INT69-2® Diagnose

INT69-2® Diagnose
Application
The motor protector INT69-2 Diagnose is a further development of the
reliable KRIWAN motor protectors. Its supplementary flexible-response
protective functions help to improve the availability and extend the
service life of a refrigeration system.
The INT69-2 Diagnose automatically saves operational and error data
in a non-volatile memory. This data can be retrieved on a PC and
analysed for diagnosis. The full scope of the diagnosis is achieved by
using a KRIWAN-specific AMS sensor.
This motor protector is mainly employed on compressors which are
qualified acc. to IEC/EN 60335.
Functional description
The temperature monitoring of the motor winding is done with two
evaluation processes:
• Static: Switch-off is immediate if the nominal response temperature
of the built-in AMS or PTC sensors is reached.
INT69-2 Diagnose
• Dynamic: If the temperature increases unusually quickly, the motor
is switched off immediately even if the temperature is still far below
the nominal response temperature. This prevents excess tempera-
L1 tures from occurring.
L2 A short circuit at an AMS or PTC input also leads to a switch-off. A short
L3 cycling leads to a reset delay.
N After expiration of the reset delay and elimination of the error or cool-
down, the compressor can be restarted.
PE
INT69-2 Diagnose DP For operation in the specified manner, the supply voltage has to be on
permanently on the INT69-2 Diagnose.
Technical specifications
Supply voltage 115-230V~ 50Hz, 120-240V~
K1 L N 1 2 12 14 11 60 Hz ±10% 3VA
Permitted ambient temperature -30...+70°C
F1 K1 Temperature measuring circuits
M °C - Type 1-2 AMS sensors in series
3 AC alternative 1-9 PTC acc. to
F2 HP
DIN 44081, DIN 44082 in series
- R25,total <1.8kΩ
LP
Motor PTC - Rtrip, static 4.5kΩ ±20%
- Rreset 2.75kΩ ±20%
- Max. length connection line 30m
Short circuit monitoring system
Wiring diagram PTC Typically <30Ω
Switching frequency overstepping 3 switch-offs in 30s
Reset delay
- Motor temperature static 1min ±12s
2.5 53 10 - Motor temperature dynamic 5min ±1min

Product group A
- Switching frequency overstep-
ping 5min ±1min
Reset of reset delay Main reset >5 sec. only possible if
3.5

4.5

there is no error current


33

Relay
- Connection Refer to wiring diagram
Max. 2.5A C300
68 50 - Mechanical service life Approx. 1 million switching cycles
Interface Diagnose port (DP)
Dimensions in mm Protection class acc. to EN 60529 IP00
Connection type Screw type terminal
The mounting, maintenance and operation are to be carried out Housing material PA glass-fibre-reinforced
by an electrician. The valid European and national standards for Mounting Screw mounted
connecting electrical equipment and cooling installations have to Dimensions Refer to dimensions in mm
Edition: 710.00429.1

be observed. Connected sensors and connection lines that Weight Approx. 150g
extend from the terminal box have to feature at least a basic insu- Check base IEC/EN 60335, IEC/EN 60730
lation. EN 61000-6-2, EN 61000-6-3
EN 61010-1
To determine the compressor running times, the INT69-2
Overvoltage category II
Diagnose has to be the last protection unit before the compressor
Pollution level 2
contacter (see wiring diagram). For that, the INT69-2 Diagnose
Approval UL File no. E75899 cURus
and the safety circuit have to be connected to the same phase of
VDE certification no. 40022017
the same supply network.
Order data
INT69-2 Diagnose 22 A 435 S80
Accessories and application
information see www.kriwan.com
Technical changes reserved