. Proper switching action taking place in power stages.
Does not mean output voltage is correct yet. A “1” when operating.
AC15-3 and AC18-3 Operations Manual....34
PFC ENABLE The PFC stages have been enabled by the logic. Is a “0” when the system is
off, turns to “1” at the end of the “walk-in” stage.
PFC TST OK The PFC tests OK when a “1” is indicated. The PFC ENABLE bit (see
above) must be set to “1” first.
SP1_OK Input power is acceptable for use by the system when a “1” is indicated.
Voltage only is checked, not frequency.
V OUT OK Hardware has determined that the output voltages are acceptable for use
when a “1” is indicated. Frequency is not checked.
INV OT Inverter or Power Supply (PFC) has over-temped and has caused a shutdown.
Should normally be a “0.”
XFMR OT One or both of the input transformers has over-temped and has/have caused a
shutdown. Should normally be a “0.”
SPARE Spare
SP1 LOW The logic has determined the input power is in the low range, 170-270VAC
when a “1” is indicated.
K1 ENABLED Should indicate a “1” when the system is in the walk-in state, for
approximately 1 second after the start of the inverter start sequence.
K3 ENABLED The output contactor has been commanded to close when a “1” is indicated.
The inverter voltage must be in an acceptable range and the ships power
button is pressed.
AC15-3 and AC18-3 Operations Manual....35
8 MAINTENANCE
Due to the design and construction of the AC15-3/AC18-3, preventative maintenance is held to a
modest level. The following table lists minimum recommended tasks and frequency.
Tighten electrical connections Every 6 months Must be adjusted by the user based upon
experience in the environment.
Frequency will vary due to wire gauge,
wire type, and applied vibration.
220/380
Brunei 50Hz 240/415
Bulgaria 50Hz 220/380
Burma 50Hz 230/400
Canada 60Hz 120/240
120/208
277/480
Canary Islands 50Hz 127/220
220/380
Cape Verde 50Hz 220/380
Cayman Islands 60Hz 120/240
120/208
Chile 50Hz 220/380
China (PRC) 50Hz 220/380
Columbia 60Hz 110/220
120/208
150/260
Costa Rica 60Hz 120/240
120/208
Cyprus 50Hz 240/415
Denmark 50Hz 220/380
Dominica 50Hz 230/400
Dominican Republic 60Hz 120/240
120/208
Ecuador 60Hz 120/240
120/208
Fiji 50Hz 240/415
Finland 50Hz 220/380
France 50Hz 115/230
115/200
AC15-3 and AC18-3 Operations Manual....38
220/380
Gibraltar 50Hz 240/415
Greece 50Hz 220/380
Greenland 50Hz 220/380
Grenada 50Hz 230/400
Guadeloupe 50Hz 220/380
Guam 60Hz 110/220
120/208
Guatemala 60Hz 120/240
120/208
Haiti 60Hz 110/220
120/208
Honduras 60Hz 110/220
120/208
Hong Kong 50Hz 220/380
Ireland 50Hz 220/380
Israel 50Hz 230/400
Italy 50Hz 127/220
220/380
Jamaica 50Hz 110/220
Japan 50Hz 100/200
60Hz 100/200
Korea 60Hz 110/220
220/380
Kuwait 50Hz 240/415
Madagascar 50Hz 127/220
220/380
Malaysia 50hz 240/415
Maldives 50Hz 230/400
AC15-3 and AC18-3 Operations Manual....39