Datablad Vertiv PCW
Datablad Vertiv PCW
Annexes
Annex A - Water Circuit Diagrams...................................55
Annex B - Dimensions and Weights................................59
Annex C - Connections.....................................................69
Annex D - Accessories......................................................75
Annex E - Additional Accessories...................................79
Item Definition
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8 9 10 11 12 13
3.3 Environment
WARNING
Do not use in explosive, acid or anyway aggressive atmosphere.
Indoor environment, protected against weather agents. Clean (no dust), well-ventilated, non-
Storage environment
condensing
Ambient temperature -20°C / +50°C
Ambient humidity <90% and preventing condensation
The total storage time should not exceed six months.
Storage time If the storage time is longer than six months, then you must check the functionality of sensors and
other electronic devices before putting in operation the unit.
Position Keep the unit vertically upright.
The unit is designed for indoor installation, protected from weather agents, with the following
Operating environment
ambient conditions.
Temperature +18°C — +45°C
Air returning to the unit
Absolute humidity 5,5 — 11 g steam / kg air
inlet
Relative humidity 20 — 60 %
(indoors conditions)
A very low thermal load will cause inaccurate temperature and humidity control
Minimum water inlet temperature 5°C
Chilled water system Maximum water pressure 16 bar
Water-Glycol mixture limit Up to 50% vol.
Analyze the water It is the user’s responsibility to establish the quality of the water and make sure that this is compatible with
the materials used in the exchangers.
material provides a support for bacteria, fungi and CJ- ppm < 50
algae; the growth of organisms may produce an PO43- ppm < 2,0
oxygen gradient and this results in rather severe
NH3 ppm < 0,5
pitting of the metallic surface.
The phenomenon of corrosion is obviously related Free Chlorine ppm < 0,5
to the material used on the liquid side of the heat Fe3+ ppm < 0,5
exchanger.
Mn++ ppm < 0,05
The table on the right shows the reference values
for corrosion on copper, these values must be CO2 ppm < 50
considered as guidelines to avoid corrosion. H 2S ppb < 50
Temperature °C < 65
Oxygen content ppm < 0,1
The unit takes the air from the front The unit takes the air from the top The unit takes the air from the top The unit takes the air from the
and deliver from the top. The unit and deliver from the front through and deliver from the bottom, with top and deliver from the bottom,
is suited for ducted application. a grill on the front panel(s). with fans running in the raised
The unit can be installed with and The unit shall be installed directly
directions permit to optimize unit
of the unit is closed. is closed.
delivery.
The unit takes the air from the front The unit takes the air from the top The unit takes the air from the top The unit takes the air from the top
and deliver from the top. The unit and deliver from the bottom, with and deliver from the back of the and deliver from the front of the fan
is suited for ducted application. fan module, with fans running on module, with fans running on the
The unit can be installed with and
The unit takes the air from the The unit takes the air from the top
top and deliver from the bottom, and deliver from the bottom, with
with fans running in the raised
Delivering the air from the back of
directions permit to optimize unit the fan module. The unit is suited
delivery.
C E
D C
F B F B
A E A D
A Coil section The coil section is completely closed by panels and by the door for protection against any
contact with electric parts and hot or cold surfaces.
B Fan section The fan section is completely closed by panels and grids for protection against any contact with
moving parts.
C Control panel The unit is usually controlled remotely by a network connection.
The control panel is optional and may be placed on the front door or inside the front door.
D Doors The doors can be opened only by the proper tool.
E Fan safeguards The fixed panels (safeguards) can be removed only by loosing the fixing screws.
F Rear safeguards
B C
Main components
A Fan
B Water coil
C Water valve
A
Dual Circuit
Operating principle
These units shall be connected to chilled water circuits
The inclined coil is manufactured from copper tubes and mechanically bonded to hydrophilic
painted aluminum fins and is pressure tested to 30 bar. The large face area/low velocity coil
allows precise control of temperature and humidity during cooling and dehumidification and
is designed to optimize fluid velocity and minimize pressure drop, reaching the highest SHR
value (Sensible Heat Ratio).
The hydrophilic coating shall significantly improve the speed of condensate drainage from the
fins and shall provide superior water carryover resistance. One stainless steel condensate
drain pan shall be provided.
The unit is equipped with a chilled water The unit is equipped with a chilled water
circuit with a 2-way modulating valve, circuit with a 3-way modulating valve,
complete with motor for the control complete with motor for the control
is suitable for up to 1400 kPa closing is suitable for up to 1400 kPa closing
pressure. The valve shall be designed pressure. The valve shall be designed
for up to 1600 kPa water pressure. for up to 1600 kPa water pressure.
PICV valve
[ l/s]
PW025 1.8
PW030 1.8
PW035 2.5
PW040 2.5
PW046 2.5
PW045 4.8
PW060 4.8
PW066 4.8
PW070 4.8
PW080 4.8
PW091 4.8
PW095 9.6
Pressure independent valves PW110 9.6
compensate for pressure variations, PW136 9.6
performing a continuous balancing PW145 9.6
function to maintain system performance PW161 9.6
at varying loads. The actuator is suitable PW170 9.6
for up to 1400 kPa closing pressure. The
PW201 9.6
valve shall be designed for up to 1600
kPa water pressure.
The unit is fitted with variable speed, high efficiency, single inlet, backward curved, centrifugal ‘plug’ type innovating EC fan(s).
The fan(s) have an impeller with curved blades corrosion resistant. The fan motors are Electronically Commutated, IP54, with
internal protections, continuous speed regulation via controller signal.
The fan wheel is statically and dynamically balanced of degree G6.3 according to ISO 21940-11:2016; the bearings are
selflubricating.
A separator should be installed between the fans to eliminate turbulence effects of one fan to the others; it shall be also
designed to increase efficiency compared to simple plate separators.
When the unit is equipped with more than one fan, the airflow is guaranteed until at least one fan will still be running, thus
granting cooling continuity.
4.4.2 Filters
Standard filters The standard filtration grade is ePM10 50% according to ISO/EN16890. The ePM10 50% standard
filters are made by paper material and are completely recyclable.
The filter pleated structure gives high filtration efficiency, low pressure drops and allows the use
of the filter without metallic or cardboard frame. The filter media is composed by fiber and latex.
They are easily accessed/replaced by opening the front panel(s).
Filters are laying on the coil surface to maximize the filtering surface so reducing air pressure drop.
On the top of the coil an L shape filter is placed to add more surface and to optimize coil exchange
rate.
High efficiency filters An extension hood with high efficiency air filter can be supplied on request and can be installed
(accessory) on top of the unit. It is available with 600mm height, it shall be the same design as the unit and
consist of sandwich panels lined with non-flammable insulation material of class A1 EU, density
20 kg/m3. Inside the hood optional high efficiency filters, filtration class ePM10 70%, ePM1 60%
or ePM1 80% in accordance with the ISO/EN 16890 standard. The filters are made of fiberglass
filter media. They are placed in “V” sections with a solid external frame in polypropylene and can
withstand remarkable pressure and flow variations.
EN ISO16890 :2017
EN779 :2012
99%
90%
F9
F8
80%
G4
70% M6 F7 F8
60%
G3
M6 F7
M5
50%
G2
40%
30%
20%
ISO Coarse ISO ePM10 ISO ePM2.5 ISO ePM1
The heating resistors are of a rigid design for extended operational life and are normally utilized
to maintain room dry-bulb conditions during a system call for dehumidification. Each stage of
the heaters is made of finned armored stainless steel AISI 304 to maintain a low surface power
density. Ionization effects are eliminated owing to the low heater surface temperature.
Heating control is of the ON-OFF type. The heaters are phase balanced and a safety air high
temperature sensor measures the air temperature at the unit outlet and switches off the heater
if the air temperature is higher than the alarm threshold, moreover, heaters are provided with a
manual reset safety thermostat to disable them in the event of a high temperature.
The heating system also incorporates Miniature Circuit Breaker(s) which protect the heater(s)
from short circuits, should the harness be damaged accidentally. Due to the heat load generated
by the electrical heaters, these devices should respect a distance of 20cm around the fan blades
circumference.
Power [kW]
Power [kW]
Power [kW]
Power [kW]
Power [kW]
Nominal
Nominal
Nominal
Nominal
Nominal
Nominal
FLA [A]
FLA [A]
FLA [A]
FLA [A]
FLA [A]
FLA [A]
PW025 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW030 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW035 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW040 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW046 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW045 10.8 7.5 - - 9.4 7.5 - - 11.4 7.5 - -
PW060 10.8 7.5 21.6 15.0 9.4 7.5 18.8 15.0 11.4 7.5 22.8 15.0
PW066 10.8 7.5 21.6 15.0 9.4 7.5 18.8 15.0 11.4 7.5 22.8 15.0
PW070 10.8 7.5 21.6 15.0 9.4 7.5 18.8 15.0 11.4 7.5 22.8 15.0
PW080 10.8 7.5 21.6 15.0 9.4 7.5 18.8 15.0 11.4 7.5 22.8 15.0
PW091 10.8 7.5 21.6 15.0 9.4 7.5 18.8 15.0 11.4 7.5 22.8 15.0
PW095 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW110 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW136 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW145 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW161 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW170 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
PW201 10.8 7.5 32.5 22.5 9.4 7.5 28.2 22.5 11.4 7.5 34.2 22.5
Hot Water reheating/heating (optional) The single hot water heating coil is installed downstream of
B
4.4.4
is mixed with the discharge air from the evaporating coil by means of a copper steam distributor.
Technical data
Main power supply Setting(1) Absorbed Power MAX water MAX water MAX
current cylinder supply drained
volume water
[V ± 10%] [kg/h] [A] [kW] [l] [l/min] [l/min]
400 V / 3 ph / 60 Hz 3,9 - 8 8,7 6 5,5 0,6 7,0
460 V / 3 ph / 60 Hz 3,9 - 8 7,5 6 5,5 0,6 7,0
380 V / 3 ph / 60 Hz 3,9 - 8 9,1 6 5,5 0,6 7,0
Technical data
The unit shall be ready for the installation on the bottom part
Technical data
transformers, controller PCB, overload relays etc. Each high voltage system component is provided with an MCB over-current
protective device. All high voltage components are touch protected. Once open, the electrical panel can be rotated on the right to
allow for an easier installation/maintenance procedure.
Each unit is equipped, on the internal electrical panel, with an ON/OFF switch which allows to turn ON-OFF the unit especially
when the unit is without display. Close to the switch a LED provides visual indication of the unit ON/OFF status.
The electrical panel complies with the IEC norm EN60204-1.
Power supply • Check that the maximum unbalance between the phases does not exceed the value given in 6.
variability Technical Data.
• Make sure to comply with the following data:
- Electrical voltage between 0.9 and 1.1 nominal voltage
- Frequency between 0.99 and 1.01 the nominal frequency
- Variability of supply voltage less than 2%
Power supply The units are equipped with electrical devices (power supplies module, control devices,...) that are
connection designed to operate properly with star-connected power (Wye) with earthed neutral (TN or TT system).
If you need three-phase distribution Delta-connected (Δ) or Star-connected power (Wye) without ground
Standard power Single supply line The unit is fed by main line, Once power is restored the
in case of power failure unit unit waits control reboots
(roughly 60 seconds) and
after start again to operate.
Dual power supply Double power supply to the The unit is fed by two Once main power restored
“parallel” same disconnecting switch separate power supplies,
main line and UPS/Genset. are available and they can be
In case of power failure only enable.
UPS/Genset is available and
unit grant cooling
Dual power supply Double power supply to the The unit is fed by two Once main power restored ATS
alternate ATS electric panel, which is separate power supplies: switch back to the main line.
connected to the main electric each power supply can
panel. Each power supply can completely feed the unit. In
supply completely the unit. case of main line failure ATS
switches to the second power
supply. This allows to have
a complete power supply
redundancy and therefore to
have full cooling redundancy.
Switching time at nominal
current excluding loss of
supply sensing time and
excluding any delay timers
applicable is at least 1.2 s
-1.5 s.
Dual power supply Double power supply to the Once main power restored
alternate with Ultracap ATS electric panel, which is Supply Alternate Version. ATS switch back to the main
for Control connected to the main electric The unit is fed by two line.
panel. Each power supply separate power supplies:
can supply completely the each power supply can
unit. Control board is powered completely feed the unit. In
through an ultracap. case of main line failure ATS
switches to the second power
supply. This allows to have
a complete power supply
redundancy and therefore to
have full cooling redundancy
during emergency mode.
Switching time at nominal
current excluding loss of
supply sensing time and
excluding any delay timers
applicable is at least 1,2-1,5 s.
The ultracapacitor when
completely charged, is
capable of maintaining alive
the CPU, the BMS card
and the passive sensors for
at least 1 minute (only the
optional small semi-graphic
display can be kept active
by the ultracapacitor), the
full charging time for the
ultracapacitor is 5 minutes.
The remote sensors are
frozen during the power OFF.
Industrial
This choice aims to comply with requirements of compatibility of light industrial environments as regards the emission of
disturbances, resisting to external disturbances without having any functionality compromised. In terms of the norm references for
emissions: the conducted voltage disturbance must be lower than 73 dBuV and radiated voltage disturbance lower than 50 dBuV
(@ 3 m).
Residential (optional)
to the same power supply, and these are more sensitive to disturbance emitted by other devices, so a higher severity is needed
when the unit emissions are measured.
In terms of the norm references for emissions: the conducted voltage disturbance must be lower than 66 dBuV and radiated
voltage disturbance lower than 40 dBuV (@ 3 m).
alarms (limits), run hours for each device, timer bands, event log, unit overview and system
overview.
system changes.
Warnings / alarms More than 240 types of warnings / alarms / messages are displayed including:
- High temperature (return/remote/supply)
- Low temperature (return/remote/supply)
- High relative humidity (return/remote)
- Low relative humidity (return/remote)
- Fan failure
- Electrical heater high temperature
- Sensor failure
Unit can storage up to 100 events in a memory.
Each unit shall have one factory mounted return temperature and humidity
settings shall be changeable by the Service Personnel during commissioning if this is necessary;
cooling capacity and fan speed PIDs can be decoupled if needed.
Temperature control
mode are available:
- Return
- Supply
- Remote
Fan speed control
mode - Return Sensor
- Remote Sensor
- Delta T between Return temperature and supply temperature
- Static Pressure
- Return CW priority
- Fixed Speed
Humidity control mode
driven.
Two options are available:
- Return Sensor
- Remote Sensor
Humidity Control Type Humidity Control Type available are:
- Relative
- Relative Compensated
- Absolute
- Dew Point
.
4.6.2 Teamwork
An U2U (unit to unit) communication between multiple units via Ethernet network (up to 32 units) allows for advanced control
functionality: teamwork modes, sharing sensor data, standby rotation, lead-lag, cascade operation, auto restart delay and rotating
master function; without the need of a dedicated sequencing panel.
Four ‘teamwork’ mode can be adopted.
No Teamwork
The units work independently on the cooling control. Sensor values and setpoints are not shared.
Teamwork mode 1
(Parallel)
is changed in any of the units, all other units will follow with the same changed setting.
Teamwork Mode 2
(Independent)
In this Teamwork mode, all relevant control parameters are shared; if a value is changed in any of
the units, all other units will follow with the same changed setting.
Teamwork Mode 3 The con
(Smart Aisle) request is used for driving cooling and heating. Note: this teamwork mode can be set only if
the smart aisle option has been enabled and remote sensors are ordered. The unit should have
Lead-lag Units, before to go in standby mode, shall continue operation for the time set in “Overlap Timer”.
Auto Restart Delay Avoid a simultaneously re-start of multiple units (no matter if teamwork is selected or not). Each
unit has a delay time between Power On and starting of the fans after a power cycle.
Cascade Usually Standby Units will start in case of an alarm of one of the Duty Units.
Cascaded units will also start in order to help the Duty Unit base on the cooling request (Teamwork
case of an alarm/failure.
Rotating Master As part of the robust architecture of the control, when the Master gets disconnected from the
network, another unit will automatically change to be the Master. All system values are available
for all connected units.
When the Master gets disconnected from the network, another unit (the unit with the lowest
U2U_ID in the remaining network) will automatically change to be the Master. This feature avoids
system reset when the Master disappears or when it comes back available in the system.
The unit is equipped by default with a special switch that allows to change easily
last position or driving it to pre-set point. Once the communication has been re-established, the valve and fans control are released
never impact the unit supply air temperature threshold, in order to guarantee the right temperature in front of the technical
equipments. This feature is available with all the chillers which implement this feature and can communicate with the indoor units.
4.6.6 Monitoring (optional)
The unit features website that can be accessed via HTTP using a common browser.
If the monitoring card is present the unit can communicate with Building Management Systems and Network Management
5.1 Performances
Chilled water perimeter cooling units’ performances are linked to working conditions: return air and water temperatures. Each unit
model can provide a wide range of capacity depending on the environment it’s applied in, with a hoc coil to best suit the new data
center market trends.
Below a description of the most common conditions currently used in data center applications, which are in continues evolution
and they differentiated according to customers’ needs.
Liebert® PCW is an extremely flexible unit able to adapt to different site needs, Vertiv™ sales force can provide the unit
performances at different working conditions through a dedicated selecting tool.
Legacy
This kind of system generally includes a freecooling chiller and works with water regimes from 10°C to 15°C. Server containment
is not so common and the return air temperature to the Liebert® PCW is around 26°C. This system gives the possibility to work
in freeccoling mode thanks to low external temperatures during the entire cold season. The inlet water temperature around 10°C
minimizes the dehumidification effect compared to a comfort application, thus reducing energy wastage.
Smart
This kind of system generally includes freecooling/adiabatic chiller and works with water regimes from 18°C to 26°C, they are
always combined with a server containment. It’s a system optimized to offer the highest energy efficiency, thanks to the closure
of the aisle the return air to the Liebert® PCW can be significantly high and therefore higher water temperatures are allowed. This
maximizes the freecooling period and makes this system suitable for all climates; even on hot countries.
Eco
This kind of system is generally made of a standard chiller without freecooling and works with water regimes from 8°C to 15°C.
This system is often applied when the same chilled water system is used both for cooling the data center as well as for other
applications. In case of an existing system, only the perimeter chilled water units are replaced and no other modifications to the
chilled water plant is required. Thanks to server containment the return air to the Liebert® PCW can be significantly high. The low
water temperatures increase the risk of dehumidification and for data center applications the dehumidification is not an advantage,
in fact the only heat load provided by the server is sensible heat load. Liebert® PCW is thus optimized to provide the highest net
sensible capacity even at low water temperatures.
Working point
Rated performances are stated in PCW Product document for the working points specified in the following table:
Coil type ESP (*) Return Air RH Inlet Water Outlet Water
[Pa] temperature [°C] [%] temperature [°C] temperature [°C]
Legacy coil 20 26 40 10 15
Smart coil 20 35 30 18 26
Eco coil 20 30 30 8 15
Dual source coil 20 24 50 7 12
(*) External Static Pressure - NOTE: For performance in specific working point, please use selection software.
Air conditions 26°C/40% RH,water conditions 10/15°C, fan modulation 80% - LEGACY COIL
"Nominal air
m3/h 7493 7348.6 10992.2 10819.6 11524.1 11927.6 20510.1 21615.5 21782.3
flow"
SHR --- 1 1 1 1 1 1 1 1 1
Downflow Up
"Net sensible
cooling kW 26.8 29.1 39.5 44.1 45.2 47.8 72.1 83.5 79.3
capacity"
"Unit power
kW 1.31 1.27 1.67 1.69 1.6 1.53 3.47 3.37 3.35
input"
Water flow l/s 1.34 1.45 1.97 2.19 2.23 2.35 3.61 4.15 3.95
Water pressure
kPa 77 74 51 90 52 46 100 99 75
drop
Air conditions 26°C/40% RH,water conditions 10/15°C, fan modulation 80% - LEGACY COIL
"Nominal air
m3/h 21412 22316.9 31336.6 30674.9 32263 31948.5 33349.1 40185.2 41947
flow"
SHR --- 1 1 1 1 1 1 1 1 1
Downflow Up
"Net sensible
cooling kW 85.5 96.9 111.1 119.8 135.8 137.2 151 168.4 188.1
capacity"
"Unit power
kW 3.39 3.27 5.16 5.22 5.04 5.07 4.92 6.99 6.83
input"
Water flow l/s 4.24 4.79 5.55 5.97 6.73 6.8 7.44 8.38 9.31
Water pressure
kPa 56 94 118 85 89 85 78 96 66
drop
Air conditions 26°C/40% RH,water conditions 10/15°C, fan modulation 80% - LEGACY COIL
"Nominal air
m3/h 7493 7348.6 10992.2 10819.6 11524.1 11927.6 20510.1 21615.5 21782.3
flow"
SHR --- 1 1 1 1 1 1 1 1 1
"Net sensible
cooling kW 26.4 28.7 39.1 43.7 45.1 47.5 71 83.2 78.4
Upflow
capacity"
"Unit power
kW 1.7 1.7 2.11 2.12 1.73 1.81 4.57 3.71 4.23
input"
Water flow l/s 1.34 1.45 1.97 2.19 2.23 2.35 3.61 4.15 3.95
Water pressure
kPa 77 74 51 90 52 46 100 99 75
drop
capacity"
"Unit power
kW 4.25 3.53 6.48 6.51
input"
Water flow l/s 4.24 4.79 5.55 5.97
Water pressure
kPa 56 94 118 85
drop
Air conditions 35°C/30% RH,water conditions 18/26°C, fan modulation 80% SMART
COIL
"Nominal air
m3/h 7208.8 10653.4 11420.3 19654.8 21615.5
flow"
SHR --- 1 1 1 1 1
Downflow Up
"Net sensible
cooling kW 30.4 46 49.1 82.5 89.3
capacity"
"Unit power
kW 1.28 1.71 1.61 3.55 3.39
input"
Water flow l/s 0.95 1.43 1.52 2.58 2.78
Water pressure
kPa 61 80 66 116 102
drop
Air conditions 35°C/30% RH,water conditions 18/26°C, fan modulation 80% SMART COIL
"Nominal air
m3/h 21056.1 22107.1 30042.9 31884.5 31948.5 33349.1 40185.2 41947
flow"
SHR --- 1 1 1 1 1 1 1 1
Downflow Up
"Net sensible
cooling kW 90.1 101.2 125.4 142.6 136.4 151.9 167.9 187.7
capacity"
"Unit power
kW 3.43 3.31 5.28 5.1 5.07 4.92 6.99 5.83
input"
Water flow l/s 2.8 3.13 3.91 4.43 4.24 4.7 5.24 5.83
Water pressure
kPa 72 94 84 98 74 77 83 68
drop
Air conditions 35°C/30% RH,water conditions 18/26°C, fan modulation 80% SMART COIL
"Nominal air
m3/h 7208.8 10653.4 11420.3 19654.8 21352.2 21056.1 22107.1 30042.9 21782.3
flow"
SHR --- 1 1 1 1 1 1 1 1 1
"Net sensible
cooling kW 30 45.6 49 81.4 89 89.2 101 124.2 78.4
Upflow
capacity"
"Unit power
kW 1.71 2.13 1.74 4.47 3.75 4.27 3.55 6.54 4.23
input"
Water flow l/s 0.95 1.43 1.52 2.58 2.78 2.8 3.13 3.91 3.95
Water pressure
kPa 61 80 66 116 102 72 94 84 75
drop
"Net sensible
cooling kW 26.1 39.8 48.2 70.4 78.6 108.9
capacity"
"Unit power
kW 1.27 1.63 1.5 3.39 3.25 5.01
input"
Water flow l/s 0.93 1.41 1.69 2.52 2.79 3.88
Water pressure
kPa 43 52 32 80 65 83
drop
capacity"
"Unit power
kW 1.69 2.09 1.79 4.55 4.19 6.42
input"
Water flow l/s 0.93 1.41 1.69 2.52 2.79 3.88
Water pressure
kPa 43 52 32 80 65 83
drop
"Net sensible
cooling kW 1.75 1.66 3.59 3.47 3.47 3.33
capacity"
"Unit power
kW 1 1 1 1
input"
Water flow l/s 1.5 1.76 2.68 3.2 3 3.51
Water pressure
kPa 85 62 92 83 72 72
drop
"Net sensible
cooling kW 5.31 5.1 5.13 4.95 7.07 6.87
capacity"
"Unit power
kW 1 1 1 1 1 1
input"
Water flow l/s 4.16 4.94 4.58 5.3 5.63 6.51
Water pressure
kPa 85 71 67 61 84 73
drop
NOTE Values given for each single fan. The model is the same both for 50 Hz and 60 Hz.
Threated Connections – optional Two threaded pipes can be supplied when the standard connections are Victaulic.
Bottom connections The unit is provided with bottom left hydraulic connections.
Dual circuit units provided with bottom left and right hydraulic connections
Top connections The unit is provided with top left hydraulic connections.
Lateral connections The unit is provided with lateral coil section (left side) hydraulic connect.
alarm signal.
Nominal Power
Unit model FLA [A]
[kW]
All models 1,6 0,15
NOTE
• Internal condensate pump kit available for 400 V / 3ph / 50 Hz and
380 V / 3ph / 60 Hz power supply.
• Internal condensate pump kit available for all units except Downflow
PW025 and Downflow PW030.
• For 460 V / 3ph / 60 Hz available only external kit.
and display unit cooling gross capacity. Water temperatures and cooling gross capacity values can be available on display and
shared with BMS system if monitoring card is present.
Measured item Unit Measuring range Expected error range
Water Temperature all 5 ÷ 35° C ± 0,2° C
PW025...PW046 0,8 ÷ 4,0 l/s ± 0,20 l/s
PW045...PW066 1,2 ÷ 6,0 l/s ± 0,30 l/s
Water Flow
PW070...PW091 2,0 ÷ 10,2 l/s ± 0,50 l/s
PW095...PW201 2,8 ÷ 14,1 l/s ± 0,70 l/s
allows to calculate and display unit cooling gross capacity. Cooling gross capacity value can be available on display and shared
with BMS system if monitoring card is present.
6.1 Introduction
Liebert® PCW units have been designed with particular care for sound and vibration problems.
Highest ventilation efficiency combined with the lowest sound emission have been obtained by the following design criteria:
- optimization of the aeraulic circuit by accurate researches made in our thermodynamic laboratories, with special focus on
coils and filters
- complete mechanical insulation of the ventilating section
PWL Sound Power Level calculated according to ISO 3744 procedure method
SPL Sound Pressure Level measured in free field conditions and at 1 meter from the unit according to ISO 3744
average method
Mode (1) Only ventilation, measured as explained in Test conditions above
Measurement conditions: High Efficiency EC fan module, 80% of fan modulation Sound
Unit
level
model Level 31.5 63 125 250 500 1000 2000 4000 8000
db(A)
PWL 62.7 62.7 68.6 73.1 75.2 77.2 75.2 70.9 62.9 81.2
PW025
SPL 59.7 59.7 65.0 65.0 57.9 51.5 46.9 38.6 30.1 60.1
PWL 62.4 62.4 68.3 72.8 74.9 76.9 74.9 70.6 62.6 80.9
PW030
SPL 59.4 59.4 64.7 64.7 57.6 51.2 46.6 38.3 29.8 59.8
PWL 71.9 71.9 76.6 81.2 84.9 86.1 81.9 87.4 72.0 91.7
PW035
SPL 63.3 63.3 68.6 68.6 61.5 55.1 50.5 42.2 33.7 63.7
PWL 71.5 71.5 76.2 80.8 84.5 85.7 81.5 87.0 71.6 91.3
PW040
SPL 62.9 62.9 68.2 68.2 61.1 54.7 50.1 41.8 33.3 63.3
PWL 74.6 74.6 79.2 84.2 88.9 90.5 85.9 89.8 74.9 95.1
PW046
SPL 41.6 41.6 61.4 64.6 61.8 60.0 56.4 48.9 39.3 64.5
PWL 72.2 72.2 76.9 81.5 85.3 86.5 82.2 87.6 72.2 92.0
PW045
SPL 62.0 62.0 67.3 67.3 60.2 53.8 49.2 40.9 32.4 62.4
PWL 67.2 67.2 73.4 78.3 81.6 83.4 80.2 79.0 68.6 87.3
PW060
SPL 65.4 65.4 70.7 70.7 63.6 57.2 52.6 44.3 35.8 65.8
PWL 77.5 77.5 82.9 87.9 91.8 93.5 89.7 90.7 78.4 97.6
PW066
SPL 45.8 45.8 65.6 68.8 66.0 64.2 60.6 53.1 43.5 68.7
Downflow Up
PWL 68.7 68.7 74.1 79.0 83.0 84.7 80.8 82.1 69.6 88.9
PW070
SPL 65.0 65.0 70.3 70.3 63.2 56.8 52.2 43.9 35.4 65.4
PWL 68.3 68.3 73.7 78.6 82.6 84.3 80.4 81.7 69.2 88.5
PW080
SPL 64.6 64.6 69.9 69.9 62.8 56.4 51.8 43.5 35.0 65.0
PWL 77.9 77.9 82.9 87.9 92.3 93.9 89.7 92.1 78.5 98.3
PW091
SPL 44.9 44.9 64.7 67.9 65.1 63.3 59.7 52.2 42.6 67.8
PWL 69.9 69.9 75.8 80.7 84.2 86.0 82.6 82.1 71.1 90.0
PW095
SPL 67.3 67.3 72.6 72.6 65.5 59.1 54.5 46.2 37.7 67.7
PWL 69.5 69.5 75.4 80.3 83.8 85.6 82.2 81.7 70.7 89.6
PW110
SPL 66.9 66.9 72.2 72.2 65.1 58.7 54.1 45.8 37.3 67.3
PWL 79.4 79.4 84.9 89.8 93.7 95.4 91.6 92.5 80.3 99.5
PW136
SPL 47.8 47.8 67.6 70.8 68.0 66.2 62.6 55.1 45.5 70.7
PWL 69.7 69.7 75.3 80.3 84.0 85.8 82.1 82.4 70.7 89.8
PW145
SPL 66.1 66.1 71.4 71.4 64.3 57.9 53.3 45.0 36.5 66.5
PWL 79.8 79.8 84.9 89.9 94.2 95.8 91.6 93.9 80.5 100.1
PW161
SPL 47.0 47.0 66.8 70.0 67.2 65.4 61.8 54.3 44.7 69.9
PWL 72.3 72.3 78.7 80.7 81.7 84.3 83.5 78.0 70.7 88.7
PW170
SPL 70.0 70.0 75.3 75.3 68.2 61.8 57.2 48.9 40.4 70.4
PWL 81.2 81.2 87.0 91.9 95.5 97.3 93.8 93.6 82.4 101.3
PW201
SPL 50.1 50.1 69.9 73.1 70.3 68.5 64.9 57.4 47.8 73.0
Measurement conditions: High Efficiency EC fan module, 80% of fan modulation Sound
Unit
level
model Level 31.5 63 125 250 500 1000 2000 4000 8000
db(A)
PWL 59.5 59.5 65.4 69.9 72.0 74.0 72.0 67.7 59.7 78.0
PW025
SPL 56.5 56.5 61.8 61.8 54.7 48.3 43.7 35.4 26.9 56.9
PWL 59.4 59.4 65.3 69.8 71.9 73.9 71.9 67.6 59.6 77.9
PW030
SPL 56.4 56.4 61.7 61.7 54.6 48.2 43.6 35.3 26.8 56.8
PWL 68.3 68.3 73.0 77.6 81.3 82.5 78.3 83.8 68.4 88.1
PW035
SPL 59.7 59.7 65.0 65.0 57.9 51.5 46.9 38.6 30.1 60.1
PWL 68.0 68.0 72.7 77.3 81.0 82.2 78.0 83.5 68.1 87.8
PW040
SPL 59.4 59.4 64.7 64.7 57.6 51.2 46.6 38.3 29.8 59.8
PWL 71.9 71.9 76.5 81.5 86.2 87.8 83.2 87.1 72.2 92.4
PW046
SPL 38.9 38.9 58.7 61.9 59.1 57.3 53.7 46.2 36.6 61.8
PWL 68.8 68.8 73.5 78.1 81.9 83.1 78.8 84.2 68.8 88.6
PW045
SPL 58.6 58.6 63.9 63.9 56.8 50.4 45.8 37.5 29.0 59.0
Upflow
PWL 63.9 63.9 70.1 75.0 78.3 80.1 76.9 75.7 65.3 84.0
PW060
SPL 62.1 62.1 67.4 67.4 60.3 53.9 49.3 41.0 32.5 62.5
PWL 74.8 74.8 80.2 85.2 89.1 90.8 87.0 88.0 75.7 94.9
PW066
SPL 43.1 43.1 62.9 66.1 63.3 61.5 57.9 50.4 40.8 66.0
PWL 68.1 68.1 73.5 78.4 82.4 84.1 80.2 81.5 69.0 88.3
PW070
SPL 64.4 64.4 69.7 69.7 62.6 56.2 51.6 43.3 34.8 64.8
PWL 64.9 64.9 70.3 75.2 79.2 80.9 77.0 78.3 65.8 85.1
PW080
SPL 61.2 61.2 66.5 66.5 59.4 53.0 48.4 40.1 31.6 61.6
PWL 75.3 75.3 80.3 85.3 89.7 91.3 87.1 89.5 75.9 95.7
PW091
SPL 42.3 42.3 62.1 65.3 62.5 60.7 57.1 49.6 40.0 65.2
PWL 66.7 66.7 72.6 77.5 81.0 82.8 79.4 78.9 67.9 86.8
PW095
SPL 64.1 64.1 69.4 69.4 62.3 55.9 51.3 43.0 34.5 64.5
PWL 66.5 66.5 72.4 77.3 80.8 82.6 79.2 78.7 67.7 86.6
PW110
SPL 63.9 63.9 69.2 69.2 62.1 55.7 51.1 42.8 34.3 64.3
NOTE: The sound levels global and for each octave band are expressed in dB with a tolerance of ( 0/+2) dB.
PWL - Sound Power Level calculated according to ISO 3744 procedure method.
SPL - Sound Pressure Level measured in free field conditions and at 2 meters from the front of the unit and 1,5 meters above the surface
according to ISO 3744 average method.
All PCW units have very high noise emission at maximum airflow.
Relevant expected values of Sound level dB(A) for lower airflow can be found in technical literature and simulation software.
The following tables show Sound Pressure Level reduction for units with one row of
silencing cartridges compared to the same units without silencing cartridges.
The measurements are made at the positions [D] and [F] as shown in the figure.
SPL reduction
Unit configuration position D position F
Downflow up -7,0 dB -4,0 dB
Upflow -12,0 dB -7,5 dB
NOTE:
Flow meter is installed on inlet pipe before T connection on straight pipe part
NOTE:
Flow meter is installed on inlet pipe before T connection on straight pipe part
NOTE:
Flow meter is installed on inlet pipe before T connection on straight pipe part
NOTE In the units of frame type 1 the coil section and the fan section are integrated. In the units with frame types 2, 3, 5, 6 and
7 the coil section and the fan section are separate modules that are assembled together.
U H D E Standard h = 1970 mm
Extended h = 2570 mm
h
h
600
The figure above shows the height from the floor for each air distribution configuration.
Accessory on top of the unit Height [D]: see the table below.
D
H - Downflow Frontal
D - Downflow Up
E - Downflow Down
D - Downflow Up
E - Downflow Down
No accessories for
With legs kit With base frame
support
Frame type
A B C A B C A B C
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1 740 760 70 Not available 804 830 30
890
840
1200
1750
2050
5 2 450 760 70 2 506 820 30 2 526 840 30
890
2550
2950
7 3 250 760 70 3 306 820 30 3 326 840 30
890
3350
NOTE [C] is the minimum free space between the unit at its final position and any back wall or obstacle. You might need more space for assembly
or installation operations. In that case, do the assembly or installation operation nearby and then place the unit at the final position.
No accessories for
With floor tiles support kit
support
Frame type
A B C A B C
[mm] [mm] [mm] [mm] [mm] [mm]
1 Not available Not available
890
840
2
890
3
890
4
890
6
890
NOTE [C] is the minimum free space between the unit at its final position and any back wall or obstacle. You might need more space for assembly
or installation operations. In that case, do the assembly or installation operation nearby and then place the unit at the final position.
Packaging
Single circuit unit Double circuit unit
MODEL "Standard “Wood “Seaworthy
[kg] [kg]
[kg]" Crate [kg]” [kg]”
Standrad Height unit
PW025 310 - 19 55 130
PW030 320 - 19 55 130
PW035 356 - 23 60 150
PW040 373 396 23 60 150
PW045 481 - 28 65 180
PW060 511 552 28 65 180
PW070 582 - 31 70 200
PW080 598 627 31 70 200
PW095 680 - 42 75 235
PW110 740 753 42 75 235
PW145 853 866 47 78 250
PW170 955 968 58 80 290
Extended Height unit [Coil Module] (1)
BFW12 91 26 60 125
BFW17 150 35 70 135
BFW20 170 41 75 150
BFW25 218 54 88 170
BFW29 245 61 95 185
BFW33 325 78 105 200
Extended Height unit [Fan Base Module/Fan Top Plenum] (1)
(1) For Extended Height version, the total unit weight must be calculated by adding the Coil Module weight and Fan Section weight
NOTICE
Add +150 mm to the total packaging height for standard and wooden crate packaging if the unit is equipped with
damper
Seaworthy packaging
In addition to the standard cardboard packing the packing contains desiccant bags, the whole unit is wrapped in VCI foil and
enclosed within a seaworthy wooden box.
Fig.11.c - Packing of unit
BFW12 1280 960 800 1382 1062 850 1376 1056 1035
BFW17 1830 960 800 1932 1062 850 1926 1056 1035
BFW20 2130 960 800 2232 1062 850 2226 1056 1035
BFW25 2630 960 800 2732 1062 850 2726 1056 1035
BFW29 3030 960 800 3132 1062 850 3126 1056 1035
BFW33 3430 960 800 3532 1062 850 3526 1056 1035
BMW12/TPW12 1280 960 800 1382 1062 850 1376 1056 1035
BMW17/TPW17 1830 960 800 1932 1062 850 1926 1056 1035
BMW20/TPW20 2130 960 800 2232 1062 850 2226 1056 1035
BMW25/TPW25 2630 960 800 2732 1062 850 2726 1056 1035
BMW29 3030 960 800 3132 1062 850 3126 1056 1035
BMW33 3430 960 800 3532 1062 850 3526 1056 1035
Chilled water
O.D. Ø64 mm** O.D. Ø64 mm** O.D. Ø64 mm**
ou- tlet Rp 1 ¼ Rp 1 ¼ Rp 1 ½ O.D. Ø54 mm**
OCW R 2½ R 2½ R 2½ 344
ISO 7/1 ISO 7/1 ISO 7/1 R 2 - ISO7/1***
ISO7/1*** ISO7/1*** ISO7/1***
Chilled water
inlet 2 Rp 1 ¼ Rp 1 ½ Rp 1 ½ O.D. Ø54 mm** O.D. Ø54 mm** O.D. Ø54 mm**
ICW2 NA 394
ISO 7/1 ISO 7/1 ISO 7/1 R 2 - ISO7/1*** R 2 ISO7/1*** R 2 - ISO7/1***
1 - Overpressure damper
2 - Motorized damper
The unit is configured with the bottom part open and the frontal panel
blacked in order to allow the air stream from the bottom to the top of
the unit. Filter positioning doesn’t need to be changed and the unit
guarantee easily access from the front of it.
5 - Alarm card
The unit shall be fitted with alarm card to allow remote monitoring
through electrical signals of most important alarms (up to 6), for
monitoring working conditions or events (failure). The outputs (all
together) can be set to N.O. (normally open) or N.C. (normally closed).
6 - Pressure control
7 - Ethernet Switch
The switch shall be accessible from the front of the unit with the door
closed and prevent access to the high-voltage electrical components
unit switched to the off positioning. The manual disconnect switch
shall be mounted in the high-voltage section of the electrical panel.
9 - Phase Detector
1 - Smoke/Fire detector
The smoke and fire detector sense the room air: in case of smoke,
unit activates the smoke alarm event without any actions; instead
in case of fire, unit activates the fire alarm event and shuts the unit
down. Dry contacts are available for a remote customer alarm. This
smoke detector is not intended to function as or replace any room
smoke detection system that may be required by local or national
codes.
4 - Legs kit
Legs kit can be supplied on request to support the unit when installed
with a raised floor. The legs are fixed with the unit frame and allow
supporting the unit at different heights, three kits are available with
different heights, adjustable in the range:
10 - Air economizer
The air economizer is an extension hood with two dampers and two
temperature sensors.
A sensor measures the temperature/humidity of the outdoor (cold)
air. The other sensor measures the temperature of the warm air
returning to the unit from the room. When the outdoor temperature
is low enough the outdoor air is mixed with the room air to adjust the
temperature. The two dampers can be placed in different positions
(front/back/top), to fit best the room and air ducts layout.
The control checks the external air condition (temperature/humidity)
and depending on environment conditions controls the dampers
system mixing the indoor unit air with cool outdoor air; it is possible to
have 100% outdoor air, mixed outdoor air and compressor cooling or
100% compressor cooling.
The unit shall use only air only if the psychometric conditions allow
this thus reducing wasting of energy humidifying or dehumidifying
once they should be not required.
Dampers arrangement
The two dampers can be placed in different positions, to fit best the room and air ducts layout. See below all the possible
arrangements.
Downflow
15 - System Display
The system Display is designed for networking multiple units
togethers. All models have a power supply that requires connection
to a single phase 230Vac power source with Schuko socket.