Mist Cooling System
Mist Cooling System
01
Where to use
● Urban areas: Landmarks, entrances of buildings, airports, ● Racing stables, pig houses, poultry houses for easing heat
stations, underground parking lots exhaustion
●Amusement facilities/cooling places: theme parks, amusement ●Green houses for controlling the temperature and humidity
parks, zoos ●Factories and workspaces for improving the environment
●Sports facilities: golf driving ranges, stadiums ●Healthcare facilities for improving the environment
●Entrances of shops, terraces, spaces for relaxation ※See pp. 3-6 for examples of installations
Surrounded air
or skin surface
95
phenomenon. We revived this idea using our technology of (electric power)of normal
fine mist sprays. air-conditioning equipment for %
lowering temperature. This power
consumption
eco-friendly low-carbon-footprint is saved
system is suitable for cooling a
wide open space.
High-pressure pump
with a controller
2
Case Study 1
4
Case Study 2
Factories / Warehouses
Fine mist spray system helps
your job under severe condition
in a forge plant, a warehouse,
or a workshop.
6
Hydraulic Nozzles
Hydraulic Spray Nozzles spray very fine mist by atomizing liquid under high pressure. It is environmental friendly compare
to Air Atomizing Nozzles, because only hydraulic pressure is used. The average particle size is about 20μm, which is
suitable for fine mist cooling systems.
Dimensions Specifications
Plastic Flow Rate
(L/h) ※
Inlet Connection : R1/4 Particle
Model Number
Operating Pressure Range : 2-8MPa 2MPa 4MPa 6MPa 8MPa diameter
(φ8.4)
approx.
R1/4 YB1/4MN-5.5V(yellow) 3.2 4.5 5.5 6.4 29μm
approx. 0.3 MPa) and strainer are
14 24 (2.5) included approx.
YB1/4MN-11V(black) 6.4 9.0 11.0 12.7 30μm
(Unit :mm)
approx.
YB1/8MN-SS1.8V 0.9 1.5 1.8 2.1
Metal 20μm
Inlet Connection: R1/8 approx.
R1/8 YB1/8MN-SS2.5V 1.2 2.0 2.5 2.9
Metal
Solenoid
valve
2.5m
Air speedometer
Rain sensor Tap water
制御盤 Clear water
Thermometer
1.5m
Hygrometer
High-pressure
pump
32.3℃ 28.1℃ 29.0℃
Pump unit※
※The installation of a high pressure pump, a pressurized piping, and other related tools ※The above data is just one example.
are necessary for this system. Please contact our sales office for details. ※The measurement result varies depending on the environment.
Dimensions Specifications
Inlet Connection : R1/8 ※
Flow Rate(L/min.)
Operating Pressure Range : 2-10MPa Particle
Model Number
diameter
(Φ8)
AT Nozzles
Sensible moisture of mist particles
AT Nozzles create middle sized particles at small flow rates, which people can
feel the moist. Doubled orifice type can spray widely in the horizontal direction.
Dimensions Specifications
Inlet Connection : R1/4(Male) ,
14.3 8.2 Flow Rate(L/min.)
adjustable using an adopter Particle ※
Model Number
Operating Pressure Range : 1.2-4MPa 2MPa 3MPa 4MPa diameter
Φ17.5
Main Materials :
Brass NiCr-plate(body) , approx.
Y1/4AT-08V 0.07 0.09 0.10 35μm
PF1/4 Ceramic(orifice)
Check valve(working pressure approx.
16 19.2
0.4 MPa) and strainer are included ※ Data at 4MPa water pressure. Measure point : 200mm under the nozzle,
33.5 Sauter Mean Diameter(SMD)
(Unit :mm)
Fine Mist Cooling System equipped with Hydraulic / Air Atomizing nozzles
8
Air Atomizing Nozzles
Air Atomizing nozzles create ultrafine mist consisting smaller particles than hydraulic nozzles by breaking up water
using low-pressure compressed air. Drop size of the mist is 10μm or less.
Example of Usage
Air atomizing General-purpose
Spray nozzles Spray Nozzles
Wide variety of portfolio / Good for using
Air Water
as an automated spray gun
Wide range of portfolio enables customers
to choose the most suitable mist type and
the spray amount. This nozzle can be
used as an automated spray gun with
Controller Solenoid valve on-off control system.
Air Solenoid valve ※See our catalog“Automatic Spray Gun”for details.
speedometer
Tap water
Rain sensor Purified water
Compressor
Thermometer
Hygrometer
Pump
Pump unit
※The installation of a compressor, liquid and air pipe lines, and other related tools are
necessary for this system. Please contact our sales office for the installation.
The hybrid functions of fine mist and air fans bring an innovation to your environment.
We offer different types of system for different locations and purposes.
※Please contact our office for the explosion-proof Misting Fan Unit.
10
Pump Unit for Misting
Discharge rate
(50Hz/60Hz)
6.9MPa
0.8L/min
(1.0L/min)
source. Multiple features are in Connection φ15 hose nipple(for water supply)
Tank: Polypropylene
Main materials Pump, solenoid valve: Brass
Features, such as the Pedestal, covers: coated SUS
materials(SUS)
, and the Mass(empty tank) Approx. 46kg
Intermittent
interlocking sensor system Timer control
spray time setting
ー
of temperature, humidity, (Minimum setup time
unit : 1 sec.)
wind speed, and rainfall ※ Under the condition of 50Hz
can be customized as
necessary. MT-PU-1
Handling Instructions
●Use an earth leakage breaker.
●The power distribution work shall be done by a qualified electrical worker in accordance with codes or standards related to electrical installations in your country. Do not
manually twist electric wires when you connect power codes. Use a“metal box for conduit”mentioned in JIS C 8340 or appropreate standards in your country.
●Use clean water for the pump. The use of water left for long or contaminated water may have a negative effect on a peron’
s health.
●If you use a tank for supplying water, remove water inside the tank regularly for keeping it clean. Before the prolonged storage, be sure to remove all water inside the tank
and the hoses.
●In the evnet of a mulfunction or a repair of this product, please contact our sales office or factory.
●Damages or trobles cauzed by the inappropreate use, repair, or remodeling are not warrantable.
Spraying Systems Co. reserves the right to make changes in specifications or design
of the products shown in the bulletin at any time without notice or obligation.
Yohkaichiba Factory