3/12/2015 ESDEP LECTURE NOTE [WG4A]

Previous | Next | Contents

ESDEP WG 4A

PROTECTION: CORROSION

Lecture 4A.5: Corrosion in Offshore


and Sheet Piling
OBJECTIVE/SCOPE

To introduce students to the protection of structures, pipes, etc. offshore and in the ground.

PREREQUISITES

Lecture 4A.1: General Corrosion

Lecture 4A.2: Factors Governing Protection of Steelwork

Lecture 4A.3: Corrosion in Buildings

Lecture 4A.4: Corrosion Protection of Bridges

SUMMARY

This lecture covers the systems available to protect fixed and mobile offshore structures. It deals with sheet piling, corrosion in soils, electrical
methods of corrosion control and, very briefly, bacterial activity and its influence on corrosion rates.

1. OFFSHORE
The North sea is far more hostile than the Texan and Arabian Gulfs. The technology used in the warmer climates has had to be adapted and modified
to meet the colder climatic conditions both in coastal construction sites and, offshore in the North Sea.
http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 1/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

The difficulty of repairing coatings or, worse still, replacing steel make it imperative that the coating system prevents loss of steel by corrosion.

Fixed offshore constructions are divided into three areas, underwater and tidal, the splash­zone and, decks.

Underwater and tidal zones

Experienced corrosion engineers are not always of the same opinion about the choice of a protective system for steel in these zones.

Some argue that the area below the lowest low waterline (LLW) is subject to mechanical damage during construction and hook up and: that no
protective coating can be expected to survive for some 25 years in the sea. Therefore cathodic protection (sacrificial anodes or impressed current) is
necessary to back up the coating systems. The argument then questions whether coatings are necessary, since cathodic protection is easily increased in
capacity and can therefore provide total protection of the uncoated steel surface.

The opposing view is that even damaged coatings reduce impressed current amperage and anode consumption. Coatings will certainly improve
corrosion protection in acute angles and in welded areas. It seems sensible therefore to at least balance the cost of coating steel against cathodic
protection only.

There is no debate regarding the advantages of using surface coatings in the tidal zone and for up to 10 metres below lowest average tide (LAT).
Increased steel thickness to allow for corrosion in this highly aggressive area may be provided, but cathodic protection combined with coatings is
always used.

The splash zone and jetties

These zones can be well protected by the coatings systems which are effective in the tidal zone. The undersides of support decks and soffit areas in
general also come into this category.

Any system chosen for service in this environment must have very good resistance to water, rust creep and oil/chemical spillage. Coatings need to be
suitable for patch repairs.

Decks

The decks on offshore platforms may require the protection of heavy duty coating systems because they are subjected to severe traffic, impact, and
chemical and oil spillage. On jetties the decks are often an extension of the approach road and not vulnerable therefore. Where they are of steel, then
the same considerations apply as are given to protecting offshore rigs.

Mobile offshore equipment

A wide range of items if involved, e.g. jack­up drilling rigs (for shallow water), self­propelled and semi­submersible drilling rigs, and supply ships.

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 2/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

Service conditions vary with operating conditions and the type of equipment. All suffer severe impacts and abrasions resulting in the destruction of
the protective coatings. Maintenance is difficult and is usually carried out at the same time as mechanical repairs and overhauls and during lay up
periods. The coatings systems used to protect mobile offshore equipment are similar to those used on fixed offshore structures.

Paint Selection

Paint selection is greatly influenced by the likely weather conditions during construction and of course, maintenance. For new work, surface
preparation (which is always abrasive blast cleaning) and the application of the first coats should be undertaken in shops where temperature and
humidity can be controlled. It is impossible to complete the final assembly of most offshore structures under cover, while the sheer complexity of
fabrication requires a great deal of spot repairs which can only be undertaken in the open. Although local abrasive blast cleaning is the normal
preparatory method when dealing with fabrication damage, there are occasions when only power tool cleaning is possible. The products used for patch
repairs must be capable of performing well (although inevitably at a reduced level) over such preparation and of application under exposed conditions,
possibly in adverse weather. The finishes used on the complete structure are also required to perform well under similar conditions.

Typical Systems for Underwater, Tidal and Splash Zones:

New Works

Surface preparation in all cases is abrasive blast cleaning to Sa 2½, ISO 8501­1 [1].

Possible primers are one coat of:

2­pack zinc silicate @ 75m

or 2­pack zinc epoxy @ 35m

or 2­pack epoxy holding primer @ 50m.

The common finishing coat would be:

2­pack coal tar epoxy, amine aduct cured,

volume solids < 60% applied by airless

spray at 200m per coat.

Maintenance in service

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 3/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

The maintenance painting of fixed offshore structures, jetties, etc. is unlikely to be possible for more than 4­5 months during the spring and summer
(the so­called "weather window"). Inevitably work is halted due to poor weather, when the last coat is exposed to complete or nearly complete
immersion, salt spray, etc. Thus, ideally each coat must be as resistant to the environment as the final finish.

It is feasible to repair underwater areas using water displacing solvent free epoxy coatings. Since these coatings would be applied by divers, the
problems are obvious. It is usual therefore to rely instead upon cathodic protection to prevent corrosion at breaks in the coating.

Damage in the tidal or splash zones must be repaired because cathodic protection is not effective for more than 0,2m above lowest waterline.

Typical Systems for Use above the Splash Zone:

New Works

The choice of primer is from those suitable for the underwater, tidal, splash zones described above. Surface preparation is abrasive blast cleaning to Sa
2½, ISO8501­1.

The finishing system is likely to consist of high build 2­pack polyamide cured epoxy intermediate coats applied at dry film thicknesses (dft) of 100­
150m per coat. Usually two coats are applied. The first may be pigmented with micaceous iron oxide to increase build on edges. The finish coat of
circa 50m dft is either a 2­pack paint described as "urethane" or "polyurethane" and probably based on an isocyanate cured acrylic resin or a 1­pack
moisture curing urethane, i.e. a material which reacts with atmospheric moisture, producing an end product with similar characteristics to 2­pack
varieties. The final coat is usually modified to ensure it can be over­coated using fabrication and maintenance painting without the need to first sweep
blast to obtain adhesion. The product description in the manufacturer's technical literature normally carries the word "recoatable". Where appearance
is not of prime importance, it is possible to use a zinc silicate primer (75m dft) followed by two coats of a 2­pack high build polyamide cured epoxy
applied at circa 150m dft per coat.

Maintenance

Maintenance usually requires blasting to Sa 2½ followed by the application of the original system. The treatment may be over all or spot depending
upon whether the coating breakdown is severe or isolated.

Where surface preparation utilises water abrasive blast cleaning, then special primers are required, e.g. 1­pack zinc rich epoxy, moisture displacing
modifications.

If blast cleaning is impossible, power tool cleaning to the St2, ISO 8501­1 followed by priming with a 2­pack epoxy aluminium pigmented "mastic"
before finishing as noted above is an alternative. Its use should be limited to minor repairs.

Typical Systems for Decks:

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 4/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

New Works

Decks require very heavy duty systems which are required to be "non­skid" as well as resistant to the rigorous conditions noted elsewhere. Solvent
free 2­pack epoxy systems are available for direct application in one coat of 3000m to blasted surfaces (Sa 2½). These coatings can contain flint to
prevent them becoming slippery in service. Non­sparking alternatives are available for use in flame­free zones.

Normal heavy duty 2­pack epoxy coatings of the type used in the splash zone are also used in two coat applications (total dft 200+m) over zinc
silicate, zinc rich or zinc­less 2­pack epoxy primers.

Maintenance

Maintenance is usually blasting to Sa 2½ followed by the re­application of the original systems, either over all or in localised areas of damage. If for
some reason blasting is not possible, then power tool cleaning to St3, ISO 8501­1 may be acceptable for the more normal coating system, i.e. 2­pack
epoxy paint system at 200m. The heavy duty coating demands a high standard of abrasive blast cleaning. Surface preparation for maintenance must
be the same as the original.

2. SHEET PILING
The steel sections used for steel sheet piling provide the maximum strength and durability (consistent with good driving properties) at the lowest
weight which good design can achieve. Sheet piling is used in both permanent and temporary works. Typical applications are sea defences, land
reclamation, quays, and coffer dams. Sheet piling can be spliced where lengths of more than 30m are required and, although sheet piling is usually
associated with "straight line" constructions, e.g. quay walls, the sections can be used to form many shapes, including complete circles.

The effective life of unprotected piling, either mild steel or high yield steel (e.g. grades S235, S275 and S355 to EN 10025) depends upon the stresses
imposed in service and the corrosion rate. The potential life of sections can vary from more than 120 years when exposed to an atmosphere with a
mean corrosion rate of 0,05mm/year to circa 80 years in a splash zone with a mean of 0,09mm/year assuming only one face of the piling is exposed.
Where both sides of a sheet piling structure are exposed to the atmosphere for example, the effective life can be reduced by some 30%.

Many environments in which steel piling is used have low corrosion rates. Piles driven into undisturbed soils are quoted as corroding at no more than
0,03mm/year. In this situation protection is superfluous. Conversely the rate in a splash zone may be as high as 0,15mm/year. If the imposed stresses
are also high, then measures to increase the life of the structure are needed. Replacing mild steel with high yield steel is a possibility, as is the
inclusion of additional steel thickness. Cathodic protection may be appropriate. High on the list of protective methods are paints.

Protective coatings should meet certain requirements:

the paints must be suitable for airless spray application.


the paints must be quick drying/fast curing.
http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 5/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

volume solids above 50% are necessary to ensure dry film thicknesses of 100­400m in no more than two coats.

These properties are necessary to ensure a speedy throughput in the shops where the initial coating is applied.

Additionally the coating must:

have excellent adhesion.


be hard and abrasive resistant.
have low water permeability and good chemical resistance to resist transit, driving and finally, the environment in which it is exposed.

A number of painting systems are available to the specifier, who should consider only those which were designed for this particular end use. One
specialist, British Steel, advocates the use of only two alternatives, both specifically designed for piling.

The first system is a high build two pack epoxy/pitch which is isocyanate cured. This is applied to abrasive blast cleaned surfaces of Sa 2½ quality at
up to 400m in one or two coats. Typical end uses are piers, jetties, harbour walls and bearing piles in corrosive soils. The typical time to first
maintenance under severe exposure conditions is quoted as 15 years. Maintenance is either blasting followed by the airless spray application of the
original coating in one coat at 400m or two coats of what is in fact the second system suggested as suitable for piling protection.

The second coating system is described as a tar­vinyl. This coating is a pitch modified with specific vinyl resins which impart a measure of elasticity.
The one part product dries soley by solvent evaporation, which makes it particularly suited to site use. It can be applied at up to 150m per coat.
Typical uses are canal and river walls and, general structures not exposed in aggressive environments. Although abrasive blast cleaning to Sa 2½ is
preferred, this material can be used effectively over power tool prepared steel St2 or 3, ISO 8501­1. Maintenance requires the application of the
original material to the initial dry film thickness or it can be overcoated with other high build pitch solutions.

Only the isocyanate cured epoxy pitch is suitable for use on catholically protected structures.

3. CORROSION IN SOILS
Corrosion in soils is similar to corrosion in water. It requires the presence of an electrolyte and circumstances which produce anodic and cathodic
areas in the steel or iron.

For soil conditions to cause corrosion there must be:

moisture present.
access to oxygen.
dissolved salts to increase electrical conductivity.
an acidic condition.
http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 6/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

Buried steel structures are rarely exposed to conditions in which the electrolyte is acidic enough to support corrosion without the presence of oxygen
to maintain the process. Corrosion usually requires the soil to be pervious to air, with variations in soil conditions giving rise to differential aeration
and the creation of cathodic and anodic areas (see Figure 1). An exception is in neutral, waterlogged clay; although oxygen cannot penetrate the soil,
corrosion occurs by a sulphate­reducing bacteria present in the soil (see Section 5).

Stray electric current can cause severe corrosion, the buried metal providing a low resistance path. The metal acts as a cathode at the point where the
positive current enters and becomes the anode where it leaves the metal. Figure 2 illustrates the problem. The effect is worse with direct current.

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 7/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

The methods of controlling corrosion in soils are limited. Where the soil is acid, then pipelines can be made less vulnerable by back­filling trenches
with limestone chippings which changes the pH. This method is unlikely to be suitable for structures or piles, where the soil is required to be
undisturbed for engineering purposes. In many cases the only effective answer is to re­route the pipeline or re­site the structure.

Traditionally, buried structures have been protected by coating with paints based on coal tar, pitch or bitumen reinforced with a resin. Today, popular
resins for such purposes are epoxy, vinyl or urethane derivatives, i.e. the coatings discussed above as suitable for protecting immersed steel or piling
in soil. In the case of buried pipes other coatings, e.g epoxy powder, three layer polyethylene or wrappings, may be more appropriate.

With all buried steel and iron, cathodic protection should be considered as a means of reinforcing the performance of the coating.

4. ELECTRICAL METHODS OF CORROSION CONTROL


http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 8/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

The best known method is cathodic protection but there are also other methods, i.e. anodic protection and electrical insulation.

Cathodic protection relies upon the fact that, if the complete surface of a metal can be made cathodic by using an external electrode, then corrosion
will not occur. Figure 3 illustrates the use of an impressed current system. Usually a low voltage direct current is the external current which confers
protection. The positive terminal of the current source is connected to an auxiliary anode which is located away from the structure requiring
protection. The structure itself is then connection to the negative terminal and current flows from the anode to the protected structure. The latter is
usually coated or wrapped because the current required to protect an uncoated structure would be too high to make the method economic. Thus, the
coating or wrapping is the prime defence with cathodic protection dealing with breaks in the coating.

Sacrificial anodes (zinc, aluminium, magnesium alloys) are also used (Figure 4). In this case the auxiliary electrode is made of a metal more active
than the one requiring protection. It becomes the anode in the corrosion cell when connected to the item requiring protection, which becomes the
http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 9/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

cathode. No external current is required, but protection ceases if the anode corrodes completely.

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 10/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 11/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

Anodic protection requires a "passive" layer to form and protect the metal from corrosion. An external current is applied in the opposite direction to
that for a cathodic system. It drains electrons from the surface, raising the potential of the anode to a value at which the metal becomes passive (see
Figure 5). The current density required is high, but once passivity is attained only a very small current is required to run the system. A further
attraction is the high "throwing" power of the current which reaches areas remote from the cathode. The system is potentially useful inside
complicated tanks and long pipelines.

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 12/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

The liquid being handled must lend itself to passivation, e.g. sulphuric acid. The current and the environment require careful monitoring to ensure that
the correct conditions are maintained. If they are not, rapid corrosion occurs.

Electrical insulation increases the resistance at some part of a corrosion cell, reducing the current flow and therefore the corrosion rate. For example,
the electrical resistivity of demineralised water is much greater than that of a salt solution and the rate of corrosion in the former is correspondingly
lower.

Re­routing pipes to avoid low resistivity corrosive soils reduces the corrosion risk. Laying pipes through soils of differing resistivities may set up
anodic areas in the metal in low resistivity soil and cathodic regions in high resistivity soil, creating corrosion cells.

Such "long line" currents are prevented by inserting insulating joints between sections of pipes.

Finally, insulating dissimilar metals from each other, e.g. aluminium cladding sheets from the supporting steel, eliminates the risks of galvanic
corrosion.

5. AEROBIC AND ANAEROBIC ORGANISMS


Although detailed explanations are beyond the scope of this lecture, engineers and architects should be aware of the effects of aerobic and anaerobic
organisms in promoting the corrosion of steel or ironwork immersed in water or buried in the ground. In practical terms expert advice should be
obtained when dealing with any project where the environment is likely to promote the growth of bacteria.

Aerobic organisms are those requiring free oxygen to prosper and anaerobic ones are organisms which require no oxygen.

In the field of corrosion, sulphate reducing bacterial (SRB) are probably the best known; they are certainly the most destructive. In our predominantly
aerobic environment they are dormant because they are strictly anaerobic organisms. As the oxygen level in an environment decreases, e.g. in stagnant
water areas on a jetty at low tide, the SRB become active. As the cells increase by­products are produced which initiate anaerobic corrosion. Their
metabolism requires the reduction of sulphate molecules to water, releasing free sulphide which reacts with hydrogen to form an extremely corrosive
gas, hydrogen sulphide. This process not only depresses the oxygen level, encouraging further growth, but reacts with the iron and steel.

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 13/14
3/12/2015 ESDEP LECTURE NOTE [WG4A]

6. CONCLUDING SUMMARY
Whilst this area of work is the province of the corrosion prevention technologist, engineers and architects need to know aspects that must be
considered.
Protective treatments for offshore structures are different for steelwork at and above deck level and at the tidal levels below deck.
Protective systems for sheet piling require knowledge of the stress levels and ranges in the product and the conditions of the soil/water in which
it is to be driven.
Damage during construction and use requires the use of coatings resistant to impact, particularly in maritime situations. Electrolytic methods of
corrosion control may offer the best solutions in these situations.
Consideration must be given to the possibility of bacteria growths which can cause corrosive action to take place on steelwork which is
immersed in water or buried in the ground.

7. ADDITIONAL READING
1. "Effect of Cathodic Protection Level and Stress Ratio on the Fatigue Strength of Welded Plate Specimens in Seawater", Microfiche Report with
OTH 89 310, London, HMSO, 1990.
2. Thorpe, T. W., "Influence of Stress Spectrum, Seawater and Cathodic Protection on Fatigue Crack Propagation in Structural Steels", London,
HMSO, 1990.
3. Carney, R. F. A., "Cathodic Protection of Steel in Real and Simulated Seawater Environments", London, HMSO, 1989.
4. Waite, D., "Steel Piles", Chapter 29 ­ Steel Designers' Manual, Oxford, Blackwell Scientific Publications, 1992.
5. Wijngaard, B. H., "Steel Piling Corrosion in Marine Environments ­ a Survey", EUR 7430, EEC, ECSC, 1982.

Previous | Next | Contents

http://www.fgg.uni­lj.si/~/pmoze/ESDEP/master/wg04a/l0500.htm#SEC_1 14/14