FusionModule2000 Smart Modular Data Center

V500R003C10
Product Description

Issue 06

Date 2020-05-21

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. i


FusionModule2000 Smart Modular Data Center
Product Description About This Document

About This Document

Purpose
The FusionModule2000 smart modular data center solution (FusionModule2000 for short)
includes smart modules A and B. This document describes the FusionModule2000 product
positioning, features, application scenarios, and system architecture, providing the systemic
information about the smart modular data center.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule2000 Smart Modular Data Center
Product Description About This Document

Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.

Issue 06 (2020-05-21)
Added section "Integrated UPS (60 kVA, 125 kVA)".
Added section "NetCol5000-A035 Smart Cooling Product".
Updated section "Server".

Issue 05 (2020-01-21)
Updated the UIM20A expansion Module.

Issue 04 (2019-12-04)
Updated the USB description.

Issue 03 (2019-11-05)
Updated section "(Optional) eLight".

Issue 02 (2019-08-30)
Updated the server model.

Issue 01 (2019-06-30)
This issue is the first release.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule2000 Smart Modular Data Center
Product Description Contents

Contents

About This Document ............................................................................................................... ii


1 Positioning ................................................................................................................................ 1
2 Features ...................................................................................................................................... 2
3 Product Description ................................................................................................................. 4
3.1 Solution Overview ................................................................................................................................................. 4
3.2 Single-Row 1200 mm Wide Aisle Containment ...................................................................................................... 5
3.3 Dual-Row 1200 mm Wide Aisle Containment ........................................................................................................ 6

4 Typical Configurations............................................................................................................ 8
5 Power Supply and Distribution System ............................................................................. 11
5.1 System Overview ................................................................................................................................................. 11
5.1.1 Power Supply and Distribution System for Smart Module A ...............................................................................16
5.1.2 Power Supply and Distribution System for Smart Module B ...............................................................................19
5.2 System Hardware .................................................................................................................................................25
5.2.1 Integrated UPS (50 kVA, 125 kVA) ....................................................................................................................25
5.2.1.1 Product Structure ............................................................................................................................................25
5.2.1.2 Power Module ................................................................................................................................................29
5.2.1.3 Bypass Module ...............................................................................................................................................30
5.2.1.4 Control Module ..............................................................................................................................................31
5.2.1.4.1 Overview .....................................................................................................................................................31
5.2.1.4.2 ECM............................................................................................................................................................31
5.2.1.4.3 Dry Contact Card .........................................................................................................................................33
5.2.1.4.4 Monitoring Interface Card ............................................................................................................................34
5.2.1.5 MDU ..............................................................................................................................................................39
5.2.1.6 Technical Specification ...................................................................................................................................41
5.2.2 Integrated UPS (60 kVA, 125 kVA) ....................................................................................................................44
5.2.2.1 Product Structure ............................................................................................................................................44
5.2.2.2 Power Module ................................................................................................................................................46
5.2.2.3 Bypass Module ...............................................................................................................................................47
5.2.2.4 Control Module ..............................................................................................................................................48
5.2.2.4.1 Overview .....................................................................................................................................................48
5.2.2.4.2 ECM............................................................................................................................................................49

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule2000 Smart Modular Data Center
Product Description Contents

5.2.2.4.3 Dry Contact Card .........................................................................................................................................50


5.2.2.4.4 Monitoring Interface Card ............................................................................................................................52
5.2.2.5 MDU ..............................................................................................................................................................57
5.2.2.6 Technical Specification ...................................................................................................................................59
5.2.3 Integrated PDF ..................................................................................................................................................63
5.2.4 Precision PDF....................................................................................................................................................66
5.2.5 New Main Way 2.0 ............................................................................................................................................67
5.2.5.1 General Input Unit ..........................................................................................................................................69
5.2.5.2 Power Distribution Unit ..................................................................................................................................72
5.2.6 Smart Cooling Product PDB ..............................................................................................................................72
5.2.7 Battery Cabinet ..................................................................................................................................................73
5.2.8 rPDU Introduction .............................................................................................................................................76
5.2.8.1 rPDU ..............................................................................................................................................................76
5.2.8.2 (Optional) Smart rPDU ...................................................................................................................................77

6 Cabinet Aisle System ............................................................................................................. 79


6.1 Cabinets and Accessories ......................................................................................................................................79
6.1.1 Network Cabinet................................................................................................................................................79
6.1.2 IT Cabinet .........................................................................................................................................................80
6.1.3 Top Sealing Plate ...............................................................................................................................................82
6.1.4 Cabinet Bottom Sealing Plate.............................................................................................................................83
6.1.5 Cabinet Enclosure Plate .....................................................................................................................................84
6.1.6 Cable Management Devices ...............................................................................................................................85
6.1.7 (Optional) Adjustable Base ................................................................................................................................88
6.2 Aisle and Mechanical Parts ...................................................................................................................................89
6.2.1 Skylight .............................................................................................................................................................89
6.2.2 Aisle End Door ..................................................................................................................................................91
6.2.2.1 Sliding Door ...................................................................................................................................................91
6.2.2.2 Revolving Door ..............................................................................................................................................91
6.2.2.3 Electric Sliding Door ......................................................................................................................................93
6.2.3 M-shaped Cable Trough .....................................................................................................................................93
6.2.4 (Optional) Mesh cable trough .............................................................................................................................94
6.2.5 (Optional) Cable Tray ........................................................................................................................................95
6.2.6 (Optional) Adaptive Frame.................................................................................................................................96
6.2.7 (Optional) Ground Copper Bar ...........................................................................................................................97

7 Temperature Control System................................................................................................ 99


7.1 System Overview .................................................................................................................................................99
7.2 NetCol5000-A025 Smart Cooling Product ............................................................................................................99
7.2.1 Indoor Unit Components....................................................................................................................................99
7.2.2 Controller ........................................................................................................................................................ 101
7.2.2.1 Appearance and Ports.................................................................................................................................... 101
7.2.2.2 Function and Features ................................................................................................................................... 103

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. v


FusionModule2000 Smart Modular Data Center
Product Description Contents

7.2.3 Application Environment ................................................................................................................................. 104


7.2.4 Technical Specifications................................................................................................................................... 107
7.3 NetCol5000-A035 Smart Cooling Product .......................................................................................................... 109
7.3.1 Indoor Unit ...................................................................................................................................................... 109
7.3.1.1 Appearance ................................................................................................................................................... 109
7.3.1.2 Components.................................................................................................................................................. 110
7.3.2 Outdoor Unit ................................................................................................................................................... 111
7.3.3 Controller ........................................................................................................................................................ 112
7.3.4 Physical Ports .................................................................................................................................................. 115
7.3.5 Technical Specifications................................................................................................................................... 115
7.4 NetCol5000-A050 Smart Cooling Product .......................................................................................................... 117
7.4.1 Product Composition ....................................................................................................................................... 118
7.4.2 Operating Environment Requirements .............................................................................................................. 121
7.4.3 Controller ........................................................................................................................................................ 123
7.4.4 Technical Specifications................................................................................................................................... 125
7.5 NetCol500 Outdoor Unit..................................................................................................................................... 126
7.5.1 Product Composition ....................................................................................................................................... 127
7.5.2 Technical Specifications................................................................................................................................... 129
7.5.3 (Optional) Low-Temperature Component ......................................................................................................... 131
7.5.4 (Optional) Sunshade ........................................................................................................................................ 133
7.6 Water Cooling Module........................................................................................................................................ 134

8 Intelligent Module Management System ......................................................................... 136


8.1 System Overview ............................................................................................................................................... 136
8.2 System Functions ............................................................................................................................................... 137
8.2.1 Monitoring ...................................................................................................................................................... 137
8.2.2 App View ........................................................................................................................................................ 137
8.2.3 Alarm .............................................................................................................................................................. 143
8.2.4 History Query .................................................................................................................................................. 143
8.2.5 Linkage Control............................................................................................................................................... 143
8.3 Key Hardware Devices ....................................................................................................................................... 144
8.3.1 ECC800-Pro Core Controller ........................................................................................................................... 144
8.3.1.1 Product Configuration ................................................................................................................................... 144
8.3.1.2 Main Control Module ................................................................................................................................... 146
8.3.1.3 Power Module .............................................................................................................................................. 154
8.3.2 UIM20A Expansion Module ............................................................................................................................ 155
8.3.3 PAD ................................................................................................................................................................ 158
8.3.4 Data Collection System .................................................................................................................................... 160
8.3.4.1 (Optional) Rack environment unit ................................................................................................................. 160
8.3.4.2 Smart ETH Gateway ..................................................................................................................................... 161
8.3.5 WiFi Module ................................................................................................................................................... 163
8.3.6 Skylight Actuator ............................................................................................................................................. 164

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. vi


FusionModule2000 Smart Modular Data Center
Product Description Contents

8.3.7 Environment Monitoring System ..................................................................................................................... 167


8.3.7.1 WLDS900 Water Sensor ............................................................................................................................... 167
8.3.7.2 (Optional) Cabinet Temperature Sensor ......................................................................................................... 168
8.3.7.3 T/H Sensor (BOM number: 02310NBS) ........................................................................................................ 169
8.3.7.4 T/H Sensor (BOM Number: 33010516) ......................................................................................................... 170
8.3.7.5 Multi-Functional Sensor ................................................................................................................................ 171
8.3.7.6 Alarm Beacon ............................................................................................................................................... 174
8.3.8 Access Control System .................................................................................................................................... 175
8.3.8.1 Access Actuator ............................................................................................................................................ 175
8.3.8.2 (Optional) Aisle Access Control System ........................................................................................................ 179
8.3.8.3 Fingerprint and Card Reader with a Keypad .................................................................................................. 179
8.3.8.4 Fingerprint and Card Reader ......................................................................................................................... 180
8.3.8.5 Card Reader with a Keypad ........................................................................................................................... 182
8.3.8.6 Magnetic Lock .............................................................................................................................................. 183
8.3.8.7 (Optional) Cabinet Access Control System .................................................................................................... 184
8.3.9 Video Surveillance System ............................................................................................................................... 185
8.3.9.1 IP Camera ..................................................................................................................................................... 185
8.3.9.2 VCN510 ....................................................................................................................................................... 187
8.3.9.3 VCN520 ....................................................................................................................................................... 188
8.3.9.4 VCN540 ....................................................................................................................................................... 189
8.3.10 Lighting System............................................................................................................................................. 190
8.3.10.1 AC Actuator ................................................................................................................................................ 191
8.3.10.2 Aisle Light (600 mm long) .......................................................................................................................... 193
8.3.11 (Optional) eLight ........................................................................................................................................... 194
8.3.12 (Optional) iBattery ......................................................................................................................................... 196
8.3.13 (Optional) Smart U Space Manager ................................................................................................................ 198

9 (Optional) NetEco6000 Intelligent Data Center Management System.......................... 199


9.1 System Functions ............................................................................................................................................... 199
9.2 Server................................................................................................................................................................. 200
9.3 LAN Switch ....................................................................................................................................................... 200

10 Surge Protection and Grounding System ....................................................................... 202


11 Integrated Cabling System................................................................................................ 204
12 UPS Derating Coefficients ................................................................................................ 206
A Acronyms and Abbreviations ............................................................................................ 207

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. vii


FusionModule2000 Smart Modular Data Center
Product Description 1 Positioning

1 Positioning

Huawei FusionModule2000 is a new-generation smart module dedicated to providing users


with simple, reliable, and efficient data center solutions. It has obtained the world's first
Uptime Tier IV Ready certification that proves the highest reliability.
The FusionModule2000 adopts modular design. It integrates power supply and distribution,
cooling, cabinet aisle, cabling, and monitoring into one module to meet the requirements for
fast delivery and on-demand deployment. Furthermore, the Huawei smart module uses the i 3
intelligent management system to comprehensively improve the reliability and energy
efficiency of power supply and cooling systems. The management system significantly
improves operation and maintenance (O&M) efficiency by alarm convergence and locating,
automatic fault isolation, and automated asset management.
The FusionModule2000 uses an air-cooled cooling system and is mainly applicable to small-
and medium-sized data centers. The solution features simple design and high building
adaptability, lowering the requirements of room height and reconstruction. It meets the data
center deployment requirements of various sectors such as enterprise headquarters or large
branches, bank headquarters and secondary branches, governments, carriers, education, and
healthcare.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule2000 Smart Modular Data Center
Product Description 2 Features

2 Features

FusionModule2000 is a new-generation smart modular data center (DC) product that adopts
an integrated solution which has advantages including security and reliability, smaller
equipment room footprint, less energy consumption, simplified and flexible installation with
higher efficiency and less manpower, architecture compatibility, fast and flexible deployment,
comprehensive monitoring, and stable cooling.

Modular Architecture and Automatic Design


 Solution productization and modular design meet the requirements for quick deployment
and flexible capacity expansion.
 The eLight status indicator reflects the module status.
 Atmosphere lights enhance user experience.
 The auto door is provided to prevent unauthorized personnel from entering an equipment
room and improve the security of the equipment room.
 The intelligent lighting system helps save energy. When a person comes into the aisle,
lights turn on automatically; when the person leaves the aisle, the lights turn off
automatically.

i3 Intelligent Management
 iPower
− The entire link status of the power supply and distribution system is displayed in
real time, and alarms are intelligently converged and located.
− Temperature detection (optional) for circuit breaker terminals on power distribution
branches avoid poor connection of branch contacts. In addition, miniature circuit
breakers (MCB) are hot-swappable and can be maintained without power-off. This
does not affect other branches.
− The iBattery intelligent battery management system (optional) monitors the battery
status in real time and isolates faults to eliminate fire hazards.
− The smart rPDU (optional) implements socket status monitoring, remote control,
and IT equipment protection.
 iCooling
− The running status of the cooling system is displayed in real time, and the status of
smart cooling products and key components is detected.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule2000 Smart Modular Data Center
Product Description 2 Features

− The 3D temperature map (optional) is linked with the cooling system to eliminate
partial hotspots, and the load power is linked with the cooling system to avoid
excessive temperature rise, ensuring the stability of the temperature field.
− Optimal efficiency adjustment based on Artificial Intelligence (AI) and automatic
load adjustment plus linkage between indoor and outdoor units save energy by 15%.
− The smart cooling product quickly restarts after power failure recovery, and this
effectively prevents a sharp increase in the aisle temperature due to the long restart
time of the smart cooling product.
− Innovative intelligent refrigerant leakage detection prevents cooling capacity
decrease or smart cooling product breakdown.
 iManage
− Room-level 3D visualized management and precise alarm locating considerably
improve O&M efficiency.
− Aisle-level face recognition and historical access control information viewing
enable access control management to be more intuitive and reliable.
− U space-level asset management (optional) implements automatic asset control to
maximize the use of cooling and power resources in the equipment room.
− Infrastructure O&M KPIs standardize O&M operations and improve device health.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule2000 Smart Modular Data Center
Product Description 3 Product Description

3 Product Description

3.1 Solution Overview


Smart module structures can be classified into the single-row 1200 mm wide aisle
containment and dual-row 1200 mm wide aisle containment.

Table 3-1 Smart module structures

Scenario Illustration
Single-row
aisle
containment

Dual-row aisle
containment

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule2000 Smart Modular Data Center
Product Description 3 Product Description

Table 3-2 Smart module installation modes

Scenario Illustration
Without a
raised floor
NOTE
Typically,
overhead
cabling and
overhead
piping

With a raised
floor
NOTE
Typically,
overhead
cabling and
underfloor/over
head piping,
bottom cabling
and
underfloor/over
head piping

3.2 Single-Row 1200 mm Wide Aisle Containment


The single-row 1200 mm wide aisle containment can be a cold or hot aisle containment that
involves the following components: IT cabinet, network cabinet, PDF, smart cooling product,
battery cabinet, skylight, end door, and cable trough. A cold aisle containment is used as an
example.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule2000 Smart Modular Data Center
Product Description 3 Product Description

Figure 3-1 Components of the single-row 1200 mm wide cold aisle containment

(1) End door (2) Control skylight (3) Flat or rotating skylight
(4) Alarm beacon (5) Cable trough (6) Access control device
(7) PAD (8) Cabinet

3.3 Dual-Row 1200 mm Wide Aisle Containment


The dual-row 1200 mm wide aisle containment can be a cold or hot aisle containment that
involves the following components: IT cabinet, network cabinet, PDF, smart cooling product,
battery cabinet, skylight, end door, and cable trough. A cold aisle containment is used as an
example.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule2000 Smart Modular Data Center
Product Description 3 Product Description

Figure 3-2 Components of the dual-row 1200 mm wide cold aisle containment

(1) End door (2) Control skylight (3) Flat or rotating skylight
(4) Alarm beacon (5) Cable trough (6) Access control device
(7) PAD (8) Cabinet

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

4 Typical Configurations

Table 4-1 Typical configurations

Smart Module Scenario Inside Smart Module Outside Smart Module


Smart module A (batteries Integrated UPS, smart -
deployed inside the cooling product, battery,
module) cabinet, aisle, and
mechanical parts
Smart module A (batteries Integrated UPS, smart Battery
deployed outside the cooling product, cabinet,
module) aisle, and mechanical parts
Smart module B Integrated power distribution UPS and battery
(integrated PDF) frame (PDF), smart cooling
product, cabinet, aisle, and
mechanical parts
Smart module B (precision Precision PDF, smart cooling UPS, battery, and smart
PDF) product, cabinet, aisle, and cooling product power
mechanical parts distribution box (PDB)
Smart module B (NMW) NMW, smart cooling UPS, battery, and smart
product, cabinet, aisle, and cooling product PDB
mechanical parts

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

Table 4-2 Scenario illustrations

Smart Module Illustration


Scenario
Smart module A
(batteries deployed
inside the module)

Smart module A
(batteries deployed
outside the module)

Smart module B
(integrated PDF)

Smart module B
(precision PDF)

Smart module B
(NMW)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule2000 Smart Modular Data Center
Product Description 4 Typical Configurations

Devices inside and outside the smart module can be deployed in one room or two rooms. If deployed in
one room, the smart module adopts the hot aisle containment design to ensure that the ambient
temperature for batteries meets requirements.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5 Power Supply and Distribution System

5.1 System Overview


Smart modules are classified into smart module A and smart module B by different power
supply and distribution systems.

Smart Module A
For smart module A, the integrated UPS is deployed inside the module and batteries can be
deployed inside or outside the module.

Figure 5-1 Layout of smart module A (batteries deployed inside the module, N+1 scenario)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-2 Layout of smart module A (batteries deployed inside the module, 2N scenario)

Figure 5-3 Layout of smart module A (batteries deployed outside the module, N+1 scenario)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-4 Layout of smart module A (batteries deployed outside the module, 2N scenario)

Table 5-1 Power distribution specifications

Item Specifications
Integrated  25 kW power modules are configured: 48 routes for IT
UPS(50kVA,125kVA) power distribution and 8 routes for smart cooling
product power distribution
 The 50 k VA and 125 k VA racks respectively provide
the single-route MCCB and dual-route ATS input.
 Supports maximum 50 kW or 125 kW IT loads.
 Supports maximum (2+1) or (5+1) 25 kW modules.
Integrated  30 kW power modules are configured: 48 routes for IT
UPS(60kVA,125kVA) power distribution and 8 routes for smart cooling
product power distribution
 The 60 k VA and 125 k VA racks respectively provide
the single-route MCCB and dual-route ATS input.
 Supports maximum 60 kW or 125 kW IT loads.
 Supports maximum (2+1) 30 kW modules or (5+1) 25
kW modules.

Smart Module B
For smart module B, the UPS is deployed outside the module. Power supply and distribution
supports the integrated PDF, precision PDF, and new main way (NMW).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-5 Layout of smart module B (integrated PDF/precision PDF, N+1 scenario)

Figure 5-6 Layout of smart module B (integrated PDF/precision PDF, 2N scenario)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-7 Layout of smart module B (NMW, N+1 scenario)

Figure 5-8 Layout of smart module B (NMW, 2N scenario)

Table 5-2 Power distribution specifications

Item Specifications
Integrated PDF 160 A/250 A power input (IT input circuit breaker and
smart cooling product input circuit breaker), 48 routes for
IT power distribution, 8 routes for smart cooling product
power distribution, and 1 route for lighting power
distribution; supports 95 kW/148.5 kW IT loads.
Precision PDF 160 A/250 A/400 A power input, supports maximum 144
routes for IT power distribution and 95 kW/148.5 kW/235
kW IT loads.
NMW 250 A/400 A power input, supports 123 kW/198 kW IT
loads.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.1.1 Power Supply and Distribution System for Smart Module A


For smart module A, the power supply and distribution system diagrams are the same
regardless of whether battery cabinets are deployed inside or outside the module.

N+1 Power Supply and Distribution System Diagram

Figure 5-9 N+1 power supply and distribution system diagram (ATS)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-10 N+1 power supply and distribution system diagram (MCCB)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N Power Supply and Distribution System Diagram

Figure 5-11 2N power supply and distribution system diagram

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.1.2 Power Supply and Distribution System for Smart Module B


N+1 Power Supply and Distribution System Diagram

Figure 5-12 N+1 power supply and distribution system diagram (integrated PDF)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-13 N+1 power supply and distribution system diagram (precision PDF)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-14 N+1 power supply and distribution system diagram (new main way)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N Power Supply and Distribution System Diagram

Figure 5-15 2N (isolation) power supply and distribution system diagram (integrated PDF)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-16 2N (non-isolation) power supply and distribution system diagram 1 (integrated PDF)

Figure 5-17 2N (non-isolation) power supply and distribution system diagram 2 (integrated PDF)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-18 2N power supply and distribution system diagram (precision PDF)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-19 2N power supply and distribution system diagram (new main way)

5.2 System Hardware


5.2.1 Integrated UPS (50 kVA, 125 kVA)
5.2.1.1 Product Structure

 The appearance of the UPS5000-E-125K-HABBS (02311FTD-002, 02311FTD-007) is similar to


that of the UPS5000-E-50K-HABBS (02311FTB-001, 02311FTB-009).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-002) is similar to that of the
UPS5000-E-50K-HASBS (02311FTC-001).
 The appearance of the UPS5000-E-125K-HASBS (02311FTE-004, 02311FTE-006) is similar to that
of the UPS5000-E-50K-HASBS (02311FTC-004, 02311FTC-006).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-20 UPS5000-E-50K-HABBS (02311FTB-001) front view

(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Power distribution circuit breaker for (5) IT load circuit (6) UPS input circuit
the smart cooling product breaker breaker
(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker
(10) Filler panel (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution monitoring board (14) UPS output
circuit breaker

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-21 UPS5000-E-125K-HASBS (02311FTE-002) front view

(1) Power input status (2) ATS (3) Lighting circuit


indicator breaker
(4) ATS handle (5) Power distribution circuit breaker (6) IT load circuit
installation slot for the smart cooling product breaker
(7) UPS input circuit (8) UPS maintenance bypass circuit (9) Control module
breaker breaker
(10) Bypass module (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution (14) UPS output circuit breaker
monitoring board

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-22 UPS5000-E-125K-HASBS (02311FTE-004) front view

(1) Power input (2) ATS drive module (3) ATS monitoring
status indicator module
(4) Lighting circuit (5) Power distribution circuit breaker (6) IT load circuit breaker
breaker for the smart cooling product
(7) UPS input (8) UPS maintenance bypass circuit (9) Control module
circuit breaker breaker
(10) Bypass module (11) Power module (12) ATS transfer switch
(13) ATS handle (14) Monitor display unit (MDU) (15) Power distribution
monitoring board
(16) UPS output
circuit breaker

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.1.2 Power Module

Appearance

Figure 5-23 Power module

(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port

Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.

Specifications
 Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
 Weight: < 21 kg
 Rated output capacity: 25 kVA/25 kW
 Power density: 17.2 W/inch3

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.1.3 Bypass Module

Appearance

Figure 5-24 Bypass module

(1) Positioning (2) Battery cold start (3) Run (4) Alarm indicator
lock button indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output
ports

Functions
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module is overloaded for a period longer than the maximum allowed period.
Both the active and standby ECMs are abnormal.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

The system fails to run properly and transfers to bypass mode.


A manual operation is performed to transfer to bypass mode.

Specifications
 Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
 Weight < 25 kg
 Maximum output power: 125 kW

5.2.1.4 Control Module


5.2.1.4.1 Overview
In a standard configuration, the control module consists of two ECMs, one dry contact card,
and one monitoring interface card (from left to right). The four cards are hot swappable. One
subrack is reserved above the dry contact card. A backfeed protection card or dry contact
extended card can be inserted into this subrack.

Figure 5-25 Signal panel on the control module

(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover

Ports are protected by a security mechanism.

5.2.1.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-26 ECM

Table 5-3 Ports on the ECM

Silk Screen Description


PARALLEL The PARALLEL port transmits parallel signals.
BSC The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.

Table 5-4 Indicator description

Indicator Color Status Description


NORMAL Green Steady on This ECM is the active ECM.
Blinking at 0.5 This ECM is the standby ECM and it is
Hz ready.
Off This ECM is not ready or the CPLD of
this ECM is being upgraded.
Blinking at 4 Hz The DSP of the ECM is being upgraded or
not configured.
ALM Yellow Steady on The ECM has a minor alarm, but it does
not need to be replaced.
Off The ECM has no minor alarm or the DSP
of the ECM is being upgraded.
FAULT Red Steady on The ECM has a critical alarm.
Off The ECM has no critical alarm or the DSP
of the ECM is being upgraded.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.1.4.3 Dry Contact Card


The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).

Figure 5-27 Dry contact card

Table 5-5 Ports on the dry contact card

Silk Description Status Initial Status


Screen
BTG Port for detecting battery  Connected: battery Disconnected
grounding faults grounding fault
 Disconnected: no
0V Port for signal ground
battery grounding
fault
GEN Port for detecting diesel  Connected: D.G. Disconnected
generator (D.G.) mode mode
 Disconnected:
0V Port for signal ground
non-D.G. mode
BCB_OL Port for detecting the BCB  Grounded: BCB Grounded
box box connected
 Disconnected:
BCB box not
connected
BCB_STA Port for monitoring the  Connected: battery Disconnected
battery switch switch ON
 Disconnected:
battery switch
OFF
BCB_DR Controls battery circuit  0 V: battery 0V
V breaker trip. When the switch not tripped
voltage is +12 V, the circuit  12 V: battery
breaker trips. switch tripped
BCB_0V Port for signal ground
EPO_NO Emergency power-off If the normally open Disconnected
(EPO) port (NO) port is
connected to the
EPO_12V +12 V EPO_12V port, EPO
is triggered.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Silk Description Status Initial Status


Screen
EPO_NC EPO port If the normally closed Connected
(NC) port is
EPO_12V +12 V disconnected from the
EPO_12V port, EPO
is triggered.
SWITCH Port for monitoring the UPS  Connected: circuit Connected
STATUS_ output circuit breaker breaker ON
OUT  Disconnected:
SWITCH Port for signal ground circuit breaker
STATUS_ OFF
0V
SWITCH Port for monitoring the  Disconnected: Disconnected
STATUS_ maintenance circuit breaker circuit breaker ON
MT  Connected: circuit
SWITCH Port for signal ground breaker OFF
STATUS_
0V
SWITCH Port for monitoring the  Connected: circuit Connected
STATUS_ bypass input circuit breaker breaker ON
BP  Disconnected:
SWITCH Port for signal ground circuit breaker
STATUS_ OFF
0V
SPD Port for monitoring the  Connected: SPD Connected
input AC surge protective enabled
device (SPD)  Disconnected:
0V Port for signal ground SPD disabled

 The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
 Set the EPO port to NO or NC as required.
 When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
 Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.

5.2.1.4.4 Monitoring Interface Card

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

 The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected and MDU communication fails. Conversely, if
the FE port is mistaken for the RS485 port during cable connection, RS485
communication fails.
 Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
 In a parallel system, ensure that used dry contacts properly connect to each UPS.

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.

Figure 5-28 Monitoring interface card

The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.

Table 5-6 Ports on the monitoring interface card

Port Silk Screen Description


DO_1 NO DO_1 is used to output alarms and indicates critical
alarms by default. It can be set to indicate minor
COM alarms, bypass mode, battery mode, or low battery
voltage.
DO_2 NO DO_2 is used to output alarms and indicates minor
alarms by default. It can be set to indicate critical
COM alarms, bypass mode, battery mode, or low battery
voltage
DO_3 NO DO_3 is used to output alarms and indicates bypass
mode by default. It can be set to indicate critical
COM alarms, minor alarms, battery mode, or low battery

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Port Silk Screen Description


voltage.
DO_4 NO DO_4 is used to output alarms and indicates battery
mode by default. It can be set to indicate critical
COM alarms, minor alarms, bypass mode, or low battery
voltage.
DB26 MDU Provides FE, RS485, I2C, and CAN signals.
Battery B_TEMP Connects to an indoor battery temperature sensor.
temperature sensor
port
Southbound COM1  Supported protocol: Modbus-RTU.
communications  Connects to an ambient temperature and
port 1 humidity sensor over two wires.
Southbound COM2  Supported protocol: Modbus-RTU.
communications  Connects to a southbound device.
port 2
Network port FE  Supported protocols: Modbus-TCP, HTTPS, and
SNMP.
 Connects to the network port on a PC.
Northbound RS485  Supported protocol: Modbus-RTU.
communications  Connects to a northbound network management
port device over two wires.

 Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
 RS485 cables and FE cables must be shielded cables.

Figure 5-29 and Figure 5-30 are recommended wiring methods for DO ports.

Figure 5-29 Wiring method 1

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-30 Wiring method 2

Figure 5-31 and Table 5-7 describe the COM1 pin definitions.

Figure 5-31 COM1 pins

Table 5-7 COM1 pin definition

Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT

Figure 5-32 and Table 5-8 describe the COM2 pin definitions.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-32 COM2 pins

Table 5-8 COM2 pin definition

Pin Description
1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0

Figure 5-33 and Table 5-9 describe the RS485 pin definitions.

Figure 5-33 RS485 pins

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-9 RS485 pin definition

Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A
8 N/A

If cables are prepared onsite, follow the three methods below:


 Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
 Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to
RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–.

5.2.1.5 MDU

Appearance

Figure 5-34 MDU

(1) Status indicator (2) LCD touchscreen

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-10 Status indicator

Status Color Meaning


On Red A critical alarm has been generated, and the buzzer sounds
continuously.
Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz.
Green The UPS is running properly or a warning has been generated.
Off N/A The MDU is powered off.

The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode.

Figure 5-35 MDU ports

Table 5-11 Description of MDU ports

No. Port Name Description


1 MUS05A Connects to the MDU and monitoring interface card
(DB26)

2 FE Network port
3 CAN Reserved
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to the
UPS over the Service Expert app. Obtain the initial
startup password during deployment. View or obtain
UPS running information during preventive
maintenance.
NOTE
Only Huawei service engineers or authorized service engineers are
allowed to use the WiFi module. To ensure security, remove the
WiFi module immediately after use.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

No. Port Name Description


 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade software.
6 RST Restart switch for the MDU
7 SD Reserved
8 DIP switch Implements specific functions by using the DIP switch and
specific buttons; controls the CAN communication build-out
resistor in a parallel system

Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.

Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm

5.2.1.6 Technical Specification

Table 5-12 Physical specifications

Item Specifications
Cable routing mode Routed in and out from the top
Routed in and out from the bottom (tail frame configured)
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts, RS485, and SNMP

Table 5-13 Environmental specifications

Item Specifications
Operating temperature 0°C to 40°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m (When the altitude is greater than 1000 m and less
than 4000 m, the rated power should be derated. For details,
see the IEC62040-3.)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-14 Safety and EMC

Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11

Table 5-15 Mains Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
At 0–40°C: The UPS works at full load when the voltage is
176–280 V AC and is linear derated to 40% load when the
voltage is 176–80 V AC.
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)

Table 5-16 Bypass Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-17 Battery specifications

Item Specifications
Battery voltage 360–528 V DC (30–44 batteries, 32 by default; derated by 6%
when there are 30 batteries)
Battery management Intelligent battery management
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.

Charging voltage  Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell by


default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell by
default (44 batteries)
 Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)

Table 5-18 Output electrical specifications

Item Specifications
Output system Three-phase, four-wire, and PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision ±1% (balanced load)
Output power factor 1
Transfer time  Uninterruptible transfer: 0 ms
 Interruptible transfer: ≤ 20 ms
Output voltage imbalance Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
 100% < load ≤ 110%: transfer to bypass mode after 60
minutes
 110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ±0.1 minute)
 125% < load ≤ 150%: transfer to bypass mode after 1
minute
 Load > 150% or a short circuit occurs: run for 200 ms
Derating coefficient of  40 A circuit breaker: 0.75
output circuit breakers  63 A circuit breaker: 0.7

Table 5-19 System electrical specifications

Item Specifications
System efficiency 96% (linear load)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
Current equalization 5%
specification

5.2.2 Integrated UPS (60 kVA, 125 kVA)


5.2.2.1 Product Structure

 The appearance of the UPS5000-E-60K-HABBS (02312TVW, 02312TWB) is similar to that of the


UPS5000-E-125K-HABBS-01 (02312TVY, 02312TWC).
 The appearance of the UPS5000-E-60K-HASBS (02312TVX) is similar to that of the
UPS5000-E-125K-HASBS-01 (02312TWA).

Figure 5-36 UPS5000-E-60K-HABBS (02312TVW) front view

(1) Power input status indicator (2) Input circuit (3) Lighting circuit
breaker breaker
(4) Power distribution circuit breaker for (5) IT load circuit (6) UPS input circuit
the smart cooling product breaker breaker
(7) UPS maintenance bypass circuit (8) Control module (9) Bypass module
breaker

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(10) Filler panel (11) Power module (12) Monitor display


unit (MDU)
(13) Power distribution monitoring board (14) UPS output
circuit breaker

Figure 5-37 UPS5000-E-125K-HASBS-01 (02312TWA) front view

(1) Power input status (2) ATS (3) Lighting circuit


indicator breaker
(4) ATS handle (5) Power distribution circuit breaker (6) IT load circuit
installation slot for the smart cooling product breaker
(7) UPS input circuit (8) UPS maintenance bypass circuit (9) Control module
breaker breaker
(10) Bypass module (11) Power module (12) Monitor display
unit (MDU)
(13) Power distribution (14) UPS output circuit breaker
monitoring board

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.2.2 Power Module

Appearance

Figure 5-38 Power module

(1) Positioning lock (2) Run indicator (3) Alarm indicator (4) Fault indicator
(5) Ready switch (6) Output port (7) Input port

Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.

Specifications
 Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
 Weight: < 21 kg
 Rated output capacity: 30 kVA/30 kW
 Power density: 20.64 W/inch3

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.2.3 Bypass Module

Appearance

Figure 5-39 Bypass module

(1) Positioning lock (2) Cold start button (3) Run indicator (4) Alarm indicator
(5) Fault indicator (6) Ready switch (7) Signal port (8) Input and output ports

Table 5-20 Indicator description

Indicator Color Status Description


Run indicator Green Steady on The system is working in
bypass mode.
Blinking at long The bypass has no output
intervals (blinking at 0.2 Hz, on for
2.5s and off for 2.5s).
Blinking at short The bypass is not configured
intervals or the DSP software is being
upgraded (blinking at 4 Hz,
on for 0.125s and off for

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Indicator Color Status Description


0.125s).
Off The bypass software is being
upgraded.
Alarm indicator Yellow Steady on A minor alarm is generated
for the bypass.
Off There is no minor alarm for
the bypass, or the software is
being upgraded.
Fault indicator Red Steady on A critical alarm is generated
for the bypass.
Off There is no critical alarm for
the bypass, or the software is
being upgraded.

Functions
The bypass module supplies power in the following cases:
If the UPS is set to ECO mode and the bypass voltage is within the specified range, the UPS
works in bypass mode.
If the power module overload times out, the UPS transfers to bypass mode.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.

Specifications
 Dimensions (H x W x D): 130 mm x 420 mm x 500 mm
 Weight: 19 kg
 Rated output capacity: 200 kVA

5.2.2.4 Control Module


5.2.2.4.1 Overview
In a standard configuration, the control module consists of two ECMs, one dry contact card,
and one monitoring interface card (from left to right). The four cards are hot swappable. One
subrack is reserved above the dry contact card. A backfeed protection card or dry contact
extended card can be inserted into this subrack.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-40 Signal panel on the control module

(1) Ground terminal (2) Parallel port 1 (3) BSC port (4) Ready switch
1 on ECM 1
(5) Indicators for ECM 1 (6) Parallel port 2 (7) BSC port (8) Ready switch
2 on ECM 2
(9) Indicators for ECM 2 (10) Dry contact card (11) Dry (12) MDU port
contacts
(13) RS485 port (14) Fast Ethernet (FE) (15) COM2 (16) COM1 port
port port
(17) Battery temperature (18) Optional card
sensor port subrack cover

Ports are protected by a security mechanism.

5.2.2.4.2 ECM
The control module consists of two ECMs that work in active/standby mode. Each card
provides two ports, that is, a BSC port in the upper part and a reserved parallel port in the
lower part.

Figure 5-41 ECM

Table 5-21 Ports on the ECM

Silk Screen Description


PARALLEL The PARALLEL port transmits parallel signals.
BSC The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Silk Screen Description


ensuring that two buses can switch with each other.
BSC cables are hot-swappable.

Table 5-22 Indicator description

Indicator Color Status Description


NORMAL Green Steady on This ECM is the active ECM.
Blinking at 0.5 This ECM is the standby ECM and it is
Hz ready.
Off This ECM is not ready or the software of
this ECM is being upgraded.
Blinking at 4 Hz The software of the ECM is being
upgraded or not configured.
ALM Yellow Steady on The ECM has a minor alarm, but it does
not need to be replaced.
Off The ECM has no minor alarm or the
software of the ECM is being upgraded.

FAULT Red Steady on The ECM has a critical alarm.


Off The ECM has no critical alarm or the
software of the ECM is being upgraded.

5.2.2.4.3 Dry Contact Card


The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).

Figure 5-42 Dry contact card

Table 5-23 Ports on the dry contact card

Silk Description Status Initial Status


Screen
BTG Port for detecting battery  Connected: battery Disconnected

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Silk Description Status Initial Status


Screen
grounding faults grounding fault
 Disconnected: no
0V Port for signal ground
battery grounding
fault
GEN Port for detecting diesel  Connected: D.G. Disconnected
generator (D.G.) mode mode
 Disconnected:
0V Port for signal ground
non-D.G. mode
BCB_OL Port for detecting the BCB  Grounded: BCB Grounded
box box connected
 Disconnected:
BCB box not
connected
BCB_STA Port for monitoring the  Connected: battery Disconnected
battery switch switch ON
 Disconnected:
battery switch
OFF
BCB_DR Controls battery circuit  0 V: battery 0V
V breaker trip. When the switch not tripped
voltage is +12 V, the circuit  12 V: battery
breaker trips. switch tripped
BCB_0V Port for signal ground
EPO_NO Emergency power-off If the normally open Disconnected
(EPO) port (NO) port is
connected to the
EPO_12V +12 V EPO_12V port, EPO
is triggered.
EPO_NC EPO port If the normally closed Connected
(NC) port is
EPO_12V +12 V disconnected from the
EPO_12V port, EPO
is triggered.
SWITCH Port for monitoring the UPS  Connected: circuit Connected
STATUS_ output circuit breaker breaker ON
OUT  Disconnected:
SWITCH Port for signal ground circuit breaker
STATUS_ OFF
0V
SWITCH Port for monitoring the  Disconnected: Disconnected
STATUS_ maintenance circuit breaker circuit breaker ON
MT  Connected: circuit
SWITCH Port for signal ground breaker OFF

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Silk Description Status Initial Status


Screen
STATUS_
0V
SWITCH Port for monitoring the  Connected: circuit Connected
STATUS_ bypass input circuit breaker breaker ON
BP  Disconnected:
SWITCH Port for signal ground circuit breaker
STATUS_ OFF
0V
SPD Port for monitoring the  Connected: SPD Connected
input AC surge protective enabled
device (SPD)  Disconnected:
0V Port for signal ground SPD disabled

 The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
 Set the EPO port to NO or NC as required.
 When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
 Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm2 to 1.5 mm2.

5.2.2.4.4 Monitoring Interface Card

 Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
 In a parallel system, ensure that used dry contacts properly connect to each UPS.

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-43 Monitoring interface card

The maximum voltage and current of ports DO_1 to DO_4 are 30 V DC, 1 A or 60 V DC, 0.5 A
respectively.

Table 5-24 Ports on the monitoring interface card

Port Silk Screen Description


DO_1 NO  DO_1, DO_2, DO_3, and DO_4 indicate alarm
outputs. Their default values are Critical alarm,
COM Minor alarm, Bypass mode, and Battery mode,
respectively.
DO_2 NO
 It can be set to Disable, Critical alarm, Minor
COM alarm, Bypass mode, Battery mode, Low batt.
volt., Low battery SOC, Abnormal mains, Sys
DO_3 NO maint breaker enable, Sys outp breaker
COM enable, Maint. breaker closed, No power
supplied, Mains supplies power, ECO mode,
DO_4 NO Battery test, and Batt. Volt. Below Thres..
 Configure power segment settings based on
COM
backup time.
DB26 MDU Provides FE, RS485, I2C, and CAN signals.
Battery B_TEMP Connects to an indoor battery temperature sensor.
temperature sensor
port
Southbound COM1  Supported protocol: Modbus-RTU.
communications  Connects to a southbound device.
port 1
Southbound COM2  Supported protocol: Modbus-RTU.
communications  In use.
port 2
Communications FE  Supported protocols: Modbus-TCP, HTTPS, and
port SNMP (reserved).
 Connects to a Huawei northbound device.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Port Silk Screen Description


Communications RS485 Supported protocol: Modbus-RTU.
port

 Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm2.
 RS485 cables and FE cables must be shielded cables.

Figure 5-44 and Figure 5-45 are recommended wiring methods for DO ports.

Figure 5-44 Wiring method 1

Figure 5-45 Wiring method 2

Figure 5-46 and Table 5-25 describe the COM1 pin definitions.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-46 COM1 pins

Table 5-25 COM1 pin definition

Pin Description
1 GND
2 N/A
3 RS485-
4 RS485+
5 N/A
6 12V_PORT

Figure 5-47 and Table 5-26 describe the COM2 pin definitions.

Figure 5-47 COM2 pins

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-26 COM2 pin definition

Pin Description
1 RS485+
2 RS485-
3 N/A
4 RS485+
5 RS485-
6 GND
7 CANH0
8 CANL0

Figure 5-48 and Table 5-27 describe the RS485 pin definitions.

Figure 5-48 RS485 pins

Table 5-27 RS485 pin definition

Pin Description
1 RS485_T+
2 RS485_T–
3 N/A
4 RS485_R+
5 RS485_R–
6 GND
7 N/A

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Pin Description
8 N/A

If cables are prepared onsite, follow the three methods below:


 Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
 Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to
RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–.

5.2.2.5 MDU

Appearance

Figure 5-49 MDU

(1) Status indicator (2) LCD touchscreen

Table 5-28 Status indicator

Status Color Meaning


On Red A critical alarm has been generated, and the buzzer sounds
continuously.
Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz.
Green The UPS is running properly or a warning has been generated.
Off N/A The MDU is powered off.

The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-50 MDU ports

Table 5-29 Description of MDU ports

No. Port Name Description


1 MUS05A Connects to the MDU and monitoring interface card
(DB26)

2 GE Connects to a Huawei northbound device.


3 CAN Reserved
4 RS485_1 Reserved
5 FE_1 Reserved
6 FE_2 Reserved
7 USB Host  After installing the WiFi module, locally connect to the
UPS over the Service Expert app. Obtain the initial
startup password during deployment. View or obtain
UPS running information during preventive
maintenance.
NOTE
Only Huawei service engineers or authorized service engineers are
allowed to use the WiFi module. To ensure security, remove the
WiFi module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade software.
8 SD Reserved
9 DIP switch Implements specific functions by using the DIP switch and
specific buttons; controls the CAN communication build-out
resistor in a parallel system

Functions
The monitor display unit (MDU) allows for general UPS operations, parameter setting,
viewing of running status and alarms, and so on.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm

5.2.2.6 Technical Specification

Table 5-30 Physical specifications

Item Specifications
Cable routing mode Routed in and out from the top
Routed in and out from the bottom (tail frame configured)
Protection level IP20
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm
Communication Dry contacts

Table 5-31 Environmental specifications

Item Specifications
Operating temperature 0°C to 40°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–1000 m (When the altitude is greater than 1000 m and less
than 4000 m, the rated power should be derated. For details,
see the IEC62040-3.)

Table 5-32 Safety and EMC

Item Specifications
Safety compliance EN62040-1, 2013
IEC62040-1, 2013
Electromagnetic EN/IEC62040-2
compatibility (EMC) IEC61000-2-2
IEC61000-4-2
EN61000-4-6: EN/IEC62040-2 2nd Ed (IEC61000-4-6)
EN61000-4-3: EN/IEC62040-2 2nd Ed (IEC61000-4-3)
EN/IEC62040-2 2nd Ed (IEC61000-4-4)
EN/IEC62040-2 2nd Ed (IEC61000-4-5)
IEC61000-4-8
IEC61000-4-11

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-33 Mains Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
 30–40°C environment: not derated when the voltage is
187–280 V; linearly derated to 40% load when the voltage
is 187–80 V
 0–30°C environment: not derated when the voltage is
176–280 V; linearly derated to 40% load when the voltage
is 176–80 V.
Input frequency range 40–70 Hz
Rated frequency 50/60Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)

Table 5-34 Bypass Input electrical specifications

Item Specifications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input frequency range 50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2
Hz by default)

Table 5-35 Battery specifications

Item Specifications
Battery voltage 360–528 V DC
 12 V battery: 30–44 batteries, 40 batteries by default; not
derated when there are 36–46 batteries; power derated to
94% when there are 34 batteries; power derated to 80%
when there are 32 or 30 batteries.
 2 V battery: 180–264 batteries, 240 batteries by default;
not derated when there are 16–276 batteries, power
derated to 0.94 when there are 204–214 batteries; power
derated to 0.8 when there are 180–212 batteries. The
number of batteries in the positive battery string must be

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
the same that of batteries in the negative battery string.
Battery management Intelligent battery management
Charger output power (6250 W±200 W) x N. The maximum charge power of a
power module is 6250 W±200 W (the maximum current is
10 A). N represents the number of power modules in the
rack.
Cold start When a mains outage occurs, batteries can start the UPS to
supply power to loads.
Charging voltage (lead-acid  Equalized charging voltage: 2.3–2.4 V/cell, 2.35 V/cell
battery) by default (30–42 batteries); 2.3–2.35 V/cell, 2.35 V/cell
by default (44 batteries)
 Float charging voltage: 2.23–2.3 V/cell; 2.25 V/cell by
default (30–44 batteries)

The UPS supports the SmartLi. For details about related parameters, see the SmartLi user
manual.

Table 5-36 Output electrical specifications

Item Specifications
Output system Three-phase, four-wire, and PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision ±1% (balanced load)
Output power factor 1
Transfer time  Uninterruptible transfer: 0 ms
 Interruptible transfer: ≤ 20 ms
Output voltage imbalance Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
 100% < load ≤ 110%: transfer to bypass mode after 60
minutes
 110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ±0.1 minute)
 125% < load ≤ 150%: transfer to bypass mode after 1
minute
 Load > 150% or a short circuit occurs: run for 200 ms
Bypass overload capability:
 30°C environment: works for a long term at 135% load.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
 40°C environment: works for a long term at 125% load.
 If the bypass single-phase or three-phase is 150%–200%
overloaded, the bypass can keep working for 5 minutes.
 If the bypass single-phase or three-phase is more than
200% overloaded, the bypass can keep working for 1
minute.
 If the load exceeds 1000%, the bypass can keep working
for 100 ms.
Derating coefficient of  40 A circuit breaker: 0.75
output circuit breakers  63 A circuit breaker: 0.7

Table 5-37 System electrical specifications

Item Specifications
System efficiency 95% (linear load)
Current equalization 5%
specification

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.3 Integrated PDF


Figure 5-51 Integrated PDF

Table 5-38 Technical specifications of the integrated PDF

Item Specifications
Engineering features Dimensions (H x W x D)  Basic dimensions: 2000 x
(mm) 600 x 1100, 2000 x 600 x
1200
 Expanded dimensions:
2200 (including a top
frame) x 600 x 1200
Weight (kg) < 350
Enclosure protection level IP20
Cable routing Routed in and out from the
top, or routed in from the
bottom and routed out from
the top

The 1100 mm deep cabinet

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
can only be routed in and out
from the top.
Maintenance mode Operated from the front and
maintained from the rear
Installation mode Installed on an ESD floor or
concrete floor
Electrical features Rated operating voltage (V 380/400/415
AC)
Rated insulation voltage (V 690
AC)
Rated frequency (Hz) 50/60
IT power distribution input  One 3-pole 160 A MCCB
mode input
 One 3-pole 250 A MCCB
input
 Two 3-pole 160 A MCCB
inputs
 Two 3-pole 250 A MCCB
inputs
Smart cooling product power  One 3-pole 160 A MCCB
distribution input mode input
 One 3-pole 250 A MCCB
input
 Two 3-pole 160 A MCCB
inputs
 Two 3-pole 250 A MCCB
inputs
Output switch (standard  IT power distribution
configuration) branch: a maximum of 48
branches (single-phase) or
16 branches (three-phase),
a maximum of 40 A
current for each branch
 Smart cooling product
power distribution branch:
a maximum of 8 branches
(three-phase), a maximum
of 63 A current for each
branch
 (Optional) Hot-swappable
MCB
Lighting PDB Smart cooling product
dual-input: two fuses
Smart cooling product

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
single-input: one fuse
Surge protection Class C; nominal discharge
current In (8/20 µs) = 20 kA,
maximum discharge current
Imax (8/20 µs) = 40 kA;
voltage protection level Up
(20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
Monitoring function Detection items Three-phase input voltage,
current, frequency, active
power, reactive power, electric
energy, power factor, and
temperature
Communications mode Supports the Modbus TCP
protocol and Modbus RTU
protocol.
(Optional) Branch temperature monitoring
Certifications CE, CCC

Table 5-39 Monitoring specifications

Item Specifications
Power distribution mains input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric energy,
total apparent power, total reactive power, busbar
temperature, circuit breaker status, and surge
protection status
Power distribution branch output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.4 Precision PDF


Figure 5-52 Precision PDF

Table 5-40 Precision PDF technical specifications

Item Specifications
Dimensions (H x W x D) Basic dimensions: 2000 x 600 x 1100, 2000 x 600 x 1200
(mm) Expanded dimensions: 2200 (including a top frame) x 600
x 1200
Weight (kg) < 400
Rated operating voltage (V) 380/400/415
Rated insulation voltage (V) 690
Rated frequency (Hz) 50/60
Rated operating current (A) 400/250/160

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications
Enclosure protection level IP20
Output switch  40 A single-phase, maximum 144 routes (single-phase)
 (Optional) Hot-swappable MCB
Surge protection Class C; nominal discharge current In (8/20 µs) = 20 kA,
maximum discharge current Imax (8/20 µs) = 40 kA;
voltage protection level Up (20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
Cable routing Routed in and out from the top or bottom
Certifications CCC, CE
Environmental friendliness RoHS, REACH

Table 5-41 Monitoring specifications

Item Specifications
Power distribution mains Phase voltage, phase current, load rate, frequency, power
input factor, total active power, total electric energy, total
apparent power, total reactive power, busbar temperature,
circuit breaker status, and surge protection status

Power distribution branch Phase current, active power, load rate, electric energy,
output temperature, and circuit breaker status

5.2.5 New Main Way 2.0


Figure 5-53 New main way

(1) General (2) Connective kit (3) Busbar (4) Power


input unit trunking unit distribution unit
(5) Column (6) Around-column busbar (7) End plug (8) Low support
trunking unit (optional)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-42 New main way features

Item Feature
High efficiency, Space saving: saves the IT cabinet space.
economical, and
rapid delivery Easy maintenance: short maintenance duration.
High scalability: Busbar trunking units can be added.
Safe, reliable, and High reliability: uses a foolproof structure with installation position
flexible O&M marks and spacing measures.
Easy O&M: can be easily maintained as the new main way is highly
reliable; allows users to replace power distribution units; supports
maintenance inside the aisle.
Easy installation: short time to install the new main way.
Intelligent Easy to network through an FE port to implement teleindication,
monitoring and telemetering, and teleadjusting.
flexible
management Flexible to manage and monitor the power usage effectiveness (PUE)
and maintenance.

Table 5-43 Technical specifications

Item Specifications
System type Three-phase, four-wire, and PE
Rated operating voltage 380 V AC, 400 V AC, or 415 V AC
Rated operating current at 40°C 250 A/400 A
Input switch  One 3-pole 250 A MCCB
 One 3-pole 400 A MCCB
Output switch Six 1-pole 40 A MCBs
Rated transient withstand current 10 kA, 1s
Rated frequency 50/60 Hz
Protection level IP30
Cabling mode Routed in from the end
Cable connection capacity  250 A rated current: 4 x 95 mm2 + 1 x
50 mm2
 400 A rated current: 4 x 185 mm2 + 1 x
95 mm2

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-44 Monitoring specifications

Item Specifications
Power distribution mains input Detects the voltage, current, active power,
reactive power, power factor, electric
energy, harmonic, and key node
temperature.
Power distribution branch output Detects the branch loop current, load
percentage, active power, apparent power,
electric energy, and key node temperature.

5.2.5.1 General Input Unit


The general input unit is classified into two types: left-installed general input unit and
right-installed general input unit.
 When the personnel are close to the cable tray and face the aisle, the left cabinets use the
left-installed general input unit, and the right cabinets use the right-installed general
input unit.
 Left-installed general input unit: Cables are routed in from the right and out from the left.
Right-installed general input unit: Cables are routed in from the left and out from the
right.

Figure 5-54 General input unit

(1) Alarm indicator (2) Monitoring (3) Integrated management (4) PWR_2
panel card port
(5) PWR_1 port (6) FE port (7) SPD (8) Input
switch
(9) SPD circuit (10) Cable inlet (11) Cable outlet
breaker

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-55 Monitoring panel

(1) Indicators (2) BLINK button (3) USB port (4) RS485 port
(5) AIDI_1 port (6) FE port (7) AIDI_2 port

Table 5-45 Indicator description

Indicator Color Status Description


RUN Green Blinking at 0.5 Hz, on The equipment is running
for 1s and then off for properly.
1s
ALM Red Steady on There is an alarm.
Off There is no alarm.
Blinking at 0.5 Hz, on The ALM indicator blinks.
for 1s and then off for
1s
PWR Green Steady on The power supply to the CPU
of the monitoring board is
normal.
Off The power supply to the CPU
of the monitoring board is
abnormal.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-56 Integrated management card

(1) PWR indicator (2) PoE port (3) 48 V output port

Figure 5-57 Port pins

Table 5-46 Pin definitions

Pin RS485 Port FE Port AIDI Port PoE Port


1 RS485+ TRX0+ - TRX0+_RTN
2 RS485- TRX0- - TRX0-_RTN
3 - TRX1+ GND TRX1+_-48V
4 RS485+ TRX2+ - TRX2+_RTN
5 RS485- TRX2- - TRX2-_RTN
6 - TRX1- GND TRX1-_-48V
7 - TRX3+ AIDI_1+ TRX3+_-48V
8 - TRX3- - TRX3-_-48V

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.5.2 Power Distribution Unit

Figure 5-58 Power distribution unit

(1) Load wiring port (2) PWR_1 (3) FE1 port (4) Monitoring panel
port
(5) Integrated (6) FE2 port (7) PWR_2 (8) Output circuit breaker
management card port (behind the cover)

5.2.6 Smart Cooling Product PDB


The smart cooling product PDB supplies power to smart cooling products and aisle lighting in
precision PDF or new main way (NMW) scenarios.

Figure 5-59 Appearance

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-47 Technical specifications

Item Technical Specifications


Rated operating voltage 380 V/400 V/415 V
Rated frequency 50/60 Hz
Rated operating current 250 A/400 A
Input switch 250 A/3P MCCB, 400 A/3P MCCB
Output switch Rated current 250 A/400 A: 8 x 63 A/3P + 2 x 10 A/1P + 1 x
32 A/1P MCB
IP rating IP20
Surge protection level Level C SPD
Certification CE, CCC
Installation mode Wall-mounted
Flame spread rating Fire-retardant materials with a flame spread rating of V0 are
used. The heat shrink tubing is at least 1 mm thick.

5.2.7 Battery Cabinet


A maximum of two battery groups and up to four battery cabinets (in 2N scenario) can be
deployed inside the smart module. If many batteries are configured, they can be deployed
outside the smart module.
 If the configured batteries can be placed in four or fewer battery cabinets, it is
recommended that battery cabinets be deployed inside the smart module (smart module
A). Battery cabinets or racks can also be deployed with UPS batteries outside smart
module A (batteries deployed outside) or smart module B.
 If the number of configured batteries exceeds the capacity of four battery cabinets, it is
recommended that battery racks be deployed outside smart module A (batteries deployed
outside) or the smart module B. Battery cabinets can also be deployed with UPS batteries
outside smart module A (batteries deployed outside) or smart module B.
The battery cabinets provide space for installation and cabling of batteries and the iBattery
intelligent battery management system for the smart module.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-60 Battery cabinet

Figure 5-61 Battery cabinet components

(1) BIB (battery control I/O board) (2) iBOX (CIM) (3) Batteries (4) Circuit breaker

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-48 Battery cabinet technical specifications

Item Technical Specifications


External dimensions (H x  Basic dimensions: 2000 mm x 600 mm x 1100 mm
W x D)  Dimensions after expansion: 2200 mm x 600 mm x 1100
mm (with the top frame)
 Basic dimensions: 2000 mm x 600 mm x 1200 mm
 Dimensions after expansion: 2200 mm x 600 mm x 1200
mm (with the top frame)
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Air channel Front and rear air channels
Installation space 42 U
Installation mode Installed on a concrete floor or ESD floor
Door opening mode The front door is a single door, and the rear door is a double
one.
Weight 128 kg (excluding batteries)
Protection level IP20

Shoto and Enersys batteries are supported.

Table 5-49 Maximum number of batteries inside a battery cabinet

Battery Specifications Maximum Number of Batteries


Inside a Battery Cabinet
26 Ah 40
40 Ah
65 Ah 20
100 Ah

Table 5-50 Configuration scenarios (for both the main and auxiliary battery cabinets)

Battery Layer (from Number of Batteries


Specifications Top to
Bottom)
- - 40 38 36 34 32

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Battery Layer (from Number of Batteries


Specifications Top to
Bottom)
26 Ah/40 Ah Layer 1 10 9 8 7 6
Layer 2 10 10 10 10 10
Layer 3 10 10 10 10 10
Layer 4 10 9 8 7 6

Table 5-51 Configuration scenarios (The main battery cabinet and auxiliary battery cabinet are
differentiated.)

Battery Layer (from Main Battery Cabinet Auxiliary Battery


Specifications Top to (Number of Batteries) Cabinet (Number of
Bottom) Batteries)
- - 20 19 18 17 16 20 19 18 17 16
65 Ah/100 Ah Layer 1 5 4 3 2 1 5 4 3 2 1
Layer 2 5 5 5 5 5 5 5 5 5 5
Layer 3 5 5 5 5 5 5 5 5 5 5
Layer 4 5 5 5 5 5 5 5 5 5 5

5.2.8 rPDU Introduction


5.2.8.1 rPDU
The rPDU uses IEC sockets by default. GB sockets are also supported.

Figure 5-62 Full-height rPDU

Figure 5-63 Half-height rPDU

The figures are for reference only. The actual products prevail.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-52 rPDU specifications

Type Model Output Port


IEC PDU2000-32-1PH-9/3-B1 9 x C13 + 3 x C19
(half height)
PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19
(full height)
PDU2000-32-3PH-12/9-B2 12 x C13 + 9 x C19
(full height)
GB PDU2000-32-1PH-9/3-B2 GB 10 A: 9
(half height) GB 16 A: 3
PDU2000-32-1PH-20/4-B2 GB 10 A: 20
(full height) GB 16 A: 4
PDU2000-32-3PH-12/9-B3 GB 10 A: 12
(full height) GB 16 A: 9

5.2.8.2 (Optional) Smart rPDU


The intelligent PDU2000 accurately and effectively monitors the real-time status changes of
the current, voltage, power, and electric energy of electrical devices in the data center.
The intelligent PDU2000 needs to support the following monitoring functions:
 Detect and display the input current.
 Detect and display the total input current.
 Detect and display the input voltage; display the voltage and current alternately.
 Provide remote input management.
 Remotely query the input voltage, total input current, input power, and input energy
through a serial port.
 Remotely query the PDU status through a serial port. The status that can be queried
includes normal input power, overcurrent, overvoltage, and undervoltage, as well as the
communication status (normal or abnormal) of the monitoring board.
 Remotely set the input overcurrent warning threshold, overvoltage alarm threshold, and
undervoltage alarm threshold through a serial port, or locally set these parameters.
 Working status indicator: The PDU has a built-in input status indicator, which indicates
the working status of the PDU.
 Input alarm: If any of input overcurrent, overvoltage, and undervoltage occur, the
working status indicator indicates the fault, and an alarm is reported over the Modbus
port.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule2000 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-64 Smart rPDU 1

(1) Input power cable (2) Main control module (3) Hydraulic circuit breaker
(4) Output sockets (5) Industrial connector

Figure 5-65 Smart rPDU 2

(1) Input power cable (2) Industrial connector (3) Main control module
(4) Output sockets (5) Hydraulic circuit breaker

Table 5-53 Technical specifications of the smart rPDU

Item Specifications
Function Supports single-phase AC 200–240 V power supply,
twenty 10 A outputs, four 16 A outputs
Dimensions (H x W x D) 1866 mm x 60 mm x 48 mm (appearance 1)
1866 mm x 56 mm x 52 mm (appearance 2)
Output quantity and system 20 x C13 + 4 x C19
Monitoring function Monitors the input power, voltage, current, power factor,
and electric energy
Monitors the power, current, power factor, and electric
energy of each output

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

6 Cabinet Aisle System

6.1 Cabinets and Accessories


6.1.1 Network Cabinet
The network cabinet provides the smart module with the space for integrated cabling and the
cable management interface.

Figure 6-1 Network cabinet

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Table 6-1 Network cabinet technical specifications

Item Technical Specifications


External dimensions (H x  2000 mm x 600 mm x 1100 mm (with castors)
W x D)  2000 mm x 600 mm x 1200 mm (with castors)
 2000 mm x 800 mm x 1100 mm (with castors)
 2000 mm x 800 mm x 1200 mm (with castors)
 2000 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 800 mm x 1200 mm (without castors)
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 The distance between the front and rear mounting bars can
be adjusted by the step of 25 mm. Positions behind the
cabinet are reserved for installing two rPDUs.
Installation mode Installed on a concrete floor, a base, or an ESD floor
Door opening mode The front door is a single door, and the rear door is a double
one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2000 mm x 800 mm x 1200 mm: 153 kg
The weight of an empty  2200 mm x 600 mm x 1200 mm: 137 kg
cabinet includes the
 2200 mm x 800 mm x 1200 mm: 164 kg
weight of the front and
rear doors.  2000 mm x 600 mm x 1100 mm: 110 kg
 2000 mm x 800 mm x 1100 mm: 135 kg
Protection level IP20

6.1.2 IT Cabinet
An IT cabinet used in the smart module complies with the International Electrotechnical
Commission (IEC) 60297-1 standard and provides stable installation space for servers,
thereby ensuring safe operation of servers.
The cabinet dimensions are unified, and both front and rear air channels are designed.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-2 IT cabinet

The cabinet provides the following features:


 The ventilation rate of the front and rear doors is at least 70%.
 Two rack power distribution units (rPDUs) can be vertically installed at the rear inside
the cabinet.
 The position of each U is marked on the vertical mounting bars.
 The front and rear doors are locked and can be unlocked only with dedicated keys.
 The cabinet supports a door status sensor and electronic access control.
 The maximum static load of the cabinet is 1800 kg.

Table 6-2 Cabinet technical specifications

Item Technical Specifications


External  2000 mm x 600 mm x 1100 mm (with castors)
dimensions (H x W  2000 mm x 600 mm x 1200 mm (with castors)
x D)
 2000 mm x 800 mm x 1100 mm (with castors)
 2000 mm x 800 mm x 1200 mm (with castors)
 2000 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 600 mm x 1200 mm (without castors)
 2200 mm x 800 mm x 1200 mm (without castors)
Color Black (PANTONE426C/RAL9005)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Item Technical Specifications


Material High-intensity class A carbon cold rolled steel plate and zinc-coated
steel plate
Air channel Front and rear air channels
Installation space  A 2000 mm high cabinet provides 42 U available space.
 A 2200 mm high cabinet provides 47 U available space.
 The distance between the front and rear mounting bars can be
adjusted for every 25 mm.
− For a 1200 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 750 mm and can be
extended to 850 mm by adjusting the mounting bars.
− For a 1100 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 700 mm and can be
extended to 750 mm by adjusting the mounting bars.
 Positions for vertically installing two rPDUs are provided in the
rear of the cabinet.
Installation mode Installed on a concrete floor, a base, or an ESD floor
Door opening mode The front door is a single door, and the rear door is a double one.
Weight of an empty  2000 mm x 600 mm x 1200 mm: 128 kg
cabinet  2000 mm x 800 mm x 1200 mm: 153 kg
The weight of an  2200 mm x 600 mm x 1200 mm: 137 kg
empty cabinet
 2200 mm x 800 mm x 1200 mm: 164 kg
includes the weight
of the front and rear  2000 mm x 600 mm x 1100 mm: 110 kg
doors.  2000 mm x 800 mm x 1100 mm: 135 kg
Protection level IP20
Optional cabinet Cable ring, bottom sealing plate, guide rail, tray, side door panel,
accessories and bottom plate

6.1.3 Top Sealing Plate


Top sealing plates are used to decorate the smart module.
The top sealing plates can be 300 mm, 600 mm, and 800 mm wide. They are installed on the
top of cabinets and smart cooling products of the respective width.
 300 mm wide: 224.5 mm x 299 mm x 59.5 mm
 600 mm wide: 224.5 mm x 599 mm x 59.5 mm
 800 mm wide: 224.5 mm x 799 mm x 59.5 mm

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-3 Top sealing plate

6.1.4 Cabinet Bottom Sealing Plate


Cabinet sealing plates are used to seal the space under cabinets to ensure that an aisle is
airtight.

Table 6-3 Cabinet bottom sealing plate specifications

Installation Position Type Notice


Middle cabinet 300 mm wide front and rear Apply to 300 mm wide
sealing plates smart cooling products.
600 mm wide front and rear Apply to cabinets that are
sealing plates 600 mm wide and 2000 mm
high.
800 mm wide front and rear Apply to cabinets that are
sealing plates 800 mm wide and 2000 mm
high.

End cabinet Bottom sealing plate Apply to end cabinets that


assembly: Front and rear are 2000 mm high.
sealing plates + side sealing
plate (assembled by five
components)

Cabinets on both sides of a Combined lower part: Front Apply to cabinets that are
column (for scenarios with and rear sealing plates + located on both sides of a
columns) side sealing plate column and are 2000 mm
(assembled by five high.
components)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-4 Bottom sealing plate assembly

(1) Side sealing plate (2) Front or rear sealing plate

Figure 6-5 600 mm/800 mm wide bottom sealing plate

Figure 6-6 300 mm wide bottom sealing plate

6.1.5 Cabinet Enclosure Plate


Enclosure plates are used for sealing an aisle. They can be 300 mm, 600 mm, and 800 mm
wide and apply only to a single row of cabinets.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-7 Cabinet enclosure plate

6.1.6 Cable Management Devices


Cables inside cabinets are sorted by cable managers, cable rings, and cable trays. Cable
managers route cables horizontally, cable rings on the cabinet side route cables vertically, and
cable trays route cables from the cabinet front to cabinet rear.

Cable Manager
A cable manager is used to manage cables inside a cabinet horizontally.

Figure 6-8 Cable manager

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Table 6-4 1 U cable manager specifications

Dimensions (H x W x D) Weight Space Occupied


43.6 mm x 482.6 mm x 91 0.56 kg 1U
mm

Cable Ring
A cable ring is installed on a side post in the cabinet to secure vertically routed cables.

Figure 6-9 Cable ring

Table 6-5 Cable ring specifications

Name Dimensions (H x W x D) Weight


Standard cable ring 55 mm x 48 mm x 188.6 0.163 kg
mm
Small cable ring 55 mm x 48 mm x 44 mm 0.096 kg

Cable Tray
A cable tray is used for forward and backward cabling. It uses mounting ears to facilitate
device installation.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-10 Cable tray

Table 6-6 Cable tray specifications

Dimensions (H x W x D) Weight Space Occupied


43.6 mm x 482.6 mm x 250 1.89 kg 1U
mm

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-11 Installation positions for cable management devices

(1) Cable rack (2) Cable ring (3) Cable tray

The installation positions for cable management devices are for reference only. Determine the
installation positions based on the actual situation.

6.1.7 (Optional) Adjustable Base


An adjustable base for the smart module can be 300 mm, 600 mm, or 800 mm wide. The
minimum adjustment range is 1 mm.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 88


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Table 6-7 Base specifications

Type Dimensions
600 mm wide smart Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
cooling product, PDF, IT (adjustable): 1000 mm, 1100 mm, or 1200 mm
cabinet, battery cabinet, or
network cabinet base Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
300 mm wide smart Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
cooling product base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm
800 mm wide IT or Height (adjustable): 270 mm ≤ H ≤ 410 mm; depth
network cabinet base (adjustable): 1000 mm, 1100 mm, or 1200 mm
Height (adjustable): 410 mm ≤ H ≤ 700 mm; depth
(adjustable): 1000 mm, 1100 mm, or 1200 mm

6.2 Aisle and Mechanical Parts


6.2.1 Skylight
Skylights are used for sealing an aisle containment. Skylights are classified as control
skylights, rotating skylights, and flat skylights.

Table 6-8 Skylight technical specifications

Item Dimensions (H x W x D) Applicable Cabinet


Dimensions (Width)
Control skylight 341 mm x 605 mm x 1334 mm 600 mm
341 mm x 805 mm x 1334 mm 800 mm
300 mm wide flat 341 mm x 305 mm x 1334 mm 300 mm
skylight
600 mm wide flat or 341 mm x 605 mm x 1334 mm 600 mm
rotating skylight

800 mm wide flat or 341 mm x 805 mm x 1334 mm 800 mm


rotating skylight

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 89


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-12 Control skylight

(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel

 Control skylights are installed on both ends of an aisle and used to install monitoring components
such as the camera, multi-functional sensor, and smoke detector.
 If the smart module is longer than 7 m, add one control skylight in the middle of the smart module
for installing a multi-functional sensor or smoke detector.

Figure 6-13 Flat or rotating skylight

(1) Magnetic lock fixing base (2) Glass skylight (3) Skylight connective plate

 A rotating skylight is designed with an eccentric structure. When the trigger is activated, a rotating
skylight falls under gravity. When a magnetic lock is triggered, the rotating skylight falls under
gravity.
 The rotating skylight requires a magnetic lock but the flat skylight does not.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 90


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

6.2.2 Aisle End Door


End doors are installed on both ends of the aisle containment, which makes the module
independent, improves equipment efficiency, and helps onsite personnel or devices move into
or out of the aisle containment.

6.2.2.1 Sliding Door

Figure 6-14 Sliding door

Sliding doors can be opened only sideways, and therefore may involve risks during fire extinguishing
system acceptance.

6.2.2.2 Revolving Door


The double revolving door is an outward opening door with an opening angle of 90 degrees. It
ensures that the aisle containment is properly sealed and separated.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 91


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-15 Double revolving door

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 92


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

6.2.2.3 Electric Sliding Door

Figure 6-16 Electric Sliding Door

Electric Sliding Door can be opened only sideways, and therefore may involve risks during fire
extinguishing system acceptance.

6.2.3 M-shaped Cable Trough


Cabinet cable troughs are categorized into signal cable troughs and power cable troughs,
which are used to route signal cables and power cables respectively. This ensures that weak
current cables are separated from strong current cables.
A cable trough consists of several parts that are clamped together. A cable trough is assembled
using two brackets, one supporting plate, and one partition plate (used to separate
weak-current optical fibers from weak-current network cables and separate strong-current
route A from strong-current route B).
A cable trough is 170 mm high and 310 mm long.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 93


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-17 300 mm wide cable trough

(1) Bracket (2) Supporting plate (3) Partition plate

Figure 6-18 600 mm or 800 mm wide cable trough

(1) (2) Supporting (3) Partition (4) Position for the smart ETH
Bracket plate plate gateway

6.2.4 (Optional) Mesh cable trough


Cabinet cable troughs are categorized into signal cable troughs and power cable troughs,
which are used to route signal cables and power cables respectively. This ensures that weak
current cables are separated from strong current cables. The length of the cable trough needs
to be cut based on the actual aisle length. The cable trough is secured to the top of the cabinet
using fasteners.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 94


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-19 Mesh cable trough

(1)Mesh cable trough (2) mounting bracket

6.2.5 (Optional) Cable Tray


Cable trays are used to route cables across two rows of cabinets in the smart module. If two
rows of cabinets are deployed, route strong-current and weak-current cables over the control
skylight at either end of the rows preferentially. If there are more than 24 cabinets, install one
cable tray on the top of end cabinets for routing power cables as there are many cables to be
routed.
A cable tray is 2.5 m long.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 95


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-20 Cable tray

(1) Cable ladder support (2) Cable ladder

6.2.6 (Optional) Adaptive Frame


To meet requirements for cabinet height and depth in different scenarios, enclosure frame, top
frames, and smart cooling product adaptive frames can be installed. In this way, all cabinets in
the smart module can have the same height and depth and the two rows of cabinets can have
the same length.

Table 6-9 Adaptive frame specifications

Component Width Depth Height Remarks


(mm) (mm) (mm)
PDF enclosure frame 600 100 2000 Increases the cabinet
depth by 100 mm.
300 mm wide smart 300 100 2000 Increases the cabinet
cooling product depth by 100 mm.
enclosure frame
600 mm wide smart 600 100 2000
cooling product
enclosure frame
300 mm wide top 300 1200 200 Increases the cabinet
frame height by 200 mm.
600 mm wide top 600 1200 200
frame
300 mm smart 300 1100 2000 When there is an odd
cooling product number of 300 mm
adaptive frame 300 1200 2000 smart cooling products,
use the adaptive frame
to supplement the
opposite position to
ensure that the two
rows of cabinets have
the same length.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 96


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

6.2.7 (Optional) Ground Copper Bar


Ground copper bars can be horizontal and vertical. Vertical ground copper bars are longer
than horizontal ones. Ground copper bars are used to ground cabinets. Ground copper bars are
installed in the battery cabinet or IT cabinet closest to the PDF.

Figure 6-21 Horizontal ground bar

Figure 6-22 Vertical ground bar

Figure 6-23 Installation position for a horizontal ground copper bar

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 97


FusionModule2000 Smart Modular Data Center
Product Description 6 Cabinet Aisle System

Figure 6-24 Installation positions for vertical ground copper bars

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 98


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7 Temperature Control System

7.1 System Overview


The cooling system uses in-row air cooled smart cooling products and an aisle containment
for cooling. The in-row air cooled smart cooling products and equipment cabinets form an
aisle containment to separate hot air from cold air.
An in-row air cooled smart cooling product works as follows: After the unit starts, the
low-pressure refrigerant vapor in the refrigerating system is suctioned into the compressor,
compressed into high-pressure vapor, and discharged to the condenser. The outdoor air drawn
in by the axial flow fan flows through the condenser and carries away the heat emitted from
the refrigerant so that the high-pressure refrigerant vapor condenses into high-pressure liquid.
The high-pressure liquid passes through the filter and flow regulating mechanism and then is
ejected to the evaporator. Then the liquid vaporizes at low pressure and absorbs ambient heat.
The cross-flow fan draws air into the fins in the evaporator to exchange heat and discharges
cooled air to the cold aisle. The indoor air flows cyclically to decrease the temperature.
In-row smart cooling products are close to heat sources, which shortens the air supply
distance, reduces airflow pressure loss and cold air loss, and maximizes the use of cooling
capacity.

7.2 NetCol5000-A025 Smart Cooling Product


This section describes the components, operating environment, and technical specifications of
the NetCol5000-A025 In-row Air Cooled Smart Cooling Product (25 kW smart cooling
product for short).

7.2.1 Indoor Unit Components


Dimensions
Dimensions (H x W x D) of the NetCol5000-A in standard configurations are 2000 mm x 300
mm x 1100 mm, as shown in Figure 7-1. The equipment depth can be extended to 1200 mm
by adding an enclosure frame to the front door.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 99


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-1 Dimensions (unit: mm)

Components
The indoor unit of the NetCol5000-A consists of a compressor, oil separator, fan, heat
exchanger, electronic expansion valve, one-way valve, filter dryer, sight glass, electric heater
(optional), electrode humidifier (optional), wet film humidifier (optional), water pump
(optional), and so on.
 Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet partial load requirements.
 Oil separator
It is an oil-gas separator that separates lubricant from the exhaust of the compressor and
brings back the separated lubricant to the compressor.
 EC fan
The EC fan implements stepless speed adjustment.
 Heat exchanger
The efficient finned evaporator, an important part in the cooling system, absorbs heat
from indoor air to ensure that the indoor temperature and humidity meet requirements.
 Electronic expansion valve
The flow regulator uses a micro controller to control the motor operation, thereby
changing the pass-through area of the valve to precisely regulate the flow of refrigerant.
 One-way valve
The one-way valve efficiently controls backflow of gas or liquid.
 Filter dryer

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 100


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

The filter dryer absorbs moisture from refrigerant pipes and filters out foreign matter,
which reduces the component damage probability and ensures efficient and reliable
operating of components.
 Sight glass
The sight glass allows you to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
 Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
 Humidifier
The electrode or wet film humidifier can be used to precisely control the equipment
room humidity.
 Water pump
The water pump provides power for top drainage with a maximum lift of 4 meters.

7.2.2 Controller
7.2.2.1 Appearance and Ports

Appearance
The controller provides a 7-inch true color touchscreen and man-machine interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the smart cooling product. Figure 7-2
shows the position of the indicator. Table 7-1 describes the mapping between indicators,
buzzers, and alarms. If alarms of different severities (critical, major, minor, or warning) are
raised simultaneously, the indicator status corresponds to the alarm with the highest severity
level and the buzzer status corresponds to the unacknowledged alarm with the highest severity
level.

Figure 7-2 Display panel

(1) Indicator (2) Display panel

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 101


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-1 Indicator and buzzer status description

Alarm Status Indicator Buzzer


The device is operating properly, or a Green No buzzing
warning is generated.
There is an unacknowledged major Yellow Intermittent buzzing
alarm.
There is an unacknowledged critical Red Constant buzzing
alarm.

Ports

Figure 7-3 Controller side ports

Table 7-2 Ports

No. Name Note


1 MUS05A Reserved
2 FE (fast Ethernet) communications port
3 CAN communications port for the main control board and
LCD
4 RS485_1 Reserved
5 USB Host  After installing the WiFi module, locally connect to
the smart cooling product over the Service Expert

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 102


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

No. Name Note


app. Obtain the initial startup password during
deployment. View or obtain the running information
about the smart cooling product during preventive
maintenance. (Applicable to V200R001C20 and later
versions)
NOTE
Only Huawei service engineers or authorized service engineers
are allowed to use the WiFi module. To ensure security, remove
the WiFi module immediately after use.
 Insert the USB flash drive, import and export the
configuration file, export run logs, and upgrade
software.
6 RST restart switch for the display
7 SD Reserved
8 SW1-4 Dual in-line package (DIP) switch on LCD

7.2.2.2 Function and Features

Function
 Single unit control: Provides logic control for the components of a single smart cooling
product to ensure that the indoor temperature and humidity meet requirements.
 Display operation: Provides a 7-inch touchscreen for you to set parameters for the smart
cooling product and query its status.
 Teamwork control: Enables multiple smart cooling products to work cooperatively,
distributes thermal loads in an optimal way to dramatically reduce power consumption,
and provides multiple standby smart cooling products to improve the reliability.
 The smart cooling product has the following four remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product.
− Teleindication: startup/shutdown states, overvoltage/overcurrent,
undervoltage/undercurrent, return air overtemperature/undertemperature, return air
overhumidity/underhumidity, filter normal/blocked, and fan normal/faulty.
− Telecontrol: smart cooling product startup/shutdown.
− Teleadjusting: temperature, humidity, and alarm threshold.
 Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management function provided by Huawei.
 Faults and alarms are recorded and stored. Up to 1500 historical fault and alarm records
can be stored.
 Access logs can be traced back. Historical user login and setting records can be
displayed. Up to 1000 historical records can be stored.

Features
 The display panel provides a touchscreen with a concise user-friendly interface.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 103


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 The controller controls the indoor temperature precisely and responds quickly.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
 The display panel displays the operating status and duration of the smart cooling product
components in real time.
 The fault diagnosis system automatically displays the information about current faults,
which facilitates the maintenance.
 The controller provides a variety of external ports including a fast Ethernet (FE) port and
universal serial bus (USB) port that is protected by a security mechanism.

7.2.3 Application Environment

Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.

Table 7-3–Table 7-7 describe the operating environment, physical ports, installation
requirements, and water quality requirements of the NetCol5000-A.

Environmental Specifications

Table 7-3 Environmental specifications

Item Specifications
Operating temperature 18–45°C
Operating humidity 20%–80% RH
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non–condensing)
Outdoor temperature  Working with the NetCol500–A032 (including
low–temperature components): –40°C to +45°C
 Working with the NetCol500–A036 (including
low–temperature components): –40°C to +55°C
 Working with the NetCol500–A036: –20°C to +55°C
 Working with the NetCol500-A026SC11E0: –20°C to
+45°C
 Working with the NetCol500-A0265S11E0: –20°C to
+55°C
 Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40°C to +45°C
Protection level  Indoor unit: IP20
 Outdoor unit: IPX5

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 104


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Altitude 0–1000 m. When the altitude is greater than 1000 meters, the
cooling capacity is derated. The maximum operating altitude is
4000 meters. For the detailed derated data, reference the Table
7-4.

Table 7-4 Altitude table

Height 0 1000 1500 2000 2500 3000 3500 4000


Density correction 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
Air volume correction 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
Refrigeration volume 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753
correction

Physical Ports

Table 7-5 Physical ports

Item Specifications
Refrigerant liquid pipe Copper pipe, with an outer diameter of 5/8 inch (15.88 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Refrigerant gas pipe Copper pipe, with an outer diameter of 3/4 inch (19.05 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Water inlet pipe to the G 1/2 inch inner screw thread
humidifier

Installation Requirements

When the total load power of servers corresponding to a single smart cooling product is less
than 5 kW or the equipment room airtightness is not satisfactory, the indoor humidity might
be relatively high, which is not a product quality issue. You are advised to install a
dehumidifier in the equipment room in this case.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 105


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-6 Installation requirements

Item Specifications
Equipment room door Width ≥ 0.9 m; height ≥ 2.3 m
Floor Bearing capacity ≥ 350 kg/m2; height of the raised floor ≥ 250
mm

Installation mode Installed on a concrete floor, a base, or an ESD floor


Pipe and cable routing Cables and pipes can be routed from the top or bottom
Equivalent length of ≤ 80 m
one-way pipe
Height difference  If the outdoor unit is placed higher than the indoor unit, the
between the indoor and maximum vertical distance between them is 20 m.
outdoor units  If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 m.
Thickness of the thermal ≥ 13 mm
insulation foam

Inner diameter of the Liquid pipe: 16 mm


thermal insulation foam Gas pipe: 19 mm
Drainage Drainpipes can withstand a high temperature greater than or
equal to 85°C (for the smart cooling products configured with
electrode humidifiers)
Power supply Leakage switches are not recommended for the main circuit. If
leakage switches are required by the customer or local
regulations, use the residual current circuit breaker (RCCB)
that is insensitive to the single-phase DC pulses and transient
current pulses
Note: If some conditions are not met, contact Huawei technical support.

Water Quality Requirements for Wet Film Humidifiers


The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1°C–40°C.
The wet film humidifier should use tap water (no water treatment facility needed for the inlet
water) that meets the following requirements:
 Non-freezing and nephelometric turbidity units (NTU): < 3
 No visible substances
 6.5 ≤ pH value ≤ 8.5
 Total hardness (in CaCO3): ≤ 450 mg/L

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 106


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Water Quality Requirements for Electrode Humidifiers

If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.

The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1°C–40°C.

Table 7-7 Water quality requirements for electrode humidifiers

Item Requirement Unit


Hydrogen ion 7–8.5 pH
Conductivity at 20°C 125–1250 µS/cm
(σ20)a
Inlet water hardness ≤ 100 mg/L
specificationsb
a: When σ20 is less than 125 µS/cm, the first vapor exhausting duration of the humidifier is
long; when σ20 greater than 1250 µS/cm, the humidifier service life is affected.
b: A water softener needs to be installed if the inlet water hardness exceeds 100 mg/L
(CaCO3).

7.2.4 Technical Specifications


Table 7-8 and Table 7-9 describe the general and optional specifications of the NetCol5000-A.

Table 7-8 General specifications

Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Air flow mode Horizontal air flow
Dimensions (H x W x D)  2000 mm x 300 mm x 1100 mm (cabinet)
 2000 mm x 300 mm x 1200 mm (cabinet with an
enclosure frame)
 2200 mm x 300 mm x 1100 mm (cabinet with an
enclosure frame, customizable)
 2200 mm x 300 mm x 1200 mm (cabinet with top and
enclosure frames)
Net weight 230 kg

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 107


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Environmental friendliness REACH, RoHS

 For a smart cooling product with heating and humidification functions, the general switch
is a 40 A, feature C switch that does not derate at 45°C. If the switch derates largely when
the temperature changes, verify that the switch can work at 40 A for a long time at 45°C.
 For a smart cooling product without heating and humidification functions, the general
switch is a 32 A, feature C switch that does not derate at 45°C. If the switch derates largely
when the temperature changes, verify that the switch can work at 25 A for a long time at
45°C.

Table 7-9 Optional specifications

Item NetCol5 NetCol5 NetCol5 NetCol5 NetCol5 NetCol5


000-A02 000-A02 000-A02 000-A02 000-A02 000-A02
5H412D 5H412D 5H412D 5H412D 5H4WE2 5H4WE0
20020E1/ 2E120E1 20020E0/ 2E120E0
NetCol5 NetCol5
000-A02 000-A02
5H40E2 5H40E0
Power supply Dual Dual Single Single Dual Single
mode power power power power power power
supplies supplies supply supply supplies supply
Maximum 20 A 30 A 20 A 30 A 30 A 30 A
current
Power system Supports the 380–415 V, 3PH+N+PE, 50 Hz/60 Hz power system, and
applies to scenarios where the voltage range is 342–457 V and
frequency range is 47–63 Hz.
Voltage If upstream voltage fluctuation exceeds the rated voltage±10%, you are
advised to add a voltage regulator. Otherwise, the smart cooling product
may generate alarms frequently and fail to work properly.
Heating No Yes No Yes Yes Yes
Humidification No Yes No Yes Yes Yes
Pipe routing Top and bottom pipe Bottom pipe routing Top and Bottom
routing bottom pipe
pipe routing
routing
Condensate Yes No Yes No
pump
Water pump lift 4m N/A 4m N/A
In the preceding table, No indicates that the corresponding model does not provide the

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 108


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item NetCol5 NetCol5 NetCol5 NetCol5 NetCol5 NetCol5


000-A02 000-A02 000-A02 000-A02 000-A02 000-A02
5H412D 5H412D 5H412D 5H412D 5H4WE2 5H4WE0
20020E1/ 2E120E1 20020E0/ 2E120E0
NetCol5 NetCol5
000-A02 000-A02
5H40E2 5H40E0
function.

7.3 NetCol5000-A035 Smart Cooling Product


This section describes the components, operating environment, and technical specifications of
the NetCol5000-A035 In-row Air Cooled Smart Cooling Product (35 kW smart cooling
product for short).

7.3.1 Indoor Unit


7.3.1.1 Appearance
Figure 7-4 shows the indoor unit of a NetCol5000-A in-row smart cooling product.

Figure 7-4 Appearance

Table 7-10 Dimensions of indoor

Dimensions H x W x D (mm) Expansion Method


Standard configuration 2000 x 300 x 1200 -
Expansion configuration 2200 x 300 x 1200 Install a top frame.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 109


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.3.1.2 Components
The NetCol5000-A indoor unit mainly consists of a compressor, oil separator, fan, heat
exchanger, electronic expansion valve, one-way valve, filter dryer, sight glass, electric heater
(optional), wet film humidifier (optional), water pump (optional), and LCD screen.

Figure 7-5 Components

(1) External signal port (2) Electric control box (3) Module subrack
(4) Driver (5) Wet film humidifier (6) Differential pressure switch
(7) Compressor (8) Drainpipe (9) Refrigerant gas pipe
(10) Refrigerant liquid pipe (11) Air filter (12) Fan
(13) Water pan cover (14) Water pump

 Compressor
The NetCol5000-A uses a variable-frequency compressor that features a compact size,
light weight, long service life, low noise, easy installation as well as high reliability,
stability, and energy efficiency.
 Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
 Fan
The energy-efficient EC fan that supports stepless speed adjustment is used to reduce the
energy consumption of the fan. Each fan is light and easy to maintain. The smart cooling
product will not shut down when a single fan fails.
 Evaporator

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 110


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

The finned-tube evaporator with a high cooling efficiency adopts the synergy field
principle and computational fluid dynamics (CFD) to optimize the flow path design,
which greatly improves the heat exchange efficiency.
 Electronic expansion valve
The flow regulator uses a miniature controller to control the operation of the step motor,
thereby changing the pass-through area of the valve to regulate the flow of refrigerant.
 One-way valve
The one-way valve effectively prevents gas or liquid backflow.
 Filter dryer
The filter dryer absorbs moisture from the refrigerant pipes and filters out foreign matter,
which reduces the component damage probability and improves operating efficiency and
reliability of components.
 Sight glass
The sight glass allows you to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
 Electric heater
It has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
 Humidifier
The wet film humidifier can be used to precisely control the equipment room humidity.
 Water pump
The water pump provides power for drainage.
 LCD screen
The indoor unit provides a 7-inch color touchscreen and man-machine interfaces for
query, setting, monitoring, and maintenance.

7.3.2 Outdoor Unit


Components
A NetCol500 outdoor unit mainly consists of an electric control box, a condenser, a rack, and
fans. The following, uses NetCol500-A060 as an example, describes the components and
configuration.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 111


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-6 Outdoor unit components

(1) Electric control box (2) Rack (3) Fan

Features
 The outdoor unit is equipped with a high-efficiency variable-frequency drive axial fan to
implement big air volume, low noise, and high efficiency.
 The outdoor unit has good waterproof performance and meets IPX5 requirements.
 The outdoor unit adopts the variable-frequency drive. The speed adjustment of the
outdoor fan ranges from 10% to 100%. The minimum operating frequency of the fan is
less than or equal to 5 Hz. The outdoor unit is running more steadily at low loads.
 The outdoor unit adopts the galvanized sheet and surface phosphatization + powder
coating techniques, the outdoor unit adapts to harsh environments with its sound rigidity
and anticorrosion performance.
 Pressure preservation is performed on the condenser before delivery, and the pipe ports
are properly sealed to prevent foreign matter from entry.

7.3.3 Controller
Appearance
The 7-inch display panel with the true-color touchscreen provides user interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the precision smart cooling product.
Figure 7-7 shows the location of the indicator. Table 7-11 lists the relationship of the alarm
status, indicator, and buzzer. If critical alarms, major alarms, and warning alarms are
generated simultaneously, the indicator shows the status of the alarm with the highest severity
level, and the buzzer shows the status of the alarm (not confirmed after the alarm generation)
with the highest severity level.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 112


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-7 LCD

(1) Indicator (2) USBa (Universal Serial Bus, reserved)


(3) 12 C/12 V (reserved) (4) DP (display port)
(5) SW (reserved)

a: USB has the following functions:


 After installing the WiFi module, locally connect to the smart cooling product over the Service
Expert app. Obtain the initial startup password during deployment. View or obtain the running
information about the smart cooling product during preventive maintenance. Only Huawei service
engineers or authorized service engineers are allowed to use the WiFi module. To ensure security,
remove the WiFi module immediately after use.
 Insert the USB flash drive, import and export the configuration file, export run logs, and upgrade
software.

Table 7-11 Indicator and buzzer status description

Alarm Status Indicators Buzzer


The device is operating properly, or a Green Silent
warning alarm occurs.
The buzzer keeps buzzing if a major Yellow Beeping intermittently
alarm is not confirmed after the
alarm generation.
The buzzer keeps buzzing if a critical Red Beeping continuously
alarm is not confirmed after the
alarm generation.

Functions
 When only one smart cooling product is running, the controller provides logic control of
components in the smart cooling product to adjust the indoor temperature and humidity.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 113


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 The 7-inch display panel with the true-color touchscreen allows you to set parameters for
the smart cooling product and query its status.
 The smart cooling product has the following three remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product
− Teleindication: startup/shutdown states, overvoltage/undervoltage, return air
overtemperature/undertemperature, return air overhumidity/underhumidity, filter
normal/blocked, and fan normal/faulty
− Teleadjust: smart cooling product startup/shutdown
 When multiple smart cooling products work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
− When a smart cooling product in the group is faulty, the backup smart cooling
product starts to operate automatically to improve the reliability of the smart
cooling product system.
− Each smart cooling product enters the active mode one by one periodically.
− The number of operating smart cooling products varies depending on the thermal
load in the equipment room to meet requirements promptly, eliminate hot spots, and
save energy.
− A mechanism is adopted to prevent the smart cooling products in the same
equipment room operating in opposite status (such as cooling and heating, or
humidification and dehumidification), in order to save energy.
 You can monitor, manage, and upgrade one or more smart cooling products using the
remote management software provided by Huawei.
 At least 1500 historical alarms can be stored.
 Access logs can be traced back. At least 1000 historical login and setting records can be
stored.
 The controller can display 30 days' temperature and humidity in colored curves. O&M
personnel can view the smart cooling product operating status onsite.
 A comprehensive power monitoring function is provided. Faults such as power open
phase, overvoltage, undervoltage, high frequency, and low frequency are diagnosed and
appropriate alarms are reported and recorded. Automatic protection, recovery, and restart
are also provided.

Features
 The controller provides a touchscreen with a user-friendly interface.
 The controller controls the indoor temperature precisely and responds quickly.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
 The controller provides multiple protection functions, such as chilled water valve
exception feedback, abnormal power-off self-recovery, and water leakage detection,
ensuring system reliability.
 The controller displays the operating status and duration of the smart cooling product
components in real time.
 The expert system automatically displays the information of the current fault, which
facilitates the maintenance.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 114


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism.
 The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
 The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
 If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.

7.3.4 Physical Ports


Table 7-12 shows the physical ports on the NetCol5000-A in-row smart cooling product.

Table 7-12 Physical port description

Item Specifications
Refrigerant liquid pipe Copper pipe; outer diameter: 5/8 in.; pressure resistance ≥ 4.5
MPa; welded

Refrigerant gas pipe Copper pipe; outer diameter: 3/4 in.; pressure resistance ≥ 4.5
MPa; welded
Humidifier water inlet Reserved port: BSPP 1/2 in.; thread connection
pipe
Top drainpipe Reserved port: BSPP 1/2 in.; thread connection
Bottom drainpipe Reserved port: copper pipe with an outer diameter of 5/8 in.;
you are advised to use a hose with an inner diameter of 14 mm
for connection.

7.3.5 Technical Specifications


Table 7-13 and Table 7-14 respectively show the main technical specifications of the
NetCol5000-A in-row smart cooling product.

Table 7-13 General specifications

Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Cooling capacity 35 kW
Air volume 6000 m3/h
Air supply mode Horizontal air supply
Certification REACH, RoHS, CE, WEEE, China Energy Conservation
Certification, and IEC
Cooling capacity test conditions: dry bulb temperature at air return vent: 37°C; relative

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 115


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
humidity at air return vent: 20%; outdoor temperature: 35°C.

Table 7-14 Technical specifications of the indoor unit

Item NetCol5000-A0 NetCol5000-A NetCol5000- NetCol5000-


35H4WE0 035H40E0 A035H4WE2 A035H40E2
Power supply Single power Single power Dual power Dual power
mode supply supply supplies supplies
Power system 380–415 V, 3PH+N+PE, 50 Hz/60 Hz
Voltage If upstream voltage fluctuation exceeds the rated voltage±10%, you are
advised to add a voltage regulator. Otherwise, the smart cooling product
may generate alarms frequently and fail to work properly.
Heating Yes No Yes No
Humidification Yes No Yes No
Pipe routing Bottom pipe routing Top and bottom pipe routing
Condensate No Yes
pump
Water pump lift - 4m
a: In the preceding table, No indicates that the corresponding model does not provide the
function.

Figure 7-8 Dimensions

Table 7-15 Technical specifications of the outdoor unit

Item NetCol500-A060 NetCol500-A120


Power supply mode Power supplied by the Power supplied by the indoor unit
indoor unit

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 116


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item NetCol500-A060 NetCol500-A120


Operating temperature -20°C to 45°C (With a -20°C to 45°C (With a
range low-temperature low-temperature component -40°C
component -40°C to 45°C) to 45°C)
Fan speed range 10%–100% 10%–100%
Number of fans 1 2
Dimensions H1 (H2) x 52273539: 1107 (677) x 52273755-002: 1107 (655) x 1356
W1 (W2) x D (mm) 1356 (1217) x 1094 (1217) x 2189
52273539-005: 1107 (655)
x 1356 (1217) x 1094
52273539-006: 1156 (725)
x 1356 (1217) x 1094
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Protection level IPX5
Altitude 0–4000 m. If the altitude exceeds 1000 m, the cooling
performance is derated. For detailed derating data, contact
Huawei technical support.
Certification RoHS, REACH, WEEE

Outdoor unit installation environments are classified as follows based on the harshness:
 Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live.
 Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%.
 Class C (harsh environment): refers to sea environments or outdoor land environments with simple
shielding measures near pollution sources.
 Class D (marine environment): environments that are within 500 m from the coast.
NetCol500-A0605S outdoor unit must not be installed in Class D environments, and other outdoor
units must not be installed in Class C or Class D environments.

7.4 NetCol5000-A050 Smart Cooling Product


This section describes the components, operating environment, and technical specifications of
the NetCol5000-A050 In-row Air Cooled Smart Cooling Product (46 kW smart cooling
product for short).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 117


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.4.1 Product Composition


Dimensions
The standard dimensions (H x W x D) of the 46 kW smart cooling product are 2000 mm x 600
mm x 1200 mm.

Figure 7-9 Dimensions (unit: mm)

(1) Cabinet connecting kit (2) Controller panel (3) Door lock (4) Front door
(5) Mounting hole (6) Side panel (7) Rear door (8) Anchor

Table 7-16 Dimensions

Dimensions H x W x D (mm) Expansion Method


Standard dimensions 2000 x 600 x 1200 -
Expanded dimensions 2200 x 600 x 1200 Install a top frame.

Components
The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan,
evaporator, electronic expansion valve (EEV), oil separator, sight glass, filter dryer, air filter,
electric heater (optional), wet film humidifier (optional), condensate pump (optional), check
valve, differential pressure switch, and temperature and humidity sensor (T/H sensor).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 118


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-10 Components

(1) Fan (2) Condensate pump


(3) Drainage check valve (4) Electric heater
(5) Strong-current box (6) Evaporator
(7) Wet film humidifier (8) Compressor
(9) Filter dryer (10) Oil separator
(11) EEV (12) Compressor driver
(13) T/H sensor (14) Weak-current box
(15) Signal cable terminal block (16) Differential pressure switch

 Compressor
− The NetCol5000-A uses a DC variable-frequency compressor that features compact
size, light weight, long service life, low noise, easy installation as well as high
reliability, stability, and energy efficiency.
− The high-precision drive automatically adapts to the system pressure fluctuations.
− The drive conducts precision self-check. Compressor and drive faults can be stored
in separate zones.
 EC fan
− The energy-efficient EC fan that supports stepless speed adjustment is used to
reduce the energy efficiency of the fan.
− There are ten EC fans in total. The smart cooling product will not shut down when a
single fan fails.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 119


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

− Fans can be maintained with power-on. You can replace one faulty fan without
shutting down the smart cooling product.
 Evaporator
− The evaporator adopts the inner threaded copper pipe and blue hydrophilic
aluminum foil to prevent water blowing due to condensate water accumulation and
improve heat exchange performance. The V-type evaporator optimizes the airflow
pattern and reduces the air resistance.
− The finned-tube evaporator with a high cooling efficiency adopts the synergy field
principle and computational fluid dynamics (CFD) to optimize the flow path design,
which greatly improves the heat exchange efficiency.
− The small diameter evaporator is adopted to enhance the heat exchange
performance, a 10%+ increase in heat exchange efficiency compared with a
traditional solution.
− The designed pressure bearing capacity of the heat exchange coil is 1.6 MPa, an
excellent pressure bearing capacity.
 EEV
− The flow regulator uses a miniature controller to control the operation of the step
motor, thereby changing the pass-through area of the valve to regulate the flow of
refrigerant.
− The EEV is equipped with an energy storage unit that prevents slugging due to
migration of refrigerant when the smart cooling product is powered off abnormally.
 Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
 Sight glass
It allows you to observe the refrigerant flow and gas content for easy maintenance and
optimization.
 Filter dryer
It absorbs water from the refrigerant pipes and filters the foreign matter, which reduces
component damage rates and improves operating efficiency and reliability.
 Air filter
The G4 air filter is used. The air filter meets the relevant requirements of the China
National Standard GB/T 14295-2008.
 Electric heater
− The positive temperature coefficient (PTC) electric heater automatically adjusts
heating capacity and provides multiple protection measures to ensure secure and
reliable operating.
− The heater features quick start, large heating capacity, and even heating.
 Wet film humidifier
− The wet film humidifier has low water quality requirements and high environment
adaptability.
− The wet film humidifier has a simple structure and is easy to remove, clean, and
maintain.
− The wet film humidifier can quickly start and generate huge humidification
capacity.
− The wet film humidifier consumes less power, saving more than 95% of energy
compared with a traditional electrode humidifier.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 120


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

− Compared with a traditional electrode humidifier, the wet film humidifier has a
longer service life and maintenance interval.
 Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
 Check valve
The check valve effectively prevents gas or liquid backflow.
 Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers an alarm,
prompting for air filter replacement.
 T/H sensor
Built-in negative temperature coefficient (NTC) temperature sensors and return air T/H
sensor are provided.

7.4.2 Operating Environment Requirements


Physical ports

Table 7-17 Physical ports

Item Specifications
Indoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch (15.88 mm),
welding
Refrigerant gas pipe Outer diameter of 7/8 inch (22.22 mm),
welding
Humidifier water inlet pipe G 1/2 inch inner screw thread (humidifier
hose is provided for the smart cooling
product)
G 3/4 inch outer screw thread (humidifier
hose is not provided for the smart cooling
product)
Drainpipe BSPP 1/2 inch inner screw thread
Outdoor unit Refrigerant liquid pipe Outer diameter of 5/8 inch (15.88 mm),
welding
Refrigerant gas pipe Outer diameter of 7/8 inch (22.22 mm),
welding
water cooling Refrigerant liquid pipe Outer diameter of 5/8 inch (15.88 mm),
module welding
Refrigerant gas pipe Outer diameter of 7/8 inch (22.22 mm),
welding
Low-temperat Connecting to indoor unit Outer diameter of 5/8 inch (15.88 mm),
ure component liquid pipe welding
(optional
component) Connecting to indoor unit Outer diameter of 7/8 inch (22.22 mm),
gas pipe welding

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 121


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Connecting to outdoor unit Outer diameter of 5/8 inch (15.88 mm),
liquid pipe welding
Connecting to outdoor unit Outer diameter of 7/8 inch (22.22 mm),
gas pipe welding

Installation requirements

Table 7-18 Installation requirements

Item Specifications
Equipment room Width: ≥ 1.2 m; height: ≥ 2.3 m
door
Floor Floor bearing capacity: ≥ 530 kg/m2
Equivalent length of ≤ 100 m
one-way pipe
Vertical difference  Outdoor unit higher than indoor unit: ≤ 30 m
between the indoor  Outdoor unit lower than indoor unit: ≤ 8 m
and outdoor units

Water supply The inlet water pressure should be in the range of 0.1–0.7 MPa (A
reducing valve must be installed if the inlet water pressure exceeds
0.7 MPa.), and the temperature should be in the range of 1°C–40°C.
The water should meet the following requirements:
 Non-freezing and nephelometric turbidity units (NTU): < 3
 No visible substances
 6.5 ≤ pH value ≤ 8.5
 Total hardness (in CaCO3): ≤ 450 mg/L
Drainage The distance between the upper drainage of the water pump and the
cabinet installation floor should not exceed 4 meters.
Power distribution Leakage circuit breakers are not recommended for the primary
route. If a leakage circuit breaker is required by the customer or by
local regulations, use the residual current circuit breaker (RCCB)
that is not sensitive to the single-phase DC pulses and transient
current pulses.
Note: If the requirements are not met, contact Huawei technical support for an optimized
solution.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 122


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.4.3 Controller
Appearance
The 7-inch display panel with the true-color touchscreen provides user interfaces for query,
setting, monitoring, and maintenance.
The indicator on the panel displays operating status of the precision smart cooling product.
Figure 7-11 shows the location of the indicator. Table 7-19 lists the relationship of the alarm
status, indicator, and buzzer. If critical alarms, major alarms, and warning alarms are
generated simultaneously, the indicator shows the status of the alarm with the highest severity
level, and the buzzer shows the status of the alarm (not confirmed after the alarm generation)
with the highest severity level.

Figure 7-11 LCD

(1) Indicator (2) USBa (Universal Serial Bus, reserved)


(3) 12 C/12 V (reserved) (4) DP (display port)
(5) SW (reserved)

a: USB has the following functions:


 After installing the WiFi module, locally connect to the smart cooling product over the Service
Expert app. Obtain the initial startup password during deployment. View or obtain the running
information about the smart cooling product during preventive maintenance. Only Huawei service
engineers or authorized service engineers are allowed to use the WiFi module. To ensure security,
remove the WiFi module immediately after use.
 Insert the USB flash drive, import and export the configuration file, export run logs, and upgrade
software.

Table 7-19 Indicator and buzzer status description

Alarm Status Indicators Buzzer


The device is operating properly, or a Green Silent
warning alarm occurs.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 123


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Alarm Status Indicators Buzzer


The buzzer keeps buzzing if a major Yellow Beeping intermittently
alarm is not confirmed after the
alarm generation.
The buzzer keeps buzzing if a critical Red Beeping continuously
alarm is not confirmed after the
alarm generation.

Functions
 When only one smart cooling product is running, the controller provides logic control of
components in the smart cooling product to adjust the indoor temperature and humidity.
 The 7-inch display panel with the true-color touchscreen allows you to set parameters for
the smart cooling product and query its status.
 The smart cooling product has the following three remote functions.
− Telemetry: supply air temperature, return air temperature, supply air humidity,
return air humidity, and working status of the smart cooling product
− Teleindication: startup/shutdown states, overvoltage/undervoltage, return air
overtemperature/undertemperature, return air overhumidity/underhumidity, filter
normal/blocked, and fan normal/faulty
− Teleadjust: smart cooling product startup/shutdown
 When multiple smart cooling products work cooperatively, the controller optimally
distributes the heat load to reduce power consumption and provides backup to improve
reliability.
− When a smart cooling product in the group is faulty, the backup smart cooling
product starts to operate automatically to improve the reliability of the smart
cooling product system.
− Each smart cooling product enters the active mode one by one periodically.
− The number of operating smart cooling products varies depending on the thermal
load in the equipment room to meet requirements promptly, eliminate hot spots, and
save energy.
− A mechanism is adopted to prevent the smart cooling products in the same
equipment room operating in opposite status (such as cooling and heating, or
humidification and dehumidification), in order to save energy.
 You can monitor, manage, and upgrade one or more smart cooling products using the
remote management software provided by Huawei.
 At least 1500 historical alarms can be stored.
 Access logs can be traced back. At least 1000 historical login and setting records can be
stored.
 The controller can display 30 days' temperature and humidity in colored curves. O&M
personnel can view the smart cooling product operating status onsite.
 A comprehensive power monitoring function is provided. Faults such as power open
phase, overvoltage, undervoltage, high frequency, and low frequency are diagnosed and
appropriate alarms are reported and recorded. Automatic protection, recovery, and restart
are also provided.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 124


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Features
 The controller provides a touchscreen with a user-friendly interface.
 The controller controls the indoor temperature precisely and responds quickly.
 The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
 Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
 The controller provides multiple protection functions, such as chilled water valve
exception feedback, abnormal power-off self-recovery, and water leakage detection,
ensuring system reliability.
 The controller displays the operating status and duration of the smart cooling product
components in real time.
 The expert system automatically displays the information of the current fault, which
facilitates the maintenance.
 The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism.
 The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
 The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
 If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.

7.4.4 Technical Specifications


Table 7-20 General specifications

Item Specifications
Refrigerant R410A
Cooling capacity 46 kW
Air supply mode Horizontal flow
Airflow 9000 m3/h
Dimensions (H x  2000 mm x 600 mm x 1200 mm (cabinet dimensions)
W x D)  2200 mm x 600 mm x 1200 mm (including a top frame)
Net weight/Gross 305 kg/342 kg
weight (full
configuration)
Certification CQC, CE, RoHS, REACH, WEEE, and IEC standard
a: Test condition is rated condition (Indoor dry-bulb temperature: 37°C. Relative humidity:
24%. Outdoor temperature: 35°C).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 125


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Table 7-21 Optional specifications

Item NetCo NetCol NetCol5 NetCol5 NetCol50 NetCol5000


l5000- 5000-A 000-A05 000-A050 00-A050H -A050H40E
A050H 050H40 0H4WE2 H40E2 4WD0 0
4WD2 D2
Power system 380–415 V AC, 50 Hz or 60 Hz 3Ph+N+PE
Tolerance: –10% to +10% of rated voltage, rated frequency±3 Hz
Power supply Dual power supplies Single power supply
mode
Pipe routing Top and bottom pipe routing Bottom pipe routing
Max Current 46 A
Condensate Yes No
pump
Heating Yes No Yes No Yes No
function
Humidificatio Yes No Yes No Yes No
n function
Humidifier No No Yes No Yes No
water inlet
hose
Reheating 6kW No 6kW No 6kW No
capacity
Connection Welding Thread connection
mode of the
compressor or
filter dryer
Castor No Yes
Humidifying 3kg/h No 3kg/h No 3kg/h No
capacity

7.5 NetCol500 Outdoor Unit


Table 7-22 Mapping between indoor and outdoor units of smart cooling products

Indoor Unit Outdoor Unit Abbreviation


25 kW smart NetCol500-A026SC11E0 NetCol500-A026
cooling product
NetCol500-A0265S11E0 NetCol500-A026
NetCol500-A0365C11E0 NetCol500-A036

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 126


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Indoor Unit Outdoor Unit Abbreviation


42 kW smart NetCol500-A0365C11E0 NetCol500-A036
cooling product
NetCol500-A0365S11E0 NetCol500-A036
NetCol500-A0725C11E0 NetCol500-A072
46 kW smart NetCol500-A060 NetCol500-A060
cooling product
NetCol500-A080 NetCol500-A080
NetCol500-A120 NetCol500-A120

7.5.1 Product Composition


Appearance

Figure 7-12 Appearance 1

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 127


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-13 Appearance 2

Components
The NetCol500 outdoor unit consists of a condenser, electric control box, rack, and fans.

Figure 7-14 Components

(1) Condenser (2) Electric control box


(3) Rack (4) Fans

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 128


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

7.5.2 Technical Specifications


Figure 7-15 Dimensions of the NetCol500 outdoor unit

Table 7-23 Technical specifications of the NetCol500 outdoor unit 1

Product NetCol500-A0 NetCol500-A0 NetCol500-A0 NetCol500-A0


Model 26SC11E0 265S11E0 365C11E0/Net 725C11E0
Col500-A0365
S11E0
Power system 220–240 V AC, 380–480 V AC, 3 Ph/N/PE, 50 Hz/60 Hz (for a unit
L/N/PE, 50 Hz with a low-temperature component, the power system
is 380–415 V AC, 3 Ph/N/PE, 50 Hz/60 Hz)
Voltage Rated voltage ±10%b
tolerance
Frequency Rated frequency ±3 Hz
tolerance
Maximum 3.3 2.5 2.5 4.5
outdoor unit
current (A)
Air volume 8000 12000 12000 26000
of fans (m3/h)
Number of 1 1 1 2
fans
Liquid pipe 5/8 in. (15.88 5/8 in. (15.88 5/8 in. (15.88 5/8 in. (15.88
outer mm) mm) mm) mm)
diameter
Gas pipe 3/4 in. (19.05 3/4 in. (19.05 7/8 in. (22.22 7/8 in. (22.22
outer mm) mm) mm) mm)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 129


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Product NetCol500-A0 NetCol500-A0 NetCol500-A0 NetCol500-A0


Model 26SC11E0 265S11E0 365C11E0/Net 725C11E0
Col500-A0365
S11E0
diameter
Dimensions 1053 x 1110 1077 x 1120 1156 x 1355 1096 x 2185
H1 x W1 (985) x 1094 (985) x 1094 (1220) x 1094 (2050) x 1094
(W2) x D
(mm)
Dimensions 599 x 1110 623 x 1120 702 x 1355 642 x 2185
H2 x W1 (985) x 1094 (985) x 1094 (1220) x 1094 (2050) x 1094
(W2) x D
(mm)
Net weight 91 132 130/147 195
(kg)
Certification RoHS, REACH, CE/CBc
Operating Depends on the indoor unit. For details, see the product overview in the
temperature indoor unit user manual.
Storage –40 to +70
temperature
(°C)
Storage 5%–95% RH (non-condensing)
humidity
Altitude 0–1000 m: normal use; above 1000 m: derating. For derating details, see
the product overview in the indoor unit user manual.
b: If the upstream voltage may fluctuate outside the voltage tolerance, install a voltage
stabilizer; otherwise, the smart cooling product may fail to run properly due to frequent
alarms.
c: CE certification is required if the NetCol500-A026SC11E0 works with the
NetCol5000-A025 (300 mm wide). CE certification is required for the other models.

Table 7-24 Technical specifications of the NetCol500 outdoor unit 2

Item NetCol500-A060 NetCo NetCol500-A120


l500-A
080
Power supply mode Power supplied by the indoor unit
Operating temperature -20°C to 45°C (With a -5°C to -20°C to 45°C (With a
range low-temperature +55°C low-temperature
component -40°C to component -40°C to
45°C) 45°C)
Number of fans 1 2 2

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 130


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item NetCol500-A060 NetCo NetCol500-A120


l500-A
080
Fan speed range 10%–100%
Dimensions (H1 (H2) x Class B: 1107 (655) x 1107 1107 (655) x 1356 x 2189
W x D) (mm) 1356 x 1094 (655) x
Class C: 1156 (725) x 2186 x
1356 x 1094 1094

Storage temperature –40°C to +70°C


Storage humidity 5%–95% RH (non-condensing)
Protection level IPX5
Altitude 0–4000 m. If the altitude exceeds 1000 m, the cooling
performance is derated. For detailed derating data, contact
Huawei technical support.
Certification CE, RoHS, REACH, CQC, WEEE, and IEC

Outdoor unit installation environments are classified as follows based on the harshness:
 Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
 Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity reaches 100% occasionally
 Class C (harsh environment): marine environments within 3.7 km away from the coast or outdoor
land environments with simple shielding measures within 1.2 km away from a pollution source
 Class D (marine environment): environments within 500 m away from the coast
The NetCol500-A0365S11E0, NetCol500-A0265S11E0 and NetCol500-A0605S outdoor units must not
be installed in class D environments, and other outdoor units must not be installed in class C or class D
environments.

7.5.3 (Optional) Low-Temperature Component


Working Principle
When the outdoor temperature is below the operating temperature lower limit specified for the
product, the condensing pressure of the system for the outdoor unit condenser with natural
cooling may still stay below the safe operating pressure of the compressor. A low-temperature
component is required to address this issue.
The low-temperature component intelligently controls the condensing pressure to ensure that
the equipment can work safely and reliably at an outdoor ambient temperature as low as
–40ºC. When detecting that the outdoor condensing pressure is low, the pressure stabilizing
valve automatically opens to bypass hot gas to the liquid storage tank of the low-temperature
component, thereby ensuring that the condensing pressure stays within the range for safe and
reliable operation. When detecting that the condensing pressure exceeds the threshold, the
pressure stabilizing valve automatically closes the bypass.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 131


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-16 Low-temperature component

(1) Safety valve (2) Connecting to indoor (3) Connecting to outdoor


unit liquid pipe unit liquid pipe
(4) Condensing pressure (5) Connecting to outdoor (6) Connecting to indoor unit
control valve unit gas pipe gas pipe

A low-temperature component is mandatory when the outdoor ambient temperature may drop
to –20ºC.

Table 7-25 Low-temperature component specifications

Item Specifications
Heater power supply 220–240 V AC, 1 Ph, 50 Hz or 60 Hz
Heater power supply voltage tolerance Rated voltage ±10%
Heater power supply frequency Rated frequency ±3 Hz
tolerance
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.88 mm)
Gas pipe outer diameter 7/8 inch (22.22 mm)
HxWxD 632 mm x 944 mm x 507 mm (with package)
470 mm x 828 mm x 300 mm (without package)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 132


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Item Specifications
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa

7.5.4 (Optional) Sunshade


When an outdoor unit is used in the T3 working condition (–5°C to +55°C), install a sunshade
if the following three conditions are met.
 The outdoor unit is installed horizontally.
 The ambient temperature exceeds 50°C.
 The outdoor unit is directly exposed to sunlight.

If the previous three conditions are met but no sunshade is installed, the smart cooling product
will shut down because the components are applied beyond specifications.

Figure 7-17 Sunshade appearance

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 133


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

Figure 7-18 Sunshade dimensions (unit: mm)

Sunshades do not apply to the NetCol500-A026.

7.6 Water Cooling Module


Product Composition
The NetCol500 water cooling module consists of an electric control box, a water valve
actuator, and a rack. The following describes the components and configuration.

Figure 7-19 Water cooled module components

(1) Water valve actuator (2) Water return (3) Water supply pipe
pipe
(4) Negative temperature coefficient (5) Liquid pipe (6) Electric control
(NTC) box
(7) Gas pipe (8) Needle valve (9) Safety valve

Features
 The water valve is pre-integrated to save onsite installation time.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 134


FusionModule2000 Smart Modular Data Center
Product Description 7 Temperature Control System

 The water cooling module can be installed in stack mode to maximize the installation
space and reduce the footprint.
 The water cooling module uses cooling water for heat exchange to improve the heat
exchange efficiency and improve the energy efficiency of the entire system to 4.0 COP.

Table 7-26 Operating environment specifications with water cooling module

Item Technical Specifications


Power system 220 V to 240 V AC 1Ph 50 Hz/60 Hz
Refrigerant R410A
Heat exchanging 55 kW
capacity
Temperature range 4°C to 45°C
Humidity range 5%–90% RH
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Inlet water 10°C to 37°C
temperature range of
chilled water
Highest operating 125
temperature of the
shell pass (°C)
Highest operating 60
temperature of the
tube pass (°C)
IP rating IPX4
Altitude 0–4000 m (derated when the altitude is greater than 1000 m)
Environment Enclosed indoor environment in which the temperature and
humidity can be controlled within the ranges of 4°C to 45°C and
5% RH to 90% RH respectively. If the indoor installation position
is ventilated, it should be more than 5 km away from the sea or
pollution sources (such as salt lakes, chemical plants, mineral
plants, thermal power plants, and coal mines).
Dimensions (H x W x 330 mm x 326 mm x 1417 mm
D)
Net weight (kg) 60
Certification CE, RoHS, REACH, WEEE, and Chinese industrial product
manufacture license

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 135


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8 Intelligent Module Management System

8.1 System Overview


Each smart module provides an independent and integral environment and power monitoring
interface. This interface constantly monitors devices such as the power supply and distribution
equipment, UPS, smart cooling products, temperature and humidity sensors, water sensors,
smoke sensors, and video surveillance equipment inside the module. If a component fault or
parameter error is detected, alarms are generated in diverse modes such as indicator light,
email, and short message service (SMS). Historical data and alarm events are recorded, and
all monitoring information is reported to the management platform.
The pad app or mobile phone app can be used to query device information in real time,
facilitating mobile O&M.
To improve the reliability of the monitoring system, Ethernet ring bus networking is used for
intelligent node signal transmission and sensor power supply.

Figure 8-1 Network diagram

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 136


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

 In the figure, RF_Z indicates wireless networking. RF_Z (1) devices can communicate with the
ECC800-Pro in wireless mode. The RF_Z (2) iBOX and iBAT communicate with each other in
wireless mode. RF_Z (1) and RF_Z (2) devices use different protocols and are isolated from each
other.
 After the access actuator, skylight actuator, multi-functional sensor and ECC800-Pro are connected
through PoE and they communicate successfully, wireless communication is automatically set up.
 Connect the signal cable from each camera and VCN to the LAN switch in the following scenarios:
(1) Four or more cameras are deployed in a single smart module. (2) The cameras outside the smart
module are connected to the smart module, and there are at least four cameras inside and outside the
smart module. (3) Multiple smart modules share one VCN. (4) There are at least two VCNs.

8.2 System Functions


8.2.1 Monitoring
 Temperature and humidity monitoring: Detects and collects statistics on the ambient
temperature and humidity inside the smart module.
 Water leakage monitoring: Detects water leakage at the bottom of the smart module and
provides real-time alarm signals.
 Smoke monitoring: Detects smoke in the smart module and provides real-time alarm
signals.
 Power distribution monitoring:
a. Detects and collects statistics on the total input phase voltage, current, frequency,
power factor, electric energy, active power, apparent power, load rate, THDv, THDi,
and cabinet interior busbar temperature for the smart module.
b. Detects the current, electric energy, switch status, contact temperature, and load rate
of the IT and smart cooling product power distribution branches; collects statistics
on electric energy by month or year.
 Smart cooling product monitoring:
a. Monitors the supply and return air temperature and humidity in real time.
b. Configures the supply air temperature set point in a unified manner, without the
need to separately configure it for each smart cooling product.
c. Monitors and displays the fan speed, and displays the running percentage.
d. Displays the cooling load rate.
e. Monitors and displays the compressor running status.
f. Provides reminders on regular air filter replacement.
g. Displays the real-time running status of the heating and humidifying.
 Video surveillance: Connects to three cameras and provides PoE power supply; accesses
real-time video images on the WebUI and invokes historical monitoring data.

8.2.2 App View

App view is for reference only.


 Generates a 3D layout view that matches the actual layout of the smart module,
including the PDF, smart cooling product, IT cabinet, and temperature and humidity

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 137


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

sensor. The app can also graphically display the power, space (optional), and temperature
(optional) of a single cabinet. In addition, the resource usage rate of electric energy,
space, and cooling capacity, PUE value, power consumption, ambient temperature and
humidity, and alarm information of the smart module are displayed on the home screen
of the app.

Figure 8-2 App home screen (electric energy)

Figure 8-3 App home screen (temperature)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 138


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

 Supports full link display of the power supply and distribution system for the smart
module. The connection mode and topology of the power supply and distribution devices
such as the integrated UPS, battery, PDF, and cabinet rPDU are included. Users can
check the switch status and running status of power supply and distribution devices in a
view.

Figure 8-4 Power supply link view

 Shows the cooling system of the smart module, displays the air inlet temperature, air
outlet temperature, and running parameters of smart cooling products, aisle temperature,
aisle humidity, and temperatures (optional) at the front and rear sides of a single cabinet.
The app also displays the detailed running parameters of a single smart cooling product
and the running status of components such as the compressor, fan, and expansion valve.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 139


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-5 iCooling view

Figure 8-6 Running view of a single smart cooling product

 Displays the resource usage of the electric energy, space, and cooling capacity of the
smart module and each cabinet.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 140


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-7 Power view

 Displays the real-time status and alarms of the aisle temperature and humidity sensor,
door status sensor, water sensor, lighting in the plan view.

Figure 8-8 Environment status view

 Displays the PUE value of the smart module in a data dashboard; allows you to view the
historical PUE curve and power consumption of the smart module by day, month, or
year.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 141


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-9 PUE curve

 Facial recognition is supported through an app installed on a tablet computer. After facial
recognition information is added, click Facial Enter to start the facial recognition. If you
do not have facial recognition permission or an error occurs during facial recognition,
you can use the user name and password login manner. After you successfully logs in
using facial recognition, the system determines whether to open the door based on your
access control configuration.

Figure 8-10 Facial recognition

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 142


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.2.3 Alarm
 The system monitors the status of smart cooling products, power distribution, and
environment. If a fault or parameter error occurs, the system generates an alarm in real
time. You can view the alarm cause and solution in the alarm details.
 Alarms can be classified into four severities: critical, major, minor, and warning. The
alarm severities can be user-defined.
 Active alarms can be filtered by device and alarm severity.
 Real-time alarms can be displayed in different colors on the power supply link view of
the app. Alarms can be associated with the alarm beacon and eLight. The color
corresponding to the alarm severity is displayed on the aisle door of the smart module.
 Alarm notifications can be sent by email and SMS.
 A maximum of 500 concurrent active alarms are supported.

8.2.4 History Query


 Historical alarm export: You can view the alarms that have been generated in the system.
The historical alarm information includes the device name, alarm name, alarm severity,
alarm generation time, and alarm clearance time.
 Performance data statistics: You can view historical data of devices to help analyze data
or problems.
 Operation log query: You can view logs of key operations, such as user login, parameter
modification, data export, device upgrade, and access control events.
 Data export: You can export historical data of the ECC800-Pro and certain southbound
devices.

8.2.5 Linkage Control


 Supports the linkage logic of aisle smoke alarms or high temperature alarms. By default,
the skylights are opened by linkage. You can manually configure the linkage to open the
end doors (automatic sliding doors), turn on the aisle lights, and shut down the smart
cooling products.

The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only dry contact
alarm signals are provided.
 The smart cooling product in the aisle can be stopped when the dry contact alarm of the
customer's fire extinguishing system is generated.
 Dry contact alarms or signals can be associated with the customer's or external fire
extinguishing system to open the skylight, the door status sensor, and the lighting
system.
 You can manually configure linkage policies for monitoring systems inside the smart
module.
 Intelligent lighting (motion detection): If a motion within the aisle is detected, the aisle
light turns on. If a motion is no longer detected within 10 minutes (can be set), the aisle
light turns off automatically.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 143


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3 Key Hardware Devices


8.3.1 ECC800-Pro Core Controller
8.3.1.1 Product Configuration
The ECC800-Pro data center controller is used to monitor the devices and environment in the
smart module. It consists of the power module and main control module. You can insert and
remove the power module.
You can configure the ECC800-Pro collector in the following two manners:
Configuration 1 (typical configuration): one power module and one main control module
Configuration 2: two power modules and one main control module.

 In configuration 1, install a filler panel in slot 2.


 In configuration 2, install power modules in slots 1 and 2.

Figure 8-11 ECC800-Pro collector in configuration 2

(1) Slot 1: power modules (2) Slot 2: power modules (3) Slot 3: main control module

Table 8-1 ECC800-Pro environmental specifications

Item Specifications
Working temperature –20°C to +50°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m (When the altitude is between 3000 m and 4000 m,
the temperature decreases by 1°C for each additional 200 m.)

Table 8-2 ECC800-Pro structural specifications

Item Specifications
Dimensions (L x W x H) 442 mm × 330 mm × 43.6 mm
Weight 7.5 kg (dual power supplies + main control

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 144


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
module)
Color Black
Installation Can be installed in a 1 U space in a standard
19-inch cabinet
Environmental protection RoHS5, REACH, WEEE

Figure 8-12 ECC800-Pro (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1


(4) AC_INPUT2

Power Ports
The ECC800-Pro provides four power ports, including two AC input ports (AC_INPUT1 and
AC_INPUT2) and two DC output ports (DC_OUTPUT1 and DC_OUTPUT2). Table 8-3
provides the power port pin definitions.

Table 8-3 Power port pin definitions

Port Type Pin Description


AC Pin 1 L
Pin 2 PE
Pin 3 N
DC Pin 1 48V+
Pin 2 48V GND

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 145


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.1.2 Main Control Module

Figure 8-13 ECC800-Pro collector main control module

(1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2


(5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE
(9) LAN2/POE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5
(13) AIDI_3 (14) DO/12V (15) RF_Z (16) WLAN
(17) 4G (18) SW button

Figure 8-14 ECC800-Pro main control module (side view)

(1) SIM card slot (2) Micro-SD card slot (reserved)

Specifications

Table 8-4 Technical specifications of the ECC800-Pro main control module

Item Specifications
Power input  Supports one AC input or two AC inputs

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 146


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
 Rated voltage: 200–240 V AC
 Rated frequency: 50/60 Hz
Power output  Output voltage: 42 - 58 V DC (rated voltage: 53.5 V DC)
 Output power of two power module supplies: 2000 W (176–300
V AC); 940 W (linear derating at 85–175 V AC)
 Output power of a single power module supply: 1000 W
(176–300 V AC); 470 W (linear derating at 85–175 V AC)
WAN port  Supports two WAN ports. WAN1 is used to connect to the
management system, and WAN2 is used for maintenance. The
ports support autonegotiation of 10/100/1000 Mbit/s
communication rates.
 Connect shielded network cables to the WAN ports.
LAN port  Supports two LAN ports, which can be connected to the LAN.
The ports support autonegotiation of 10/100/1000 Mbit/s
communication rates.
 Connect shielded network cables to the LAN ports.
RS485 serial port  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)
expansion  Supports four RS485 ports with the default communications rate
of 9600 bit/s.
 COM1–COM3 ports provide 12 V DC power.
 The power supply can be switched on or off and is on by
default.
POE expansion Supports two POE (GE) ports for expansion of the POE bus, and
supports network isolation and ring network.

AIDI expansion  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)


(RJ45)  Provides five universal AIDI ports for connecting to sensors
such as smoke sensors, water sensors, and NTC sensors. AIDI_1
to AIDI_3 are full-function AIDI ports, and AIDI_4 to AIDI_5
are simplified AIDI ports without type identification.
 The power supply can be switched on or off and is on by
default.
DO expansion  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)
(RJ45)  One DO port. Supports active DO.
 The power supply can be switched on or off and is on by
default.
Fault isolation There are three groups of 12 V ports. A group has a maximum
current of 660 mA, a route has a maximum current of 800 mA, and
the maximum total current is 2 A.
Group 1: 12 V of the AIDI_1 and DO/12V ports
Group 2: 12 V of the AIDI_2, COM1/AIDI_4, and COM3/12V
ports
Group 3: 12 V of the AIDI_3 and COM2/AIDI_5 ports

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 147


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
Wireless Supports wireless communication that complies with
communication IEEE802.15.4.
4G Supports the 4G module. The ECC800-Pro supports short message
service (SMS) message sending and 4G communication, is
compatible with 3G (WCDMA) communication, and provides a
standard SIM card slot.
 4G: Wireless mode (FDD-LTE, TDD-LTE). Coverage band
(B1, B3, B5, B7, B8, B20)
 3G: Wireless mode (WCDMA). Coverage band (B38, B40,
B41)
 2G: Wireless mode (GSM). Coverage band (900/1800MHz)
NOTE
The prerequisite for using a SIM card is that the site has signal coverage.

USB  Supports USB 2.0 and 5 V, 1 A power supply.


 After installing the WiFi module, connect the WiFi module to
the ECC800-Pro using the app on the mobile phone or tablet
computer to view the basic information about the smart module,
such as layout, resources, energy efficiency, environment, and
alarms.
 You can insert a USB flash drive to export historical data and
configuration files and import configuration files.
SW Button  Restoring the default IP address, factory settings, and user
information.
 Supports RF_Z networking.

Table 8-5 ECC800-Pro RF_Z parameters

Item Specifications
RF_Z Operation 2405–2480 MHz
Frequency
RF_Z EIRP 8 dBm
(max.)

Table 8-6 ECC800-Pro 4G parameters

Item Specifications
3G/4G Operation LTE (FDD): BAND1, BAND2, BAND3, BAND4, BAND5, BAND7,
Frequency BAND8, BAND20
DC-HSPA+/HSPA+/HSPA/UMTS: 850/900/1900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900 MHz

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 148


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
3G/4G EIRP 23 dBm
(max.)

Communications Port
The ECC800-Pro provides the following communications ports. Figure 8-15 shows the pins
of the RJ45 port.

Figure 8-15 RJ45 port pins

There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN ports
(LAN1/POE and LAN2/POE).

Table 8-7 GE port pin definitions

Item Description
Pin sequence Pin 1 GE1+
Pin 2 GE1-
Pin 3 GE2+
Pin 4 GE3+
Pin 5 GE3-
Pin 6 GE2-
Pin 7 GE4+
Pin 8 GE4-
Indicator Green Linked, steady on
indicator
Yellow ACT data communication, blinking
indicator

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 149


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Table 8-8 COM1/AIDI_4, COM2/AIDI_5 port pin definitions

Item Description
Pin sequence Pin 1 RS485+
Pin 2 RS485-
Pin 3 12 V DC_OUT
Pin 4 RS485+
Pin 5 RS485-
Pin 6 DI-
Pin 7 DI+
Pin 8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 8-9 COM3/12V port pin definitions

Item Description
Pin sequence Pin 1 RS485+
Pin 2 RS485-
Pin 3 12 V DC_OUT
Pin 4 RS485+
Pin 5 RS485-
Pin 6 N/A
Pin 7 N/A
Pin 8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 8-10 COM4/CAN port pin definitions

Item Description
Pin sequence Pin 1 RS485+
Pin 2 RS485-

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 150


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Description
Pin 3 N/A
Pin 4 RS485+
Pin 5 RS485-
Pin 6 N/A
Pin 7 CAN_H
Pin 8 CAN_L

The following provides the AIDI_1, AIDI_2 and AIDI_3 ports pin definitions.

 Pins 1, 2, 4, and 5 identify sensor types.


 Pin 3 and Pin 8 are power output ports.
 Pin 6 and Pin 7 collect sensor data. Pin 7 can detect current type sensors (4–20 mA). Pin 6 and Pin 7
can detect the output status of passive dry contact type sensors. Pin 3 and Pin 7 can detect
temperature sensors.

Table 8-11 AIDI_1, AIDI_2 and AIDI_3 ports pin definitions

Item Description
Pin sequence Pin 1 Type_1
Pin 2 Type_2
Pin 3 12 V DC
Pin 4 Type_3
Pin 5 Type_4
Pin 6 DI-
Pin 7 DI+
Pin 8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 8-12 DO/12V port pin definitions

Item Description
Pin sequence Pin 1 N/A
Pin 2 N/A

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 151


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Description
Pin 3 12 V DC_OUT
Pin 4 N/A
Pin 5 N/A
Pin 6 DO_OUT+
Pin 7 DO_OUT-
Pin 8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 8-13 USB port pin definitions

Item Description
Pin sequence Pin 1 5V
Pin 2 DM
Pin 3 DP
Pin 4 GND

Indicators

Table 8-14 Indicators on the ECC800-Pro main control module

Indicator Color Name Status Description


RUN Green Running Steady on The power supply is normal, the
status program is being loaded.
indicator
Off The power supply is abnormal.
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for
intervals 1s and then off for 1s) or the
ECC800-Pro registers with the
NetEco successfully.
Blinking at The ECC800-Pro does not
short register with the NetEco (the
intervals indicator blinks at 5 Hz, on for
0.125s and then off for 0.125s).
ALM Red Alarm Steady on A system failure alarm is

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 152


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


indicator generated.
Off The system is normal.
RF_Z Green Communic Blinking at A network is set up, and no node
ation status long access is allowed (the indicator
indicator intervals blinks at 0.5 Hz, on for 1s and
then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).

SW Button

Table 8-15 SW button description

Function Operation Description Indicator Status


Description
Wireless network In non-wireless network (802.15.4) The RF_Z indicator is
RF_Z (802.15.4) pairing mode, press and hold down the blinking at super short
pairing button for 3s to 5s to enter the wireless intervals.
network pairing mode.
In wireless network (802.15.4) pairing The RF_Z indicator is
mode, press and hold down the button for blinking at long
3s to 5s to exit the pairing mode; or the intervals.
system automatically exits the pairing
mode after 30 minutes without pressing
the button.
Press and hold down the button for more The RF_Z indicator is
than 8s to 20s to clear network blinking at super short
parameters. intervals.
Turning on WLAN Press the button for less than 3s to turn on None
the WLAN service.

Restoring the Hold down for 1 minute None


default IP address,
factory settings,
and user
information

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 153


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.1.3 Power Module

Indicator

Table 8-16 PSU indicator description

Indicator Color Name Status Description


Green Power Steady on The converter has a power
indicator input.

Off The converter has no


power input or is faulty.
Blinking at The converter is being
long queried (the indicator
intervals blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The converter application
short program is being loaded
intervals (the indicator blinks at 4
Hz, on for 0.125s and then
off for 0.125s).
Yellow Alarm Steady on The converter generates a
indicator forewarning indicating that
power will be limited due
to ambient
overtemperature, or
generates a protection
shutdown alarm due to
ambient overtemperature
or undertemperature.

Power input overvoltage


or undervoltage protection
Reverse DC input
connection
Slight current imbalance
Output overvoltage
Hibernation
Off The converter generates no
protection alarms.
Blinking at The communication
long between the converter and
intervals the outside is interrupted
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).
Red Fault Steady on The converter locks out

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 154


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


indicator due to output overvoltage.
The converter delivers no
output due to internal
faults.
Off The converter is working
properly.

8.3.2 UIM20A Expansion Module


Figure 8-16 UIM20A expansion module front panel

(1) Indicators and button (2) COM1/AI/DI_1 - COM8/AI/DI_8 (3) POE

Figure 8-17 UIM20A expansion module rear panel

(1) DIP switch (2) COM_OUT (3) COM_IN

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 155


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Table 8-17 UIM20A expansion module specifications

Item Specifications
Width 120 mm
Depth 200 mm
Height 43 mm
Operating -30°C to +65°C
temperature
Installation Installed in a 19-inch rack
requirements
Environmenta RoHS5
l protection

Specifications

Table 8-18 User interface technical specifications

Item Specifications
Power input Supports the RS485 or POE power supply.
COM/AIDI (RJ45)  Supports eight RS485 or AI/DI signal inputs.
 Can connect to sensors such as the smoke detector, water sensor,
door status sensor, and infrared sensor.
 Each port can supply power. Two RJ45 ports share one 12 V DC
power supply that is controlled independently. The maximum
output current is 900 mA when the voltage is 12 V.
(COM1/AIDI_1 and COM2/AIDI_2 form a group,
COM3/AIDI_3 and COM4/AIDI_4 form a group,
COM5/AIDI_5 and COM6/AIDI_6 form a group, and
COM7/AIDI_7 and COM8/AIDI_8 form a group).
 The 12 V DC power supply can be switched on or off and is on
by default.
POE Connects to the ECC800-Pro through the POE port.
DIP switch  One 4-bit DIP switch is used to set the RS485 address.
 OFF indicates 0 and ON indicates 1.
 Bit 1 is the least significant bit, and bit 4 is the most significant
bit. For example, if the board address is 5, the corresponding
bits are ON, OFF, ON, and OFF, and the corresponding binary
number is 1010 (ON is 1 and OFF is 0).
COM_IN and  Used for cascading ports when the UIM20A expansion module
COM_OUT replaces the independent deployment module.
(reserved)  In this scenario, the RS485 ports among the eight COM/AIDI
ports on the front panel are no longer used as southbound ports.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 156


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
E-label 4.0 Supported

Communications Ports
The following table describes the pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8.

Table 8-19 Pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8

Item Description
Pins Pin1 RS485+
Pin2 RS485-
Pin3 12V
Pin4 RS485+
Pin5 RS485-
Pin6 D-
Pin7 D+
Pin8 GND

The following table describes the pin assignments for the COM_IN and COM_OUT ports.

Table 8-20 Pin assignment for the COM_IN and COM_OUT ports

Item Description
Pins Pin1 RS485+
Pin2 RS485-
Pin3 12 V (input power, supplying power to the module)
Pin4 RS485+
Pin5 RS485-
Pin6 N/A
Pin7 N/A
Pin8 GND

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 157


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicators and Buttons

Table 8-21 User interface indicators

Indicator Status Status Description


RUN Steady on A board application is being loaded.
Off The board is not running.
Blinking at long The ECC800-Pro is successfully registered, and the
intervals software runs properly (blinking at long intervals
(0.5 Hz), on for 1s and then off for 1s).

Blinking at short The communication is interrupted or the


intervals ECC800-Pro is unsuccessfully registered (blinking
at short intervals (2.5 Hz), on for 0.2s and then off
for 0.2s).
Blinking Blinking at super short intervals for 0.5s and then
off for 0.5s; last 10s (blinking at super short
intervals: 10 Hz, on for 0.05s and then off for
0.05s)
ALM Steady on A system fault alarm is raised.
Steady off The system is normal.

Table 8-22 Blinking description

Function Instructions Indicator Status


Description
Blinking Press the button for 1s The RUN indicator blinks at super short
intervals (10 Hz), on for 0.05s and off for
0.05s, and lasts for 10s.

8.3.3 PAD
The pad allows the wireless access from the data center management system. You can monitor
the equipment in the data center and environmental parameters in real time over the APP.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 158


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-18 PAD

Table 8-23 Pad structural specifications

Item Specifications
Dimensions (L x W x 243 mm x 164 mm x 7.8 mm
H)
Weight About 460 g

Table 8-24 PAD technical specifications

Item Specifications
Touchscreen 10.1-inch, IPS full view, IPS screen, and capacitive five-point
touch
Storage  Machine: 32 GB
 Memory: 3 GB
 LPDDR3 extension card: microSD, a maximum of 256 GB
(non-standard configuration)
Button/Port  Touch button + power switch and volume button
 3.5 mm stereo headphones port
 Micro SD card port
 MicroUSB port
Camera  Rear camera: 8-megapixel, F2.0 aperture, automatic focus
 Front camera: 2-megapixel, F2.4 aperture, fixed focus
 Sensor type: BSI
 Flash: not supported
 Video recording: rear camera up to 1080 pixels at 30 FPS;
front camera up to 720 pixels at 30 FPS
 Zoom mode: digital zoom
 Photo resolution: rear camera up to 8 M (3264 x 2448

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 159


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
pixels); front camera up to 1.9 M (1600x 1200 pixels)
Battery  Materials: Li-polymer
 Capacity: 5100 mAh (typical value) or 4980 mAh (rated
value)
 WiFi connection/web page browse time: about 6.5 hours
 Power adapter charge time: about 3.5 hours (5 V 2A adapter)

8.3.4 Data Collection System


8.3.4.1 (Optional) Rack environment unit
The rack environment unit collects and controls the environmental data of IT cabinets.

Figure 8-19 Rack environment unit

(1) Ground port (2) 48 V DC power input (3) PoE port (4) COM1/12 V
port port
(5) COM2/12 V (6) COM3 port (7) COM4 port (8) NTC1–3 ports
port
(9) NTC4–6 ports (10) AI/DI_1 port (11) AI/DI_2 port (12) 12 V_1 port
(13) 12 V_2 port (14) BLINK button (15) Status
indicator

Specifications

Table 8-25 Technical specifications of the rack environment unit

Item Specifications
Power input  DC input: Phoenix terminal, with an input voltage range of 36–60 V
DC
 PoE input: One PoE port that complies with IEEE802.3at.
12 V power Two 12 V DC power outputs with the rated output current of 250 mA
output

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 160


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
FE port FE communication with the rate of 10/100M
RS485 serial  Four RS485 ports with the default communications rate of 9600 bit/s
port  Among the four RS485 ports, two support 12 V DC power output with
expansion the rated current of 400 mA.
 The other two are isolated, with the default communications rate of
9600 bit/s, and do not support power output.
AI/DI input Two active 12 V DC, 200 mA (rated) AI/DI input ports
Temperature Provides two RJ45 ports to connect to six temperature sensors, each RJ45
sensor port port connecting to three temperature sensors.
BLINK Supports the blinking function.
button

8.3.4.2 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800-Pro and can be flexibly deployed in a smart module.

Figure 8-20 Smart ETH gateway

(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 161


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Specifications

Table 8-26 Technical specifications for a smart ETH gateway

Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
POE port Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.

Indicators

Table 8-27 Indicators on a smart ETH gateway

Indicator Color Name Status Description


PWR Green Power input Steady on The power input is normal.
status indicator
Off There is no power input.
RUN Green Module Off The power supply is
running status abnormal.
indicator
Blinking at The smart ETH gateway
long successfully registers with
intervals the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at The smart ETH gateway does
short not register with the
intervals ECC800-Pro (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 162


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is
generated.

8.3.5 WiFi Module


The WiFi module provides WiFi signals for equipment such as pads and mobile phones to
interact with the host computer.

Figure 8-21 WiFi module

Table 8-28 Technical specifications

Item Specifications
Wireless standard IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b
Network  11n: up to 150 Mbps
bandwidth  11g: up to 54 Mbps
 11b: up to 11 Mbps

Frequency band 2.4-2.4835 GHz


Wireless 20 dBm (MAX EIRP)
transmission
power
Supported Windows 2000/XP/Vista/Linux/Win 7
operating system
Ports USB 2.0 high-speed connector
Voltage range 5.0 V DC±5%

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 163


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
Operating -20°C to +70°C
temperature
Storage -40°C to +90°C
temperature
Relative humidity 10%–90% RH (non-condensing)
Storage humidity 5%–90% RH (non-condensing)
Power < 0.8 W

8.3.6 Skylight Actuator


The skylight actuator controls the rotating skylight on the aisle containment of the smart
module through the alarm linkage information from the fire extinguishing system or the
control information from the upper computer. The skylight actuator supports E-labels and
wireless networking (802.15.4).

Figure 8-22 Skylight actuator

(1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor
magnetic lock DO window open button input port input port
output port DI input port
(5) BLINK button (6) Status indicator (7) Address DIP (8) COM1 port
switch
(9) COM2 port (10) POE port (11) 48 V power port

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 164


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Specifications

Table 8-29 Skylight actuator technical specifications

Item Specifications
Power input  DC input: Terminal, with input voltage of 36 V DC – 60 V DC
 POE input: One POE port that complies with IEEE802.3 at.
POE port FE communication with the rate of 10/100M
Wireless One wireless port that complies with IEEE802.15.4, mutual backup
communication with FE communication
AI/DI port Two AI/DI ports for detecting fire extinguishing linkage signals;
smoke detection signals also supported
DO output One 12 V DC power output for controlling the skylight magnetic lock;
driving six skylight magnetic locks simultaneously
DI input One DI input port for connecting to the window open button
BLINK button  Hold down the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a network and
start networking.
 Hold down the button for more than 10 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch

E-label Supported

Indicators

Table 8-30 Skylight actuator indicator description

Indicator Color Name Status Description


Power Green Power input Steady on The power input is normal.
status indicator
Off There is no power input.
RUN Green Operating Off The power is abnormal or the
status indicator board program is loading.
Blinking at The skylight actuator
long intervals successfully registers with the
ECC800-Pro and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s and
then off for 1s).
Blinking at The communication fails or the
short intervals skylight actuator fails to register

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 165


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


with the ECC800-Pro (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s (blinking
at 10 Hz, on for 0.05s and then
off for 0.05s) and then turns off
for 0.5s. The cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is generated.
RF_Z Green Communicatio Steady on No network parameters exist, or
n status a network is to be created.
indicator
Blinking at A network is set up, and no node
long intervals access is allowed (the indicator
blinks at 0.5 Hz, on for 1sand
then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking The skylight actuator is
intermittently searching for a network (the
at super short indicator blinks at super short
intervals intervals for 0.5s and then turns
off for 0.5s).

Communications Ports
The skylight actuator provides one DO port (LOCK/GND) and one DI port (BUTTON/GND).
Table 8-31 lists the LOCK/GND/BUTTON/GND port pin definitions.

Table 8-31 LOCK/GND/BUTTON/GND port pin definitions

Item Description
LOCK/GND LOCK 12V_OUT
pin sequence
GND GND
BUTTON/GN BUTTON DI3
D pin
sequence GND GND

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 166


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.7 Environment Monitoring System


8.3.7.1 WLDS900 Water Sensor
The WLDS900 water sensor with the BOM number of 33010352 consists of a water detection
cable, a water detector, and a conversion cable.

Figure 8-23 WLDS900 water sensor

(1) Water detector (2) Conversion cable end A, connected (3) Conversion cable
to the water detector
(4) Conversion cable (5) Water detection cable end A, (6) Water detection
end B, connected to connected to the conversion cable cable
the water detection
cable

Table 8-32 WLDS900 water sensor specifications

Item Specification
Operating 12 V DC (9–16 V DC)
voltage
Operating –20°C to +70°C
temperature
Storage –40°C to +85°C
temperature

Humidity 10%–80% RH (non-condensing)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 167


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.7.2 (Optional) Cabinet Temperature Sensor

Figure 8-24 Cabinet temperature sensor

Table 8-33 Technical specifications of the cabinet temperature sensor

Item Specifications
Power ≤ 50 mW (Single NTC)
Temperature detection range –10°C to +55°C
Temperature detection  ±1°C (-10°C to 25°C)
tolerance  ±1°C (+25°C to +55°C)
 ±0.5°C (25°C)
Operating temperature –10°C to +55°C
Operating humidity 5%–95% RH
Storage temperature –40°C to +70°C
Storage humidity ≤ 95% RH, non-condensing

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 168


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.7.3 T/H Sensor (BOM number: 02310NBS)

Figure 8-25 Appearance

(1) Status indicator (2) RS485_IN


(3) RS485_OUT (4) Address DIP switch

The RS485 communications ports of the T/H sensor use RJ11 (6P6C) connectors.

Figure 8-26 Pins of an RJ11 connector

Table 8-34 Pin description of an RJ11 connector

Pin Description
Pin 1 or Pin 2 GND
Pin 3 RS485-
Pin 4 RS485+
Pin 5 or Pin 6 12V

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 169


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Table 8-35 Temperature and humidity sensor specifications

Item Specifications
Temperature measuring range –20°C to +70°C
Temperature accuracy ±1°C
Operating temperature –10°C to +55°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +70°C
Output RS485

8.3.7.4 T/H Sensor (BOM Number: 33010516)

Figure 8-27 Appearance

The T/H sensor uses an RJ45 connector.

Figure 8-28 Pins of an RJ45 connector

Table 8-36 Pin description of an RJ45 connector

Pin Description
Pin1 or Pin 4 A
Pin2 or Pin 5 B
Pin3 V+

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 170


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Pin Description
Pin6 V-
Pin7 Reserved

Table 8-37 Temperature and humidity sensor specifications

Item Specifications
Temperature measuring range –20°C to +80°C
Temperature accuracy ±0.5°C (25°C)
≤±1°C (full measuring range)
Operating temperature –20°C to +80°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +80°C
Output RS485

8.3.7.5 Multi-Functional Sensor


A multi-functional sensor integrates the temperature and humidity (T/H) sensor, smoke sensor
and infrared detection. The multi-functional sensor can connect to the ECC800-Pro over FE
or wireless communication.

The infrared detection function is enabled only when the intelligent lighting function is enabled.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 171


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-29 Multi-functional sensor

(1) Address DIP switch (2) BLINK button (3) TEST button
(4) RF_Z indicator (5) RUN indicator (6) ALM indicator

Specifications

Table 8-38 Multi-functional sensor technical specifications

Item Specifications
Temperature –40°C to 70°C. Precision ≤ ±0.5 °C (0-50 °C).
monitoring
Humidity 0 to 100% RH. Precision ≤ ±5% RH (25°C, 20%–80% RH).
monitoring
Smoke Complies with Ul217. The smoke sensor generates an alarm when
monitoring testing 3.2% weak dust for each foot.
POE port One POE port that complies with IEEE802.3 at.
RS485 port Reserves one RS485 port.
DI input One DI input port, 12 V DC power input.
BLINK button Wireless communication:
 If the sensor is not connected to the network, after you hold down
the button for 2s to 3s, the sensor connects to the network in RF_Z
mode.
 If the sensor is connected to network, after you hold down the button
for 2s to 3s, the RUN indicator blinks.
 Hold down the button for more than 6s to clear network parameters.
Test button Supports the smoke sensor test.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 172


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
(Smoke sensor Hold down the button for 3s to trigger a smoke alarm, and release the
test button) button to stop the smoke alarm.
E-label Supported

Indicators

Table 8-39 Description of the indicators on the multi-functional sensor

Indicator Color Name Status Description


RUN Green Module Blinking at The multi-functional sensor
running status long successfully registers with
indicator intervals the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Blinking at The multi-functional sensor


short fails to register with the
intervals ECC800-Pro or the
communication fails (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off No system alarm is


generated.
RF_Z Green Communicati Steady on No network parameters exist,
on status or a network is to be created.
indicator
Blinking at A network is set up, and no
long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at A network is set up, and
super short node access is allowed (the
intervals indicator blinks at 10 Hz, on
for 0.05s and then off for
0.05s).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 173


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


Blinking The multi-functional sensor
intermittentl is searching for a network
y at super (the indicator blinks at super
short short intervals for 0.5s and
intervals then turns off for 0.5s).

8.3.7.6 Alarm Beacon


When a fire occurs or smokes are generated in the micro-modular equipment room, the alarm
beacon generates an audible signal and flashes to inform operators of fire and security risks.

Figure 8-30 Alarm beacon

Table 8-40 Structural specifications of an alarm beacon

Item Specifications
Dimensions (L x W x H) 130 mm x 75 mm x 55 mm
Installation requirements Installed on a wall
Environmental RoHS, Reach
requirements

Table 8-41 Technical specifications of an alarm beacon

Item Specifications
Power input RJ45 port, input voltage 9–16 V DC, operating current ≤ 400
mA

Sound pressure ≥ 100 ± 3 dB/30 cm


Continuous operating ≥ 45 min
time

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 174


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.8 Access Control System


8.3.8.1 Access Actuator
The access actuator is the control component for the aisle door in a smart module. It connects
to the ECC800-Pro controller over FE port, wireless networking (802.15.4). It opens the
magnetic lock by detecting the card swiping information of the card reader, door open button
information, and fire linkage information. It has access right management, access event record,
and alarm record functions.

Figure 8-31 Access actuator

(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry (11) AI/DI_1 dry (12) LOCK/GND/GATE/COM door
contact (Reserved port contact (Reserved port status or magnetic lock port
for linkage control or for exit button)
third-party fire
extinguishing system
dry contacts)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 175


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Specifications

Table 8-42 Access actuator technical specifications

Item Specifications
Power input  DC input: Terminal, with input voltage of 36–60 V DC
 POE input: One POE port that complies with IEEE802.3at.
POE port FE communication, 10/100M communications rate
Wireless One wireless communication port that complies with IEEE802.15.4,
communication mutual backup with FE communication
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO/DI port  One 12 V DC power output that controls magnetic locks, terminal
 One DI input port for connecting to the door status switch
RS485 serial port Two RS485 ports (one route) with the default communications rate of
expansion 9600 bit/s, physical port cascading supported (reserved function)
Wiegand interface Two Wiegand interfaces, 12 V DC card reader operating power
output; two routes of card readers (non-fingerprint readers) can
operate at the same time.
BLINK button  Press the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a network and
start networking.
 Hold down the button for more than 10 seconds to clear network
parameters.

Address DIP 4-pin address DIP switch


switch
E-label Supported

Indicators

Table 8-43 Access actuator indicator description

Indicator Color Name Status


PWR Green Power input status  Steady on: The power
indicator input is normal.
 Off: There is no
power input.
RUN Green Communication status  Off: The power is
indicator abnormal or the
board program is
loading.
 Blinking at long

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 176


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status


intervals: The access
actuator successfully
registers with the
ECC800-Pro and the
software runs
properly (the
indicator blinks at 0.5
Hz, on for 1s and
then off for 1s).
 Blinking at short
intervals: The
communication is
disconnected or the
access actuator fails
to register with the
ECC800-Pro (the
indicator blinks at 4
Hz, on for 0.125s and
then off for 0.125s).
 Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then turns
off for 0.5s. The
cycle lasts for 5s.
ALM Red Alarm indicator  Steady on: A system
failure alarm is
generated.
 Off: No system alarm
is generated.
RF_Z Green Wireless  Steady on: No
communication status network parameters
indicator exist, or a network is
to be created.
 Blinking at long
intervals: A network
is set up, and no node
access is allowed (the
indicator blinks at 0.5
Hz, on for 1s and
then off for 1s).
 Blinking at super
short intervals: A
network is set up, and
node access is
allowed (the indicator
blinks at 10 Hz, on

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 177


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status


for 0.05s and then off
for 0.05s).
 Blinking
intermittently at super
short intervals: The
access actuator is
searching for a
network (the
indicator blinks at
super short intervals
for 0.5s and then
turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 8-44 lists the LOCK/GND/GATE/COM port pin definitions.

Table 8-44 LOCK/GND/GATE/COM port pin definitions

Item Description
LOCK/GND LOCK 12V_OUT
(control
magnetic GND GND
locks) pin
sequence
GATE/COM GATE DI1
(door status)
pin sequence COM COM

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 178


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.8.2 (Optional) Aisle Access Control System


8.3.8.3 Fingerprint and Card Reader with a Keypad

Figure 8-32 Fingerprint and card reader with a keypad

(1) Fingerprint reader (2) LED indicator

Table 8-45 Specifications for the fingerprint and card reader with a keypad

Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC ±15%
Rated operating current 300 mA ±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports

Table 8-46 Access control device operating status

Item New Version


Standby LED indicator The indicator is steady blue.
Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 179


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item New Version


Buzzer sounds The buzzer sounds three.
Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.

Fingerprint reader The indicator turns on


(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

8.3.8.4 Fingerprint and Card Reader

Figure 8-33 Fingerprint and card reader

(1) Fingerprint reader (2) LED indicator

Table 8-47 Fingerprint and card reader

Item Specifications
Dimensions (L x Wx H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC ±5%
Rated operating current 300 mA ±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 180


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
Communications mode RS485 and Wiegand communications ports

Table 8-48 Access control device operating status

Item New Version


Standby LED indicator The indicator is steady blue.
Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds three.
Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 181


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.8.5 Card Reader with a Keypad

Figure 8-34 Card reader with a keypad

Table 8-49 Specifications of a card reader with a keypad

Item Specifications
Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current 80 mA, dynamic operating current
(card swiping, key pressing) 150 mA, minimum input
current 12 V DC/300 mA
Communications mode Wiegand communications port

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 182


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.8.6 Magnetic Lock

Figure 8-35 Double door magnetic lock

Figure 8-36 Single door magnetic lock

Figure 8-37 Magnetic lock for a sliding door

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 183


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.8.7 (Optional) Cabinet Access Control System


The cabinet door access control system applies to cabinets in the aisle containment to ensure
data and device security.

Cabinet Electronic Lock

Figure 8-38 Cabinet electronic lock

Table 8-50 Cabinet electronic lock specifications

Item Specifications
Rated input voltage 12 V DC
Rated current 200–300 mA
Unlock mode Power on to unlock
Card type supported IC card
Mechanically unlock Supported

Features:
 An IC card can be used after being authorized using software.
 An IC card can be authorized for one lock or all locks.
 Door opening information is recorded through a network.
 The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
 The system supports remote door opening.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 184


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

(Optional) Mechanical Code Lock

Figure 8-39 Cabinet code lock

Functions and features


 The cabinet door can be opened with only the key and without the password.
 The cabinet door can be opened with only the password and without the key.
 The user can set a password.
 A password should only contain three digits.
 If a user forgot the password, he can reset it.

8.3.9 Video Surveillance System


The video surveillance subsystem consists of the cameras and VCN (a network video recorder)
and implements real-time monitoring, video storage, and video playback.

8.3.9.1 IP Camera
The IPC6325-WD-VR IP camera (IPC6325 camera for short) is a two-megapixel wide
dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.
The camera monitors the module interior in real time, records videos, and implements 7x24h
storage.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 185


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-40 IPC6325 camera

Table 8-51 IPC6325 camera technical specifications

Item Specifications
Image sensor 1/2.7" two-megapixel progressive scan CMOS
Lowest illuminance  Color: 0.01 lux (F1.4, AGC ON)
 Black and white: 0.004 lux (F1.4, AGC ON)
0 lux (infrared enabled)

Wide dynamic range 120 dB


Focal length 2.8–12 mm manual zoom, 4.3x optical zoom
Video coding format H.265/H.264/MJPEG
Maximum resolution 1920x1080
Power supply PoE (802.3at/af), 24 V AC±25%, 24 V DC±25%, 12 V
DC±25% (polarity-insensitive DC power supply),
applicable to DC/AC adapter and PoE hot backup
Protection level IP66; complying with IEC 60529
Vandal-proof class IK10; complying with IEC 62262

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 186


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.9.2 VCN510

Figure 8-41 Appearance

Table 8-52 Performance Specifications

Item Specification
Device access and video storage Supports a maximum of eight video access
channels or 128 Mbit/s video access
bandwidth.
Video forwarding Supports a maximum of 32 video
forwarding channels or 256 Mbit/s video
forwarding bandwidth.
Video playback and download Supports a maximum of eight video
playback and download channels or 128
Mbit/s video playback and download
bandwidth.
Ingress and egress bandwidth The ingress bandwidth does not exceed 128
Mbit/s.
The egress bandwidth does not exceed 256
Mbit/s.

Table 8-53 Hardware specifications

Item Specification
Number of disks 2
Whether the hard disk supports hot swap No
Supported hard disk type 3 TB, 4 TB, 6 TB, or 8 TB SATA disks
CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz
Memory capacity 1 GB
Network port Two GE network ports
Power parameters One power module
AC power (100 V AC to 240 V AC; 50
or 60 Hz)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 187


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specification
Weight in full configuration (including ≤ 5 kg
disks)
Maximum power consumption (including < 60 W
hard disks)
Dimensions (H x W x D) 43.6 mm (1 U) x 442 mm x 310 mm
(excluding the panel)
43.6 mm (1 U) x 442 mm x 320 mm
(including the panel)

8.3.9.3 VCN520

Figure 8-42 Appearance

Table 8-54 Performance Specifications

Item Specification
Device access and video storage Supports a maximum of 32 video access
channels or 320 Mbit/s video access
bandwidth.
Video forwarding Supports a maximum of 128 video
forwarding channels or 320 Mbit/s video
forwarding bandwidth.

Video playback and download Supports a maximum of 32 video playback


and download channels or 320 Mbit/s video
playback and download bandwidth.
Ingress and egress bandwidth The ingress bandwidth does not exceed 320
Mbit/s.
The egress bandwidth does not exceed 320
Mbit/s.
NOTE
 If cameras are connected through the GB/T
28181 or DHSDK protocol, both the ingress
bandwidth and egress bandwidth do not
exceed 256 Mbit/s.
 In the cluster or external domain connection
scenario, the ingress bandwidth and egress
bandwidth of the master server do not exceed
256 Mbit/s separately.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 188


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Table 8-55 Hardware specifications

Item Specification
Number of disks 4
Whether the hard disk supports hot swap Yes
Supported hard disk type 3 TB, 4 TB, 6 TB, or 8 TB SATA disks
CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz
Memory capacity 2 GB
Network port Two GE network ports
Power parameters  One power module
 AC power (100 V AC to 240 V AC; 50
or 60 Hz)
Weight in full configuration (including ≤ 10.8 kg
disks)
Maximum power consumption (including < 100 W
hard disks)
Dimensions (H x W x D) 86.1 x 442 x 420 (2U, excluding panels)
86.1 x 442 x 450 (2U, including panels)

8.3.9.4 VCN540

Figure 8-43 Appearance

Table 8-56 Performance Specifications

Item Specification
Device access and video storage Supports a maximum of 64 video access
channels or 320 Mbit/s video access
bandwidth.
Video forwarding Supports a maximum of 128 video
forwarding channels or 320 Mbit/s video
forwarding bandwidth.
Video playback and download Supports a maximum of 32 video playback

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 189


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specification
and download channels or 320 Mbit/s video
playback and download bandwidth.
Ingress and egress bandwidth The ingress bandwidth does not exceed 320
Mbit/s.
The egress bandwidth does not exceed 320
Mbit/s.
NOTE
 If cameras are connected through the GB/T
28181 or DHSDK protocol, both the ingress
bandwidth and egress bandwidth do not
exceed 256 Mbit/s.
 In the cluster or external domain connection
scenario, the ingress bandwidth and egress
bandwidth of the master server do not exceed
256 Mbit/s separately.

Table 8-57 Hardware specifications

Item Specification
Number of disks 8
Whether the hard disk supports hot swap Yes
Supported hard disk type 3 TB, 4 TB, 6 TB, or 8 TB SATA disks
CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz
Memory capacity 2 GB
Network port Two GE network ports
Power parameters  One power module
 AC power (100 V AC to 240 V AC; 50
or 60 Hz)

Weight in full configuration (including ≤ 14 kg


disks)
Maximum power consumption (including < 150 W
hard disks)
Dimensions (H x W x D) 86.1 x 442 x 420 (2U, excluding panels)
86.1 x 442 x 450 (2U, including panels)

8.3.10 Lighting System


The lighting system is composed of AC actuators and aisle lights. They can be configured
based on site requirements.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 190


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.10.1 AC Actuator
The AC actuator is used in a smart module to control the lighting inside the smart module by
receiving commands from the access control system or host, infrared linkage information
(disabled by default), or signals from the light button. It also provides a charging port for the
pad.

Figure 8-44 AC actuator

(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator
(5) BLINK button (6) AI/DI dry (7) COM1–2 RS485
contact port

Specifications

Table 8-58 AC actuator technical specifications

Item Specifications
Power input One AC input, 100–240 V AC.
Power output  AC OUT1: two AC outputs, 100–240 V AC, maximum total
current: 5 A.
 AC OUT2: one AC output, 100–240 V AC, maximum
current: 5 A.
Wireless One wireless communication port, complying with

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 191


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Item Specifications
communication IEEE802.15.4.
RS485 port One route of dual RS485 ports, not isolated (reserved).
AI/DI detection Two AI/DI dry contacts, connecting to two light buttons.
BLINK button  Press the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a network
and start networking.
 Hold down the button for more than 10 seconds to clear
network parameters.

Indicators

Table 8-59 AC actuator indicators

Indicator Color Name Status Description


Power Green Power status Steady on The power input is normal.
indicator
Off There is no power input.
RUN Green Running Off The power is abnormal or the
status board program is loading.
indicator
Blinking at The AC actuator successfully
long intervals registers with the ECC800-Pro
and the software runs properly
(the indicator blinks at 0.5 Hz,
on for 1s and then off for 1s).
Blinking at The communication is
short intervals disconnected or the AC
actuator fails to register with
the ECC800-Pro (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is generated.
RF_Z Green Communicati Steady on No network parameters exist,
on status or a network is to be created.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 192


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Indicator Color Name Status Description


indicator Blinking at A network is set up, and no
long intervals node access is allowed (the
indicator blinks at 0.5 Hz, on
for 1sand then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s
and then off for 0.05s).
Blinking The AC actuator is searching
intermittently for a network (the indicator
at super short blinks at super short intervals
intervals for 0.5sand then turns off for
0.5s).

8.3.10.2 Aisle Light (600 mm long)


Light emitting diode (LED) lights are used for lighting in an aisle. The lights are installed on
the top at the two sides of the aisle.

Figure 8-45 LED light

Table 8-60 LED light technical specifications

Item Specifications
Installation mode Ceiling-mounted
Light base requirement The light base and light are integrated.
Protection level ≥ IP20
Electrical insulation class Class I
Standards compliance IEC 60598
Rated operating voltage 220 V AC – 240 V AC
Light color Pure white
Luminous flux Each AC light: ≥ 800 lm
Rated power Less than 12 W

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 193


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.11 (Optional) eLight


The eLight system consists of the eLight power, eLight actuator, eLight strip light, and cables.
The eLight strip light is installed in the inverted U-shaped light slot in the frame of an
automatic sliding door.

Figure 8-46 Installed eLight strip light

Figure 8-47 eLight strip light

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 194


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Figure 8-48 eLight actuator

The appearance of the eLight actuator depends on the product delivered onsite.

Table 8-61 Color definitions of the eLight strip light

Scenario Light Color Remarks


Entrance  If access authorization succeeds, the Associated with the
light is blinking for 3 seconds in access control for an
green color, indicating that the door end door.
can be opened.
 If access authorization fails, the light
is blinking for 3 seconds in red color,
indicating that the door cannot be
opened.
Unassociated alarm Blue -
severity NOTE
When Associated alarm severity in
ECC800-Pro WebUI is selected to None.

Associated alarm  Mapping between smart module Critical and major


severity alarm severities and strip light colors: alarms are associated by
− Critical alarm: red default. Alarms of any
severity can be
− Major alarm: orange associated manually.
− Minor alarm: yellow Alarms are associated
− Warning alarm: gray with the eLight on both
ends. If associated
 No alarm: strip light off alarms of multiple
severities appear, the
strip light color
indicates only the
highest alarm severity.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 195


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Scenario Light Color Remarks


eLight fault The strip light flashes in red if eLight -
fails to communicate with the
ECC800-Pro.

Table 8-62 eLight system technical specifications

Item Specifications
eLight power  Rated input voltage: 220 V AC/230 V AC/240 V AC
 Frequency: 50/60 Hz
 Output: ≥ 93 W, 24 V DC
 Certification: CE
eLight actuator  Rated input voltage: 24 V DC
 Two output channels. The I output is connected to the
RGBW flexible strip light, and supplies different voltages
depending on host instructions so that the light can be in
different colors. The II output supplies a fixed voltage of 24
V DC.
 Modbus communications protocol, RS485 interface, two
RJ45 ports
 Certification: CE
eLight strip light  Rated input voltage: 24 V DC
 Light type: RGBW LED strip light, in different colors
depending on instructions
 Power: RGB fully on under the maximum working
condition, power P ≤ 12 W/m
 Installation mode: buckled in a sheet metal light slot
 Certifications: CE and CCC
Protection level ≥ IP20
Operating environment  Operating temperature range: 4–40°C
 Humidity range: 5%–95%, non-condensing

8.3.12 (Optional) iBattery


The iBattery consists of the iBOX and iBAT.
The iBOX is a battery information collection module. It collects battery status data from a
group of downstream iBATs through wireless communication, and sends the data to the
upstream management unit through a COM or PoE port.
The iBAT is a battery monitoring module that supports 12 V power input and monitors the
voltages, internal resistances, and pole temperatures of batteries.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 196


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

Appearance

Figure 8-49 iBOX appearance

Figure 8-50 iBAT appearance

iBOX Features
 Each iBOX can manage a maximum of four battery strings composed of 200 batteries in
total.
 An external Hall effect sensor is connected to the iBOX to monitor the current of each
battery string. Each iBOX can connect to a maximum of eight Hall effect sensors.
 Calculates the SOC and SOH of batteries and battery strings.
 Accurately identifies batteries with lower voltages in a battery string.
 Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.
 Supports WebUI display, and northbound communication over FE and RS485.
 Allows the upstream management unit to upgrade the iBOX and iBAT online.

iBAT Features
 Monitors the voltages, internal resistances, and pole temperatures of batteries.
 Uploads battery data to the iBOX through wireless communication.
 Has the hibernation function.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 197


FusionModule2000 Smart Modular Data Center
Product Description 8 Intelligent Module Management System

8.3.13 (Optional) Smart U Space Manager


The smart U space manager is designed for IT asset management of the data center. The
system automatically detects the physical location of IT devices in the data center, collects IT
asset codes and the information about U space usage.

Figure 8-51 Smart U space manager

(1) Asset detection strip (2) U space electronic label (3) Main control box

Table 8-63 Technical specifications of the smart U space manager

Item Specifications
Characteristic Applicable to 42 U cabinets
Communications port RS485, Modbus-RTU
Communication Rate: 9600 bit/s
Communication format: one start bit, eight data bits, no
parity bit, one stop bit
Power input 12 V DC±5% (RJ45)
Rated current and power 250 mA
consumption
Data upload port One RS485 route (two RJ45 ports)
Dimensions (mm) Main control box: 71 mm x 70 mm x 25 mm
Detection strip: 1867 mm x 18 mm x 6.5 mm (H x W x
D)
Weight ≤ 0.2 kg (main control box), ≤ 0.35 kg (asset detection
strip)
Installation mode Magnet-based installation

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 198


FusionModule2000 Smart Modular Data Center 9 (Optional) NetEco6000 Intelligent Data Center
Product Description Management System

9 (Optional) NetEco6000 Intelligent Data


Center Management System

9.1 System Functions


With a flexible structure and modular design, the NetEco can manage infrastructure of a
single smart module or multiple smart modules in different areas in a centralized manner.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system can monitor the following equipment:
 Power equipment, including in-room smart cooling products, integrated PDFs, UPSs,
and so on.
 Environment monitoring equipment, including water sensor, temperature and humidity
sensor, and so on.
 Video equipment, including cameras.
 Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
 Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 199


FusionModule2000 Smart Modular Data Center 9 (Optional) NetEco6000 Intelligent Data Center
Product Description Management System

Figure 9-1 Networking

9.2 Server
There are two models of server optional for the NetEco depending on the management scale:
TaiShan 200 (Model 2280) in standard configuration and TaiShan 200 (Model 2180) in basic
configuration.

Table 9-1 Server

Model Configuration
TaiShan 200 (Model 2280) in 2 x Kunpeng 920 [email protected] GHz, 4 x 32 GB
standard configuration memory, 2 x 1.2 TB + 8 x 1.8 TB drives
TaiShan 200 (Model 2180) in basic 1 x Kunpeng 920 [email protected] GHz, 2 x 32 GB
configuration memory, 2 x 1.2 TB drives

9.3 LAN Switch


You can select a device model as required.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 200


FusionModule2000 Smart Modular Data Center 9 (Optional) NetEco6000 Intelligent Data Center
Product Description Management System

Table 9-2 LAN Switch

Model Maximum Number of Interfaces


S5320-28X-PWR-SI 24 BASE-T Ethernet 10/100/1000 ports (4 of which are
dual-purpose 10/100/1000 or SFP), 4 10Gig SFP+ ports
S5720-28X-PWR-SI 24 BASE-T Ethernet 10/100/1000 ports (4 of which are
dual-purpose 10/100/1000 or SFP), 4 10Gig SFP+ ports
S2700-26TP-PWR-EI 24 BASE-TX Ethernet 10/100 ports and 2 BASE-T Ethernet
10/100/1000 ports (2 of which are dual-purpose 10/100/1000 or
SFP)
S2326TP-PWR-EI 24 BASE-T Ethernet 10/100 ports and 2 Gig combo ports
(10/100/1000 BASE-T+100/1000 BASE-X)

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 201


FusionModule2000 Smart Modular Data Center
Product Description 10 Surge Protection and Grounding System

10 Surge Protection and Grounding


System

The surge protection and grounding system consists of the surge protection solution and
grounding solution.

Surge Protection Solution


SPDs are installed in front of the target equipment. The conducting wires to each SPD are
short (within 0.15 m) and straight. The SPD wires are copper wires with a minimum
cross-sectional area of 10 mm2, and the ground cables to SPDs are copper cables with a
minimum cross-sectional area of 16 mm2.

M-shaped (Grid) Grounding (Recommended)

Figure 10-1 M-shaped (grid) grounding solution for a single-row aisle containment

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 202


FusionModule2000 Smart Modular Data Center
Product Description 10 Surge Protection and Grounding System

Figure 10-2 M-shaped (grid) grounding solution for a dual-row aisle containment

1. Each cabinet in the smart module connects to the ground grid nearby using ground cables
with a minimum cross-sectional area of 16 mm2.
2. Use 100 mm x 0.3 mm copper foils or 25 mm2 braided copper strips for the equipotential
bonding grid, and use 30 mm x 3 mm red copper strips for the equipotential bonding bar
based on the customer's configurations.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 203


FusionModule2000 Smart Modular Data Center
Product Description 11 Integrated Cabling System

11 Integrated Cabling System

The integrated cabling system of the smart module mainly consists of cabling devices and
cables.

Cable Troughs
Cable troughs are installed on the top of cabinets for routing cables. There are two types of
cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDF and one network cabinet, power
cables need to be routed to the other end of the module through the control skylight on the top
of the PDF while signal cables need to be routed to the other end of the module through the
control skylight on the top of the network cabinet.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 204


FusionModule2000 Smart Modular Data Center
Product Description 11 Integrated Cabling System

Figure 11-1 Cable routes through cable troughs

(1) Network cabinet (2) Optical fiber (3) Signal cable


(4) Smart ETH gateway (5) PDF (6) Power cable

Cable
 The power cables include power cables to the UPS, battery cabinet, smart cooling
product, and rPDU.
 The ground cables include ground cables to the PDU8000, battery cabinet, and IT
cabinet.
 The monitoring cables include monitoring cables to the smart cooling product, UPS, and
video devices, access control alarm cables, cables in the network cabinet, and various
sensor cables.
 Cables to the fire extinguishing auxiliary components include cables to the alarm beacon
and skylight actuator.

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 205


FusionModule2000 Smart Modular Data Center
Product Description 12 UPS Derating Coefficients

12 UPS Derating Coefficients

Table 12-1 lists the UPS5000 derating coefficients.

Coefficients in Table 12-1 are based on the dry air density (sea level temperature +15°C) of 1.225 kg/m 3.

Table 12-1 UPS5000 derating coefficients

Altitude (Unit: m) Derating Coefficient


1000 1.0
1500 0.95
2000 0.91
2500 0.86
3000 0.82
3500 0.78
4000 0.74
4500 0.7
5000 0.67

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 206


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
AC alternate current
ATS Auto Transfer Switch

B
BCB Battery Circuit Breaker
BIB Battery control I/O board
BIM Battery Interface Module
BSPP British Standard Pipe Parallel Thread

C
CAN Controller Area Network
CE ConformitéEuropéenne
CFD Computational Fluid Dynamics
CIM Communication Interface Module

D
DC direct current

E
EC Electronic Commutation
ECC Energy Control Center
ETH Ethernet

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 207


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

F
FE Fast Ethernet

I
iBAT ibattery
IC Integrated Circuit
IDC Internet Data Center
IDS integrated data-center solution
IT Internet Technology

L
LCD Liquid Crystal Display
LED Light Emitting Diode

M
MTBF mean time between failures
MTTR mean time to repair

N
NTC negative temperature coefficient

P
PDU Power Distribution Unit
PE Protective Earthing
PoE Power over Ethernet
PUE power usage effectiveness

R
RCCB Residual Current Circuit Breaker

S
SD Secure Digital Memory
SIM Subscriber Identity Module

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 208


FusionModule2000 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

SNMP Simple Network Management Protocol


SPD surge protective device

U
USB Universal Series Bus
UPS uninterruptible power system

V
VCN Video Cloud Node

W
WiFi Wireless Fidelity

Issue 06 (2020-05-21) Copyright © Huawei Technologies Co., Ltd. 209