0% found this document useful (0 votes)
71 views22 pages

Kollmorgen Aco5000

The document provides technical information and instructions for the ACO5000 high frequency inverter. It includes product descriptions, specifications, mounting instructions, wiring diagrams, safety procedures and other operational details.

Uploaded by

zyr23
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views22 pages

Kollmorgen Aco5000

The document provides technical information and instructions for the ACO5000 high frequency inverter. It includes product descriptions, specifications, mounting instructions, wiring diagrams, safety procedures and other operational details.

Uploaded by

zyr23
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

www.DanaherMotion.

com

High frequency inverter


ACO5000 by ACOMEL

USER MANUAL
DANAHER MOTION S.A. La Pierreire 2, CH-1029 Villars-Ste-Croix
Telephone +41 21 631 33 33, Telefax +41 21 636 05 09
E-mail: [email protected]
www.DanaherMotion.com

28-01-19 S610-GB-0825
Table of content
Safety instructions ..................................................................................................................................... 3
Information on the Operating Manual....................................................................................................... 3
The Basic Safety Rules .............................................................................................................................. 3
Programming of the drive .......................................................................................................................... 4
Product description .................................................................................................................................... 5
General technical data ............................................................................................................................... 6
Examples of product configuration and weight ...................................................................................... 6
Mounting and installation .......................................................................................................................... 7
Mechanical dimensions ............................................................................................................................. 7
Description and connection ...................................................................................................................... 8
Power terminals .......................................................................................................................................... 8
How to unlock the power terminals .......................................................................................................... 9
Power terminal coding ............................................................................................................................... 9
Front panel description .............................................................................................................................. 9
Front panel description ............................................................................................................................ 10
Description of the control terminals X1 ................................................................................................. 10
Connecting and wiring instructions ....................................................................................................... 12
The wiring diagram ................................................................................................................................... 12
EMC Requirements ................................................................................................................................... 12
Connecting the shielding ......................................................................................................................... 13
Intended use of operation ........................................................................................................................ 13
The start options and the wiring diagram to use .................................................................................. 14
No SAFE INTERLOCK, start by permanent contact .............................................................................. 14
No SAFE INTERLOCK, start / stop by impulse contacts ...................................................................... 14
THE SAFE INTERLOCK PROCEDURE .................................................................................................... 15
Power up procedure ................................................................................................................................. 15
Procedure to make a START from the safe interlock mode ................................................................. 15
Procedure to return to the safe interlock mode .................................................................................... 15
Timing for the safe interlock procedure with permanent signals for the START and STOP ............ 16
SAFE INTERLOCK implemented, start by permanent contact ............................................................ 16
Timing for the safe interlock procedure with impulse signals for the START and the STOP .......... 17
SAFE INTERLOCK implemented, start / stop by impulse contacts .................................................... 17
Instruction to the product integrator ...................................................................................................... 18
Connecting cables to the ENABLE, STOP and START inputs ............................................................. 18
Sensor input .............................................................................................................................................. 19
7 Segments display .................................................................................................................................. 19
Codification of failure ............................................................................................................................... 20
DECLARATION OF CONFORMITY .......................................................................................................... 21
Assistance and Trouble shooting ........................................................................................................... 21

CAUTION

DO NOT INSTALL THE WINDOW PROGRAMMING SOFTWARE BEFORE


TO INSTALL THE USB PORT CONNECTION AND DRIVER.

FOLLOW THE INSTRUCTION OF THE INSTALLATION CARD DELIVERED WITH


THE WINDOWS SOFTWARE.

Page 2 / 22 User Manual ACO5000


Safety instructions

Information on the Operating Manual


This operating manual applies to the ACO5000 frequency inverter family. It describes the connections
and basic functions of the standard models.

CAUTION! Danger of death by electrocution

CAUTION! Absolutely essential

Be careful! Incorrect operation, may lead to damage.

The Basic Safety Rules

First read the user manual


Before installing and commissioning, it is important for such personal to read carefully the
operating instructions and safety warnings.

Electric drives are potentially dangerous

 Electrical voltages > 230 V/460 V


 High voltages may still be present up to 5 minutes after the power
has been cut off. Therefore you must always check for presence
of power and voltages!
 In STOP mode, the drive remains active and the motor terminals are at a potential of 300 VDC
against the ground.
 Rotating parts
 Hot surfaces

Your qualification

 In order to prevent personal injury and damage to property, only personnel with
electrical engineering qualifications may work on the device.
 The person must be familiar with the user manual.
 Have knowledge of national standards and accident prevention regulations

S610-GB-0825 User Manual ACO5000 Page 3 / 22


Working instruction

During installation observe the following instructions:


 Always comply with the suggested connecting diagram and technical specifications.
 Comply with the standards for electrical installations, such as regarding wire gauges, grounding
lead and ground connections.
 Without prior writing agreement you are not allowed to open the drive. If you do it, the warranty
will be void.

Over speed protection


If an application required an over speed protection, it must be provided by the motor
manufacturer, as this function is not integrated in the drive.

Overload protection
The drive doesn't integrate any input line overload protection. An external overload
protection is required for the AC main and the supplied 24 VDC.

Proper installation
Inverter drives are components that are intended for installation within electrical systems or
machines. The inverter may not be commissioned or put into operation until it has been
established that the machine as a unit complies with the provisions of the EC Machinery
Directive (98/37/EC) as well with the standard EN 60204-1998 (Safety of machines).

For the drive connection please refer to the schematics and instructions included in this manual (see
chapter “The start option”)

If the frequency inverter is used for special applications the specific standards and regulations for this
environment must always be observed.

Repairs may only be carried out by authorized repair workshops. Unauthorized opening and incorrect
intervention could lead to physical injury or material damage. The warranty provided by DANAHER-
MOTION would thereby be void.

If you have to do it, bear in mind that the converter control board uses a large number of MOS (Metal
Oxide Semiconductor), which are highly sensitive to electrostatic charge.

To avoid any damages to the control board:

 Make sure you are working on an earthen anti-static floor or being properly earthed.
 use anti-static packing material only

Responsibility
Electronic devices are fundamentally not fail-safe. The company setting up and/or operating the
machine or plant is itself responsible for ensuring that the machine is rendered safe if the drive
fails.

Programming of the drive


The drive is programmed using windows based software. The details of the programming and setup are
described in the manual S620_GB_xx. Programming software, drivers and the programming manual are
included on CD-rom supplied with this documentation.

Page 4 / 22 User Manual ACO5000


Product description

Highlights
 PAM – Pulse Amplitude Modulation – a technology with regulated intermediate DC bus
 Traditional ACOMEL SHS – Selective Harmonic Suppression – modulation
 Windows based programming software
 Can be operated via Terminal Block, dedicated terminal TL5 or Profibus
 Large number of free programmable parameters
 32 complete sets of motor parameters can be stored and selected
 CE and UL (pending)

Power supply module


 Input voltage 200 – 480 VAC, +10% / -15%, 50/60 Hz, auto-ranging
 DC power output max. 36 A for the ACO5000A
 DC power output max. 45 A for the ACO5030A
 Power IN connect to the bottom
 Integrated dynamic braking resistor, 830  / 100W (1000 W peak)
 Possibility to add an external braking resistor module
 24 VDC, auxiliary power input supplied by customer, 2 to 4 A depending of the number of axis
 USB port, internally interconnected to the drive(s)
 RS485 port dedicated to remote KeyPad TL5
 Article designation: ACO5000A

External braking resistor module


 Same dimensions as the power supply module
 Internal connection to the power supply module
 Used when full braking power is required
 Rating 22  / 1200 W (5 kW peak)
 Article designation: ACO5000R for the basic version
 Article designation: ACO5000R1 for version with fan cooling for improved performances.

Power Drive module


 Internal connections to the power supply module
 Motor power OUT and PTC input connect to the bottom
 Pluggable screw terminals – see "Control terminals description"
 Safety relay with feed back info to the CNC or PLC
o Standard: the free potential contact CLOSED when the relay is enabled (contact NO)
o Option –C: the free potential contact OPENS when the relay is enabled (contact NC)
 All "Control terminals" are opto-insulated
 PROFIBUS port (Option)
 Sensor feedback connector (not compulsory to drive a motor)
 7 segments status display
 5 power ratings: 5, 8, 12, 20 and 30 A, 3 physical sizes
 Max output frequency 5000 Hz
 Article designation: ACO50xxD (see "Power ratings" table)

Power ratings

Drive Nominal Peak Max output Max. Output Max. power


current current Power @ 230 V Power @ 400 VAC dissipation
ACO5005D 5A 7.5 A 3 kVA 5 kVA 200 W
ACO5008D 8A 12 A 5 kVA 8 kVA 320 W
ACO5012D 12 A 18 A 7 kVA 12 kVA 480 W
ACO5020D 20 A 30 A 12 kVA 20 kVA 800 W
ACO5030D 30 A 45 A 18 kVA 30 kVA 1200 W

S610-GB-0825 User Manual ACO5000 Page 5 / 22


General technical data

Unit Comment
Output frequency step Hz   0.5% of the set frequency
Type of load Resistive / Inductive
Short-circuit protection between phases At terminals
Ground short-circuit protection At power ON and at terminals
Efficiency at nominal load % 96
Max. ambient temperature °C 40
Output power derating relative to the > 1000 m, derating of 5% per 1000 m. Max.
operating altitude operating altitude 2000 m – derating 10%
Output power derating relative to the %/°C 3% / °C over the ambient of 40°C
operating ambient temperature Max. ambient temperature 50° C
Relative humidity % 15 … 85 not condensing
Storage temperature °C -25 to +55 according VDE0160
Shipping temperature °C -25 to +70 according VDE0160

Examples of product configuration and weight

Designation ACO ACO ACO ACO ACO ACO ACO Size Weight
5000A 5005D 5008D 5012D 5020D 5030D 5000R kg
5030A 5000R1
SINGLE AXIS
ACO5-0005T 1 1 2 11.5
ACO5-0005R 1 1 1 3 13.8
ACO5-0008T 1 1 2 11.5
ACO5-0008R 1 1 1 3 13.8
ACO5-0012T 1 1 3 18.6
ACO5-0012R 1 1 1 4 20.7
ACO5-0020T 1 1 3 18.6
ACO5-0020R 1 1 1 4 20.7
ACO5-0030R1 1 1 1 5 31.7
MULTI-AXIS
ACO5-0055T 1 2 3 16.9
ACO5-0055R 1 2 1 4 19.2
ACO5-0085T 1 1 1 3 16.9
ACO5-5555T 1 4 5 27.6
ACO5-5555R 1 4 1 6 29.9
ACO5-0888R 1 3 1 5 24.5
ACO5-1255T 1 2 1 5 26.7
ACO5-1285R 1 1 1 1 1 6 29.0
ACO5-1212R 1 2 1 6 33.3

Any configuration up to size 6 (6 modules units) so far at any time, the sum of the currents doesn't
exceed 36A as peak power. Any configuration exceeding the max. is not allowed, the power supply
being not protected for overload. Only the drive(s) integrated a current limitation and an overload
protection. No multi-axis configuration allowed with the ACO5030A and ACO5030D

The configurations with external braking resistor module can be made using the ACO5000R or
ACO5000R1, except for the ACO5030R1 where the module with additional fan cooling is mandatory.

Page 6 / 22 User Manual ACO5000


Mounting and installation

Mechanical dimensions

71/142/213

Module dimensions

 ACO5000A
 ACO5000R
 ACO5005D
 ACO5008D
o Width 71 mm

 ACO5012D
 ACO5020D
o Width 142 mm
 ACO5030D
o Width 213 mm

 Mounting position
vertical
 Cabinet integration:
For proper cooling
leave 10 cm free
space on top of the
inverter.

Configuration A B
"2 modules unit" made of:
 1 ACO5000A 145 124
 1 ACO5005D / 08D
"3 modules unit" made of:
 one of the above and 216 195
1 ACO5000R, or
1 ACO5000A and
2 ACO5005D / 08D, or
1 ACO5000A, and
1 ACO5012D / 20D
"4 modules unit" made of:
 any combination of 287 266
1 ACO5000A, drive(s)
ACO50xxD and/or 1
ACO5000R (R1)
"5 modules unit" made of:
 any combination of 358 337
1 ACO5000A, drive(s)
ACO50xxD and/or 1
ACO5000R (R1)
"6 modules unit" made of:
 any combination of 429 408
1 ACO5000A, drive(s)
ACO50xxD and/or 1
ACO5000R
Mounting screws: 4 x M6
NOTE: At any time, the sum of the
current of any drive combination must
not exceed 36A (45A) as peak power.

S610-GB-0825 User Manual ACO5000 Page 7 / 22


Description and connection

Power terminals

TERMINAL BLOCK XA1


 24 VDC INPUT
 0V TERMINAL BLOCK XD1
 PE Principal Earth  PTC INPUT
 Mains input L3  PTC INPUT
 L2  Earth
 L1  W motor output
 All terminals 10 mm2  V
 One block,  U
removable  All terminals 10 mm2
 External overload  One block, removable
protection required

ACO5000A ACO50xxD

Specifications of the input terminal block XA1


 AC line
o Input voltage
 min. 200 V single phase –15%
 max. 3 phases 480 V
 50 / 60 Hz
o Single phase input connect to any 2 of L1, L2 or L3
o External overload protection required.
 Circuit breaker or line fuses max. 32 AT
o Use copper conductors 75°C

 24 VDC external power supply


o Voltage tolerances 10%
o Required power min. 1 A per module up to ACO5020 and 3A min. for ACO5030R1
o External overload protection required if not short-circuit proof

Specification of the output terminal block XD1


 Motor power
o Max. output voltage 3 phases 480 V, 5000 Hz
o Use power cable according to the recommendation of the motor manufacturer
o Cable gauge according the motor current requirements

 PTC input
o This input is over voltage proof up to 500 VAC
o In case of use of temperature sensor, program the appropriate input calibration.

Page 8 / 22 User Manual ACO5000


How to unlock the power terminals

PRESS
PULL

Power terminal foolproofing

To avoid the risk of inverting the connectors of


the power supply and the drive(s), both
connectors are coded. The pictures show the
coding position (white square) and the way to
insert the coding tag (the right pictures show a
half inserted tag).

Foolproofing of the power


supply

Foolproofing of the drive(s)

Power supply Driver

S610-GB-0825 User Manual ACO5000 Page 9 / 22


Front panel description

Power supply module

D-sub 9 poles connector for the specific user


interface TL5

USB Port dedicated as service port to:


 Program the drive(s)
 Up-date the firmware
 Commission the installation
 Testing and debugging
 Internally connected to the drive(s)
Note: Not to be used to operate the equipment
in production.

Power Drive module

7-segments display shows the current status of


drive, used as fault indicator too.

PROGRAM: a service push button used to


upgrade the firmware via the USB port. Pressing
this button at power ON or under power for more
than 5 sec will initiate a point-to-point connection.
This port is used to set the # of the drive(s) and
their PROFIBUS address.

PROFIBUS D-sub 9 poles connector.


This field bus is an option, not to be retrofit in the
field. Ask for the specific user manual.

SENSOR input for speed feedback.


TTL encoder or magneto-resistive sensor

Removable CONTROL TERMINALS


See “Description of the control terminals X2”

Page 10 / 22 User Manual ACO5000


Description of the control terminals X1

Hardware ENABLE input from The +24 VDC OUT are common to the 24 VDC
PLC in accordance with the supplied and short-circuit protected
EN954-1 standard +24V_OUT 1 16 +24V_OUT
24 VDC to power safety relay Enable IN 2 17 IN1
Safety relay floating contact, 3 18 IN2 8 programmable
closed (opened in version –C) 4 19 IN3 digital inputs
when drive is enabled 5 20 IN4
Drive failure output. Floating 6 21 IN5
contact, closed when ready START 7 22 IN6 Function allocated
by user
STOP 8 23 IN7
RESET 9 24 IN8
0 V 10 25 0 V
2 programmable analogue A_OUT1 11 26 OUT1 4 programmable
outputs 0 … 10 V A_OUT2 12 27 OUT2 digital outputs
Internal 10 VDC and +10 VDC 13 28 OUT3 Function allocated
analogue input 0 … 10 V for A_IN 14 29 OUT4 by user
speed reference 0V 15 30 0V
All "0 V" are inter-connected

NOTE: All digital and analogue inputs and outputs are opto-isolated. All outputs are short-circuit proof.

# Name DESCRIPTION
1 24V_OUT Same potential as the external supplied 24 VDC. Available to activate an input. This
output is short circuit protected.
2 ENABLE This enable is used in connection with the SAFETY RELATED DRIVE INTERLOCK
(called SAFE INTERLOCK in the chapter “The start options”). Apply 24 VDC to activate.
3 EN_A This NO or NC (version –C) relay contact will close when the "ENABLE" is powered.
4 EN_A This relay contact is potential free. Max contact load 230VAC /2A or 24VDC/2A
5 DR_R This NO relay potential free contact will close when the drive is READY resp. the relay
6 DR_R energized, The contact will be open in case of FAILURE.
X1-1

Maximal contact load 125VAC/0.6A resp. 30VDC/2A or 110VDC/0.6A


7 START Apply 24 VDC to START the drive.
For detailed information, see chapter “The start options”
8 STOP The drive will STOP when the 24 VDC is not applied to this input.
For detailed information, see chapter “The start options”
NOTE: the 24 VDC must be applied at least 10 ms before the START signal, if not a
failure will be generated. NEVER apply both (STAR and STOP) at the same time.
9 RESET Apply 24 VDC to reset. Need always to be done after a failure.
Don't apply a permanent 24 VDC as the reset is triggered by the positive edge of the
signal. Min. duration of the pulse: 5 ms
10 0V Electronic ground of the drive, linked to the 0 V of the external 24 VDC

11 A_OUT1 2 free programmable 0 to 10 V analogue outputs. Allocated parameters selected by


12 A_OUT2 program. Refer to 0 V, terminal X1-2/15.
Max. load 10 mA, short-circuit proof.
X1-2

13 + 10 VDC Available to connect a potentiometer between +10VDC (X1-2/13) and 0V (X1-2/15), with
the cursor to the input A_IN (X1-2/14) to make a manual analogue speed reference.
Use a 10 k potentiometer.
14 A_IN Analogue speed reference input 0 to 10 V, referred to 0 V (X1-2/15)
15 0V Electronic ground of the drive, linked to the 0 V of the external 24 VDC

S610-GB-0825 User Manual ACO5000 Page 11 / 22


# Name DESCRIPTION
16 24V_OUT Same potential as the external supplied 24 VDC. Available to activate an input
17 IN1
18 IN2 8 programmable digital inputs
19 IN3 Function allocated by user
X1-3

20 IN4 All inputs are opto-isolated


21 IN5
Insulated type 24 VDC
22 IN6
VOFF [VDC] -0.3 - 5.0 @ 1 mA (max)
23 IN7
VON [VDC] 15 - 30 @ 10 mA (typical)
24 IN8
25 0V Electronic ground of the drive, linked to the 0 V of the external 24 VDC

26 OUT1 4 programmable digital outputs, function allocated by user


27 OUT2 All outputs are opto-isolated, max. load 10 mA, 24 VDC
X1-4

28 OUT3 By allocating the output frequency SDIG (6 times the output frequency) to one
29 OUT4 of these outputs, use a load resistors of max. 3.3 kΩ
30 0V Electronic ground of the drive, linked to the 0 V of the external 24 VDC

Connecting and wiring instructions

The wiring diagram

PLC ACO5000A ACO5000D


Safety switch
+24 V
ENABLE
EN_A
EN_A
DR_R
DR_R
START
STOP
RESET
0V
24 V L1 L2 L3 PTC U V W

+24 V

L1 Motor
L2
L3

EMC Requirements
Mounting instructions related to the EMC - directive 89/336/EEC
1. The frequency converter must be mounted in a closed metal cabinet.
2. The power connection between converter and motor must be made using shield cables, grounded at
both ends.
3. The control connection must utilize shielded cables, grounded on both ends.
4. The shield of the cables must be grounded at both ends.
5. Power connections and control connection must be placed in separated canals.
6. No external filter required.
Page 12 / 22 User Manual ACO5000
Connecting the shielding

1. Remove the insulation in the area under the clamping system to get a correct grounding of the
shielding.
2. The clamping system has two functions:
a. Provide for a proper grounding of the shielding.
b. Provide for a strength relief of the cable, holding it mechanically.

Intended use of operation


The ACO5000 is a variable speed drive whose primary utilization is to drive safely high speed machining
spindles. The concept of the drive provides the necessary features to achieve a Safety related drive
interlock once integrated in the machine with respect to the instruction described in this manual.

The concept of the drive gives the machine manufacturer the choice of the safety level of the operation:

1. According EN954-1, category 3. It is mandatory to implement the safety related drive interlock as
described in this manual. It requires to comply to the following requirements:
a. Use the ENABLE input
b. Follow the start sequence procedure as described in this manual to START and STOP
the drive.

2. According EN954-1, category 1. In this case you need to:


a. Put a jumper between the terminal +24V_OUT and the input ENABLE
b. START and STOP the drive with the corresponding terminal inputs as described in the
next chapter.

S610-GB-0825 User Manual ACO5000 Page 13 / 22


The start options and the wiring diagram to use
This chapter describes various ways or processes to start the drive. It includes 4 subsections:
 The SAFE INTERLOCK feature is not implemented on the machine and the start is using:
o A permanent contact
o An impulsion contact
 The SAFE INTERLOCK feature is implemented on the machine and the start is using:
o A permanent contact
o An impulsion contact
The selection of the start mode using a permanent or an impulsion contact is made by software
during the parameterisation of the drive.

No SAFE INTERLOCK, start by permanent contact

# Name DESCRIPTION
1 24V_OUT Same potential as the external supplied
24 VDC.
2 ENABLE NOT USED
Must be connected to 24 VDC via a jumper
3 EN_A NOT
4 EN_A USED
To the machine 5 DR_R READY Relay output
controller (PLC) NO potential free contact.
6 DR_R Closed when ready
Failure when open
From the
machine
7 START Apply 24 VDC to START the drive.
controller
Must be connected to 24 VDC via a jumper.
8 STOP This input has the function of a START
enable.
9 RESET Apply 24 VDC to reset. DON’T use a jumper.
10 0V Electronic ground of the drive

No SAFE INTERLOCK, start / stop by impulse contacts

# Name DESCRIPTION
1 24V_OUT Same potential as the external supplied
24 VDC.
2 ENABLE NOT USED
Must be connected to 24 VDC via a jumper
3 EN_A NOT
4 EN_A USED
To the machine 5 DR_R READY Relay output
controller (PLC) NO potential free contact.
6 DR_R Closed when ready
Failure when open
Apply 24 VDC to START the drive.
From the
7 START Impulse 5 ms min.
machine
controller
Apply 24 VDC to enable the start
(PLC)
8 STOP Signal interruption 5 ms min. to stop.

9 RESET Apply 24 VDC to reset. DON’T use a jumper.


10 0V Electronic ground of the drive

Page 14 / 22 User Manual ACO5000


THE SAFE INTERLOCK PROCEDURE
The safe interlock procedure describes how to control the ACO5000 drive with a PLC to have the
maximum safety concerning an unexpected start. It describes the logic concerning all the terminal block
signals according to the diagram presented in the last paragraph.
The START and STOP input can be activated by two types of signals. There are permanent signals or
impulse signals (duration min. 5 ms in order to avoid unexpected activation by parasitic signal) selected
by program (parameter).

Power up procedure
1. Switch on the external +24 V power supply to feed the drive control.
ENABLE, STOP and START inputs are tied to 0 V.
2. Switch on the main power (400 VAC).
3. Wait until the READY relay close the output DR_R.
If the drive is in failure mode, it can be removed by the RESET input to let the READY relay be
energized.
4. At this point, the drive is in safe interlock mode.

 It is possible to switch on the external +24 V power supply and the main power at the same
time.
 If the ENABLE input is tied to +24 V before switching on the drive, the safe interlock mode
will not be available.
 If the START input is tied to +24 V before switching on the drive, the start command will not
be activated. In this case, it will be necessary to apply 0 V on the START input before
applying +24 V again to activate de start command.
 When the external +24 V power supply is on, if the ENABLE input is activated before the
READY relay has closed the output contact DR_R, the drive will go to a failure mode (E4 :
Power Fail) and a RESET command will be needed after the closing of the DR_R contact.
 If the ENABLE input is activated before the main is applied, the drive is going to failure mode
(E4 : Power Fail) and a RESET command will be needed after the closing of the DR_R
contact.

Procedure to make a START from the safe interlock mode


1. Energized the safety relay by applying +24 V to the ENABLE input.
2. Wait until the safety relay feed-back contact EN_A is closed (open in the case of option –C)
3. Apply +24 V to the STOP input to enable the START input.
4. Wait for min. 10 ms before applying +24 V to the START input.
In the permanent signals option, maintain +24 V to the START input to keep the START mode.
In the impulse signals option, a 5 ms pulse is enough to maintain the START mode.
5. At this point, the drive is in START mode and the motor will begin to move.

 If the START command is activated before the ENABLE input, the drive will go to a failure mode
(E0 : ENABLE) and a RESET command will be needed.
 If +24 V is applied to the START input before or less then 10 ms after the STOP input, the
START command will not be activated. It will be necessary to apply 0 V on the START input and
do the correct procedure.

Procedure to return to the safe interlock mode


1. Make a STOP and wait until the rotor comes to a standstill.
(zero frequency signal can be used to know when the motor ends its deceleration)
In the permanent signals option, apply 0 V to the START input
In the impulse signals option, apply 0 V to the STOP input for more than 5 ms
2. Apply 0 V to the ENABLE input to release the safety relay.
3. Verify that the feed-back contact EN_A is open (standard version shown on the graphs below)
4. At this point the drive is in the safe interlock mode.

If the safety relay is released by applying 0 V to the ENABLE input before the STOP operation were
completed, the motor will run in free-wheel.

S610-GB-0825 User Manual ACO5000 Page 15 / 22


Timing for the safe interlock procedure with permanent signals for the START and STOP

+24 VDC

L1, L2, L3

closed
DR_R open

Safe interlock
required

ENABLE
min. 50 ms
closed
EN_A open

STOP
min. 10 ms min. 10 ms
START

STATUS POWER UP START STOP SAFE START POWER DOWN

SAFE INTERLOCK implemented, start by permanent contact

# Name DESCRIPTION
1 24V_OUT NOT TO BE USED when the SAFE
From the machine INTERLOCK is active.
controller (PLC) 2 ENABLE Signal is delivered by the PLC only after
reception of the READY signal /
terminals 5-6 DR_R
3 EN_A Confirmation back to the PLC that the
To the machine 4 EN_A ENABLE has been activated.
controller (PLC) 5 DR_R READY Relay output
NO potential free contact.
6 DR_R Closed when ready
Failure when open

From the 7 START Apply 24 VDC to START the drive.


machine
controller Signal is delivered by the PLC only after the
(PLC) 8 STOP reception of the ENABLE confirmation /
terminals 3-4 EN_A. This input has the
function of a START enable.
9 RESET Apply 24 VDC to reset. DON’T use a jumper.
10 0V Electronic ground of the drive

Page 16 / 22 User Manual ACO5000


Timing for the safe interlock procedure with impulse signals for the START and the STOP

+24 VDC

L1, L2, L3

closed
DR_R open

Safe interlock
required

ENABLE min. 50 ms
closed
EN_A open
min. 5 ms
STOP
min. 10 ms min. 10 ms
min. 5 ms
START

STATUS POWER UP START STOP SAFE START POWER DOWN

SAFE INTERLOCK implemented, start / stop by impulse contacts

# Name DESCRIPTION
1 24V_OUT NOT TO BE USED when the SAFE
From the machine INTERLOCK is active.
controller (PLC) 2 ENABLE Signal is delivered by the PLC only after
reception of the READY signal /
terminals 5-6 DR_R
3 EN_A Confirmation back to the PLC that the
To the machine 4 EN_A ENABLE has been activated.
controller (PLC) 5 DR_R READY Relay output
NO potential free contact.
6 DR_R Closed when ready
Failure when open

From the 7 START Apply 24 VDC to START the drive.


machine
controller Signal is delivered by the PLC only after the
(PLC) 8 STOP reception of the ENABLE confirmation /
terminals 3-4 EN_A. This input has the
function of a START enable.
9 RESET Apply 24 VDC to reset. DON’T use a jumper.
10 0V Electronic ground of the drive

S610-GB-0825 User Manual ACO5000 Page 17 / 22


Instruction to the product integrator

The safe interlock according EN954-1, category 3 is only provided if:

 The sequence of signals according to the safe interlock procedure is respected. If ignored, the
safe interlock function is no more achieved.
 The mounting instructions of the user manual are respected.
 The external connections are made according to the proposed wiring diagram.

Additional information to the machine manufacturer

 The recommendations of the machine directives are respected.


 A corresponding risk analysis of the complete machine has been done.

The safe interlock function is a feature to allow the product integrators to satisfy the requirement of the
standards to secure a safe interlock of the drive and its connected motor.

Connecting cables to the ENABLE, STOP and START inputs

Those connecting cables have to comply with the requirement of the table D.5 of ISO13849-2. The
elimination of the risk that short-circuits would lead to an unexpected start of the drive (reducing the
number of safety barriers) is valid under following considerations:

 Cables must be protected against external damages (i.e use of cable channel, protective tubes)
or,
 The above signals are located in separate cables.

Connections outside of our drive are the responsibility of the machine manufacturer.

Page 18 / 22 User Manual ACO5000


Sensor input

1 Sensor detect +5 VDC 9 RESERVED


8 2 NA 10 RESERVED
3 RESERVED 11 RESERVED
4 Input magneto-resistive sensor 12 INDEX -
5 INDEX + 13 Channel B -
6 Channel B + 14 Channel A -
7 Channel A + 15 + 5 VDC power supply sensor
9 8 Ground 0 V The case must be connected to earth
1
The sensor input accept either 5 V TTL encoder signals or the signal from a magneto-
resistive sensor (Siemens – FP210 D 250-22 or FP212 D 250-22)
Fmax: > 2MHz

7 Segments display

The drive is in STOP mode

START mode: the segment is rotating clockwise or counter-clockwise according to the


direction of the rotation of the motor

E flashing indicates a failure. The display will show alternatively an "E" and an alphanumeric
character indicating the type of failure. For detail see paragraph "Codification of failure"

Intermediate DC bus voltage > 50 VDC

Indicate that the DC current braking is active (FCC)

Indicate that the permanent DC braking current is active (FCP)

The dot indicates that the serial connection via USB port is active point-to-point with this
drive. This mode is activated by pressing the push button PROGRAM during more than 5 s.

S610-GB-0825 User Manual ACO5000 Page 19 / 22


Codification of failure

Enable not released. This error is displayed when a START is given before the ENABLE has
been released

Converter overload.

Short-circuit to ground

Over voltage on intermediate DC-Bus. Indicate a voltage surge on the DC-bus exceeding 900
DC peak. This peak could come from the mains or back from the motor.

Power fails. Will be shown when the ENABLE is activated and the AC voltage is missing.

Auxiliary power supply failures. Indicates that one of the auxiliary voltages ± 15 VDC
or 5 VDC is missing or +24VDC<20VDC

External interlock is open

Motor temperature too high (PTC)

Converter temperature too high (NTC)

Klixon contact open. Indicate that the temperature of the external braking resistor is too high
or that this external module has been removed and the safety jumper not put in place.

Motor overload, i.e. Im > Iref

Regen/Accel: this indicates that the dynamic braking process has been activated during the
acceleration. A START was probably activated when the motor was still spinning.

Not allocated

Not allocated

Not allocated

Not allocated

Page 20 / 22 User Manual ACO5000


DECLARATION OF CONFORMITY

We: Danaher Motion S.A


La Pierreire 2
CH - 1029 Villars-Ste-Croix

declare under our sole responsibility that the products of the family ACO5000, are exclusively designed
for incorporation in an other machine. The operation of the product is submitted to the conformity of the
complete equipment, following the provisions of the directive 98/37/EC

The conformity of the above specified products with the provisions of the Directive 73/23/EEC is
supported by the respect of the standards CEI/IEC 1010-1

If the mounting and connecting instructions of the installation’s manual have been respected, this product
will be conform to the standards EN 61000-6-4, EN 61000-6-2 and EN61800-3 +A11 relating to the EMC
directive 89/336/EEC.

Mounting instructions related to the EMC - directive 89/336/EEC

1. The frequency converter must be mounted in a closed metal cabinet.


2. The power connection between converter and motor must be made using shield cable.
3. The control connection must utilize shielded cables.
4. The shield of the cables must be grounded at both ends.
5. Power connections and control connection must be placed in separated canals.
6. No external input filter is required.

The R&D manager:

André Schwendener

Assistance and Trouble shooting

All our products are manufactured in accordance with an accurate quality process. Before
delivery they are checked for many hours under power. The quality system and production
process guarantee that all products are shipped free of default.
The respect of the installation procedure describes in this manual and a correct definition of the
application should avoid any commissioning problems.
Should you meet some problems during installation or commissioning of the frequency inverter
our technical staff are available for assistance. Please contact your local supplier or the local
DANAHER-MOTION subsidiary.
Please includes following information:

1. Description of the application


2. Default or problem you met
3. Copy of the programmed parameters
4. Wiring diagram

In case of emergency: Danaher Motion S.A.


La Pierreire 2
CH - 1029 Villars-Ste-Croix

Tel. +41 21 631 33 33


Fax. +41 21 636 05 09
E-mail: [email protected]

S610-GB-0825 User Manual ACO5000 Page 21 / 22


Please contact

AHS Antriebstechnik GmbH


Fichtenweg 17
64319 Pfungstadt
+49 6157 – 9866110
[email protected]

Page 22 / 22 User Manual ACO5000

You might also like