Manual Generac 4000xl
Manual Generac 4000xl
Pro
Q blem
Bef
ore
uesti s?
bac takin ons?
k g
call to th your
the e u
h gen store, nit
1-80 lpline rator
e e
0-2 at
M-F 70-1
8-5 408
CT
Model No. 9777–2 (4000 Watt AC Generator) Manual No. B4400 Revision 4 (9/20/2000)
Visit our Generac website: www.generac-portables.com
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
• The generator produces a very powerful voltage that can • Never operate the generator:
cause serious injury or death by electrocution. Never in rain; in any enclosed compartment; when connected
touch bare wires or receptacles. Never permit a child electrical devices overheat; if electrical output is lost; if
or any unqualified person to operate the generator. engine or generator sparks; if flame or smoke is
• Never handle any kind of electrical cord or device while observed while unit is running; if unit vibrates
standing in water, while barefoot or while hands or feet excessively.
are wet. Death or serious injury from electrocution may
result. GROUNDING THE
• Use a ground fault circuit interrupter (GFCI) in any damp
or highly conductive area (such as metal decking or steel
GENERATOR
work). The National Electrical Code requires that the frame and
• Never use worn, bare, frayed or otherwise damaged external electrically conductive parts of this generator be
electrical cords with the generator. Death, serious injury properly connected to an approved earth ground. Local
and property damage from electrical shock may result. electrical codes may also require proper grounding of the
• Gasoline is highly FLAMMABLE and its vapors unit. For that purpose, a GROUNDING WING NUT is
are EXPLOSIVE. Never allow smoking, open provided on the generator end (Figure 1).
flames, sparks or heat in the vicinity while Figure 1 — Grounding Wing Nut
handling gasoline. Avoid spilling gasoline on a hot
engine. Comply with all laws regulating storage and
handling of gasoline.
• Do Not overfill the fuel tank. Always allow room for
fuel expansion. If tank is overfilled, fuel can overflow
onto a hot engine and cause a FIRE or an
EXPLOSION.
• Never store a generator with fuel in the tank where
Grounding
gasoline vapors might reach an open flame, spark or pilot Wing Nut
light (as on a furnace, water heater, clothes dryer). FIRE
or an EXPLOSION may result.
• The unit requires an adequate flow of cooling air for its Generally, connecting a No. 12 AWG (American Wire
continued proper operation. Never operate the unit Gauge) stranded copper wire to the grounding wing nut
inside any room or enclosure where the free flow of and to an earth-driven copper or brass grounding rod
cooling air into and out of the unit might be obstructed. (electrode) provides adequate protection against electrical
Allow at least 2 feet of clearance on all sides of generator, shock. Be careful to keep the grounding wire attached after
even while operating unit outdoors, or you could damage connecting the stranded copper wire. However, local codes
the unit. See “Cold Weather Operation” on page 10. may vary widely. Consult with a local electrician for
• Never start or stop the unit with electrical loads grounding requirements in your area.
connected to receptacles with the connected devices Properly grounding the generator helps prevent electrical
turned ON. Start the engine and let it stabilize before shock if a ground fault condition exists in the generator or
connecting any electrical loads. Disconnect all electrical in connected electrical devices. Proper grounding also helps
loads before shutting down the generator. dissipate static electricity, which often builds up in
• Do Not insert any object through cooling slots of the ungrounded devices.
engine. You could damage the unit or injure yourself.
Fuel Tank
Circuit Breakers (AC)
12 Volt DC, 10 Amp Receptacle — Use this receptacle Circuit Breakers (AC) — Each receptacle is provided
with battery charge cables to charge a 12 Volt battery. with a circuit breaker to protect the generator against
120 Volt AC, 15 Amp Duplex Receptacle — May be electrical overload. Breakers are "push to reset" type.
used to supply electrical power for the operation of Fuel Shut Off Valve — Controls fuel supply to engine.
120 Volt AC, 15 Amp, single phase, 60 Hz electrical Fuel Tank — Capacity of 4 U.S. gallons (15 liters).
lighting, appliance, tool and motor loads.
Grounding Wing Nut — Provides a tie-point for
120 Volt AC, 30 Amp Receptacle — May be used to connecting the generator frame to earth ground.
supply electrical power for the operation of 120 Volt AC,
30 Amp, single phase, 60 Hz electrical lighting, appliance, Idle Control Switch — The idle control runs the engine
tool and motor loads. at normal (high) speeds when there is an electrical load
present and runs the engine at idle (low) speeds when a
120/240 Volt AC, 20 Amp Receptacle — May be used load is not present. This feature greatly improves fuel
to supply electrical power for the operation of 120 and/or economy, extends the life of the engine, and reduces engine
240 Volt AC, 20 Amp, single phase, 60 Hz electrical lighting, noise.
appliance, tool and motor loads.
Run/Stop Switch — Must be in “Run” position to start
engine. Set to “Stop” to stop a running engine.
OPERATING THE 5. Grasp the recoil handle and pull slowly until slight
resistance is felt. Then pull rapidly one time only to
GENERATOR start engine.
• If engine starts, proceed to step 7.
CAUTION! Never start or stop the engine with
electrical loads connected to the unit and with the • If engine fails to start, proceed to step 6.
connected devices turned ON. 6. Move the choke lever to “Half” choke position, and
pull recoil handle twice.
Starting the Engine • If engine fails to start, repeat steps 4 thru 6.
Disconnect all electrical loads from the generator. Use the 7. Move choke lever to “Run” position. If engine falters,
following start instruction steps by numerical order: move choke lever to “Half” choke position until the
1. Make sure the Idle Control switch is in “Off” position. engine runs smoothly, and then to “Run” position.
2. Turn the fuel valve to the “On” position (Figure 3). NOTE: If engine still fails to start after 3 pulls, check for
proper oil level in crankcase. This unit is equipped with a
Figure 3 — Fuel Valve in Open Position. Low Oil Shutdown System. See engine manual.
Cold Weather Operation • Ensure a minimum of two feet clearance between open
side of box and nearest object.
Under certain weather conditions (temperatures below
40°F [4°C] and a high dew point), your Generac generator • Face exposed end away from wind and elements.
may experience icing of the carburetor and/or the • Enclosure should hold enough heat created by the
crankcase breather system. generator to prevent problems.
In an emergency, use the original shipping box as a
temporary shelter:
CAUTION! NEVER run unit indoors; Do Not
enclose generator any more than shown. Remove
• Cut off all flaps. shelter when temperatures are above 40°F [4°C].
• Cut out one of the long sides of the box to expose
exhaust side of unit. Ensure a minimum of two feet
clearance between open side of box and nearest object.
RECEPTACLES
• Cut appropriate slots to access receptacles of unit.
120 Volt AC, 15 Amp Receptacles
• Start unit, then place box over it.
Each of these outlets is protected against overload by
IMPORTANT: Remove shelter when temperature is 15 Amp push-to-reset type circuit breakers (Figure 8).
above 40°F [4°C].
Figure 8 — 120 Volt AC, 15 Amp Duplex Receptacle
For a more permanent shelter, build a structure that will
enclose three sides and the top of the generator:
• Make sure entire muffler-side of generator is exposed
(Figure 7).
Figure 7 — Temporary Cold Weather Shelter
Wind
120/240 Volt AC, 20 Amp Locking 120 Volt AC, 30 Amp Locking
Receptacle Receptacle
Use a NEMA L14-20 plug with this receptacle. Connect a Use a NEMA L5-30 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volts at 20 Amps (or greater) 3-wire cord set rated for 125 Volts AC at 30 Amps to the
(Figure 9). You can use the same 4-wire cord if you plan to plug (Figure 10).
run a 120 Volt load.
Figure 10 — 120 Volt AC, 30 Amp Locking Receptacle
Figure 9 — 120/240 Volt AC, 20 Amp Receptacle
This receptacle powers 120/240 Volt AC, 60 Hz, single 12 Volt DC, 10 Amp Receptacle
phase loads requiring up to 2,400 watts of power at
This connector (identified by the legend “12-VOLT D.C.”)
20 Amps for 120 Volts; 4,000 watts of power (4.0 kW) at
supplies 12 Volts DC at 10 Amps through battery charging
16.7 Amps for 240 Volts. The outlet is protected by a
cables for recharging 12 Volt batteries (Figure 11). See
20 Amp push-to-reset circuit breaker.
“Charging a Battery” on page 7.
Figure 11 — 12 Volt DC, 10 Amp Receptacle
DON’T OVERLOAD THE • If the appliance, tool or motor does not give wattage,
multiply 120 Volts times ampere rating to determine
GENERATOR watts (volts x amps = watts).
• Some electric motors, such as induction types, require
Overloading a generator in excess of its rated wattage about three times more watts of power for starting than
capacity can result in damage to the generator and/or for running. This surge of power lasts for only a few
connected electrical devices. Observe the following, to seconds when starting such motors. Be sure you allow
prevent overloading the unit: for this high starting wattage when selecting electrical
• Add up the total wattage of all electrical devices to be devices to connect to your generator. First estimate the
connected at one time. This total should NOT be watts needed to start the largest motor. Add to that
greater than the generator’s wattage capacity. figure the running watts of all other connected loads.
• The rated wattage of lights can be taken from light bulbs. • The wattage reference guide (Figure 11) is provided to
The rated wattage of tools, appliances and motors can help you to determine how many items the generator
usually be found on a data plate or decal affixed to the can operate at one time.
device.
10
11
TROUBLESHOOTING
12
NOTES
13
ELECTRICAL SCHEMATIC
14
WIRING DIAGRAM
15
16
17
18
NOTES
19
GENERAC PORTABLE PRODUCTS (hereafter referred to as the COMPANY) warrants to the original purchaser that the
alternator and control panel for its portable generator will be free from defects in materials or workmanship for the items
and period set forth below from the date of original purchase. This warranty is not transferable and applies only to portable
generators driven by a GN-Series engine.
Consumer* Commercial*
Alternator 2 years (2nd year parts only) 1 year
Engine Warranted solely by the engine manufacturer
With the exception of European Community Countries, all units bound for export shall be warranted for One (1)
Year in Consumer applications, and 90 days in Commercial applications as defined below.
*NOTE: For the purpose of this warranty "consumer use" means personal residential household use by
original purchaser. This warranty does not apply to units used for Prime Power in place of utility.
"Commercial Use" means all other uses, including rental, construction, commercial and income producing
purposes. Once a generator has experienced commercial use, it shall thereafter be considered a
commercial use generator for the purposes of this warranty.
During said warranty period, the COMPANY will, at is option, repair or replace any part which, upon examination by the
COMPANY, is found to be defective under normal use and service**. Starting batteries are not warranted by the
COMPANY. All transportation costs under warranty, including return to the factory if necessary, are to be borne by the
purchaser and prepaid by the purchaser. This warranty does not cover normal maintenance and service and does not apply
to a generator set, alternator, or parts which have been subjected to improper or unauthorized installation or alteration,
misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as, in the COMPANY’s
judgement, to adversely affect its performance and reliability.
**NORMAL WEAR: As with all mechanical devices, the generator need periodic parts service and
replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of
a part or generator.
THERE IS NO OTHER EXPRESS WARRANTY. THE COMPANY HEREBY DISCLAIMS ANY AND ALL
IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THOSE OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT PERMITTED BY LAW. THE DURATION OF
ANY IMPLIED WARRANTIES WHICH CANNOT BE DISCLAIMED IS LIMITED TO THE TIME PERIOD AS
SPECIFIED IN THE EXPRESS WARRANTY. LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL
DAMAGES UNDER ANY AND ALL WARRANTIES IS EXCLUDED. THE COMPANY ALSO DISCLAIMS
ANY RESPONSIBILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, SUCH AS THE LOSS OF
TIME OR THE USE OF THE POWER EQUIPMENT, OR ANY COMMERCIAL LOSS DUE TO THE FAILURE
OF THE EQUIPMENT: AND ANY IMPLIED WARRANTIES ARE LIMITED TO THE DURATION OF THIS
WRITTEN WARRANTY.
Some states do not allow limitations on how long an implied warranty lasts, or the exclusion or limitation of incidental or
consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal
rights and you may also have other rights, which vary from state to state.
For service, see your nearest COMPANY authorized warranty service facility or call 1-877-544-0982. Warranty service can
be performed only by a COMPANY authorized service facility. This warranty will not apply to service at any other facility.
At the time of requesting warranty service, evidence of original purchase date must be presented.