Fusion Module5000n Datasheet

The document describes a modular data center solution called FusionModule5000. It can support flexible single or dual row deployments with up to 21kW of power per rack. Key features include reliable power supply and monitoring, efficient cooling, and simple standardized and modular architecture for on-demand deployment.

Uploaded by

urooj.hamid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views2 pages

Fusion Module5000n Datasheet

The document describes a modular data center solution called FusionModule5000. It can support flexible single or dual row deployments with up to 21kW of power per rack. Key features include reliable power supply and monitoring, efficient cooling, and simple standardized and modular architecture for on-demand deployment.

Uploaded by

urooj.hamid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Modular Data Center

FusionModule5000 Smart Modular Data Center

Introduction
HUAWEI FusionModule5000 is a new generation smart modular data
center solution with complete integration of cabinets, power supply and
distribution systems, cooling systems, cabling systems, management
software, and other subsystems. It supports flexible deployment with
single or dual row, cold or hot aisle containment. The maximum IT power
can be up to 21kW/rack.

Application Scenarios
• Maximum IT power per module can be up to 310kW, which meet FusionModule5000 (Dual-row)
the requirements of large-scale data center for industries like ISP,
government, education, healthcare, finance, telecom, etc.
• Designed for chilled water cooling scenarios.

Features & Value


Reliable
• Single/dual power supply, Tier IV supportive, Precise monitoring of
power branch temperature prevents fire caused by loose contact and
overheat
• Water leakage monitoring keeps room away from flooding
• Ring network of monitoring system
• Warning of component expired, aging, damaged FusionModule5000 (Single-row)
• Optional aisle/cabinet-level door access keeps the data center safe

Efficient
• Closely coupled cooling to efficiently avoid partial hot spot, high-
density deployment supportive
• Hot/cold aisle containment for isolation of hot and cold air
• Local/remote monitoring, PAD or cell phone mobile O&M

Simple
• Standardized devices, modular architecture, on-demand deployment
• Busway for power distribution is optional , easy installation

01
Specifications

Item Specifications
Single-row with aisle containment (L×W×H (IT cabinets)):
L×2400×2000mm, L≤15 m
L×2300×2000mm, L≤15 m
L×2400×2200mm, L≤15 m
Dimensions
Dual-row with aisle containment (L×W×H (IT cabinets)):
L×3600×2000mm, L≤15 m
L×3400×2000mm, L≤15 m
L×3600×2200mm, L≤15 m
Cabinet number per
System Single row: 2-24; Dual row: 6-48
module
Power supply 380/400/415Vac, 50/60Hz, 3Ph+N+PE
IT power consumption per UPS inside: 112kW
module UPS outside: 310kW
Maximum power per rack 21kW/R
Availability Tier II or Tier III (up to Tier IV)
Altitude 0-4000m (derating above 1000m)
Installation Installed on concrete or base support
2000mm×600/800mm×1200mm
Dimensions (H×W×D) 2000mm×600/800mm×1100mm
Cabinet 2200mm×600/800mm×1200mm
Space available 42U/47U
Protection level IP20
Cooling capacity 30kW
Chilled water
Dimensions (H×W×D) 2000mm×300mm×1200mm
In-row air
Power supply 200~240V (1Ph, 50/60Hz)
conditioner
Refrigerant Water/Ethylene Glycol
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Input power factor Full load > 0.99, Half load > 0.98
Integrated UPS
Rated capacity 40~160kVA
(UPS inside)
Efficiency ≥ 96%
AC SPD 20kA, 8/20μs
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Precision power
Rated capacity 400/250/160A
distribution
AC SPD 20kA, 8/20μs
cabinet (UPS
outside) 16A/20A/32A/40A optional, max branches up to 144 (single phase), or 48
Output
(three phase)
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Smart busway Rated capacity 250/160A
(UPS outside) 40A/1P (6 branches in one Power Distribution Unit, can be expand with
Output
the length of cabinets)