Lecture 4-Equivalent Circuits - Transformers
Lecture 4-Equivalent Circuits - Transformers
Lecture 4-Equivalent Circuits - Transformers
TRANSFORMERS
Impedance Ratio
Consider a transformer having
impedance Z2 in the secondary as shown
Hence impedance ratio (Z2/Z1) is equal
to the square of voltage transformation
ratio.
In other words, an impedance Z2 in
secondary becomes Z2/K2 when
transferred to primary.
Likewise, an impedance Z1 in the
primary becomes K2*K1 when
transferred to the secondary.
Similarly, R2/R1 = K2 and X2/X1 = K2
2
Impedance Ratio
The importance of above relations is that we can transfer the parameters from one
winding to the other. Thus:
iii. A reactance X1 in the primary becomes K2*X1 when transferred to the secondary.
iv. A reactance X2 in the secondary becomes X2/K2 when transferred to the primary.
When transferring voltage or current from one winding to the other, only K is
used.
3
Shifting Impedances in A Transformer
The figure below shows a transformer where resistances and reactance are
shown external to the windings.
5
Equivalent Resistance
The resistance of the two windings can be transferred to any side either
primary or secondary without affecting the performance of the transformer.
The transfer of the resistances on any one side is advantageous as it makes the
calculations very easy.
6
Equivalent Resistance
7
Transformer Referred to Primary
8
Transformer Referred to Secondary
9
Impedance Equivalent
10
Practice Question
Qn 1: A 33 kVA, 2200/220V, 50Hz single phase transformer has the
following parameters. Primary winding resistance R1 = 2.4Ω, Leakage
reactance X1 = 6 Ω, Secondary winding resistance R2 = 0.03Ω,
Leakage reactance X2 = 0.07 Ω. Then find Primary, Secondary and
equivalent resistance and reactance.
12
Solution Q2
13
Practice Questions
14
Equivalent Circuit of a Transformer
15
Equivalent Circuit of a Transformer
It is important to describe the behavior of an electrical machine in terms of its
equivalent circuit so that the analysis can be done using normal methods of circuit
theory.
The exact equivalent circuit of a transformer on load is as shown below:
Note that equivalent circuit has created two normal electrical circuits
separated only by an ideal transformer whose function is to change values
according to the equation:
17
Points to note
The following points may be noted from the equivalent circuit:
18
Points to Note
19
Equivalent circuit referred to primary
20
Equivalent circuit referred to primary
21
Equivalent circuit of transformer referred to primary
22
Equivalent circuit of transformer referred to secondary
23
Equivalent circuit of transformer referred to secondary
Note: The same final answers will be obtained whether we use the
equivalent circuit referred to primary or secondary. The use of a particular
equivalent circuit would depend upon the conditions of the problem. 24
Approximate Voltage Drop in a Transformer
25
Approximate Voltage Drop in a Transformer
26
Voltage Regulation
27
Practice Question
Qn 1.: A 250/125V, 5 kVA single phase transformer has primary
resistance of 0.2 Ω and reactance of 0.75Ω. The secondary resistance is
0.05 Ω and reactance of 0.2 Ω. Determine:
ii. The secondary terminal voltage on full load and 0.8 leading p.f.
28
Solution Q1
29
Solution Q 1
30
Practice Question
Qn 1.: A single phase transformer with a ratio 5: 1 has primary
resistance of 0.4 ohm and reactance of 1.2ohm and the secondary
resistance of 0.01 and reactance of 0.04 ohm. Determine the percentage
regulation when delivering 125 A at 600 V at
(iii) unity.
31
Efficiency of a Transformer
32
Practice Question
Qn 1.: A 500 kVA, 600/400V, one-phase transformer has primary and
secondary winding resistance of 0.42 Ω and 0.0011 Ω, respectively. The
primary and secondary voltages are 600 V and 400 V, Ωrespectively. The
iron loss is 2.9 kW. Calculate the efficiency at half full load at a power
factor of 0.8 lagging.
Qn 2.: In a 25 kVA, 2000/200 V power transformer the iron and full load
copper losses are 350 W and 400 W, respectively. Calculate the efficiency
at unity power factor at (i) full load and (ii) half load.
34
Solution Qn 2
35
TRANSFORMER TESTS
The circuit constants, efficiency and voltage regulation of a transformer
can be determined by two simple tests i.e.:
✓ open-circuit test
✓ short-circuit lest.
These tests are very convenient as they provide the required information
without actually loading the transformer.
Further, the power required to carry out these tests is very small as
compared with full-load output of the transformer.
These tests consist of measuring the input voltage, current and power to
the primary first with secondary open-circuited (open-circuit test) and
then with the secondary short-circuited (short circuit test).
36
Open-Circuit or No-Load Test
This test is conducted to determine the iron losses (or core losses) and parameters
R0 and X0 of the transformer.
In this test, the rated voltage is applied to the primary (usually low-voltage
winding) while the secondary is left open-circuited.
The applied primary voltage V1 is measured by the voltmeter, the no-load current I0
by ammeter and no-load input power W0 by wattmeter as shown in Figure (i).
As the normal rated voltage is applied to the primary, therefore, normal iron losses
will occur in the transformer core.
Hence wattmeter will record the iron losses and small copper loss in the primary. 37
Open-Circuit or No-Load Test
38
Short-Circuit or Impedance Test
This test is conducted to determine R01 (or R02), X01 (or X02) and
full-load copper losses of the transformer.
The low input voltage is gradually raised till at voltage VSC, full-
load current I1 flows in the primary.
39
Short-Circuit or Impedance Test
There is no output from the transformer under short-circuit conditions.
Therefore, input power is all loss and this loss is almost entirely copper
loss.
It is because iron loss in the core is negligibly small since the voltage VSC
is very small.
40
Short-Circuit or Impedance Test
• Note: The SC test will give full-load Cu loss only if the applied
voltage VSC is such so as to circulate full-load currents in the
windings.
41
Advantages of Transformer Tests
1. The power required to carry out these tests is very small as compared
to the full-load output of the transformer. In case of open-circuit lest,
power required is equal to the iron loss whereas for a short-circuit test,
power required is equal to full-load copper loss.
3. The short-circuit test enables us to determine R01 and X01 (or R02 and
X02). We can thus find the total voltage drop in the transformer as
referred to primary or secondary. This permits us to calculate voltage
regulation of the transformer.
42
Practice Question
Qn 1.: A 15 kVA, 440/230 V, 50 Hz, single phase transformer gave the
following test results:
Open Circuit (LV side) 250 V, 1.8A, 95 W.
Short Circuit Test (HV side) 80 V, 12.0 A, 380 W.
Compute the parameters of the equivalent circuit referred to LV side
Qn 2.: A 50 MVA, 60 Hz single-phase transformer indicates that it has a
voltage rating of 8 kV: 78 kV. Open circuit test and short circuit test gave
the following results:
Open Circuit Test: 8 kV, 61.9 A and 136 kW
Short Circuit Test: 650 V, 6.25 kA and 103 kW.
Determine the efficiency and voltage regulation if the transformer is
operating at rated voltage and a load of 0.9 p.f. lagging.
43
Solution Qn 1
44
Solution Qn 2
45
Conti…Solution Qn 2
46
Self Assessment
• What is voltage regulation of a transformer?
• Why does voltage drop in a transformer?
• Is the regulation at rated load of a transformer same at 0.8 p.f. lagging
and 0.8 p.f. leading?
• Is the percentage impedance of a transformer same on primary and on
secondary?
• Obtain the equivalent circuit of a 200/400V, 50Hz, single phase
transformer from the following test data:
O.C test: 200V, 0.7A, 70W-on LV side
SC test:15V, 10A, 85W-on HV side
Calculate the secondary voltage when delivering 5kW at 0.8 p.f. lagging.
47