2200 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Compu-Aire System 2200 Microprocessor

Compu-Aire
System 2200
Programmable Controller

COMPU-AIRE, Inc. 8167 Byron Road Whittier, CA 90606


Ph: (562) 945-8971 FAX: (562) 696-0724

2200 MANUAL_ Ver. 4.x 1 10/15/03


Compu-Aire System 2200 Microprocessor

ABOUT THE SYSTEM 2200...................................................................................................................................3


Functions of the buttons in COMPU-AIRE standard application programs: ............................................................4
OPERATING THE SYSTEM 2200 ..........................................................................................................................6
VIEWING SYSTEM STATUS.................................................................................................................................8
SYSTEM CONTROL MENUS.................................................................................................................................8
PASSWORDS ...........................................................................................................................................................8
ENTERING CONTROL SETPOINTS .....................................................................................................................9
SETTING THE REAL TIME CLOCK ...................................................................................................................10
CONTROLLING THE PRINTER...........................................................................................................................10
MONITORING EQUIPMENT RUN HOURS........................................................................................................11
ENABLING SYSTEMS & MANUAL CONTROL ................................................................................................11
SETTING CONTROL BANDS & TYPE OF CONTROL......................................................................................12
CALIBRATING SENSORS....................................................................................................................................13
VIEWING THE ALARM HISTORY .....................................................................................................................13
SETTING THE REMOTE ALARM RELAYS.......................................................................................................15
SETTING USER PASSWORDS.............................................................................................................................15
SETTING UP THE SYSTEM FOR A SUPERVISOR COMPUTER OR MODEM ..............................................15
FACTORY SETUPS & SYSTEM CONFIGURATION .........................................................................................16
ALARMS.................................................................................................................................................................21
TECHNICAL INFORMATION..............................................................................................................................25
SYSTEM 2200 MAIN BOARD ..............................................................................................................................25
MAIN BOARD CONNECTIONS...........................................................................................................................26
Connecting Inputs ....................................................................................................................................................29
DIGITAL INPUTS ..............................................................................................................................................29
ANALOG INPUTS .............................................................................................................................................29
Connecting Outputs .................................................................................................................................................30
DIGITAL OUTPUTS ..........................................................................................................................................30
ANALOG OUTPUTS .........................................................................................................................................30
Mounting Optional Boards ......................................................................................................................................30
REAL TIME CLOCK BOARD...........................................................................................................................30
RS422/485 SERIAL NETWORK BOARD.........................................................................................................30
INSTALLING A NEW PROGRAM EPROM ........................................................................................................31
LISTING OF PROGRAMMABLE PARAMETERS ..................................................................................................32

2200 MANUAL_ Ver. 4.x 2 10/15/03


Compu-Aire System 2200 Microprocessor
ABOUT THE SYSTEM 2200

The System 2200 is a new programmable controller based on a double microprocessor designed
for precise "smart" control of an air handling system. The System 2200 is made up of a
microprocessor-based MAIN BOARD equipped with a set of terminals used to connect the board
to the controlled devices (ie: valves, compressors, fans). The program is contained in an Eprom
and parameters are permanently stored (even in case of power failure) in a special electronic
component called Eeprom. The Main Board can be linked to a supervisory/telemaintenance
system via serial line through the RS422 standard and communication protocol.

System 2200 also includes a microprocessor-based TERMINAL unit complete with display,
keypad and led indicators allowing you to easily set the main control parameters (set-points,
bands, alarm thresholds) and carry out the main working operations (on/off, displaying controlled
variables, printouts). Connection between the terminal unit and main board is necessary only
when programming System 2200's basic parameters.

The basic sequence of operation is:


· start the fan on demand for cooling, heating, humidifying or dehumidifying or operate
continuously
· sequence the compressors on in stages with programmed delays, to meet demand for cooling
· sequence the heaters on in stages with programmed delays, to meet demand for heating
· activate the humidifier as needed when the humidity falls below the setpoint
· activate dehumidification by means of cooling to reduce the humidity level when it rises above
the setpoint. If the temperature falls below the temperature setpoint, heating is brought on at the
same time to maintain temperature.
· monitor the sensors, compressors and heaters for failure. On a sensor failure, the applicable
systems are disabled. On a compressor failure by low or high pressure, the compressor is locked
out and other compressors substituted. On a heater failure the heaters are locked out, but
automatically reset.

In addition to the basic sequence of operation, optional features are available:


· a discharge air temperature sensor to prevent overheating or cooling of the air stream
· an outside air temperature sensor for automatic temperature adjustment or economizer action
· a freecooling temperature sensor for water cooled systems
· hot gas bypass either by solenoid or by modulating electronic valve
· redundant system operation of two or more units with automatic crossover and compensation
· networking to a central command computer, or to an existing building automation system

The System 2200 is truly one of the most powerful and flexible controllers available on HVAC
units today.

2200 MANUAL_ Ver. 4.x 3 10/15/03


Compu-Aire System 2200 Microprocessor
Front panel view of System 2200 controller:
The System 2200 consists of a microprocessor
controller board located in the electrical panel of the
Compu-aire unit, and the front panel mounted
keypad/display microprocessor unit shown at left. In
this manual, “controller” means the microprocessor
board, “keypad” or “display” refers to the panel
mounted unit shown at left.

The keypad/display provides a backlit, supertwist


LCD screen having 4 rows of 20 characters. There
are also three LEDs to indicate Power, On/Off
status, and Alarms (red).

To enter setpoints and other parameters, the System 2200 has 10 buttons arranged on a touchpad.
Six of the buttons are arranged in pairs to permit easy access to the menus or specifric items.

In this manual, individual displays will be referred to as “screens”, areas on each screen where
you may change values will be referred to as “fields”.

Functions of the buttons in COMPU-AIRE standard application programs:

The first set of buttons, labeled MENU, control access to the screens. Pressing the down
button takes you to the next screen in the loop. Pressing the up button takes you to the
previous screen in the loop. On reaching the last screen in the loop, you will roll over to
the beginning of the loop again.

The next set of buttons to the right, labeled SELECT, control access to each line or item
of a screen. Pressing the down button takes you to the next line or field in the currently
displayed screen. Pressing the up button takes you to the previous line or field in the
currently displayed screen. On reaching the last field in the screen, you will roll over to
the first field again.

The next set of buttons to the right, labeled EDIT allow you to modify the value of a field
on the currently displayed screen. Press the up button to increase the value or to toggle it
if it is an on/off type. Press the down button to decrease the value or to toggle it if it is an
on/off type. To lock in a value, press any button EXCEPT the EXIT button. Pressing the
EXIT button returns the value of the field to the starting point, and takes you to the
opening screen in the program.

2200 MANUAL_ Ver. 4.x 4 10/15/03


Compu-Aire System 2200 Microprocessor

The ON/OFF button controls unit operation. Pressing this button toggle the unit operation
on or off. The LED immediately below the button is lit only when the unit is on.

The ALARM button is used to silence the alarm horn and view the alarm screens. When
an alarm sounds, the LED directly under the ALARM button will glow red, and an
audible horn will sound. The first press of the ALARM button silences the alarm. Each
press of the ALARM button then brings up each alarm screen in turn.

The EXIT button is used to exit from a loop of screens and return to the main display
screen of the program. Pressing this button also reverses any change to the current field
you are in.

The HELP button takes you to helpful screens that instruct you on how to operate this
program or on any special features.

The POWER LED will glow amber whenever there is power to the
keypad/display unit. This does not necessarily indicate power to the unit or the
controller board.

All Compu-Aire programs are arranged in a “tree” format, using loops of screens and menus to
access all parts of the program. Example:

2200 MANUAL_ Ver. 4.x 5 10/15/03


Compu-Aire System 2200 Microprocessor
+)))))))))))))))))))),
* ROOM/RETURN AIR *
*Temperature:000.0 F *
*Humidity :000.0%RH*
*Occupied mode *
.))))))))))))))))))))-

+)))))))))))))))))))),
* SYSTEMS STATUS *
*Cooling stages:1234 *
*Heating stages:1234 *
*Dehumidify *
.))))))))))))))))))))-

+)))))))))))))))))))), +)))))))))))))))))))),
*CONTROL SETPOINTS.> * * ROOM SETPOINTS *
*TIME CLOCK SETUP..> * * *
*PRINTER SETUP.....> * *Temperature >000.0 F*
*EQUIP RUN HOURS...> * *Humidity >000.0 %*
.))))))))))))))))))))- .))))))))))))))))))))-

+)))))))))))))))))))), +)))))))))))))))))))),
*SYSTEMS SETUP.....> * *DISCHARGE TEMP LIMIT*
*CONTROL SETUP.....> * * High >000.0 F *
*SENSOR CALIBRATION> * * Low >000.0 F *
*ALARM HISTORY.....> * * Band >000.0 F *
.))))))))))))))))))))- .))))))))))))))))))))-

OPERATING THE SYSTEM 2200


Whenever power is first turned on to the System 2200, the version screen is the first displayed:
U00 COMPU AIRE
HVAC CONTROLLER

V1.0 DATE:00/00/00

This screen shows the version number of the software, and the date it was created. This is
the first screen in the first loop of screens.

Pressing MENU down will take you to the next screen in the loop which is the main screen. This
is where the EXIT button will always take you as well.
U00 ROOM/RETURN AIR
TEMPERATURE: 000.0¯F
HUMIDITY : 000.0%
U MODE

This screen displays the current temperature and humidity. The bottom line shows the
mode of operation whether “Occupied” or “Standby”.

The following screens will be in the main display loop if the sensors that they display are
activated at the factory.
U00 OPTIONAL SENSORS
DISCHARGE : 000.0¯F
COIL TEMP : 000.0¯F

2200 MANUAL_ Ver. 4.x 6 10/15/03


Compu-Aire System 2200 Microprocessor
U00 OPTIONAL SENSORS
OUTSIDE TMP: 000.0¯F
OUTSIDE HUM: 000.0

U00 OPTIONAL SENSORS


WATER IN : 000.0
WATER OUT: 000.0

Pressing the ON/OFF button toggles the mode status and turns the unit on or off.

2200 MANUAL_ Ver. 4.x 7 10/15/03


Compu-Aire System 2200 Microprocessor

VIEWING SYSTEM STATUS


In the main screen loop, there are the following two screens. A quick way to get here is to press
EXIT and then MENU down until these screens display.

U00 SYSTEMS STATUS


Cooling stages:1234 Shows how many stages of cooling are on if any.
Heating stages:1234 Shows how many stages of heating are on if any.
Dehumidify Indicates humidify or dehumidify modes.

U00 7/01/96 12:30 Shows actual day, date and time per the internl clock.
Mode: MON UNOCC Shows clock mode.
Override mode> OFF Toggling this field to ON overrides any night setback.
Override time>060min Enter override time in minutes.

SYSTEM CONTROL MENUS

In the main screen loop, as you continue to press MENU down, you will arrive at three menus
giving you a variety of choices. To select any choice, press SELECT up or down. When the
cursor is at the end of the line showing the area you want, press EDIT up or down and you will
then move to that area in the program.

U00 SETPOINTS.....> Goes to setpoint screens, and alarm setpoint screens.


TIME CLOCK SETUP..> Goes to time clock setup, night/day setback control.
PRINTER SETUP.....> Goes to printer setup, if your System 2200 has this.
EQUIP RUN HOURS...> Goes to screens showing equipment run time hours.

U00 SYSTEMS SETUP.> Goes to On/Off and manual control of systems.


CONTROL SETUP.....> Goes to
SENSOR CALIBRATION> Goes to sensor calibration screens.
ALARM HISTORY.....> Goes to screens showing the history of the alarms.

U00
ALARM RELAY.......> Goes to screens to setup alarm 2 relay.
SUPERVISOR SETUP..> Goes to the supervisor program set up.
FACTORY SETUP.....> Goes to factory setup, control of all functions,
delays, and configurations.

PASSWORDS

Many areas of the program are protected by password. There are three levels of password. Level
1 is for the operator who needs to change setpoints. Level 2 is for maintenance personnel who
need access to other areas. Level 3 is reserved for factory personnel and controls all configuration
setups.

When you try to enter an area protected by password, you see the following screen:
2200 MANUAL_ Ver. 4.x 8 10/15/03
Compu-Aire System 2200 Microprocessor
U00 Use the EDIT up and down buttons to enter the proper
ENTER password. The wrong password will show the response at
PASSWORD> 0000 left. The proper password takes you to the screens you
PRESS MENU DOWN want.

ENTERING CONTROL SETPOINTS

From the first menu, select CONTROL SETPOINTS and press the EDIT up or down button. You
will then see these screens in order (after the password):
U00 ROOM SETPOINTS These are the system control setpoints.

Temperature >068.0 F
Humidity >045.0 %

U00 DISCHARGE LIMIT These are the discharge temperature limit setpoints.
High >120.0 F These are only used when there is a discharge air
Low >045.0 F temperature sensor installed in you unit. These set-
Band >005.0 F points prevent overheating or cooling of the air.

U00 COIL SETPOINTS If your system has a coil temperature sensor, you may
Freeze protection enter the freeze protection setpoints in this screen.
Setpoint >034.0 F
Band >001.0 F

U00 ECONOMIZER If your system has freecooling, enter those setpoints


Water temperature in this screen.
Setpoint >050.0 F
Hysteresis >005.0 F

U00 ECONOMIZER
DISCHARGE TEMP
SETPOINT >000.0¯F
HYSTERESIS >000.0¯F

U00 OA SETPOINTS If your system is operating with economizer control,


AIR ECONOMIZER enter the economizer setpoints and hysteresis here.
Setpoint >055.0 F
Hysteresis >004.0 F

U00 ROOM ALARMS In this screen enter the room temperature and humidity
TEMP HUM alarm setpoints. If room temperature goes above or
HIGH> 000.0¯F 000.0% below either setpoint, an alarm sounds and the
LOW > 000.0¯F 000.0% appropriate system (cooling or heating) is shut down.

2200 MANUAL_ Ver. 4.x 9 10/15/03


Compu-Aire System 2200 Microprocessor
SETTING THE REAL TIME CLOCK

From the first menu, select TIME CLOCK SETUP and press the EDIT up or down button. If
your System 2200 has a real time clock board installed, you may enter night/day setback modes,
and the alarms will also be date/time stamped as to when they occur.

U00 REAL TIME CLOCK


The first screen in the loop allows you to set the
SET> 00:00 00/00/00 real time clock, which is battery backed for 10 years.

U00
ENABLE NIGHT
SETBACK>OFF Set to ON if you wish to use night setback mode.
NIGHT MIN ON >000S Enter the minimum on time for night setback mode.
If OFF, the system will run continuously.

U00 NIGHT SETBACK


TEMP>OFF HUM>OFF Set to ON if you wish night setback to operate
HIGH>000.0¯F >000.0% Enter the high and low activation points. When
LOW >000.0¯F >000.0% the room is within these setpoints, the unit is off.

NOTE: always set your alarm setpoints wider than your night setback setpoints
or you will have alarms to deal with every morning.

U00 SETBACK MON>NO In this screen you select the days of the week when
TUE>NO WED>NO night setback is to be in effect. Any day with NO
THU>NO FRI>NO selected will run continuously for the full 24 hours
SAT>YES SUN>YES until the next night setback selected day.

U00 OCC MON>01:30 Enter occupied mode start times for each day of the
TUE>13:00 WED>00:00 week (international time). Example, mode starts on
THU>00:00 FRI>00:00 Monday at 1:30 a.m. On Tuesday it starts at 1:00 p.m.
SAT>00:00 SUN>00:00 and on Wednsday through Sunday it starts at midnight.

U00 UNOCC MON>14:00 Enter the unoccupied mode start times.


TUE>00:00 WED>00:00
THU>00:00 FRI>00:00 Example: Monday occupied mode starts at 1:30 a.m. and
SAT>00:00 SUN>00:00 the unoccupied mode starts at 2:00 p.m.

CONTROLLING THE PRINTER

If your System 2200 has the optional RS232 printer serial port, you may connect a standard serial
printer to this port for data printouts. The printer must be configured for 1200 Baud, 8 bits, No
parity, 2 stop bits. See the technical manual for more detail.

From the menus, select PRINTER SETUP and press the EDIT up or down button. You will then
see the following screen:

2200 MANUAL_ Ver. 4.x 10 10/15/03


Compu-Aire System 2200 Microprocessor
U00 PRINTER >OFF Set to ON to activate timed cycle printing.
PRINT CYCLE >00MIN Enter the minutes between each printout.
MANUAL PRINT >OFF Set to ON for force one manual printout.
PRINT ON ALARM>OFF Set to ON if you want the printer to print all data
every time there is an alarm.

MONITORING EQUIPMENT RUN HOURS

From the menus, select EQUIP RUN HOURS and press the EDIT up or down button. You will
then see the following screen:
U00 FAN > 00000
RUN HUMIDIFY > 00000
HRS In these screens are displayed the actual run hours
for each item in the system.

U00 COMP 1 > 00000


RUN COMP 2 > 00000
HRS COMP 3 > 00000
COMP 4 > 00000

U00 HEAT 1 > 00000


RUN HEAT 2 > 00000
HRS HEAT 3 > 00000
HEAT 4 > 00000

ENABLING SYSTEMS & MANUAL CONTROL

From the menus, select SYSTEMS SETUP and press the EDIT up or down button. You will then
see the following screens:

In these screens you may set any component of the


U00 COMP 1> ON System 2200 to manual ON or OFF or AUTO modes.
COMP 2> OFF When set to ON, the component runs continuously. OFF
UNL 1> AUTO means the component is off permanently. AUTO allows
UNL 2> AUTO the component to run as needed automatically.

WARNING: It is not wise to leave any component in the


U00 HEAT 1> AUTO ON mode for longer than a manual test.
HEAT 2> AUTO
HEAT 3> AUTO
HEAT 4> AUTO

2200 MANUAL_ Ver. 4.x 11 10/15/03


Compu-Aire System 2200 Microprocessor

U00
HUMIDIFIER > AUTO If a modulating humidifier is present, you may enter a
DEHUMIDIFY >OFF value for its output to force a manual test.

U00 ANALOG OUTPUTS If an analog output is select in configuration,


A1: OFF >000% then manual control of the device will appear.
A2: OFF >000% Enter the % output desired for manual testing.

SETTING CONTROL BANDS & TYPE OF CONTROL

From the menus, select CONTROL SETUP and press the EDIT up or down button. You will
then see the following screens:

Enter control type. When P+I is chosen, you are also


U00 ROOM CONTROL asked for the integration time in seconds. Enter the
TYPE INT BAND bandwidths for control. The band is split in half so
TEMP>P 000 00.0¯F that for example, at 70F, with a band of 5,control is
HUM >P 000 00.0% within the range of 67.5 and 72.5. The humidity band
should always be twice the band set for temperature.

Setpoint = 70.0 degrees F


Band = 5.0 degrees F

Band
100%

Cool

Demand 0%

Heat

100%
67.5 70.0 72.5
Setpoint

Relationship between setpoint and band

2200 MANUAL_ Ver. 4.x 12 10/15/03


Compu-Aire System 2200 Microprocessor
CALIBRATING SENSORS

From the menus, select SENSOR CALIBRATION and press the EDIT up or down button. You
will then see the following screens:

These screens allow you to enter an offset to any


U00 SENSOR CAL sensor reading, allowing you to calibrate the sensors
ROOM TEMP > 000.0 F from the controller.
ROOM HUMID> 000.0 % For example, the discharge air temperature sensor has
DISCH TEMP>-002.0 F an offset of -2F. If the incoming reading is 60, it
will display and control as 58.

U00 SENSOR CAL

OA TEMPERA> 000.0 F
OA HUMIDIT> 000.0 %

U00 SENSOR CAL


COIL TEMP > 000.0 F
WATER IN > 000.0 F
WATER OUT > 000.0 F

In the user sensors, calibration is more involved.


U00 X1> 0.0 Vdc You must range the sensor by selecting its input
B7 CAL X2> 0.0 Vdc voltage range x1 to x2 (0-1Vdc or .2-1Vdc for
Y1> 000.0 4-20mA) and then selecting the display range y1 to y2.
Y2> 000.0 Usually the factory will enter these values.

U00 X1> 0.0 Vdc


B8 CAL X2> 0.0 Vdc
Y1> 000.0
Y2> 000.0

VIEWING THE ALARM HISTORY

From the menus, select ALARM HISTORY and press the EDIT up or down button. You will
then see the following screens:

U00 24 HOUR MIN/MAX This screen displays the minimum and maximum
MIN MAX temperature and humidity of the system.
TEMP: 000.0¯F 000.0 The values will be reset to actual room values at
HUM : 000.0% 000.0% 1:01 am everyday, if a clock board is installed.

U00 ALARM LIST 00 The alarm list holds the last ten alarms. The time
and date is recorded each time an alarm sounds. Use
DATE: 00/00 the DOWN menu key to display the active alarms. Use
TIME: 00:00 the UP/DOWN edit key to view the ten alarms.

U00 ALARM LIST 00 One or more of the following screens will be visiable
2200 MANUAL_ Ver. 4.x 13 10/15/03
Compu-Aire System 2200 Microprocessor
HIGH TEMP for each of the ten alarm occurances.
HIGH HUM
AIRFLOW LOSS

U00 ALARM LIST 00


CONDENSATE AL
SMOKE AL
FILTER AL

U00 ALARM LIST 00


C1 LO PRES
C2 LO PRES

U00 ALARM LIST 00


HI-LIMIT HEAT
WATER LOSS
SENSOR FAILURE

U00 ALARM LIST 00


STAND-BY PUMP ON
DISCHARGE COOL AL
DISCHARGE HEAT AL

U00 ALARM LIST 00


FAN OVER LOAD
C1 SHORT CYCLE
C2 SHORT CYCLE

U00 ALARM LIST 00


C1 PUMP DOWN FAILED
C2 PUMP DOWN FAILED

2200 MANUAL_ Ver. 4.x 14 10/15/03


Compu-Aire System 2200 Microprocessor

SETTING THE REMOTE ALARM RELAYS

The System 2200 has two relays that may be assigned as remote alarm indicators. The first relay
is activated on any alarm that also sounds the horn. To control the second alarm relay, from the
menus, select REMOTE ALARM RELAY and press the EDIT up or down button. You will then
see the following screens:

U00 ALARM RELAY 2


TEMP >OFF AIRFL>OFF To activate remote alarm relay #2, set to ON.
HUM >OFF SMOKE>OFF
COMPS>OFF EPROM>OFF

U00 ALARM RELAY 2


TEMP >OFF AIRFL>OFF Set each alarm to ON which you want to activate alarm
HUM >OFF SMOKE>OFF relay #2 when this alarm occurs.
COMPS>OFF EPROM>OFF

SETTING USER PASSWORDS

The System 2200 also allows you to enter two levels of passwords to prevent unauthorized
tampering with setpoints and parameters. To reach this control screen, contract factory.

CHANGE PASSWORD
LEVEL 1>0000 Enter the various level passwords and don’t forget
LEVEL 2>0000 them.

NOTE: Level 3 password is set at the factory and is generally not handed out.

SETTING UP THE SYSTEM FOR A SUPERVISOR COMPUTER OR MODEM

If your System 2200 is to be connected to a computer or modem for remote control and
supervision, you need to identify each unit on the network by assigning a unit identification
number. To reach this control screen, select SUPERVISOR SETUP and press the EDIT up or
down button.

U00 COMMUNICATIONS

UNIT IDENT> 01 Enter this unit’s identification number (1-32)


BAUD RATE > 1200 Enter the communications BAUD rate (1200 - 9600)
NOTE: All units on one network must have the same
BAUD rates.

2200 MANUAL_ Ver. 4.x 15 10/15/03


Compu-Aire System 2200 Microprocessor
FACTORY SETUPS & SYSTEM CONFIGURATION

The following screens are reserved for factory personnel and are only accessible under the Level
3 password. They are accessed by selecting FACTORY SETUP from menus and pressing EDIT
up or down to select.

The following screens tell System 2200 which sensors and devices are connected to the system.

U00 INSTALLED SENSOR Activate which sensors are connected to the system.
ROOM TEMPERATURE>NO Turning off sensors deactivates their control loops
ROOM HUMIDITY >NO and alarms.
DISCHARGE TEMP >NO

U00 INSTALLED SENSOR


OUTSIDE AIR TEMP>NO
OUTSIDE AIR HUM >NO

U00 INSTALLED SENSOR


ANALOG B3 >NO B3 can be selected as “coil” or “water in”.
ANALOG B7 >NO B7 can be selected as “user 1” or “water in”.
ANALOG B8 >NO B8 can be selected as “user 2” or “water out”.

Set which digital input devices are connected to the


U00 DIGITAL INPUTS system. Set to YES if the device is present.
AIRFL>NO FILTER>NO
SMOKE>NO DRAIN >NO
HI HT>NO WATER >NO

U00 DIGITAL INPUTS


C1 LP>NO C1 HP>NO
C2 LP>NO C2 HP>NO Digital input 11 can be selected as "PUMP" or "FAN".
DI 11>OFF DI 12>OFF Digital input 12 can be selected as "OVR" or "FAN"

U00 DIGITAL OUTPUTS


DO 5> HEATER 4

AIR FLOW>OPEN CLOSE


SMOKE >OPEN CLOSE
HI HEAT >OPEN CLOSE
FILTER >OPEN CLOSE

2200 MANUAL_ Ver. 4.x 16 10/15/03


Compu-Aire System 2200 Microprocessor
CONDENS >OPEN CLOSE
WATER FL>OPEN CLOSE
C1 LOW P>OPEN CLOSE
C1 HI P >OPEN CLOSE

C2 LOW P>OPEN CLOSE


C2 HI P >OPEN CLOSE
DIN 11 >OPEN CLOSE
DIN 12 >OPEN CLOSE

U00 AO1> OFF DIR Output 1 can be "HEAT","COOL","ECON","HUM" or "ALARM 2"


Y1>00.0 Y2>00.0 Vdc The output can be direct or reverse acting and scaled.
AO2> OFF DIR Output 2 can be "HEAT","COOL","ECON","HUM" or "ALARM 2"
Y1>00.0 Y2>00.0 Vdc

U00 START DELAY>000S Enter the system delay on initial startup.


FAN OPERATION >AUTO Set fan to AUTO (demand) or CONTinous operation.
FAN MINIMUM ON >030S Enter the minimum ON time for the fan.
FAN MINIMUM OFF>030S Enter the minimum OFF time for the fan.

U00 CL RAMP ST> 010 Enter the start and end points for the control ramps.
COOL RAMP END > 100 The ramp operates within the band that has been set.
HEAT RAMP START> 010 Negative numbers may be entered to skew the ramp in
HEAT RAMP END > 100 one direction or another.

U00 HUM RAMP ST> 010


HUMRAMP END > 100
DEHUM RAMP STRT> 010
DEHUM RAMP END > 100

Setpoint = 70.0 degrees F Cooling Start = 10% Heat Start = 10%


Band = 5.0 degrees F Cooling End = 90% Heat End = 90%

Band
100%

Cool Cool ramp

Demand 0%
+/- 10% dead band
Heat Heat ramp

100%
67.5 70.0 72.5
Setpoint

Relationship between setpoint,band, cooling and heating start and end

2200 MANUAL_ Ver. 4.x 17 10/15/03


Compu-Aire System 2200 Microprocessor

U00 DISCHARGE ALARMS


COOL> 00.0¯F >000sec
HEAT> 00.0¯F >000sec

U00 COOLING> COMPS Select whether compressors or floating point valve.


COMPS>0 UNLOADERS>0 Enter the number of compressors in the system.
VALVE TIME > 000 Enter the number of unloaders per compressor.
PUMP DOWN > OFF Enter the floating point valve stroke time if selected.

U00 COOLING STAGES Enter the compressor start points and hysteresis.
COOLING HYSTER >009 For example: compressor 1 will start at 19% of the ramp
COOLING 1 START >010 and shut off when the demand drops to 1% of the ramp.
COOLING 2 START >030 Compressor 2 starts at 39% an shuts off at 21%

Setpoint = 70.0 degrees F Cooling Start = 10% Compressor St = 50%


Band = 5.0 degrees F Cooling End = 90% Compressor Hys = 10%

½ Band

100%

60%
Compressor ON (start + hys)
Cooling 50%
40% Compressor Start
Ramp
Compressor OFF (start - hys)

0%
70.0 72.5
Setpoint

Relationship between cooling ramp and compressor start and hys.

U00 COOLING STAGES


C1 UNL STOP >000%
C2 UNL STOP >000%
SHORT CYCLE >000/HR

U00 COMPRESSOR SETUP


LP DEL>000 TBC>000 Enter the low pressure alarm delay on compressor start.
MIN ON>000 OFF>000 Enter the minimum ON time for any compressor.
ROTATE>NO ECON>OFF Enter the minimum OFF time for any compressor.

U00 HEATING >HEATERS Select heaters or heating valve for heating method.
NUMBER >2 Enter the number of heaters in the system

2200 MANUAL_ Ver. 4.x 18 10/15/03


Compu-Aire System 2200 Microprocessor
VALVE TIME>120S Enter the heating valve stroke time if selected.

U00 HEATER SETUP


STAGE RP>OFF TYPE>2S Set to ON if you have one heater with modulation and
STAGE DELAY> 000 sec other heaters ON/OFF. Enter 2 stage or 3 stage if there
MIN ON> 000 OFF>000 are two unequal size heaters. Enter the delay between
heater stages.

Two stage heating, for systems with two stages of equal size
On
Ht 1

Off
On
Ht 2
Off
Three stage heating, for systems with second stage larger then first stage
On
Ht 1
Off
On
Ht 2
Off
Ht 1 ON Ht 2 ON 100%
Heating demand
Difference between two stage and three stage heating

U00 HEATING STAGES


HEATING HYS >000% Enter the heater start points and hysteresis.
ST 1>000% ST 2>000%
ST 3>000% ST 4>000%

U00 HUMIDIFIER
HUMIDIFIER START>000
HUMIDIFIER HYS >000 Enter the heater start points and hysteresis.
DEHUMIDIFY COMP2>OFF

2200 MANUAL_ Ver. 4.x 19 10/15/03


Compu-Aire System 2200 Microprocessor
Single SCR
100%
SCR
0%
Single SCR with two stages of ON/OFF
100%
SCR
0%

On
Ht 1
Off
On
Ht 2
Off
Ht 1 ON Ht 2 ON 100%
Heating demand
Difference between single SCR and SCR with two ON/OFF stages

If your unit has an infra-red humidifier, you may set


U00 HUMIDIFIER DRAIN the unit to automatically drain the reservoir.
AUTO DRAIN >OFF Set to ON for auto draining.
DRAIN CYCLE>0024 HRS Enter drain cycle time.
DRAIN TIME >0060 SEC Enter drain duration.

U00
DISPLAY>FAHRENHEIT Set to FAHRENHEIT or CELCIUS. If you change this
SHUT DOWN FAN ON setting, you must then reenter all setpoints and bands
AIRFLOW LOSS> NO in the proper unit. Set to YES if you want the fan to
shut down on an air flow loss alarm.

U00 ASSIST COOL >OFF


ASSIST HEAT >OFF
ASSIST HUM >OFF
ASSIST DEH >OFF

UNIT U1>OFF U9 >OFF


NET U3>OFF U11>OFF
WORK U5>OFF U13>OFF
ROT. U7>OFF U15>OFF

SYSTEM ROTATION
TIME >000day
STEP ROTATION>OFF
INITIALIZER >OFF

2200 MANUAL_ Ver. 4.x 20 10/15/03


Compu-Aire System 2200 Microprocessor

ALARMS
When an alarm occurs in the System 2200, the Alarm LED will glow red, and a horn will sound.
After a few seconds, the LCD display will begin scrolling through the alarms as well as the
normal displays. Pressing the ALARM button will first silence the horn, and then take you to the
alarm screens loop.

Pressing the ALARM button again will scroll you through the alarm screens that are active and,
after leaving the alarm screens loop, will clear the alarm and reset it. If alarms still exist, the
Alarm LED will relight and the horn will sound again.
U00 * ALARM *

EEPROM FAILURE Parameter memory has failed. Since your setpoints have
been lost it is best to shut down the unit.

U00 * ALARM *
00:00 00/00 Time and date alarm occurred.
AIRFLOW LOSS
SYSTEM OFF System turns off only if selected to do so in the
factory setup section.

U00 * ALARM *
00:00 00/00
HEATER OVERHEAT
HEATER OFF

U00 * ALARM *
00:00 00/00
SMOKE ALARM Smoke alarm always shuts down the system.
SYSTEM OFF

U00 * ALARM * With compressor alarms, once they clear, the compressor
00:00 00/00 will come back on line automatically.
C1 LOW PRESSURE
COMPRESSOR OFF

U00 * ALARM *
00:00 00/00
C1 HIGH PRESSURE NOTE: There is a manual high pressure reset on the
COMPRESSOR OFF refrigerant lines.

U00 * ALARM *
00:00 00/00
C2 LOW PRESSURE
COMPRESSOR OFF

2200 MANUAL_ Ver. 4.x 21 10/15/03


Compu-Aire System 2200 Microprocessor
U00 * ALARM *
00:00 00/00
C2 HIGH PRESSURE
COMPRESSOR OFF

U00 * ALARM *
00:00 00/00
COMPRESSOR 1
SHORT CYCLE
U00 * ALARM *
00:00 00/00
COMPRESSOR 2
SHORT CYCLE

U00 * ALARM *
00:00 00/00
CONDENSATE OVERFLOW
CHECK DRAIN

U00 * ALARM *
00:00 00/00
HIGH TEMPERATURE
ROOM

U00 * ALARM *
00:00 00/00
LOW TEMPERATURE
ROOM

U00 * ALARM *
00:00 00/00
HIGH HUMIDITY
ROOM

U00 * ALARM *
00:00 00/00
LOW HUMIDITY
ROOM

U00 * ALARM * If a sensor fails, it is indicated as FAIL, otherwise


ROOM TEMPERATUR:FAIL OK indicates the sensor is fine.
ROOM HUMIDITY :OK
OA TEMPERATURE :OK

2200 MANUAL_ Ver. 4.x 22 10/15/03


Compu-Aire System 2200 Microprocessor
U00 * ALARM *
FREECOOL TEMPER:OK
DISCH TEMPERATU:OK
ROOM PRESSURE :OK

U00 * ALARM *
00:00 00/00
FILTER DIRTY

U00 * ALARM *
00:00 00/00
DISCHARGE AIR
HEATING ALARM

U00 * ALARM *
00:00 00/00
DISCHARGE AIR
COOLING ALARM

U00 * ALARM *
00:00 00/00
FAN MOTOR OVERLOAD

U00 * ALARM *
00:00 00/00 This alarm only operates on water cooled units.
WATER FLOW LOSS
COMPRESSORS OFF

U00 * ALARM *
00:00 00/00
COMPRESSOR 1
PUMP DOWN FAILED

U00 * ALARM *
00:00 00/00
COMPRESSOR 2
PUMP DOWN FAILED

U00 * ALARM *
WARNING SYSTEM WILL
SHUT DOWN IN 48HRS
CONTACT FACTORY

2200 MANUAL_ Ver. 4.x 23 10/15/03


Compu-Aire System 2200 Microprocessor
U00 * ALARM *
WARNING SYSTEM
HAS BEEN SHUT DOWN
CONTACT FACTORY

U00 * ALARM *
00:00 00/00
MAIN PUMP FAILURE
STAND BY PUMP ON

U00 * ALARM *
NO MORE ALARMS Last alarm screen.

2200 MANUAL_ Ver. 4.x 24 10/15/03


Compu-Aire System 2200 Microprocessor

TECHNICAL INFORMATION

SYSTEM 2200 MAIN BOARD

G
1 G0
RS422 4
EPROM
6

B8

J1 +24
B7
2

J15 J14 B6
3 AVSS
B5
B4 5
1 AVSS
VG0 J2
B3
VG1
J20 B2
Y1
AVSS
Y0
1 B1
ID11R 1
IDCM2
ID10
ID11 ID9
J21 J3
ID8
ID12R
ID7

1 ID6
ID12
IDCM1
NO11 1
ID5
C11
R11 ID4
NC11 J4 ID3
ID2
NO10
1 ID1
C10 J22
NC10
R10 R1 C1
NO1

NO9
C9
R9 R2
J5
C2
NC9 1 NO2

NO8 1 C3
C8
R8 R3 NO3

NO7 C4
J24 R7 R4 J6
NO4
C7

NO6
R6 R5 C5
C6 NO5

NO13 R13 R12 C12


C13 1 NO12

The System 2200 main board is the core of the unit and will operate stand-alone without the need
for the terminal unit. The main board is where all sensors and controlled devices are connected.
The main parts are:

1. 24 Vac power input connection


2. RJ-11 phone cord (6 wire) connection to terminal unit and also to pLAN network
3. Optional real time clock plug-in board
4. Optional RS422/485 serial plug-in board for network communications.
5. Jumpers to select 0-1 Vdc or 0-20 mADC active sensor inputs for inputs 5 through 8.
6. Program and BIOS Eprom

Additionally there are 13 - 10 Amp relays to control on/off devices, and two analog outputs (0-10
Vdc). Relays R12 and R13 are strapped to analog outputs 1 & 2 respectively.
2200 MANUAL_ Ver. 4.x 25 10/15/03
Compu-Aire System 2200 Microprocessor
MAIN BOARD CONNECTIONS

Connector Signals Description Software Use


J17 - 1 G Power supply +24 Vac, 50/60 Hz, 15 VA

J17 - 2 G0 Power supply reference 0Vac

J19 Terminal 6-wire RJ11 telephone connection for


terminal and PlAN network
J20 - 1 VG0 Power supply to optoinsulated analog
output 0 Vac
J20 - 2 VG1 Power supply to optoinsulated analog
output 24 Vac
J20 - 3 Y0 Analog output 1 (0-10 Vdc) Heat OR Cool OR humidfier OR
Economizer OR remote alarm #2
J20 - 4 Y1 Analog output 2 (0-10 Vdc) Heat OR Cool OR humidfier OR
Economizer OR remote alarm #2
J21 -1 ID11R Common digital input 11

J21 - 2 No connection

J21 - 3 ID11 Digital input 11 (12 to 250 Vac/dc) Stand-by pump on alarm OR Fan overload

J21 - 4 No connection

J21 - 5 ID12R Common digital input 12

J21 - 6 No connection

J21 - 7 ID12 Digital input 12 (12 to 250 Vac/dc) Manual override switch OR Fan overload

J22 - 1 NO-R11 Normally open contact relay no.11 Remote alarm 1

J22 - 2 C-R11 Common relay no.11

J22 - 3 NC-R11 Normally closed contact relay no.11

J22 - 4 No connection

J22 - 5 NO-R10 Normally open contact relay no.10 Compressor 2 unloader

J22 - 6 C10 Common relay no.10

J22 - 7 NC-R10 Normally closed contact relay no.10

J22 - 8 No connection

J22 - 9 NO-R9 Normally open contact relay no.9 Compressor 1 unloader

J22 - 10 C9 Common relay no.9

J22 - 11 NC-R9 Normally closed contact relay no.9

J24 - 1 NO-R8 Normally open contact relay no.8 Compressor 2

J24 - 2 C8 Common relay no.8

2200 MANUAL_ Ver. 4.x 26 10/15/03


Compu-Aire System 2200 Microprocessor
Connector Signals Description Software Use
J24 - 3 No connection

J24 - 4 NO-R7 Normally open contact relay no.7 Compressor 1

J24 - 5 C7 Common relay no.7

J24 - 6 No connection

J24 - 7 NO-R6 Normally open contact relay no.6 Humidifier

J24 - 8 C6 Common relay no.6

J24 - 9 No connection

J24 - 10 NO-R13 Normally open contact relay no.13 Same functions as analog output 2
J24 - 11 C13 Common relay no.13

J6 - 1 NO-R12 Normally open contact relay no.12 Same functions as analog output 1
J6 - 2 C12 Common relay 12

J6 - 3 No connection

J6 - 4 NO-R5 Normally open contact relay no.5 Heater 4 or remote alarm relay 2

J6 - 5 C5 Common relay no.5

J6 - 6 No connection

J6 - 7 NO-R4 Normally open contact relay no.4 Heater 3

J6 - 8 C4 Common relay no.4

J6 - 9 No connection

J6 - 10 NO-R3 Normally open contact relay no.3 Heater 2

J6 - 11 C3 Common relay no.3

J5 - 1 NO-R2 Normally open contact relay no.2 Heater 1

J5 - 2 C2 Common relay no.2

J5 - 3 No connection

J5 - 4 NO-R1 Normally open contact relay no.1 Fan

J5 - 5 C1 Common relay no.1

J4 - 1 ID1 Digital Input no.1 (12 to 24 Vac/dc) Airflow loss alarm

J4 - 2 ID2 Digital Input no.2 (12 to 24 Vac/dc) Smoke detector alarm

J4 - 3 ID3 Digital Input no.3 (12 to 24 Vac/dc) Heater overheat alarm

J4 - 4 ID4 Digital Input no.4 (12 to 24 Vac/dc) Dirty filter alarm

2200 MANUAL_ Ver. 4.x 27 10/15/03


Compu-Aire System 2200 Microprocessor
Connector Signals Description Software Use
J4 - 5 ID5 Digital Input no.5 (12 to 24 Vac/dc) Condensate drain alarm

J4 - 6 IDCM1 Common digital inputs ID1-ID5

J3 - 1 ID6 Digital input no.6 (12 to 24 Vac/dc) Water flow alarm

J3 - 2 ID7 Digital input no.7 (12 to 24 Vac/dc) Compressor 1 low pressure alarm

J3 - 3 ID8 Digital input no.8 (12 to 24 Vac/dc) Compressor 1 high pressure alarm

J3 - 4 ID9 Digital input no.9 (12 to 24 Vac/dc) Compressor 2 low pressure alarm

J3 - 5 ID10 Digital input no.10 (12 to 24 Vac/dc) Compressor 2 high pressure alarm

J3 - 6 IDCM2 Common digital inputs ID6-ID10

J2 - 1 B1 Analog input no.1 (NTC) Room or return air temperature

J2 - 2 AVSS Common analog inputs

J2 - 3 B2 Analog input no.2 (NTC) Discharge air temperature

J2 - 4 B3 Analog input no.3 (NTC) Coil temperature OR Water In temperature

J2 - 5 AVSS Common analog inputs

J2 - 6 B4 Analog input no 4 (NTC) Outside air temperature

J2 - 7 B5 Analog input no 5 (0-1 Vdc or 0-20 Room or return air humidity


mADC)
J2 - 8 AVSS Common analog inputs

J2 - 9 B6 Analog input no.6 (0-1 Vdc or 0-20 Outside air humidity


mADC)
J1 - 1 B7 Analog input no.7 (0-1 Vdc or 0-20 Customer generic sensor input 1 OR Water
mADC) In temperature
J1 - 2 +24 Power supply to external active sensors 24
Vdc (max. 80 mA)
J1 - 3 B8 Analog input no.8 (0-1 Vdc or 0-20 Customer generic sensor input 2 OR Water
mADC) Out temperature

2200 MANUAL_ Ver. 4.x 28 10/15/03


Compu-Aire System 2200 Microprocessor

Connecting Inputs

DIGITAL INPUTS

The digital inputs are designed


to work with 24 Vac or 24
Vdc. However, when using dc
voltage input, the common
must come into the actual
digital input port, and must
also be the same as the
connection to the G0 terminal.

ANALOG INPUTS

There are eight possible analog inputs. B1 through B4 are reserved as resistance type NTC
temperature sensor inputs. The NTC temperature sensors are connected as follows. There is no
polarity to the sensors.
AVSS
Bn

B5 through B8 are for active sensor inputs and may be either 0-1 Vdc or 0-20
mADC, jumper selectable through jumpers J14 and J15. The figure to the right
shows the jumper position for 4-20 mADC input.

Terminals B5 through B8 are the signal inputs (+), and terminal AVSS is the
signal ground, which is also referenced to G0 or the grounded side of the power 3 2 1
transformer.

2200 MANUAL_ Ver. 4.x 29 10/15/03


Compu-Aire System 2200 Microprocessor
Connecting Outputs

DIGITAL OUTPUTS

The 13 relay outputs are each capable of


handling up to 10 Amps at 250 Vac. To
power a device connect one side of the power supply to the device, and the other side must then
be connected through the relay on the control board as shown.

ANALOG OUTPUTS

The analog outputs are 0-10 Vdc


modulating. The analog output
circuit must be powered by 24
Vac, which may be the same
power as for the control board
itself.

Mounting Optional Boards

REAL TIME CLOCK BOARD

The real time clock board is plugged into the #3 connector in the
center of the control board. This board is necessary if date/time
operations are to be performed. The clock board is powered by a 10
year Lithium battery. CAUTION: NEVER plug-in or remove the real
time clock board when the control board is powered.

RS422/485 SERIAL NETWORK BOARD

The RS422/485 serial board is used to connect the Supervisor system


to a modem or computer. This board is plugged into the #4 connector
on the edge of the control board. CAUTION: NEVER plug-in or
remove the RS422/485 serial board when the control board is
powered.

2200 MANUAL_ Ver. 4.x 30 10/15/03


Compu-Aire System 2200 Microprocessor

INSTALLING A NEW PROGRAM EPROM

Installed on the control board is a plug-in EPROM chip that contains the program and BIOS
operating system. If your system ever requires software upgrades or modifications, Compu-Aire
will provide you with a new EPROM.

To replace the existing EPROM with the new one, follow these steps:

1. Go through the screens and copy down all the current field
settings.

2. Turn off power to the control board (the red LED in the center of the board will go out).

3. Gently pry out the existing chip with a small screwdriver, being careful not to damage the
control board or the chip.

4. Insert the new chip into the socket being


careful not to bend any of the pins, and make
sure you align the notch in the chip with
either the notch in the socket, or the white
arrow indicator as shown at left.

5. Power on the control board, and wait. The


main display screen will appear and the
words “WAIT - RESETTING” will appear
on the top line. When the program has reset,
another screen will appear instructing you to
power off the unit again and then repower it.
This resets and clears all memory and
returns things to factory default settings.

6. Reenter your previously-recorded field settings.

2200 MANUAL_ Ver. 4.x 31 10/15/03


Compu-Aire System 2200 Microprocessor

LISTING OF PROGRAMMABLE PARAMETERS

Parameter/Description Default Setting Lower/Upper Limits Unit of Measure


Room temperature set point 72 50/90 °F or °C selectable

Room temperature band 5 0/99 %

Room humidity set point 50 35/85 %RH

Room humidity band 10 0/99 %

Room hi/lo temperature alarm 80/60 50/120 °F or °C selectable

Room hi/lo humidity alarm 65/35 0/100 %RH

Enable night setback OFF On/Off

Night minimum on 300 0-999 seconds

Night setback hi/lo temp 90/55 50/120 °F or °C selectable

Night setback hi/lo humidity 65/35 0/100 %RH

Occupied/unoccupied times 6/18:00 0/24:00/59 Hours/minutes

Temperature control type Proportional Prop/Prop + Integral

Humidity control Proportional Prop/Prop + Integral

Supervisor unit ident 1 1/32

Supervisor baud rate 1200 300/9600 Baud

2200 MANUAL_ Ver. 4.x 32 10/15/03

You might also like