Final Analysis Report

The document provides design details for a residential building with RCC frame structure including slab, beam, column and wall load calculations and designs. Reinforcement details are provided for slab, column and wall designs. Load combinations used for analysis include dead, live, equipment/storage, floor finish and earthquake loads.

Uploaded by

Himanshu Dev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views12 pages

Final Analysis Report

The document provides design details for a residential building with RCC frame structure including slab, beam, column and wall load calculations and designs. Reinforcement details are provided for slab, column and wall designs. Load combinations used for analysis include dead, live, equipment/storage, floor finish and earthquake loads.

Uploaded by

Himanshu Dev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

DESIGN DATA

1 Building Type : Residential

2 Type of structure : RCC Frame Structure

3 No. of Storey : 2 Storey

4 Concrete Grade : M20

5 Reinforcement Used : Fe500

6 Cement Used : Ordinary Portland Cement

7 Load Taken
Dead
Live roof
Wall
Partition Wall
Live storage
Live normal
Floor Finish
Dead load of staircase
Water tank
Earthquake Load

8 Design Philosophy - Limit State Design Confirming NBC 105:2020

9 Analysis Software Used = Etabs VER 20

10 Earthquake Load Consideration = User Coefficient


.LOAD CALCULATIONS

A. Slab Load
Slab weight 0.127 25 3.175
Floor Finish 1.095
Total 4.27 kN/Sqm

B. Beam Load
B D Density WEIGHT/M
0.254 0.432 25 2.74

C. Column Load
L B Density H WEIGHT
Column 0.355 0.355 25 2.97 9.37
Total 9.37 kN/m

D. Wall Load
60 % of Adopted
L B Density H WEIGHT wall Value
10 " wall 0.25 19.2 2.693 12.9264 7.75584 9.67 kN/m
5" wall 0.127 19.2 2.693 6.56661 3.93997 4.92 kN/m
Parapet Wall 0.115 19.2 1 2.208 2.2 kN/m
Stair Load 20 kN/m 20 kN/m
Assuming 30 % of Openings

Live Load
Room 2 kN/m²
Corridor, Staircase 3 kN/m²
Hall 3 kN/m²
LOAD CASES AND COMBINATIONS USED FOR ANALYSIS

LOAD CASES Load Combination

Load Case Name Load Case Type


as per NBC 105:2020
Dead Linear Static 1.2DL + 1.5 LL
Live Linear Static For Dynamic analysis
Modal Modal - Eigen DL + µLL ± E DL + µLL ± E
Wall Linear Static where, µ = 0.6 for storage facilities
P. Wall Linear Static µ = 0.3 for other usages
Floor Finish Linear Static

DL of staircase Linear Static


Live storage Linear Static
Live normal Linear Static
water tank Linear Static
EQx Linear Static
EQy Linear Static
EQx SLS Linear Static
EQy SLS Linear Static
RSX Response Spectrum
RSY Response Spectrum
DESIGN OF SLAB
Analysis
Shorter Span (Lx) = 4.2672 m Load detail lower upper exact
Longer Span (Ly) = 4.8768 m dead Load= 3.175 kn / m2 now, Ly / Lx = 1.1 Ly / Lx = 1.2 Ly / Lx = 1.14286
Now, Ly / Lx = 1.14286 ok live load= 4 kn / m2 coff. ax ax ax ay
other= 1.095 kn / m2 edge 0.053 0.06 0.056 0.047
Type of Panel (case No.) = 4 8.27 mid 0.04 0.045 0.04214 0.035
Suggested Span / depth (L/d) = 26 Load Calculation
Then, depth (d) = 187.569 mm Wx= 12.41 kn / m2 moment about Y axis about X axis
Shear force (Vx) = 17.64487 kn Edge -10.61648189 -12.64942523
depth Taken (d)= 112 mm (Vy)= 14.88786 kn mid 7.905890769 9.519337865
(D)= 127 mm Verification of depth d min= 67.69878 mm fy= 500 n/mm2
check "dadopt >dmin" OKAY fck= 20 n/mm2

Reinforcement Design
a) Along X-Direction

End Reinforcement Mid Reinforcement


Adopt d = 112 mm Adopt d = 112 mm
No Deflection contrl finding area of steel (Ast) according to deflection control criteria
needed at end portion Hence, moment (M)= 7.905891 kn-m
moment (M)= 10.6165 kn-m Ast = 168.6184 mm2
Ast = 229.684 mm2 Req. Ast = 168.6184 mm2
Req. Ast = 229.684 mm2 actual L/d = 38.1
Provided L/d= 26 * modification factor
provide the steel as = Hence needed M.F.= 1.465385 Changing steel can make safe against deflection
8 mm dia 150 mm c/c distance
then provided steel = 335.103 provide the steel as 8 mm dia 150 mm c/c distance
% of tension steel= 0.2992
Okay then provided steel = 335.1032 Okay % of tension steel= 0.2992
fs= 145.9232
Date: May 2016 hence, modification factor = 2
Ok and Finished

b) Along Y-Direction

End Reinforcement Mid Reinforcement


Adopt d = 107 mm Adopt d = 107 mm
No Deflection contrl finding area of steel (Ast) according to deflection control criteria
needed at end portion Hence, moment (M)= 9.519338 kn-m
moment (M)= 9.51934 kn-m Ast = 215.3549 mm2
Ast = 215.355 mm2 Req. Ast = 215.3549 mm2
Req. Ast = 215.355 mm2 actual L/d = 39.88037
Provided L/d= 26 * modification factor
provide the steel as = Hence needed M.F.= 1.533861 Changing steel can make safe against deflection
8 mm dia 150 mm c/c distance
then provided steel = 335.103 provide the steel as 8 mm dia 150 mm c/c distance
% of tension steel= 0.31318
Okay then provided steel = 335.1032 Okay % of tension steel= 0.31318
fs= 186.3692
hence, modification factor = 1.9609
Ok and Finished
DESIGN OF COLUMN
Concrete Grade (fck): 20 Steel Grade (fy): 500 Effective Cover: 40 mm
Column Size Ast Bars Provided Lateral Ties (Fe500)
Required Percentage
Column Total Ast Shear
Floor Width as per of Steel
Column Type Depth ( Area Bar Bar Nos. of Provided Stirrup Reinforce Result
name (Y) ETABS No. No. Provided
X ) mm (mm2) (mm) (mm) Bars (mm2) Legs ment Dia.
mm DESIGN (Pt%)
Provided (mm)
(mm2)
8 16
C1 355 355 126025 1569 8 1609 1.27673081 4 8 ok
FOR Grids B1/C1
GF
4 16 4 12
C2 355 355 126025 1121 8 1257 0.99742115 4 8 ok
FOR Rest of The Grids
4 16 4 12
FF C2 355 355 126025 1121 8 1257 0.99742115 4 8 ok
FOR Rest of The Grids
DESIGN OF BEAM (Slab beam)

Fck = 20 Effective cover = 25mm


Fy = 500 Beam size = 10" * 17"
TOP STEEL 2-16mm & 1-12mm
GROUND FLOOR
BOTTOM STEEL 3-12 mm

TOP STEEL 2-16mm & 1-12mm


FIRST FLOOR
BOTTOM STEEL 3-12 mm

TOP STEEL 3-12 mm


TIE BEAM (10"*12")
BOTTOM STEEL 3-12 mm

TOP STEEL 3-12 mm


BASE BEAM (10"*15")
BOTTOM STEEL 3-12 mm
TABLE: Joint Reactions
Story Label Output Case Case Type Step TypeStep Number FX FY FZ MX MY MZ
kN kN kN kN-m kN-m kN-m
Base 29 1.2 DL + 1.5 LL Combination -0.7729 6.2652 386.0718 -8.8418 0.5884 -0.2301
Base 26 1.2 DL + 1.5 LL Combination 5.8941 9.5258 366.1162 -12.7307 7.0193 -0.2301
Base 28 1.2 DL + 1.5 LL Combination -2.8916 13.0323 301.0725 -15.3693 -2.1061 -0.2301
Base 19 1.2 DL + 1.5 LL Combination -1.6706 28.5704 286.7499 -26.2484 1.9147 -0.453
Base 32 1.2 DL + 1.5 LL Combination -5.9432 4.6229 210.4797 -6.6998 -4.3989 -0.2301
Base 17 1.2 DL + 1.5 LL Combination 7.9869 8.3767 205.3069 -12.1801 9.038 -0.2301
Base 31 1.2 DL + 1.5 LL Combination -4.8353 10.7977 157.9852 -12.656 -3.9811 -0.2301
Base 1 1.2 DL + 1.5 LL Combination 5.0354 12.2978 153.3389 -15.9624 5.5402 -0.2301
Base 30 1.2 DL + 1.5 LL Combination 7.1889 -11.6854 86.6544 8.4732 9.012 -0.2301
Base 27 1.2 DL + 1.5 LL Combination -1.91 -11.1472 83.809 7.2104 0.2353 -0.2301
Base 18 1.2 DL + 1.5 LL Combination 9.3359 -7.5192 64.626 3.153 11.083 -0.2301
DESIGN OF FOUNDATION
Isolated /eccentricFooting Design (F1)
for All joint labels (5' * 5')
Required Data
size of colunm=
l= 0.355 m
b= 0.355 m
Bearing Capacity of Soil= 150 KN/m²
Strength of Steel (fy)= 500 N/mm²
Strength of Concrete (fck)= 20 N/mm² ( M 20 )
Axial Load = 387 KN
Eccentricity of loading (ex) = 0.000 m
Eccentricity of loading (ey) = 0.000 m

Approximate area of footing= 2.58 m²


Design Load = 580.5 KN
Actual Area= 3.8700 m²
Size of Square Footing = 1.967 m

Adopted size=
L= 1.524 m
B= 1.524 m
Actual area of footing = 2.322576 m²
Net Pressure acting upwads = 249.94 KN/m²
B. M. at the face of column about an axis = 43 KN-m/m
(Per unit meter width)

The effective depth required is given by


BM= 0.138 fck*bd^2

Date: May 2016


req d= 100.7 mm
adopt d= 140 mm
Adopt D = 2 to 3 Times of calculated value of d for Shear considerations.

Adop. D= 381 mm

Check for one-way Shear action


The critical section is taken at distance d away from the face of column

Shear force Vu= 77.48 KN


Nominal shear stress (Tv) = Vu/b*d = 0.13 N/mm²

Allowable Shear Stress of Concrete for pt% of Steel < = 0.15 & ( M 20 )
Tc = 0.315783 N/sq.mm (From IS 456: 2000, table 19)
Hence, OK
Tc should be equal to or greater than Tv

Check for two-way Shear action

The critical section is taken at a distance of 0.5d away from the face of column ,
Shear force Vu= 445.07 KN
Nominal Shear Stress(Tv) = Vu/b'd (Where b' is the periphery of critical section )
and b' = 2944.39 mm

So, Nominal Shear Stress(Tv) = 0.40 N/mm²


Shear Strength of concrete is
Tc = 1.12 N/sq.mm
T'c = Ks*Tc Where Ks=(0.5+Bc)
Bc=length of shorter side of column/length of longer side of column
Bc= 1
Ks= 1.5 should not be greater than 1
Take(Ks)= 1
T'c= 1.12 N/mm²
Hence, OK T'c should be greater than Tv

Area of Steel Calculation


Area of Steel is given by formula, BM = 0.87* fy* At*{d-fy*At/(fck*b)}
Then,
Ast = 260.46 sq.mm < Ast min = 0.12% of b * d
457.3171 mm²
Req. Area of steel = 457.3171 mm²
Steel requied as 12 mm bar @ 247.3061737 mm c/c distance.

Provide Steel as = 12 mm bar @ 152.4 mm c/c distance.


Provided steel = 742.1085 mm²
Hence Ok.
Percent of steel = 0.195