Delivery program
Product range Accessories
Contacts
N/O = Normally open 1 N/O
Contact diagram
Contact sequence
Technical data
Auxiliary contacts
Rated impulse withstand voltage Uimp V AC 6000
Ue V AC 500
Ue V DC 250
AC-15
380 - 415 V Ie A 2
440 V 500 V Ie A 1
24 V Ie A 2
60 V Ie A 1
110 V Ie A 0.5
220 V Ie A 0.25
Lifespan S
Fuse A gG/gL 10
Terminal capacities
Solid or flexible conductor, with ferrule mm
2 0,75 - 2,5
AC operated A600
DC operated Q300
General Use
AC V 600
AC A 5
DC V 250
DC A 1
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block
(ecl@ss10.0.1-27-37-13-02 [AKN342013])
Approvals
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
1: Motor-protective circuit-breakers
2: Trip-indicating auxiliary contact
Dimensions