FMDS0729
FMDS0729
FMDS0729
Table of Contents
Page
©2020-2024 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
7-29 Ignitable Liquid Storage in Portable Containers
Page 2 FM Global Property Loss Prevention Data Sheets
List of Figures
Fig. 2.2.1.1. Location and construction of ignitable liquid storage areas: outdoor storage, detached
low value buildings, detached protected buildings, and cutoff rooms. ................................... 12
Fig. 2.2.3.1.1. Prefabricated ignitable liquid storage building (PILSB) ......................................................... 20
Fig. 2.2.3.2. Ignitable liquid storage locker ................................................................................................... 21
Fig. 2.4.8.2. Minimum flue space between palletized storage arrays (plan view) ...................................... 53
Fig. 2.4.8.3.A. Loading aisle draft curtain arrangement (plan view) ............................................................ 54
Fig. 2.4.8.3.B. Loading aisle trench drain arrangement (plan view) ............................................................ 54
Fig. 2.4.9.1. Flue space and walkway layout for on-side barrel storage in racks (plan view) .................... 56
Fig. A.1. Plan view (white area represents open area fraction) .................................................................. 71
Fig. D.2.1.1. Single-row rack sprinkler layout: IBC protection scheme ....................................................... 78
Fig. D.2.1.2. Single-row rack sprinkler layout: IBC protection scheme ....................................................... 79
Fig. D.2.1.3. Double-row rack sprinkler layout: IBC protection scheme ..................................................... 80
Fig. D.2.1.4. Single-row rack sprinkler layout: drum protection scheme .................................................... 81
Fig. D.2.1.5. Double-row rack sprinkler layout: drum protection scheme ................................................... 82
Fig. D.2.1.6. Double-row rack sprinkler layout: drum protection scheme ................................................. 83
Fig. D.2.1.7. Multiple-row rack sprinkler layout: drum protection scheme (elevation view) ......................... 84
Fig. D.2.1.8. Multiple-row rack sprinkler layout: drum protection scheme (plan view) ................................ 85
Fig. D.2.1.9. Single-row rack sprinkler layout: drum protection scheme .................................................... 86
Fig. D.2.1.10. Double-row rack sprinkler layout: drum protection scheme ................................................. 87
Fig. D.2.1.11. Single-row rack sprinkler layout: drum protection scheme ................................................... 88
Fig. D.2.1.12. Double-row rack sprinkler layout: drum protection scheme .................................................. 89
Fig. D.2.1.13. Single-row rack sprinkler layout: drum protection scheme .................................................. 90
Fig. D.2.1.14. Double-row rack sprinkler layout: drum protection scheme ................................................. 91
Fig. D.2.1.15. Single-row rack sprinkler layout: drum protection scheme .................................................. 92
Fig. D.2.1.16. Double-row rack sprinkler layout: drum protection scheme ................................................. 93
Fig. D.2.1.17. Single-row rack sprinkler layout: small metal containers ...................................................... 94
Fig. D.2.1.18. Double-row rack sprinkler layout: small metal containers (with face sprinklers) ................. 95
Fig. D.2.1.19. Double-row rack sprinkler layout: small metal containers (no face sprinklers) .................... 96
Fig. D.2.1.20. Multiple-row rack sprinkler layout: small metal containers (elevation view) ........................ 97
Fig. D.2.1.21. Multiple-row rack sprinkler layout: small metal containers (plan view) ................................ 98
Fig. D.2.1.22. Single-row rack sprinkler layout: water-miscible liquids in small metal containers .............. 99
Fig. D.2.1.23. Double-row rack sprinkler layout: water-miscible liquids in small metal containers .......... 100
Fig. D.2.1.24. Multiple-row rack sprinkler layout: water-miscible liquids in small metal containers
(elevation view) ................................................................................................................... 101
Fig. D.2.1.25. Multiple-row rack sprinkler layout: water-miscible liquids in small metal containers
(plan view) ........................................................................................................................... 102
Fig. D.2.1.26. Single-row rack sprinkler layout: quick response sprinklers protection scheme ................ 103
Fig. D.2.1.27. Double-row rack sprinkler layout: quick response sprinklers protection scheme .............. 104
Fig. D.2.1.28. Single-row rack sprinkler layout: quick response sprinklers protection scheme ................ 105
Fig. D.2.1.29. Double-row rack sprinkler layout: quick response sprinklers protection scheme .............. 106
Fig. D.2.1.30. Single-row rack sprinkler layout: quick response sprinklers protection scheme ................ 107
Fig. D.2.1.31. Double-row rack sprinkler layout: quick response sprinklers protection scheme ............... 108
Fig. D.2.1.32. Single-row rack sprinkler layout: quick response sprinklers protection scheme ................ 109
Fig. D.2.1.33. Double-row rack sprinkler layout: quick response sprinklers protection scheme .............. 110
Fig. D.2.1.34. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(plan view) ........................................................................................................................... 111
Fig. D.2.1.35. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(elevation view) ................................................................................................................... 112
Fig. D.2.1.36. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(plan view) ........................................................................................................................... 113
Fig. D.2.1.37. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(elevation view) ................................................................................................................... 114
Fig. D.2.1.38. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(plan view) ........................................................................................................................... 115
Fig. D.2.1.39. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(elevation view) ................................................................................................................... 116
Fig. D.2.1.40. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(plan view) ........................................................................................................................... 117
Fig. D.2.1.41. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme
(elevation view) ................................................................................................................... 118
Fig. D.2.1.42. Single-row rack storage of water-miscible liquids .............................................................. 119
Fig. D.2.1.43. Double-row rack storage of water-miscible liquids ............................................................. 120
Fig. D.2.1.44. Single-row rack storage of water-miscible liquids .............................................................. 121
Fig. D.2.1.45. Double-row rack storage of water-miscible liquids ............................................................. 122
Fig. D.2.1.46. Single-row rack storage of Group 3 water-miscible liquids ................................................ 123
Fig. D.2.1.47. Double-row rack storage of Group 3 water-miscible liquids .............................................. 124
Fig. D.2.1.48. In-rack sprinkler layout for distilled spirits in wooden barrels (plan view) .......................... 125
Fig. D.2.1.49. In-rack sprinkler layout for distilled spirits in wooden barrels (elevation view) .................. 125
Fig. D.2.2.1.1. Single-row rack sprinkler layout: fire protection scheme A ................................................ 128
Fig. D.2.2.1.2. Single-row rack sprinkler layout: fire protection scheme A ................................................ 129
Fig. D.2.2.1.3. Double-row rack sprinkler layout: fire protection scheme A ............................................... 130
Fig. D.2.2.1.4. Multiple-row rack sprinkler layout: fire protection scheme A .............................................. 131
Fig. D.2.2.2.1. Single-row rack sprinkler layout: fire protection scheme B ................................................ 133
Fig. D.2.2.2.2. Single-row rack sprinkler layout: fire protection scheme B ................................................ 134
Fig. D.2.2.2.3. Double-row rack sprinkler layout: fire protection scheme B ............................................... 135
Fig. D.2.2.2.4. Multiple-row rack sprinkler layout: fire protection scheme B .............................................. 136
Fig. D.2.2.3.1. Single-row rack sprinkler layout: fire protection scheme C ................................................ 138
Fig. D.2.2.3.2. Single-row rack sprinkler layout: fire protection scheme C ................................................ 139
Fig. D.2.2.3.3. Double-row rack sprinkler layout: fire protection scheme C ............................................... 140
Fig. D.2.2.4.1. Single-row rack sprinkler layout: fire protection scheme D ............................................... 143
Fig. D.2.2.4.2. Single-row rack sprinkler layout: fire protection scheme D ................................................ 144
Fig. D.2.2.4.3. Double-row rack sprinkler layout: fire protection scheme D ............................................. 145
Fig. D.2.2.5.1. Single-row rack sprinkler layout: fire protection scheme E ................................................ 146
Fig. D.2.2.5.2. Double-row rack sprinkler layout: fire protection scheme E .............................................. 147
Fig. D.2.2.6.1a. Single row rack sprinkler layout: fire protection scheme F .............................................. 149
Fig. D.2.2.6.1b. Single row rack sprinkler alternate layout: fire protection scheme F ............................... 150
Fig. D.2.2.6.1c. Double row rack layout: fire protection scheme F ............................................................ 151
Fig. E.1.B. Water spray protection for steel columns ................................................................................ 152
List of Tables
Table 2.1.2.2. Water-Miscible Liquid Groupings ............................................................................................ 7
Table 2.1.3.1.6. Drainage and Containment for Very High Flash Point Liquids ............................................. 9
Table 2.1.3.1.7. Protection for Very High Flash Point Liquids ........................................................................ 9
Table 2.1.3.7.1. Glycol-Water and Glycerin-Water Mixtures ........................................................................ 11
Table 2.2.1.1.A. Location 1: Construction and Space Separation for Ignitable Liquid Storage Areas:
Outdoor Storage or Detached Low Value Buildings .......................................................... 12
Table 2.2.1.1.B. Location and Construction for Ignitable Liquid Storage Areas: Detached Protected
Buildings, Cut-off Rooms, or General-Purpose Warehouses ........................................... 13
Table 2.2.2.1.A. Drainage and Containment Requirements for Liquid Storage in Metal Containers
or FM Approved Composite IBCs in Cutoff Rooms/Buildings .......................................... 16
Table 2.2.2.1.A. Drainage and Containment Requirements for Liquid Storage in Metal Containers
or FM Approved Composite IBCs in Cutoff Rooms/Buildings (continued) ........................ 17
Table 2.2.2.1.B. Drainage and Containment Requirements for Liquid Storage in Plastic Containers
in Cutoff Rooms/Buildings ................................................................................................. 18
Table 2.2.2.1.B. Drainage and Containment Requirements for Liquid Storage in Plastic Containers
in Cutoff Rooms/Buildings (continued) .............................................................................. 19
Table 2.4.2.1. Palletized or Solid-Pile Storage of Ignitable Liquids in Relieving-Style Metal Containers
Larger
than 60 gal (230 L) and FM Approved Composite IBCs (Note 1) ....................................... 25
Table 2.4.2.2. Rack Storage of Ignitable Liquids in Relieving-Style Metal Containers Larger than
60 gal (230 L) and FM Approved Composite IBCs (Note 1) ................................................. 26
Table 2.4.3.1. Rack Storage of Ignitable Liquids in Metal Containers larger than 6.5 gal (25 L)
Up to and Including 60 gal (230 L) (Note 1) ......................................................................... 29
Table 2.4.3.1. Rack Storage of Ignitable Liquids in Metal Containers larger than 6.5 gal (25 L)
Up to and Including 60 gal (230 L) (Note 1) (continued) ...................................................... 30
Table 2.4.3.1 Rack Storage of Ignitable Liquids in Metal Containers larger than 6.5 gal (25 L)
Up to and Including 60 gal (230 L) (Note 1) (continued) ....................................................... 31
Table 2.4.3.2. Palletized/Solid-Pile Storage of Ignitable Liquids in Metal Containers Larger than 6.5 gal
(25 L) Up to and Including 60 gal (230 L)
(Apply Table in Accordance with Recommendation 2.4.3.2) (Note 1) ................................. 32
Table 2.4.3.2. Palletized/Solid-Pile Storage of Ignitable Liquids in Metal Containers Larger than 6.5 gal
(25 L) Up to and Including 60 gal (230 L)
(Apply Table in Accordance with Recommendation 2.4.3.2) (Note 1) (continued) ............... 33
Table 2.4.4.1.A. Rack Storage of Ignitable Liquid in Metal Containers Up to and Including 6.5 gal (25 L) . 35
Table 2.4.4.1.B. Protection for Any Ignitable Liquid in Relieving-Style Metal Containers Up to and
Including 6.5 gal (25 L), Excluding Ignitable Liquids with a Boiling Point Below 100°F
(38°C) (Note 1) .................................................................................................................. 36
Table 2.4.4.2. Palletized/Solid-Pile Storage of Liquids In Non Relieving-Style Metal Containers Up
to and Including 6.5 gal (25 L) (Note 1) ............................................................................... 37
Table 2.4.4.3. Shelf Storage of Liquids in Metal Containers Up to and Including 6.5 gal (25 L) (Note 1) . 37
Table 2.4.5.1. Fire Protection Criteria for Ignitable Liquids in Plastic or Glass Containers (Note 1) ......... 38
Table 2.4.6.1. Storage of Liquids in Composite IBCs (blow molded bottle in a wire cage on a wood
or steel pallet)(Note 1) .......................................................................................................... 40
Table 2.4.7.1. Rack Storage of Liquids in Plastic or Glass Containers with Flash Points Below 200°F
(93°C) (Note 1) ..................................................................................................................... 41
Table 2.4.7.2.1. Rack Storage of Liquids in Plastic or Glass Containers with Flash Points At or Above
200°F (93°C)(Note 1) ......................................................................................................... 43
Table 2.4.7.2.1. Rack Storage of Liquids in Plastic or Glass Containers with Flash Points At or Above
200°F (93°C) (Note 1) (continued) .................................................................................... 44
Table 2.4.7.2.2. Palletized/Solid Pile Storage of Liquids with Closed-Cup Flash Points At or Above
200°F (93°C) in Plastic Containers (Note 1) ..................................................................... 45
Table 2.4.7.2.2. Palletized/Solid Pile Storage of Liquids with Closed-Cup Flash Points At or Above
200°F (93°C) in Plastic Containers (Note 1) (continued) .................................................. 46
Table 2.4.7.3.1. Rack Storage of Group 1, 2, 3, and 4 Water-Miscible Liquids in Plastic or Glass
Containers (Note 1) ........................................................................................................... 48
Table 2.4.7.3.1. Rack Storage of Group 1, 2, 3, and 4 Water-Miscible Liquids in Plastic or Glass
Containers (Note 1) (continued) ........................................................................................ 49
Table 2.4.7.3.2. Palletized/Solid Pile Storage of Groups 1 through 4 Water-Miscible Liquids in Plastic
or Glass Containers (Note 1) ............................................................................................. 51
Table 2.4.7.3.2. Palletized/Solid Pile Storage of Groups 1 through 4 Water-Miscible Liquids in Plastic
or Glass Containers (Note 1) (continued) ......................................................................... 52
Table 2.4.8.4. Palletized Storage of Distilled Spirits with up to 75% Alcohol by Volume in Wooden Barrels . 55
Table 2.4.9.4. Rack Storage of Distilled Spirits in Wooden Barrels (Note 1) ............................................... 57
Table 2.8.1. Electrical Equipment Ratings and Lift Truck Ratings for Ignitable Liquids Storage
Occupancies ............................................................................................................................ 60
Table D.2.2.1.3. Liquid-Container Combinations for Use With Scheme A Without Balancing the
Ceiling and In-rack Designs ............................................................................................. 127
Table D.2.2.1.4. Liquid-Container Combinations for Use With Scheme A Where Balancing the
Ceiling and In-rack Designs is Needed ............................................................................ 127
1.0 SCOPE
This data sheet covers the storage of chemically stable liquids that can burn (i.e., ignitable liquids) stored
in portable, non-pressurized, metal, glass, fiberboard, plastic, or composite containers of any size.
For the purposes of this document, the term ″ignitable liquid″ is used for any liquid that has a measurable
flash point. The term ″flash point″ refers to the closed-cup flash point unless stated otherwise.
This data sheet does not address the following subjects:
A. The dispensing of ignitable liquids. Use FM Global Property Loss Prevention Data Sheet 7-32, Ignitable
Liquid Operations, to evaluate all ignitable liquid dispensing operations.
B. Combustible solids or unstable liquids (i.e., liquids that have the potential to self-react or polymerize).
C. Liquids that have a flash point but no fire point (see Appendix A).
D. Aerosols. See Data Sheet 7-31, Storage of Aerosol Products.
E. Reactive chemicals, including water-reactive and pyrophoric materials.
F. Stationary tanks. See Data Sheet 7-88, Outdoor Ignitable Liquid Storage Tanks, and Data Sheet 7-32,
(for internal ignitable liquid storage tanks).
G. Compressed or flammable liquefied gases. See Data Sheet 7-50, Compressed Gases in Portable
Cylinders and Bulk Storage and Data Sheet 7-55, Liquefied Petroleum Gas (LPG) Storage in Stationary
Installations.
1.1 Hazard
Ignitable liquids in sealed containers create many different fire scenarios. With metal containers, there is
the potential for the violent failure of the container or jetting if it is not adequately cooled. It is nearly impossible
to prevent the failure of a plastic container filled with an ignitable liquid, which creates the potential for the
development of a large growing pool fire.
Apart from the type of fire hazard that can be created, it does not take a lot of ignitable liquid storage to
create an unacceptably large fire in a general purpose warehouse. Full-scale fire tests have shown that even
a relatively small quantity of ignitable liquid can quickly overwhelm a sprinkler system designed for general
storage.
1.2 Changes
January 2024. Interim revision. Significant changes include the following:
A. Revised guidance, in Table 2.1.3.1.7, Protection for Very High Flash Point Liquids, to allow for the use
of quick-response sprinklers.
B. Provided clarification on fire-rated construction (Section 2.2.1). All new fire-rated construction should
be made of noncombustible materials.
C. Provided guidance, in Table 2.4.8.4, Palletized Storage of Distilled Spirits with up to 75% Alcohol by
Volume in Wooden Barrels, for K16.8 (K235), quick-response sprinklers.
D. Added N-Methylpyrrolidone (NMP) and Dimethyl Sulfoxide (DMSO) as water-miscible liquids (Table
2.1.2.2).
E. Completed various grammar and editorial revisions.
2.1 Introduction
Use FM Approved equipment, materials, and services whenever they are applicable and available. For a
list of products and services that are FM Approved, see the Approval Guide or RoofNav, online resources
of FM Approvals.
2.1.1 General
2.1.1.1 Apply all elements of this data sheet to liquids that have a flash point and a fire point.
2.1.1.2 Arrange, locate, and protect dispensing operations in accordance with Data Sheet 7-32.
2.1.1.2.1 Arrange cutoff rooms or detached buildings with both storage and dispensing to meet all applicable
recommendations in both this data sheet and Data Sheet 7-32, Ignitable Liquid Operations.
2.1.1.3 Do not mix storage of ignitable liquids with oxidizers, peroxides, or flammable gas.
2.1.1.4 Any level of aerosol product may be stored with ignitable liquids in maximum 1 qt (0.9 L) metal
containers if the provided fire protection scheme, isolation, and construction features are fully adequate for
both storage types. See Data Sheet 7-31 for information on aerosols.
2.1.1.5 Handle, store, and protect partially full ignitable liquid containers as full containers.
2.1.1.6 Store empty ignitable liquid containers that have not been cleaned and purged outside the facility.
2.1.1.7 Do not use plastic pallets for storage of ignitable liquids unless the protection scheme specifies that
they are acceptable.
2.1.1.8 FM Approved composite intermediate bulk containers (IBC) filled with liquids having a flash point
greater than or equal to 100°F (38°C) may be protected as metal containers in accordance with this data
sheet.
2.1.2.2.1 From a fire hazard standpoint, treat Group 5 water-miscible liquids as nonignitable liquids.
2.1.2.2.2 Treat a mixture of alcohol and another water miscible liquid by adding up the percentages and basing
the group on the total alcohol percentage. For example, treat a mixture comprised of 40% alcohol, 30%
propylene glycol, and 30% water as 70% alcohol (Group 2).
2.1.2.3 Protect viscous mixtures (see Section 3.2.3 for definition) of ignitable liquids with solids as follows:
2.1.2.3.1 When in metal containers, protect as a Class 3 commodity in accordance with Data Sheet 8-9,
Storage of Class 1, 2, 3, 4 and Plastic Commodities.
2.1.2.3.2 When in plastic containers, protect as a cartoned unexpanded plastic in accordance with Data Sheet
8-9.
2.1.2.4 Protect materials that are solid at room temperature (68°F [20°C]) in accordance with the applicable
FM Global data sheet.
Table 2.1.3.1.6. Drainage and Containment for Very High Flash Point Liquids
Container
Type Container Size Drainage and Containment Guidance
Metal Any Drainage or containment is not required.
Plastic Composite IBCs on a Provide containment around the IBC storage area sized for the contents of
wood, steel, or plastic four IBCs. Drainage is not required.
pallet
All-plastic IBCs Provide containment around the IBC storage area sized for the contents of
all stored IBCs. Drainage is not required.
≤60 gal (230 L) Drainage or containment is not required.
Bag-in-Box IBCs Provide containment around the IBC storage area sized for the contents of
twelve IBCs. Drainage is not required.
2.1.3.1.7 Protect very high flash point liquids in accordance with Table 2.1.3.1.7.
2.1.3.2.2 Protect straight-chain silicone fluids (also referred to as siloxanes or methyl siloxanes) that have
a closed-cup flash point of 414°F (212°C) or greater as very high flash point liquids in accordance with this
data sheet.
2.1.3.2.3 Protect all other silicone fluids (e.g., methylhydrogen siloxanes, organofunctional silanes) as
ignitable liquids in accordance with their flash point and this data sheet.
Plastic/Glass Containers:
≤80% and >35% Protect as a cartoned unexpanded plastic.
Metal Containers:
Protect for the provided packaging.
Plastic/Glass Containers:
≤35% Protect as a non-ignitable liquid in a plastic container.
Metal Containers:
Protect for the provided packaging.
2.2.1 General
2.2.1.1 Segregate ignitable liquid storage from occupancies not designed for ignitable liquid hazards using
outdoor locations, detached low value buildings, cutoff rooms, or general purpose warehouses in accordance
with Figure 2.2.1.1, Table 2.2.1.1.A, Table 2.2.1.1.B, and this section.
Outside cut-off rooms may be attached to the main building or detached. Properly designed and protected
detached outside cut-off rooms (Location 2) do not require space separation from the main building.
.A
Definitions:
Location 1 - Outside Storage / Detached Low Value Building Location 3 & 4 - Inside Cut-Off Room
Location 2 - Outside Cut-Off Room (Attached or Detached) Location 5 - General Purpose Warehouse
Fig. 2.2.1.1. Location and construction of ignitable liquid storage areas: outdoor storage, detached low value buildings,
detached protected buildings, and cutoff rooms.
Table 2.2.1.1.A. Location 1: Construction and Space Separation for Ignitable Liquid Storage Areas: Outdoor Storage or
Detached Low Value Buildings
Location ’C’ Wall
Separation Distance Construction Type
Flash Point, Liquid to Main Building [ft (Note 1) or Fire
Container Type Type Container Size (m)] Rating (Note 2)
Any < 200°F (93°C) Any 50 (15) Any
25 (7.6) NC
≥ 200°F (93°C) Any 25 (7.6) Any
15 (4.6) NC
Any Any 5 (1.5) 1 hour
Note 1. NC = Noncombustible.
Note 2. Fire ratings are per ASTM E119 ratings or local code equivalent, and materials shall be noncombustible.
Table 2.2.1.1.B. Location and Construction for Ignitable Liquid Storage Areas: Detached Protected Buildings, Cut-off
Rooms, or General-Purpose Warehouses
Construction Type
Flash Point, Storage Location (Note 2) or Fire
Container Type Liquid Type Container Size (Note 1) Wall Location Rating (Note 3)
Metal Any ≤ 6.5 gal (25 L) 2, 3, 4, 5 A, B, C NC
> 6.5 gal (25 L) 2, 3, 4 A NC
B 1 hour
Very high flash ≥ 40 gal (150L) 2, 3, 4, 5 A, B, C NC
point
SG > 1 > 6.5 gal (25 L) 2, 3, 4, 5 A, B NC
FM Approved ≥100°F (38°C) Any 2, 3, 4 A, B NC
composite IBC
Plastic, Glass, or ≥ 200°F (93°C) ≤ 6.5 gal (25 L) 2, 3, 4, 5 A, B, C NC
Other > 6.5 gal (25 L) 2, 3, 4 A NC
Combustible B 2 hour
Containers Water-miscible ≤ 1 gal (4 L) 2, 3, 4, 5 A, B, C NC
> 1 gal (4 L) and 2, 3, 4 A NC
≤ 60 gal (230 L) B 1 hour
> 60 gal (230 L) 2, 3, 4 A NC
B 2 hour
<200°F (93°C) ≤ 5 oz (150 ml) 2, 3, 4, 5 A, B, C NC
> 5 oz (150 ml) 2, 3, 4 A NC
B 2 hour
Very high flash ≥ 40 gal (150L) 2, 3, 4, 5 A, B, C NC
point
Note 1: Location 5 represents a general-purpose warehouse. The liquid-package combination is assumed to be adequately protected in
accordance with this data sheet.
Note 2. NC = Noncombustible.
Note 3. Fire ratings are per ASTM E119 ratings or local code equivalent, and materials shall be noncombustible.
2.2.1.1.1 Treat detached buildings that are adequately protected as a cut-off room. Space separation is not
needed.
2.2.1.2 Locate storage areas on ground floors.
2.2.1.3 Arrange outdoor storage or storage in low value detached buildings as follows:
2.2.1.3.1 For non-relieving-style containers larger than 6.5 gal (25 L) in size, limit storage height as follows:
A. Limit to one container high when using separation distances in Table 2.2.1.1.A
B. Limit to three containers high when storage is located a minimum of 50 ft (15 m) from important buildings
or equipment, regardless of the exposed building construction
2.2.1.3.1.1 This does not apply to storage located in prefabricated ignitable liquid storage buildings (PILSBs)
due to the limited storage quantities that can fit into one of these units.
2.2.1.3.2 Limit relieving-style containers larger than 6.5 gal (25 L) in size to three containers high.
2.2.1.3.3 Limit any one dimension of the storage pad/area/building to 100 ft (30.5 m).
2.2.1.3.4 Provide curbs, dikes, or drainage to prevent released liquids from exposing important buildings or
equipment.
2.2.1.3.4.1 If the ground is clearly sloped away from important buildings or equipment, dikes are not required
for property protection purposes.
2.2.1.3.5 Arrange curbed/diked areas to permit removal of impounded liquids.
2.2.1.3.6 Provide adequate and safe access to the liquid storage areas for the fire service.
2.2.1.3.7 Provide fire hydrants that are safely accessible to the fire service, spaced no more than 200 ft
(60 m) from liquid storage areas.
2.2.1.3.8 Treat outdoor storage that is provided with a noncombustible roof as a detached protected building
if the storage arrangements and sprinkler designs are in accordance with this data sheet.
2.2.1.4 Where spacing between Location 1 and important buildings or equipment is inadequate, provide
deluge water spray on the exposed wall at a rate of 0.3 gpm/ft2 (12 mm/min) of exposed wall.
2.2.1.4.1 Arrange the detection system to reliably activate the deluge water spray system if a fire involves
the outdoor storage or detached low value building.
2.2.1.4.2 Arrange the exposure protection system in accordance with Section 2.4 of Data Sheet 1-20,
Protection Against Exterior Fire Exposure.
2.2.1.4.2.1 Use spacing and arrangement criteria for “storage greater than 30 ft (9 m) high.”
2.2.1.4.2.2 Provide exposure protection for the length of the exposing storage footprint and 30 ft (9 m) beyond.
2.2.1.4.3 Include a 500 gpm (1900 L/min) hose stream allowance.
2.2.1.4.4 Provide a water supply duration of two hours.
2.2.1.5 For liquid-container combinations requiring a 1-hour fire-rated cutoff room, construct cutoff rooms
as follows:
2.2.1.5.1 Provide noncombustible, fire-rated walls per ASTM E119, Standard Test Methods for Fire Tests of
Building Construction and Materials, or local equivalent.
2.2.1.5.2 Design walls to be liquid-tight so released liquids (e.g., ignitable liquids, sprinkler discharge, inside
hose streams) will be contained.
2.2.1.5.3 Design walls for the hydraulic pressure created by the contained liquid level.
2.2.1.5.4 Provide impact protection for fire-rated walls constructed of low-impact strength materials (e.g.,
gypsum board) to a height equal to the storage height when storage is adjacent to the wall, or 5 ft (1.5 m)
when the storage is away from the wall.
2.2.1.5.5 Provide at least one outside access door for the cutoff room.
2.2.1.5.6 Protect necessary interior openings with a properly fire-rated, normally closed, automatically closing,
FM Approved fire door installed on the storage side of the wall.
2.2.1.5.6.1 When an FM Approved automatic spill barrier is installed, locate the fire door on the non-storage
side of the wall.
2.2.1.5.6.2 A less desirable alternative is to arrange a normally open fire door to automatically close actuated
by a fire inside or directly outside the room (e.g., provide a fusible link on both sides of the fire wall).
2.2.1.6 For liquid-container combinations requiring a 2-hour fire-rated cutoff room construct cutoff rooms in
accordance with Section 2.2.1.5 and as follows:
2.2.1.6.1 Provide noncombustible, fire rated walls per ASTM E119, Standard Test Methods for Fire Tests of
Building Construction and Materials, or local equivalent.
2.2.1.6.2 If the liquid pool fire will affect all four sides of a steel column located inside a cutoff room, protect
columns using the guidance in Appendix E.
2.2.1.6.3 For Location 2 storage areas, provide noncombustible wall construction with no openings for the
wall on the main building/warehouse side for 10 ft (3 m) beyond each side of an exterior cutoff room.
2.2.1.7 Construct roofs and ceilings of cutoff rooms and detached protected buildings as follows:
2.2.1.7.1 For cutoff rooms that have ceilings below the main building’s roof, provide a ceiling assembly that
has the same fire resistance as the interior walls of the cutoff room.
2.2.1.7.2 For cutoff rooms that share the main building roof or detached protected buildings, provide a
non-combustible roof, an FM Approved Class 1 steel deck roof or an FM Approved insulated metal panel
roof in accordance with Data Sheet 1-29, Roof Deck Securement and Above-Deck Roof Components.
2.2.1.7.3 For cutoff rooms and detached protected buildings that have wooden roof assemblies, sheath the
wooden roof with material that achieves the same fire resistance as needed for the interior walls of the cutoff
room.
2.2.1.7.4 Provide sprinklers in any combustible or concealed spaces in accordance with Data Sheet 1-12,
Ceilings and Concealed Spaces.
2.2.1.8 Arrange cutoff rooms as follows:
2.2.1.8.1 Provide the cutoff rooms with dedicated exterior shipping docks.
2.2.1.8.2 If shipping docks are not provided in the cutoff room, locate cutoff rooms next to shipping docks
to minimize the ignitable liquid fire hazard along liquid transportation routes in buildings that are not protected
for the hazard.
2.2.1.8.3 Provide space in the cutoff rooms for staging products, if needed, before they are placed in storage
or while they are awaiting shipment.
2.2.1.9 For loading docks on which ignitable liquid containers are staged, provide construction, protection,
containment, and emergency drainage as recommended by this data sheet. The term ″staged″ in this context
excludes uninterrupted movement of containers from inside the shipping vehicle directly to the properly
designed storage area.
2.2.1.10 Provide self-supporting rack structures for distilled spirit barrel storage warehouses. Follow guidance
in Section 2.5.3 for operation and maintenance at these warehouses.
Page 16
7-29
Container Flash Point,
Type Liquid Type Container Size Drainage and/or Containment Options and Alternatives
Metal Very high flash Any See Section 2.1.3.1.6
point
≥200°F (93°C) ≤6.5 gal (25 L) None
>6.5 gal (25 L) 1. Provide containment arranged to prevent spilled liquid and actual sprinkler discharge (Note 1) from spreading to other building
Or
3. Provide containment and a special protection system as per this data sheet. Design the containment designed to keep spilled
liquid and actual sprinkler discharge (Note 1) plus special protection system discharge from spreading to other building areas
not protected for an ignitable liquid fire hazard for 20 minutes. Provide no less than 3 in. (76 mm) of containment across all
interior openings.
<200°F (93°C) ≤6.5 gal (25 L) None
>6.5 gal (25 L) 1. Provide containment arranged to prevent spilled liquid and actual sprinkler discharge (Note 1) from spreading to other building
and ≤60 gal areas not protected for an ignitable liquid fire hazard for 30 minutes. Provide no less than 3 in. (76 mm) of containment across all
(230 L) interior openings.
Or
2. Provide emergency drainage and containment. Provide no less than 3 in. (76 mm) of containment across all interior openings.
2. Provide emergency drainage and containment. Provide no less than 3 in. (76 mm) of containment across all interior openings.
©2020-2024 Factory Mutual Insurance Company. All rights reserved.
Or
3. Provide containment and a special protection system per this data sheet. Design the containment designed to keep spilled
liquid and actual sprinkler discharge (Note 1) plus special protection system discharge from spreading to other building areas
not protected for an ignitable liquid fire hazard for 20 minutes. Provide no less than 3 in. (76 mm) of containment across all
interior openings.
≥100°F (38°C) Any 1. Provide emergency drainage and containment designed to limit the liquid pool to no more than the sprinkler operating area, to
prevent spilled liquid and actual sprinkler discharge (Note 1) from spreading to other building areas not protected for an
ignitable liquid fire hazard. Provide no less than 3 in. (76 mm) of containment across all interior openings.
Or
2. Provide containment and a special protection system per this data sheet. Design containment to keep spilled liquid and actual
sprinkler discharge (Note 1) plus special protection discharge from spreading to other building areas not protected for an
ignitable liquid fire hazard for 20 minutes. Provide no less than 3 in. (76 mm) of containment across all interior openings.
SG >1 Any Provide containment sized to hold the largest expected ignitable liquid release plus an additional 2 in. (51 mm) of freeboard. Limit
the containment footprint to an area no larger than the sprinkler operating area.
Note: 1. The amount of water that will discharge from the sprinklers based on the available water supply, not the theoretical sprinkler discharge.
Page 17
7-29
Table 2.2.2.1.B. Drainage and Containment Requirements for Liquid Storage in Plastic Containers in Cutoff Rooms/Buildings
Page 18
7-29
Flash Point, Liquid
Container Type Type (Note 1) Container Size Drainage and/or Containment Options and Alternatives
Plastic, Glass, or Very high flash point Any See Section 2.1.3.1.6.
Other Combustible ≥200°F (93°C) ≤6.5 gal (25 L) None
Containers >6.5 gal (25 L) 1. Provide emergency drainage and containment arranged to prevent spilled liquid and actual sprinkler discharge (Note 1) from spreading to other building areas not
protected for an ignitable liquid fire hazard for 30 minutes. Arrange the drains to subdivide the room into the smallest practical drainage areas but no larger than 5000
Or
2. Provide containment and a special protection system as per this data sheet. Design the containment to keep spilled liquid and actual sprinkler discharge (Note 1) plus
©2020-2024 Factory Mutual Insurance Company. All rights reserved.
special protection system discharge from spreading to other building areas not protected for an ignitable liquid fire hazard for 20 minutes. Provide no less than 3 in.
(76 mm) of containment across all interior openings.
Or
3. For composite IBC storage protected in accordance with Table 2.4.6.1, provide emergency drainage and containment or containment alone arranged to prevent spilled
liquid and actual sprinkler discharge (Note 1) from spreading to other buildingareas not protected for an ignitable liquid fire hazard for 30 minutes. Provide no less than
3 in. (76 mm) of containment across all interior openings.
<200°F (93°C) ≤2 oz (60 ml) None
> 2 oz (60 ml) and For rack storage protected using Table 2.4.7.1, provide no less than 3 in. (76 mm) of containment across all interior openings. For all other storage arrangements, follow
≤ 1 gal (4 L) the guidance for containers larger than 1 gal (4 L).
Or
2. Provide containment and a special protection system as per this data sheet. Design the containment to keep spilled liquid plus actual sprinkler discharge (Note 1) plus
special protection system discharge from spreading to areas not protected for an ignitable liquid fire hazard outside the room/building of origin for 20 minutes. Provide
no less than 3 in. (76 mm) of containment across all interior openings.
Table 2.2.2.1.B. Drainage and Containment Requirements for Liquid Storage in Plastic Containers in Cutoff Rooms/Buildings (continued)
ft2 (465 m2). Provide no less than 3 in. (76 mm) of containment across all interior openings. All containers in the cutoff room are expected to fail.
Or
2. Provide containment and a special protection system as per this data sheet. Design the containment to keep spilled liquid and actual sprinkler discharge (Note 1) plus
special protection system discharge from spreading to other building areas not protected for an ignitable liquid fire hazard for 20 minutes. Provide no less than 3 in.
(76 mm) of containment across all interior openings.
Or
3. For composite IBC storage protected in accordance with Table 2.4.6.1, provide emergency drainage and containment or containment alone arranged to prevent spilled
liquid plus actual sprinkler discharge (Note 1) from spreading to areas not protected for an ignitable liquid fire hazard outside the room/building of origin for 30
minutes. Provide no less than 3 in. (76 mm) of containment across all interior openings.
Note: 1. The amount of water that will actually discharge from the sprinklers based on the available water supply, not the theoretical sprinkler discharge.
Page 19
7-29
7-29 Ignitable Liquid Storage in Portable Containers
Page 20 FM Global Property Loss Prevention Data Sheets
2.2.2.2 For liquids with a viscosity greater than 10,000 cP, containment without emergency drainage is
sufficient.
2.2.2.3 For locations with multiple ignitable liquid storage warehouses, provide grading between the
warehouses so liquids do not flow to adjacent buildings.
2.2.2.4 Design emergency drainage and containment systems in accordance with Data Sheet 7-83, Drainage
and Containment Systems for Ignitable Liquids, to prevent the flow of liquid into adjacent areas of the facility
that are not protected for an ignitable liquid fire hazard.
2.2.2.5 Do not include hose stream demands in the drainage or containment design unless inside hose
stations are provided.
2.2.2.5.1 Use 50 gpm (190 L/min) for one hose station, or 100 gpm (380 L/min) for more than one in the
fire area.
2.2.2.6 For special protection systems, containment without emergency drainage is sufficient.
2.2.2.6.1 Arrange containment to prevent the flow of liquid into adjacent areas within the facility that are not
protected for an ignitable liquid fire hazard for at least 20 minutes.
2.2.3.1.2 Provide all the active and passive protection features recommended in this data sheet (fire rating,
containment and drainage, ventilation, ignition source control, and automatic fire protection) for the PILSB.
2.2.3.1.3 Do not use PILSB units with explosion venting inside a building.
2.2.3.2 Use FM Approved ignitable liquid storage lockers, as shown in Figure 2.2.3.2, for outdoor storage
of liquids.
2.2.3.2.1 If a storage locker is located inside the building, locate the unit in a cut-off room and protect in
accordance with this standard or Data Sheet 7-32, depending on how it is used (i.e., just storage or storage
and dispensing).
2.2.3.3 Use FM Approved ignitable liquid storage cabinets to hold limited quantities of ignitable liquids in
general-purpose warehouses, subject to the following limitations:
2.2.3.3.1 For cabinets designed to hold containers larger than 5 gal (19 L), restrict ignitable liquid quantities
to ensure the cabinet will contain the largest expected liquid release (e.g., largest metal container and
contents of all the plastic containers).
2.2.3.3.2 Provide a minimum of 20 ft (6 m) separation between cabinets and non-liquid warehouse areas.
2.2.3.3.3 Do not put cabinets within non-liquid rack storage arrangements.
2.2.3.3.4 Do not dispense ignitable liquids from containers located in storage cabinets in warehouse
occupancies.
2.3 Occupancy
2.3.1 Housekeeping
2.3.1.1 Establish and implement a housekeeping program for areas storing ignitable liquids that adheres to
the highest standards and includes the following elements.
A. Clean up spills promptly.
B. Keep waste materials in FM Approved oily waste cans.
C. Remove waste daily.
D. Maintain adequate aisles to permit unobstructed movement of personnel and access for firefighting.
E. Do not store other combustibles in the area nor permit any material that might wash into or plug drains.
F. Keep outdoor storage areas clear of grass, weeds, and other combustibles.
2.3.2 Ventilation
2.3.2.1 Provide continuous low-level ventilation designed in accordance with Data Sheet 7-32, if the following
scenarios are present:
2.3.2.1.1 For storage occupancies containing liquids with a boiling point below 100°F (38°C) provide a design
of 0.5 cfm/ft2 (0.15 m3/min/m2).
2.3.2.1.2 For storage occupancies with poorly maintained and leaking containers or occupancies with
dispensing operations use the ventilation rate recommended in Data Sheet 7-32.
2.4 Protection
2.4.1 General
2.4.1.2.2.6 To protect the flue space created between a single row rack and a wall located with 1 ft (0.3 m)
horizontally of the rack structure, position the in-rack sprinkler outside the footprint of the single row rack
structure as detailed within Data Sheet 8-9.
2.4.1.2.3 Balance the ceiling and in-rack demands at their point of connection unless using a protection
scheme that specifically says the systems do not need to be balanced.
2.4.1.2.4 Provide a minimum discharge pressure of 10 psig (0.7 bar) for in-rack sprinkler designs where the
in-rack sprinkler has a K-factor ≥11.2 (K161).
2.4.1.2.4.1 Provide a minimum discharge pressure of 7 psig (0.5 bar), where the in-rack sprinkler has a
K-factor < 11.2 (K160).
2.4.2 Metal Containers (Including IBCs) Larger than 60 gal (230 L) and FM Approved Composite
IBCs
2.4.2.1 Protect palletized or solid pile storage of relieving-style metal containers, including metallic IBCs,
and FM Approved composite IBCs in accordance with Table 2.4.2.1.
2.4.2.2 Protect rack storage of relieving-style metal containers, including metallic IBCs, and FM Approved
composite IBCs in accordance with Table 2.4.2.2.
Table 2.4.2.1. Palletized or Solid-Pile Storage of Ignitable Liquids in Relieving-Style Metal Containers Larger
than 60 gal (230 L) and FM Approved Composite IBCs (Note 1)
Ceiling Sprinkler Protection
Response / K-factor gpm/ Design, #
Nominal psi1/2 (L/min/ Sprinklers @
Maximum Maximum Temperature bar1/2) Pressure psi
Container Liquid Type/ Ceiling Storage Height Rating / (bar)
Type Flash Point Height ft (m) (No. of IBCs) Orientation
Metal <200°F 30 (9.1) 1 high SR/High/Any ≥11.2 (161) 50 @ 7 (0.5)
(93°C) (Note 2, 3)
FM Approved ≥100°F 30 (9.1) 1 high SR/High/Any ≥11.2 (161) 50 @ 7 (0.5)
Composite (38°C) (Note 2, 3)
IBC
Metal ≥200°F 30 (9.1) 2 high SR/Ordinary/Any 11.2 (161) 50 @ 29 (2.0)
Or (93°C) (Note 2) 30 @ 51 (3.5)
FM Approved 14.0 (202) 50 @ 18 (1.2)
Composite 30 @ 33 (2.3)
IBC
16.8 (235) 50 @ 13 (0.9)
30 @ 23 (1.6)
25.2 (363) 50 @ 7 (0.5)
30 @ 10 (0.7)
QR/Ordinary/Any 25.2EC (363EC) 26 @ 22 (1.5)
15 @ 39 (2.7)
1 high SR/Ordinary/Any ≥11.2 (161) 50 @ 7 (0.5)
(Note 2, 3)
11.2 (161) 30 @ 29 (2.0)
(Note 2)
14.0 (202) 30 @ 18 (1.2)
16.8 (235) 30 @ 13 (0.9)
25.2 (363) 30 @ 7 (0.5)
QR/Ordinary/Any 25.2EC (363EC) 15 @ 22 (1.5)
Any Very high See Section 2.1.3.1
flash point
liquid
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. If a foam-water sprinkler system is used, use of K 8.0 (K115) ceiling sprinklers is acceptable as long as an equivalent flow is provided
from the K8.0 (K115) sprinkler.
Note 3. The K19.6 (K280) sprinkler is not acceptable for use in this protection table.
Page 26
7-29
Ceiling Sprinkler Protection In-Rack Sprinkler Protection
Response/ K-factor Design, Layout Response/ K-factor Design,
Maximum Maximum Nominal gpm/psi1/2 # Sprinklers @ (see figure Nominal gpm/psi1/2 # Sprinklers @
Flash Point Ceiling Storage Temperature (L/min/bar1/2) Pressure indicated) Temperature (L/min/bar1/2) Flow gpm
OR Height Height Rating/ psi (bar) Rating (L/min)
Container type Liquid Type ft (m) (No. of IBCs) Orientation (see 2.4.1.2)
2.4.3 Metal Containers Larger than 6.5 gal (25 L) Up to and Including 60 gal (230 L)
2.4.3.1 Protect rack storage in accordance with Table 2.4.3.1.
2.4.3.1.1 Protect rack storage greater than the listed 30 ft (9.1 m) roof heights as follows:
2.4.3.1.1.1 Continue the in-rack protection layout recommended for 25 ft (7.6 m) high storage over each
additional tier of storage.
2.4.3.1.1.2 For water-only protection, add a line of face sprinklers above the second tier regardless of roof
design.
2.4.3.1.1.3 For each additional tier of storage, add three (3) in-rack sprinklers to the in-rack hydraulic design.
2.4.3.1.1.4 All packaging for the containers must be noncombustible. Wooden pallets are acceptable.
2.4.3.2 Protect palletized or solid-pile storage in accordance with Table 2.4.3.2 and the following limitations:
2.4.3.2.1 Limit the storage height of liquids with a boiling point below 100°F (38°C) to one container high.
2.4.3.2.2 Where a relieving-style container is used, refer to Section 2.4.3.3.
2.4.3.2.3 Design and install foam-water sprinkler systems in accordance with Section 2.4.1.4.4.
2.4.3.2.3.1 Design foam-water sprinkler systems to deliver foam discharge out of the most remote 4 operating
sprinklers within 2 minutes of sprinkler operation.
2.4.3.2.3.1.1 Pre-prime (i.e., pre-fill the sprinkler piping with the correct foam-water mixture) foam-water
sprinkler systems that cannot meet the 2-minute delivery time.
2.4.3.3 Where ignitable liquids are stored in relieving-style containers, the following requirements must be
met:
2.4.3.3.1 Provide FM Approved fusible closures on the 2 in. (51 mm) and 3/4 in. (19 mm) openings in the
top of the steel drum.
2.4.3.3.2 Provide fusible closures on steel drums that do not exceed 60 gal (227 L) in size and have thread
dimensions in accordance with ISO 228-1:2000 or ASME B1.20.1-2013 (R2018). Regardless of which thread
standard is used, the threads must also be within the defined tolerance of the other standard.
2.4.3.3.3 Provide fusible closures with drums that are either a tight head (DOT/UN specification 1A1) or
removable head (DOT/UN specification 1A2) design.
Tight head drums must be capable of resisting an internal pressure of 20 psig (1.4 barg) when fully engulfed
in an ignitable liquid pool fire (i.e., all cylindrical surfaces exposed to a consistent flame that extends above
the top of the drum) without rupture or leakage of the drum.
2.4.3.3.4 Provide fusible closures on drums that are in transit or in storage.
2.4.3.3.4.1 Do not use fusible closures for dispensing, as they are not equivalent to safety bungs.
2.4.3.3.5 Do not use metallic cap seals over the fusible closure. Thin thermoplastic cap seals are acceptable.
Do not paint fusible closures.
2.4.3.3.6 Fusible closures shall be installed on the drum before it is delivered.
2.4.3.3.7 Develop and implement a management control system to ensure the proper fusible closures are
provided in accordance with Section 2.7.5.
2.4.3.3.8 Use steel drums that have at least an 0.039 in. (1 mm) wall/top/bottom thickness as relieving-style
drums.
2.4.3.3.9 Store relieving-style containers on-end. On-side storage arrangement will allow relieving-style drums
to empty if the fusible closure opens.
2.4.3.3.10 Palletize relieving-style containers on open deck (i.e., slatted) pallets. Solid top pallets will prevent
the fusible closure from functioning.
2.4.3.3.11 Do not solid pile the drums.
2.4.3.3.12 Do not store on plastic pallets. Plastic pallets will allow the array to collapse and release ignitable
liquids.
<200°F (93°C)) 30 (9.1) 25 (7.6) On-End 8 (2.4) Water SR/High/Any ≥11.2 (161) (Note 50 @ 7 (0.5) Fig. D.2.1.4, QR/Ordinary ≥8.0 (115) 18 @ 45 (170) (6
2, 3) D.2.1.5, D.2.1.7 per tier per rack)
and D.2.1.8
SR/High/Any 11.2 (161) (Note 50 @ 29 (2.0) Fig. D.2.1.4, QR/Ordinary ≥8.0 (115) 18 @ 45 (170) (6
2) D.2.1.6, D.2.1.7 per tier per rack)
14.0 (202) 50 @ 18 (1.2) and D.2.1.8
16.8 (235) 50 @ 13 (0.9)
25.2 (363) 50 @ 7 (0.5)
On-Side 8 (2.4) Water SR/High/Any ≥11.2 (161) (Note 50 @ 7 (0.5) Fig. D.2.1.9, QR/Ordinary ≥8.0 (115) 18 @ 35 (133) (6
2, 3) D.2.1.10 per tier per rack)
Water SR/High/Any 11.2 (161) (Note 50 @ 29 (2.0) Fig. D.2.1.11, QR/Ordinary ≥8.0 (115) 18 @ 35 (133) (6
2) D.2.1.12 per tier per rack)
14.0 (202) 50 @ 18 (1.2)
16.8 (235) 50 @ 13 (0.9)
25.2 (363) 50 @ 7 (0.5)
Page 29
7-29
Table 2.4.3.1. Rack Storage of Ignitable Liquids in Metal Containers larger than 6.5 gal (25 L) Up to and Including 60 gal (230 L) (Note 1) (continued)
Page 30
7-29
Ceiling Sprinkler Protection In-Rack Sprinkler Protection
Protection Type Response / K-factor gpm/ Design,# Layout Response/ K-factor gpm/psi1/2 Design, #
Nominal psi1/2 (L/min/ Sprinklers @ (see figure Nominal (L/min/bar1/2) Sprinklers @ Flow
Flash Point OR Maximum Ceiling Maximum Storage Temperature bar1/2) Pressure indicated) Temperature gpm (l/min) (see
Liquid Type Height Height Drum Minimum Aisle Rating / psi (bar) Rating 2.4.1.2)
(Note 3) ft (m) ft (m) Orientation Width ft (m) Orientation
Page 31
7-29
Table 2.4.3.2. Palletized/Solid-Pile Storage of Ignitable Liquids in Metal Containers Larger than 6.5 gal (25 L) Up to and Including 60 gal (230 L)
Page 32
7-29
(Apply Table in Accordance with Recommendation 2.4.3.2) (Note 1)
Ceiling Sprinkler Protection
Liquid Type, Maximum Ceiling Maximum Height Relieving-style Drum Protection Type Response / Nominal Temperature Rating / K-factor gpm/psi1/2 Design, # Sprinklers @ Pressure psi (bar)
Flash Point Height ft (m) Drum Orientation (No. Drums) Required (Yes/No) Orientation (L/min/bar1/2)
Any 30 (9.1) On-End 1 No Water SR/High/Any ≥11.2 (161)(Note 3) 50 @ 7 (0.5)
Foam-Water SR/High/Any ≥11.2 (161)(Note 3) 30 @ 7 (0.5)
Page 33
7-29
7-29 Ignitable Liquid Storage in Portable Containers
Page 34 FM Global Property Loss Prevention Data Sheets
Any 30 (9.1) 25 (7.6) Uncartoned 8 (2.4) SR/Ordinary /Any ≥11.2 (161) 20 @ 7 (0.5) Figs. D.2.1.17, QR/Ordinary ≥8.0 (115) 45 (170)
and/or Cartoned (Note 3, 4) D.2.1.18,
QR/Ordinary /Any 25.2EC (363EC) 11 @ 7 (0.5) D.2.1.20 and
D.2.1.21
Cartoned Only 8 (2.4) SR/Ordinary /Any ≥11.2 (161) 50 @ 7 (0.5) Figs. D.2.1.17, QR/Ordinary ≥8.0 (115) 45 (170)
(Note 3, 4) D.2.1.18,
QR/Ordinary /Any 25.2EC (363EC) 26 @ 7 (0.5) D.2.1.19,
D.2.1.20 and
D.2.1.21
SR/High/Any ≥11.2 (161) 30 @ 7 (0.5) Figs.D.2.1.17, QR/Ordinary ≥8.0 (115) 45 (170)
(Note 3, 4) D.2.1.19,
D.2.1.20 and
D.2.1.21
Water-miscible 30 (9.1) 25 (7.6) Uncartoned 8 (2.4) SR/Ordinary /Any ≥11.2 (161) 20 @ 7 (0.5) Figs. D.2.1.22, QR/Ordinary ≥8.0 (115) 30 (114)
and/or Cartoned (Note 3, 4) D.2.1.23,
QR/Ordinary /Any 25.2EC (363EC) 11 @ 7 (0.5) D.2.1.24 and
D.2.1.25
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. Base the in-rack sprinkler water demand on the simultaneous operation of the most hydraulically remote sprinklers as follows:
a. Eight (8) sprinklers where only one level of in-rack sprinklers is installed
b. Twelve (12) sprinklers (six on each two top levels) where two levels of in-rack sprinklers are installed
c. Eighteen (18) sprinklers (six on top three levels) where more than two levels of in-rack sprinklers are installed
d. The in-rack end head pressure as provided in this Table.
Note 3. If a foam-water sprinkler system is used, use of K 8.0 (K115) ceiling sprinklers is acceptable as long as an equivalent flow is provided from the K8.0 (K115) sprinkler.
Note 4. The K19.6 (K280) sprinkler is not acceptable for use.
Page 35
7-29
Table 2.4.4.1.B. Protection for Any Ignitable Liquid in Relieving-Style Metal Containers Up to and Including 6.5 gal (25 L), Excluding Ignitable Liquids with a
Page 36
7-29
Boiling Point Below 100°F (38°C) (Note 1)
Ceiling Sprinkler Protection In-Rack Sprinkler Protection
Response/Nominal K-factor gpm/psi1/2 Design, # of Layout (see figure Response / K-factor gpm/psi1/2 Design Flow
Minimum Aisle Maximum Ceiling Maximum Storage Temperature (L/min/bar1/2) Sprinklers @ indicated) Nominal (L/min/bar1/2) gpm (l/min)
Storage Width Height Height Rating/Sprinkler Pressure psi (bar) Temperature (see 2.4.1.2)
Arrangement ft (m) ft (m) ft (m) Packaging Type Orientation Rating (Note 2)
Cartoned Only QR/Ordinary/ 14.0 (202) 12 @ 50 (3.4) Figs. QR/Ordinary ≥8.0 (115) 30 (114)
Pendent 16.8 (235) 12 @ 35 (2.4) D.2.1.30, D.2.1.31,
22.4 (320) 12 @ 25 (1.7) D.2.1.32, D.2.1.33
25.2 (363) 12 @ 20 (1.4)
30 (9.1) 20 (6) Cartoned Only QR/Ordinary/ 14.0 (202) 12 @ 75 (5.2) None
Pendent 16.8 (235) 12 @ 52 (3.6)
22.4 (320) 12 @ 51 (3.5)
25.2 (363) 12 @ 40 (2.8)
Multiple Row None 33 (10) 25 (7.6) Uncartoned and/or QR/Ordinary/ 14.0 (202) 12 @ 75 (5.2) Figs. D.2.1.34 and QR/Ordinary ≥8.0 (115) 45 (170)
Racks Cartoned Pendent D.2.1.35 or
Table 2.4.4.2. Palletized/Solid-Pile Storage of Liquids In Non Relieving-Style Metal Containers Up to and Including 6.5
gal (25 L) (Note 1)
Ceiling Sprinkler Protection
Response/Nominal K-factor Design,
Maximum Ceiling Maximum Storage Temperature Rating/ gpm/psi1/2 (L/min/ # of Sprinklers @
Liquid Type, Flash Height Height Orientation bar1/2) Pressure
Point ft (m) ft (m) Packaging Type psi (bar)
Any 30 (9.1) 5 (1.5) Uncartoned and/or QR/Ordinary/Any 14.0 (202) 50 @ 18 (1.2)
Cartoned 16.8 (235) 50 @ 13 (0.9)
≥22.4 (320) 50 @ 7 (0.5)
12 (3.7) Cartoned Only SR/Ordinary/Any 11.2 (161) 50 @ 29 (2.0)
(Note 2)
14.0 (202) 50 @ 18 (1.2)
16.8 (235) 50 @ 13 (0.9)
25.2 (360) 50 @ 7 (0.5)
QR/Ordinary/Any 25.2EC (360EC) 26 @ 22 (1.5)
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. If a foam-water sprinkler system is used, use of K 8.0 (K115) ceiling sprinklers is acceptable as long as an equivalent flow i s provided
from the K8.0 (K115) sprinkler.
Table 2.4.4.3. Shelf Storage of Liquids in Metal Containers Up to and Including 6.5 gal (25 L) (Note 1)
Ceiling Sprinkler Protection
Maximum Storage Response / Nominal K-factor gpm/psi1/2 Design, # of Sprinklers
Maximum Ceiling Height Height Temperature Rating / (L/min/bar1/2) @ Pressure psi (bar)
Liquid Type, Flash Point ft (m) ft (m) Orientation
<200°F (93°C) 30 (9.1) 7 (2.1) SR/Ordinary/Any ≥11.2 (161) (Note 2, 3) 50 @ 7 (0.5)
QR/Ordinary/Any 25.2EC (363EC) 26 @ 7 (0.5)
SR/High/Any ≥11.2 (161) (Note 2, 3) 30 @ 7 (0.5)
≥200°F (93°C) or water- 30 (9.1) 15 (4.6) SR/Ordinary/Any ≥11.2 (161) (Note 2, 3) 30 @ 7 (0.5)
miscible QR/Ordinary/Any 25.2EC (363EC) 15 @ 7 (0.5)
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. If a foam-water sprinkler system is used, use of K 8.0 (K115) ceiling sprinklers is acceptable as long as an equivalent flow is provided
from the K8.0 (K115) sprinkler.
Note 3. The K19.6 (K280) sprinkler is not acceptable for use in this protection table.
Table 2.4.5.1. Fire Protection Criteria for Ignitable Liquids in Plastic or Glass Containers (Note 1)
Ceiling Sprinkler Protection
Response / Nominal K-factor gpm/ Design, # of Sprinklers @
Maximum Maximum Ceiling Temperature Rating / psi1/2 Pressure psi (bar)
Liquid Type, Container Size Storage Ceiling Height Storage Heigh Sprinkler Orientation (L/min/bar1/2)
Flash Point gal (L) Arrangement ft (m) tft (m) System Type (Note 2)
<200°F(93°C) >1 (4) Palletized/ 30 (9.1) 5 (1.5) Any SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 75 (5.2)
Shelf 14.0 (202) Entire Room @ 48 (3.3)
16.8 (235) Entire Room @ 33 (2.3)
22.4 (320) Entire Room @ 19 (1.3)
25.2 (363) Entire Room @ 15 (1.0)
Deluge or SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 50 (3.5)
Foam-Water 14.0 (202) Entire Room @ 32 (2.2)
16.8 (235) Entire Room @ 22 (1.5)
22.4 (320) Entire Room @ 12 (0.8)
25.2 (363) Entire Room @ 10 (0.7)
Rack Storage No options; use criteria for palletized storage.
≤1 (4) Palletized/ 30 (9.1) 5 (1.5) Any SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 75 (5.2)
Shelf 14.0 (202) Entire Room @ 48 (3.3)
16.8 (235) Entire Room @ 33 (2.3)
22.4 (320) Entire Room @ 19 (1.3)
25.2 (363) Entire Room @ 15 (1.0)
Deluge or SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 50 (3.5)
Foam-Water 14.0 (202) Entire Room @ 32 (2.2)
16.8 (235) Entire Room @ 22 (1.5)
22.4 (320) Entire Room @ 12 (0.8)
25.2 (363) Entire Room @ 10 (0.7)
Rack Storage Use Section 2.4.7.1 and Table 2.4.7.1. If liquid-package combination is not covered by Table 2.4.7.1, use criteria for palletized storage
above.
Water-miscible >6.5 (25) Palletized/ 30 (9.1) 5 (1.5) Any SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 30 (2.0)
liquids Shelf 14.0 (202) Entire Room @ 19 (1.3)
16.8 (235) Entire Room @ 13 (0.9)
≥22.4 (320) Entire Room @ 7 (0.5)
Rack Storage Use Section 2.4.6 and Table 2.4.6.1, or Section 2.4.7.3 and Table 2.4.7.3.1, for Group 1, 2, 3, and 4 water-miscible liquids (defined in
Section 3.2.1). If liquid-package combination is not covered by Table 2.4.6.1, use criteria for palletized storage above.
≤6.5 (25) Use Section 2.4.7.3 and Tables 2.4.7.3.1 and 2.4.7.3.2 for Group 1, 2, 3, and 4 water-miscible liquids (defined in Section 3.1.1). Protect water-miscible
liquids that are not included in one of the groups or Tables 2.4.7.3.1 and 2.4.7.3.2 using the criteria provided for water-miscible liquids in containers
>6.5 gal (25 L) in this table.
Distilled Spirits in wooden barrels use Section 2.4.8 or 2.4.9. If liquid-container combination is not covered by this section, protect per this table.
Propylene ≥60 (230) and Palletized See Tables 2.4.6.1 (IBCs) or 2.4.7.3.2 (Drums)
glycol, ≤300 (1100)
ethylene
glycol, or
glycerin
(>80%)
≥200°F(93°C) >6.5 (25) Palletized/ 30 (9.1) 5 (1.5) Any SR or QR/Ordinary/Any 11.2 (161) Entire Room @ 30 (2.0)
Shelf 14.0 (202) Entire Room @ 19 (1.3)
16.8 (235) Entire Room @ 13 (0.9)
≥ 22.4 (320) Entire Room @ 7 (0.5)
Rack Storage Use Section 2.4.6 and Table 2.4.6.1. If liquid-package combination is not covered by Table 2.4.6.1, use criteria for palletized storage
above.
≤6.5 (25) Use Section 2.4.7.2 and Tables 2.4.7.2.1 and 2.4.7.2.2. If liquid-package combination is not covered by Tables 2.4.7.2.1 or 2.4.7.2.2, use criteria for
containers >6.5 gal (25 L) in this table.
Very high Use the following tables, depending on liquid-packaging combinations:
flash point - For rack storage of containers <40 gal (150 L), use protection guidance in Table 2.4.7.2.1.
liquid - For palletized storage of containers ≤6.5 gal (25 L), use protection guidance in Table 2.4.7.2.2.
- For all other combinations, use protection guidance in Table 2.1.3.1.7.
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. The K19.6 (K280) sprinkler is not acceptable for use in this protection table.
2.4.6 Composite (blow molded bottle in a wire cage on a wood or steel pallet) IBC Storage of
Liquids with a Flash Point At or Above 200°F (93°C) or Alcohol in Racks or Palletized Storage of
Propylene Glycol, Ethylene Glycol, or Glycerin
2.4.6.1 Protect rack storage of liquids with a flash point at or above 200°F (93°C) or alcohol (isopropyl alcohol,
ethyl alcohol, methyl alcohol) in composite IBCs consisting of a blow molded bottle in a wire cage on a wood
or steel pallet in accordance with Table 2.4.6.1.
2.4.6.1.1 Protect all tiers of the rack with the same level of fire protection.
2.4.6.1.2 Limit IBC storage to the first tier of the rack. Upper tiers may be used for storage of other
liquid-packaging combinations that are 60 gal (230 L) or less in size and that can be protected by protection
Scheme A or protection Scheme D.
2.4.6.1.3 Arrange the room to ensure all storage is kept in the racks and not staged or stored on the floor.
The provided ceiling protection will not prevent failure of any IBC not stored in the racks and will only provide
limited protection for large pool fires.
2.4.6.2 Protect palletized storage of propylene glycol, ethylene glycol, or glycerin in composite IBCs in
accordance with Table 2.4.6.1.
2.4.6.2.1 Isolate palletized IBCs from other storage due to potential for a pool fire.
2.4.6.3 Protect FM Approved composite IBCs in accordance with Section 2.1.1.8.
Table 2.4.6.1. Storage of Liquids in Composite IBCs (blow molded bottle in a wire cage on a wood or steel pallet)
(Note 1)
Ceiling Sprinkler Protection
Response/ K-factor Design, # of
Maximum Nominal gpm/psi1/2 Sprinklers
Container Ceiling Maximum Minimum Temperature (L/min/ @ Pressure In-Rack
Liquid Type, Size Storage Height Storage Aisle Width Rating/ bar1/2) psi (bar) Sprinkler
Flash Point gal (L) Array ft (m) Height ft (m) Rack Type Orientation Protection
≥200˚F >60 (230) Rack 30 (9.1) 1 IBC high 8 (2.4) Single or SR/Ordinary/ 11.2 (161) 30 @ 13 Scheme D
(93˚C) and ≤300 in bottom Double Row Any (0.9)
or Alcohol (1100) tier of rack (Note 3)
14.0 (202) 30 @ 8
(0.6)
(Note 3)
≥16.8 (235) 30 @ 7
(Note 2) (0.5)
(Note 3)
QR/Ordinary/ 25.2EC 16 @ 10
Any (363 EC) (0.7)
(Note 3)
Very High ≥60 (150) Rack or See Section 2.1.3.1.
Flash Point and ≤300 Palletized
(1150)
Propylene >60 (230) Palletized 30 (9.1) 1 IBC high DNA DNA SR/Ordinary/ ≥11.2 (161) 20 @ 7 DNA
glycol, and ≤300 Any (Note 2) (0.5)
ethylene (1100) DNA DNA QR/Ordinary/ 25.2EC 10 @ 7 DNA
glycol, or Any (363 EC) (0.5)
glycerin 3 IBCs high DNA DNA SR/Ordinary/ 11.2 (161) 20 @ 28 DNA
(>80%) Any (1.9)
14.0 (202) 20 @ 18 DNA
(1.2)
16.8 (235) 20 @ 13 DNA
(0.9)
≥22.4 (310) 20 @ 7 DNA
(0.5)
DNA DNA QR/Ordinary/ 25.2EC 10 @ 22 DNA
Any (363 EC) (1.5)
Note 1. See Section D.1 for explanation of abbreviations. See Section D.2.2 for fire protection schemes.
Note 2. The K19.6 (K280) sprinkler is not acceptable for use in this protection table.
Note 3. In cutoff rooms where on-floor storage is impossible, i.e., only rack storage and transport aisles, the ceiling sprinkler operating area
can be reduced to 20 sprinklers for non-EC sprinklers and 10 sprinklers for the K25.2 EC (360 EC) sprinkler.
2.4.7 Plastic, Glass, or Other Combustible/Brittle Containers Up to and Including 60 gal (230 L)
2.4.7.1 Protect storage of non-water-miscible liquids with flash points below 200°F (93°C) as follows:
2.4.7.1.1 Provide sprinkler protection in accordance with Table 2.4.5.1 or 2.4.7.1, based on container size,
storage arrangement, roof/ceiling height, and storage height.
2.4.7.1.2 When needed, provide foam-water protection in accordance with this data sheet and Data Sheet
4-12.
Note 1. See Section D.1 for explanation of abbreviations. See Section D.2.2 for fire protection schemes.
Note 2. Applies to open frame racks.
Note 3. If a foam-water sprinkler system is used, use of K 8.0 (K115) ceiling sprinklers is acceptable as long as an equivalent flow is provided from the K8.0 (K115) sprinkler.
Note 4. The K19.6 (K280) sprinkler is not acceptable for use.
Page 41
7-29
7-29 Ignitable Liquid Storage in Portable Containers
Page 42 FM Global Property Loss Prevention Data Sheets
2.4.7.2 Protect storage of liquids with flash points at or above 200°F (93°C) as follows:
2.4.7.2.1 Provide sprinkler protection per Table 2.4.7.2.1 or Table 2.4.7.2.2, as applicable, based on storage
arrangement, roof/ceiling height, and storage height.
2.4.7.2.2 Semi-solid liquids with flash points at or above 200°F (93°C) in bag-in-box type containers (i.e.,
plastic bag in a corrugated box) up to 10 gal (38 L) in size can be protected in accordance with Table 2.4.7.2.1.
Unlimited Unlimited Uncartoned and/or Cartoned 4 (1.2) Any Any Any Scheme A
(Note 3) (8 mm/min)
Very high flash ≥40 gal (150 L) and See Section 2.1.3.1.
point liquid ≤60 gal (230 L)
<40 gal (150 L) Unlimited Unlimited Uncartoned 8 (2.4) Single or Any Any Minimum 0.2 gpm/ft2 Scheme A
Double Row (8 mm/min)
≤6.5 gal (25 L) Unlimited Unlimited Uncartoned and/or Cartoned 4 (1.2) Any Any Any Minimum 0.2 gpm/ft2 Scheme A
(Note 3) (8 mm/min)
40 (12.1) 35 (10.7) Uncartoned and/or Cartoned 4 (1.2) Any SR/Ordinary/Any ≥11.2 (161) 20 @ 7 (0.5) Scheme B
(Note 3) (Note 2)
QR/Ordinary/Any 25.2EC (363EC) 11 @ 7 (0.5)
Cartoned Only 8 (2.4) Single or SR/Ordinary/Any 11.2 (161) 20 @ 29 (2.0) Scheme C
Double Row 14.0 (202) 20 @ 18 (1.2)
16.8 (235) 20 @ 13 (0.9)
25.2 (363) 20 @ 7 (0.5)
QR/Ordinary/Any 25.2EC (363EC) 11 @ 22 (1.5)
Page 43
7-29
Table 2.4.7.2.1. Rack Storage of Liquids in Plastic or Glass Containers with Flash Points At or Above 200°F (93°C) (Note 1) (continued)
Page 44
7-29
Ceiling Sprinkler Protection
Response/Nominal K-factor gpm/psi1/2 Design, # of Sprinklers @
Maximum Ceiling Maximum Storage Minimum Aisle Temperature Rating/ (L/min/bar1/2) Pressure psi (bar)
Flash Point Container Size Height ft (m) Height ft (m) Packaging Type Width ft (m) Rack Type Orientation In-Rack Sprinkler Protection
Very high flash ≤6.5 gal 30 (9.1) 25 (7.6) Uncartoned and/or Cartoned 8 (2.4) Single or SR/Ordinary/Any ≥11.2 (161) (Note 2) 20 @ 7 (0.5) Scheme C
point liquid Double Row QR/Ordinary/Any 25.2EC (363EC) 11 @ 7 (0.5)
Page 45
7-29
Table 2.4.7.2.2. Palletized/Solid Pile Storage of Liquids with Closed-Cup Flash Points At or Above 200°F (93°C) in Plastic Containers (Note 1) (continued)
Page 46
7-29
Ceiling Sprinkler Protection
Liquid Type, Response / Nominal Temperature Rating / K-factor gpm/psi1/2 Design, # of Sprinklers @ Pressure psi
Flash Point Container Size Packaging Type Maximum Ceiling Height ft (m) Maximum Storage Height ft (m) Orientation (L/min/bar1/2) (Note 2) (bar)
Very high flash ≤6.5 gal (25 L) Uncartoned 40 (12.1) 15 (4.6) QR/Ordinary/Pendent 14.0 (202) 12 @ 75 (5.2)
point liquid and/or 16.8 (235) 12 @ 50 (3.5)
Cartoned 30 (9.1) 15 (4.6) QR/Ordinary/Pendent 14.0 (202) 12 @ 50 (3.5)
2.4.7.3 Protect Group 1, 2, 3, and 4 water-miscible liquids in accordance with Table 2.4.7.3.1 or Table
2.4.7.3.2, as applicable, based on storage arrangement, roof/ceiling height, and storage height.
2.4.7.4 Protect Group 5 water-miscible liquids as non-ignitable liquids.
2.4.7.4.1 Determine the appropriate commodity classification using Data Sheet 8-1.
Page 48
7-29
Ceiling Sprinkler Protection In-Rack Sprinkler Protection
Response / K-factor gpm/ Design, # of Layout Response K-factor Design Flow
Nominal psi1/2 Sprinklers @ / Nominal gpm/psi1/2 gpm (L/min)
Water-miscible Maximum Temperature (L/min/bar1/2) Pressure psi Temperature (L/min/ (See 2.4.1.2) (Note 3)
Group (see Maximum Ceiling Height Storage Height Rating / (bar) Rating bar1/2)
Section 3.2.1) Container Size ft (m) ft (m) Packaging Type Minimum Aisle Width ft (m) Rack Type Orientation
≤ 6.5 gal(25 L) 35 (11) 10 (3) Uncartoned 8 (2.4) Single or SR/Ordinary/ 11.2 (161) 30 @ 13 (0.9) Scheme A
and/or Double Row Any 14.0 (202) 30 @ 8 (0.6)
Cartoned ≥16.8 (235) 30 @ 7 (0.5)
(Note 2)
QR/Ordinary/ 25.2EC 15 @ 10 (0.7)
Any (363EC)
≤1 gal(4 L) Unlimited Unlimited Cartoned Only Any Any Any Minimum 0.2 gpm/ft2 (8 mm/min) Scheme A
(Note 5)
≤6 oz(180 ml) 30 (9.1) 25 (7.6) Cartoned Only 8 (2.4) Single or QR/Ordinary/ 14.0 (202) 12 @ 50 (3.4) None
Double Row Pendent 16.8 (235) 12 @ 35 (2.4)
(Note 2)
SR/Ordinary/ 11.2 (161) 20 @ 29 (2.0) Fig. QR/Ordinary ≥8.0 (115) 45 (170)
Any 14.0 (202) 20 @ 18 (1.2) D.2.1.46,
16.8 (235) 20 @ 13 (0.9) D.2.1.47
25.2 (363) 20 @ 7 (0.5)
QR/Ordinary/ 25.2EC 10 @ 22 (1.5)
Any (363EC)
SR/Ordinary/ ≥11.2 (161) 20 @ 7 (0.5) Fig. QR/Ordinary ≥8.0 (115) 45 (170)
Any (Note 2) D.2.2.3.1,
QR/Ordinary/ 25.2EC 10 @ 22 (1.5) D.2.2.3.2,
Any (363EC) D.2.2.3.3
(Note 4)
≤ 59 oz (1.75 Unlimited Unlimited Cartoned 4 (1.2) Any (Note 5) SR/Ordinary/ ≥11.2 (160) 20 @ 7 (0.5) Scheme E
L) Any ≤ 5 ft (1.5 m) storage above top level of in-rack sprinklers
QR/Ordinary/ 25.2EC 10 @ 7 (0.5)
Any (363EC)
SR/Ordinary/ 11.2 (160) 20 @ 29 (2.0) Scheme E
Any 14.0 (202) 20 @ 18 (1.2) ≤ 10 ft (3 m) storage above top level of in-rack sprinklers
16.8 (235) 20 @ 13 (0.9)
25.2 (363) 20 @ 7 (0.5)
QR/Ordinary/ 25.2EC 10 @ 22 (1.5)
Any (363EC)
Page 49
7-29
Table 2.4.7.3.1. Rack Storage of Group 1, 2, 3, and 4 Water-Miscible Liquids in Plastic or Glass Containers (Note 1) (continued)
Page 50
7-29
Ceiling Sprinkler Protection In-Rack Sprinkler Protection
Response / K-factor gpm/ Design, # of Layout Response K-factor Design Pressure gpm (L/min)
Nominal psi1/2 Sprinklers @ / Nominal gpm/psi1/2 (See 2.4.1.2) (Note 3)
Water-miscible Maximum Temperature (L/min/bar1/2) Pressure psi Temperature (L/min/
Group (see Maximum Ceiling Height Storage Height Rating / (bar) Rating bar1/2)
Section 3.2.1) Container Size ft (m) ft (m) Packaging Type Minimum Aisle Width ft (m) Rack Type Orientation
Page 51
7-29
16.8 (235) 20 @ 13 (0.9)
Table 2.4.7.3.2. Palletized/Solid Pile Storage of Groups 1 through 4 Water-Miscible Liquids in Plastic or Glass Containers (Note 1) (continued)
Page 52
7-29
Ceiling Sprinkler Protection
Maximum Ceiling Height Maximum Storage Height Response / Nominal K-factor gpm/psi1/2 Design, # of Sprinklers @
Liquid Type (Note 2) Container Size, Type Packaging Type ft (m) ft (m) Temperature Rating / Orientation (L/min/bar1/2) Pressure psi (bar)
Group 4 ≤6.5 gal (25 L), Any Uncartoned or Cartoned 30 (9.1) 20 (6.1) QR/Ordinary/Pendent 14.0 (202) 12 @ 50 (3.4)
SR/Ordinary/Any 11.2 (161) 30 @ 13 (0.9)
14.0 (202) 30 @ 8 (0.6)
Fig. 2.4.8.2. Minimum flue space between palletized storage arrays (plan view)
2.4.8.3 Arrange palletized storage that is provided with a defined loading aisle using one of the options below:
A. Provide a draft curtain along the side of palletized storage facing the loading aisle as shown in Figure
2.4.8.3.A. Design the draft curtains in accordance with Data Sheet 1-10, Interaction of Sprinklers, Smoke
and Heat Vents, and Draft Curtains, and Data Sheet 2-0.
B. Provide a trench drain on each side of the loading aisle as shown in Figure 2.4.8.3.B arranged to remove
any spilled distilled spirits in the aisle space out of the building and prevent it from spreading into the
barrel storage area.
C. Band all the barrels on each pallet to prevent barrels from falling off the pallet during transportation
and loading into the storage array.
2.4.8.4 Protect palletized storage arrangements in accordance with Table 2.4.8.4 and the following criteria:
2.4.8.4.1 The protection applies to alcohol-water mixtures up to 75% alcohol by volume and wooden barrel
sizes of 53–130 gal (200–500 L).
2.4.8.4.2 Provide a 500 gpm (1900 L/min) hose stream allowance.
2.4.8.4.3 Provide a water supply that can deliver the total sprinkler and hose stream demand for a duration
of at least one hour.
2.4.8.4.4 When a permanent loading aisle is provided, the Barrel Storage system and Loading Aisle system
do not need to be hydraulically balanced.
2.4.8.4.5 If a dry sprinkler system is permitted, provide water delivery within 40 seconds to the most remote
4 sprinklers.
Table 2.4.8.4. Palletized Storage of Distilled Spirits with up to 75% Alcohol by Volume in Wooden Barrels (Note 1)
Ceiling Sprinkler Protection
Response/ K-factor Design, # of
Nominal gpm/psi1/2 Sprinklers @
Temperature (L/min/bar1/2) Pressure
Ceiling Height Storage Height Rating/ psi (bar)
Protection Area System Type ft (m) ft (m)/# drums Orientation
Barrel Storage Wet 30 ft (9.1 m) 24 ft (7.3 m) / QR / Ordinary / 14.0 (202) 12 @ 18 (1.25)
7 drums Pendent
QR / Ordinary / 16.8 (240) 12 @ 13 (0.9)
Pendent
Dry SR / High / 16.8 (240) 24 @ 13 (0.9)
Upright
Loading Aisle Wet / Dry NA SR / High / 5.6 (80) 100 @ 13 (0.9)
with Draft Any >8.0 (115) 100 @ 7 (0.5)
Curtain (Note 2)
Loading Aisle Provide the palletized storage design across the entire roof area (i.e., storage area and loading aisle)
with Trench
Drains or
Banded Barrels
or No
Permanent
Loading Aisle
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. The K 19.6 (K280) sprinkler is not acceptable for use in this protection table.
Fig. 2.4.9.1. Flue space and walkway layout for on-side barrel storage in racks (plan view)
2.4.9.4 Protect rack storage arrangements in accordance with Table 2.4.9.4 and the following criteria:
2.4.9.4.1 Any rack type is acceptable if the needed open fraction and flue spaces are provided.
2.4.9.4.2 For walkways that do not meet the criteria in Section 2.4.9.2.2 or Section 2.4.9.2.2.1, provide
sprinkler protection below walkways at every level.
2.4.9.4.3 The protection applies to alcohol-water mixtures up to 75% alcohol by volume and wooden barrel
sizes of 53–130 gal (200–500 L).
2.4.9.4.4 Provide a 500 gpm (1900 L/min) hose stream allowance.
2.4.9.4.5 Provide a water supply that can deliver the total sprinkler and hose stream demand for a duration
of at least one hour.
2.4.9.4.6 If a dry sprinkler system is permitted, provide water delivery within 40 seconds to the most remote
4 sprinklers.
45 (170) [more
than one level of
in racks]
On-End Wet 30 (9.1) 25 (7.6) / 5 8 (2.4) SR / High / Any ≥ 11.2 (160) 50 @ 7 (0.5) Fig D.2.1.4, QR / Ordinary / ≥ 8.0 (115) 6 @ 25 (95) [one
barrels (Note 2) D.2.1.6, D.2.1. 7 Any level] or 12 @ 25
and D.2.1.8 (95 ) [more than
one level]
Note 1. See Section D.1 for explanation of abbreviations.
Note 2. The K19.6 (K280) sprinkler is not acceptable for use in this protection table.
2.4.9.5 Provide a curb between the loading aisle and the racks. This is to help prevent a spill from a dropped
barrel spreading under the rack storage.
2.4.9.6 If barrels are filled/emptied in place while in storage, i.e., alcohol is transferred, then apply Data Sheet
7-32. The protection recommendations above remain applicable provided that the maximum anticipated spill
is equivalent to the volume of one barrel.
2.6 Training
2.6.1 Create a training program for all employees (including lift truck operators, emergency response team
members, and security personnel) who have access to or work in areas containing ignitable liquid storage. At
a minimum, include the following subjects in the program:
A. The hazards created by the liquids and their associated containers
B. Proper liquid/container handling procedures (i.e., lift truck operations, liquid transport through the facility,
etc.)
C. Emergency procedures, including the location, proper type and proper use of fire extinguishers and
small hose stations
D. Fixed extinguishing systems operation and function
E. The consequences of failing to follow the procedures
2.6.2 Provide training for all new employees, with refresher programs as needed.
2.7.2 Establish an emergency response plan designed to control the extent of damage due to fire in
accordance with Data Sheet 10-1, Pre-Incident and Emergency Response, at locations storing ignitable
liquids.
2.7.2.1 Include spill-response procedures aimed at limiting spill size (e.g., prompt removal of breached
containers), containing released liquid (e.g., use of sand bags or other barriers), and elimination of all ignition
sources that may be exposed by the spill or flammable vapor until the spill is cleaned up.
2.7.2.2 Develop and maintain a pre-incident plan in accordance with Data Sheet 10-1.
2.7.2.3 Conduct emergency response drills to reinforce the employee training programs (including emergency
response team).
2.7.3 Arrange security rounds to include all areas storing ignitable liquids.
2.7.3.1 Train security personnel to recognize and provide prompt notification of a leak.
2.7.4 Provide a raw materials inspection program to ensure delivery of expected liquids and prevent the
introduction of incompatible liquids into a storage facility.
2.7.4.1 Only accept, ship, and use containers that comply with U.S. Department of Transportation (DOT),
United Nations, or equivalent specifications.
2.7.4.2 Maintain the vapor space no less than that permitted by the specific regulation.
2.7.5 Conduct fusible closure supervision in accordance with the following recommendations at locations
where FM Approved fusible closures for steel drums are used.
2.7.5.1 Develop a management reporting system that includes:
A. Qualified personnel responsible for program implementation.
B. Periodic management audits to ensure the program is implemented as intended.
2.7.5.2 Create purchasing requirements that include:
A. A list of qualified suppliers.
B. A list of FM Approved fusible closures that are installed by each supplier.
2.7.5.3 Develop drum inspection requirements for receiving and storage areas that include:
A. Visual inspections to ensure FM Approved fusible closures are installed on all incoming drums.
B. Recorded incoming drum inspections.
C. An up-to-date list of qualified suppliers and FM Approved fusible closures.
D. Clear authorization to reject any shipments containing non-Approved fusible closures.
E. Reporting requirement for any unsatisfactory conditions to ensure prompt corrective measures.
2.7.5.4 Provide awareness training for employees who receive and handle drums fitted with FM Approved
fusible closures.
2.7.5.4.1 Ensure the training addresses the following:
A. Role of FM Approved fusible closures and proper storage practices
B. Potential consequences of unapproved fusible closures and improper storage
C. Recognizing FM Approved and unapproved fusible closures
D. Inspection and reporting procedures
E. Initial training and periodic refreshers
2.7.5.5 Provide documentation of all procedures, suppliers, inspection records, and training.
2.7.5.5.1 Ensure documentation is maintained in a central location on site that is accessible for loss prevention
audits.
2.7.5.6 Use Management of Change procedures to:
A. Maintain an up-to-date roster of designated employees and their role in fusible closure supervision.
B. Communicate new suppliers and fusible closure manufacturers to all areas of the supervision program.
2.7.6 Clearly label all containers filled with ignitable liquids.
2.7.6.1 Inspect drums for leaks upon receipt, when in use, and while stored.
2.7.6.2 Promptly remove any leaking, corroded, or damaged drums, and immediately clean up any spillage
and dispose of it in a manner acceptable to the authority having jurisdiction.
2.7.7 Strictly control all changes in storage arrangements, locations, and types of ignitable liquids.
2.7.7.1 Conduct a full review of all planned changes with qualified loss prevention consultants as well as
other authorities having jurisdiction before the project begins.
Table 2.8.1. Electrical Equipment Ratings and Lift Truck Ratings for Ignitable Liquids Storage Occupancies
Electrical Equipment Rating within 6 ft (1.8 m)
of Floor Level Lift Truck Rating for
US (NEC 500) US (NEC 505) Handling or
Liquid Type Container Size IECCENELEC Transporting Liquids
BP < 100°F (38°C) Any Class 1 Division 2 Class 1 Zone 2 Type EE or DY
FP <100°F (38°C) Any Ordinary Ordinary Type EE or DY
AND
BP ≥ 100°F (38°C)
FP ≥100°F(38°C) Any Ordinary Ordinary Ordinary
Note: FP = flash point, and BP = boiling point.
2.8.2 Use Table 2.8.1 to determine when lift trucks that are FM Approved for Class 1, Division 2 locations
are needed to handle and/or transport liquid storage.
2.8.2.1 Use of electric Type E, gasoline Type GS, diesel Type DS, and LP-gas Type LPS to transport all
liquid types outdoors is acceptable.
2.8.2.2 Use of air-powered or manually-operated hoists, hand trucks, or other manual equipment are
acceptable and are generally preferred for use with all ignitable liquids.
2.8.2.3 Do not use hydrogen fuel cell lift trucks for handling ignitable liquids since they are not currently rated
for hazardous location use and may create an explosion hazard if they are fueled in the building where they
are being used.
2.8.2.4 Rated lift trucks are not required for liquids stored in general purpose warehouses.
2.8.3 Provide grounding in accordance with Data Sheet 5-8, Static Electricity and NFPA 70, National Electrical
Code, Articles 250 and 500, for equipment subject to static accumulations, such as racks, ventilating ducts,
hoists, etc. Proper grounding of equipment reduces the potential for buildup of electric charge on separated
pieces of equipment due to static accumulations or stray electric currents.
2.8.4 Prohibit smoking or the use of open flames in all rooms, buildings, or outdoor storage areas that are
used for the storage of ignitable liquids.
2.8.4.1 Post conspicuous signs to define hazardous areas and state restrictions for the area.
2.8.5 When heating rooms or buildings, including hot box or warming room, that contain ignitable liquid
storage, use a system that does not introduce an ignition source (e.g., steam, hot water, or hazardous location
rated electric heat).
2.8.5.1 Direct natural gas/fuel oil-fired make-up air heaters are acceptable if the heating unit is located outside
the room or building and there is no air recirculation.
2.8.5.2 Keep heating equipment surface temperatures below the auto-ignition point of the liquids present in
the room.
2.8.5.3 Keep heating equipment at least 5 ft (1.5 m) away from liquid storage containers.
2.8.5.4 If storage containers are opened in the room, use Data Sheet 7-32.
2.8.6 Do not allow hot work of any kind in areas (indoors and outdoors) storing ignitable liquids. Instead,
use methods that do not create a potential ignition source, or relocate any hot work to a nonhazardous
location. When relocation is not possible, use the FM Global Hot Work Permit System. See Data Sheet 10-3.
3.1 General
The currently FM Approved composite IBC is Approved for use with liquids that have a flash point greater
than or equal to 100°F (38°C).
There are only a small number of ignitable liquids that meet the definition of water-miscible provided in this
data sheet. Most liquids that meet the definition are low molecular weight alcohols and acetone. Only the
liquids listed in Table 2.1.2.2 should be considered water-miscible. If a liquid is thought to be water-miscible,
it must be confirmed by testing a range of volume percentages to clearly demonstrate its ability to mix in
all proportions with water.
Water-miscible liquids do mix with water. However, they are also lighter than water so they float on its surface.
Most of the mixing in a sprinklered pool fire scenario is due to sprinkler discharge impacting the liquid surface.
Full-scale tests by FM Global have shown that, although mixing does occur, it is a very slow process and
should not be depended on to reduce fire protection needs in a storage arrangement.
Some protection criteria required for water-miscible liquids as a general group can be reduced due to the
lower heat release rates and lower flame radiation (e.g., location and construction requirements, sprinkler
protection for liquids in metal containers). Some protection criteria (e.g., drainage requirements) can be
reduced due to the expected dilution effect of water. In other cases, water-miscible liquids need to be broken
down by the specific liquid, liquid concentration, and storage container construction (e.g., sprinkler protection
for liquids in plastic containers). Since plastic or glass containers cannot prevent the release of a water-
miscible liquid during a fire, the liquid type and concentration must be considered. All water-miscible liquids
do not present the same fire hazard. Acetone creates a more severe fire hazard than isopropyl alcohol (IPA).
Unfortunately, fire testing conducted to date has only looked at alcohols. This base of test data allows the
grouping of all water-miscible alcohols by volume percent. One series of small-scale testing indicates that
80% acetone presents a fire hazard similar to 100% IPA. Since different levels of fire protection criteria are
possible for various mixtures of some miscible liquids and water, mixtures with similar fire hazards were
grouped.
Miscible liquid mixtures in plastic or glass containers that are not included in the groups have not been
evaluated. Use the guidance in Table 2.4.5.1 to determine acceptable fire protection for these liquids.
3.2.2 Emulsions
An emulsion is a stable mixture of two or more immiscible substances held in suspension by a small
percentage of substances called emulsifiers. A common example of this type of product is a water-borne paint
or coating. Latex paints generally have little or no ignitable liquid content. Some newer paints have various
percentages of ignitable liquid in a water base. The ignitable liquids can be water-miscible or immiscible.
Bench-scale testing on a large number of paint products with up to 20% immiscible ignitable liquid has shown
these materials to present no measurable fire hazard. Many of these materials cannot be easily tested using
standard flash or fire point test methods. However, efforts to ignite larger quantities of liquid than required
by these tests also failed to produce any sustained combustion. All emulsion products with unknown ignitable
liquid content require testing to confirm if the product has a fire point.
An important benefit of viscous liquids is their reduced flow capacity. Highly viscous liquids will resist free
flow, which results in reduced surface area. As discussed earlier, surface area has a direct impact on liquid
fire severity. Unfortunately, the viscosity of many materials decreases with elevated temperatures. Since
current viscosity measurement techniques do not provide viscosities at fire temperatures, a reduction in fire
hazard for viscous homogenous materials cannot be determined.
There are other liquids that consist of a mixture of solids and an ignitable liquid. In cases where there is a
high solid content, a reduction in fire hazard is expected. Liquids with a viscosity of 10,000 cP and less than
10% ignitable liquid, or a viscosity of 100,000 cP and less than 50% ignitable liquid, can be protected using
reduced protection criteria. Straight interpolation may be used to calculate the maximum solvent content
for mixtures with viscosities between 10,000 cP and 100,000 cP. One example is automobile repair putty,
which consists of a viscous base material combined with a small quantity of low flash point solvent.
Liquid drainage systems are not needed for any liquid with a viscosity greater than 10,000 cP. Even though
these liquids may experience a reduction in viscosity when exposed to a fire, if the sprinkler protection is
adequate, the liquids should cool quickly on the floor. The reduced flow characteristics of a highly viscous
liquid negates the effectiveness of a drainage system in removing the liquid.
recognize that these products do burn either as a pure liquid or as a gel and if not properly protected in
accordance with this data sheet, they could represent a significant fire hazard to a facility.
3.4 Ventilation
Ventilation systems are designed to confine, dilute, and remove the normal amount of flammable vapor
released from leaks of ignitable liquids in storage or use occupancies. Today’s modern containers should
not allow any leakage of flammable vapor under normal conditions so specially designed ventilation systems
are not generally needed in storage occupancies. Certain highly volatile liquids, like those with boiling points
below 100°F (38°C), justify the use of a specially designed ventilation system due to their high vapor
pressures. Warehouses with poorly maintained containers or with liquid dispensing do still need specially
designed ventilation systems.
Ventilation is an active system designed to prevent the buildup of flammable vapor due to small leaks or
spills. These systems must be properly designed and laid out to ensure all floor areas of the warehouse or
cutoff room are covered by the system. In large buildings, a test of the system using a smoke generating
device may be needed to ensure the system layout is adequate.
3.5 Protection
3.5.1 General
Determining adequate fire protection for the storage of ignitable liquids is not a straightforward effort. In
general, there is a lack of full-scale testing to draw conclusions from due to the high cost and potential risk
of conducting this type of testing. However, even if the testing is done, the number of variables that could
drastically impact the outcome of a test are incalculable. Potential fire scenarios range from a point ignition
of a common combustible material in an ignitable liquids storage occupancy to the ignition of the contents
of a 350 gal (1.3 m3) IBC that emptied onto the floor.
For containers larger than 6.5 gal (25 L) in size, the fire scenario used to evaluate protection involves a
breached container that leaks ignitable liquid at a fixed rate until empty, with ignition after approximately 10
gal (38 L) have been released. The recommended fire protection may not be adequate for the scenario
involving the complete release of a large container before ignition in warehouses or cutoff rooms that are
larger than the provided sprinkler operating area. Due to the variability of defining fire protection for ignitable
liquids, sprinkler protection alone will not ensure adequate protection. Construction features, space
separation, and prevention measures must be included in any ignitable liquid warehouse/cutoff room design.
3.7 Training
Thorough employee training is a fundamental component of any ignitable liquid storage facility. Such training
contributes to reducing the potential for a fire, as well as reducing the frequency and severity of such events.
Proper employee training for spill response and lift truck operation can help ensure that a small fire is
contained and does not escalate into a major loss.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-10, Interaction of Sprinklers, Smoke and Heat Vents and Draft Curtains
Data Sheet 1-12, Ceilings and Concealed Spaces
Data Sheet 1-20, Protection Against Exterior Fire Exposure
Data Sheet 1-21, Fire Resistance of Building Assemblies
Data Sheet 1-29, Roof Deck Securement and Above-Deck Roof Components
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 2-81, Fire Protection System Inspection, Testing and Maintenance
Data Sheet 4-0, Special Protection Systems
Data Sheet 4-1N, Fixed Water Spray Systems for Fire Protection
Data Sheet 4-12, Foam Extinguishing Systems
Data Sheet 5-8, Static Electricity
Data Sheet 5-11, Lightning and Surge Protection for Electrical Systems
Data Sheet 5-48, Automatic Fire Detection
Data Sheet 7-31, Storage of Aerosol Products
Data Sheet 7-32, Ignitable Liquid Operations
Data Sheet 7-50, Compressed Gases in Portable Cylinders and Bulk Storage
Data Sheet 7-55, Liquefied Petroleum Gas (LPG) Storage in Stationary Installations
Data Sheet 7-83, Drainage and Containment Systems for Ignitable Liquids
Data Sheet 7-88, Outdoor Ignitable Liquid Storage Tanks
Data Sheet 7-96, Printing Plants
Data Sheet 8-1, Commodity Classification
Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities
Data Sheet 9-0/17-0, Asset Integrity
Data Sheet 10-0, The Human Factor of Property Conservation
Data Sheet 10-1, Pre-Incident and Emergency Response Planning
Data Sheet 10-3, Hot Work Management
Approval Guide, an online resource of FM Approvals
RoofNav, an online resource of FM Approvals
4.2 NFPA
National Fire Protection Association (NFPA). NFPA 30, Flammable and Combustible Liquids Code.
National Fire Protection Association (NFPA). NFPA 70, National Electrical Code.
4.3 Other
American Society of Mechanical Engineers (ASME). Pipe Threads, General Purpose. B1.20.1.
ASTM International. Standard Test Methods for Fire Tests of Building Construction and Materials. ASTM
E119.
ASTM International. Standard Test Method for Flash Point by Tag Closed Tester. ASTM D56.
ASTM International. Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester. ASTM
D93.
International Organization for Standardization (ISO). Pipe threads where pressure-tight joints are not made
on the threads - Part 1. ISO 228-1.
International Organization for Standardization (ISO). Determination of Flash Point - Pensky-Martens Closed
Cup Method. ISO 2719.
liquids because it is conservative (i.e., produces lowest flash point for liquid), and it represents the conditions
in which most liquids are handled (i.e., most liquids are contained in closed containers or equipment).
FM Approved: Product and services that have satisfied the criteria for FM Approval. Refer to the Approval
Guide or RoofNav, online resources of FM Approvals, for a complete list of products and services that are
FM Approved.
Foam-water sprinkler system: A foam-water sprinkler system consists of a closed or open head sprinkler
system that is connected to a low expansion foam concentrate proportioning system designed to deliver a
fixed foam concentration. The major advantage to installing a foam system is they can be added to an existing
sprinkler system. Closed and open head foam-water sprinkler systems are described in Data Sheet 4-12,
Foam Extinguishing Systems.
General purpose warehouse: A warehouse used to store general commodities such as plastics or Class
3 commodities. A general purpose warehouse does not require emergency drainage, containment, rated
electrical equipment, or ventilation.
Heat of combustion: The amount of heat released when a unit quantity of fuel is oxidized completely to
yield stable end products. The measurement is generally made in an oxygen bomb calorimeter. A similar term
is the ″chemical heat of combustion,″ which represents the amount of heat released when a unit quantity
of fuel is combusted in air. The chemical heat of combustion is less than the heat of combustion due to the
inefficiency of the combustion process in air.
Heat release rate: The rate at which energy is released in a fire. The heat release rate is a function of the
fuel’s heat of combustion, mass loss rate, and the exposed surface area.
Ignitable liquid: Any liquid or liquid mixture that has a measurable closed cup flash point. The hazard of a
liquid depends on its ability to sustain combustion or create a flammable vapor-air mixture above its surface.
Flash point is one way of understanding if a liquid can create that flammable vapor-air mixture. For a liquid
to burn in a pool, it must have a fire point as well as a flash point. Ignitable liquids include flammable liquids,
combustible liquids, inflammable liquids, and any other term for a liquid that will burn.
Intermediate bulk container (IBC): Defined by the U.S. Department of Transportation in CFR Title 49, Part
178, Subpart N, dated October 1, 1997, and the United Nations Recommendations on the Transport of
Dangerous Goods, Ninth Edition, Chapter 16. The container size is limited to 793 gal (3 m3). There are no
other specific requirements on the design or material of construction. All IBCs must pass the required
performance-based testing designed to evaluate their resistance to leakage during transport. No existing test
requirements evaluate the container’s performance when exposed to fire. The IBC category also includes
the containers previously defined as portable tanks or tote tanks. Some limitations on the type of liquid storage
allowed in an IBC used for transportation do exist. However, for most commonly transported ignitable liquids,
there are few limitations.
In general, the maximum-size IBC used for liquid transport is approximately 660 gal (2.5 m3) due to overall
package weight. More common sizes range from 250 to 330 gal (0.95 to 1.3 m3). Common IBC construction
types include all-plastic self-supporting containers; plastic-supported plastic containers (plastic composite
containers that consist of a rigid plastic frame supporting a plastic container); and metal-supported plastic
containers (metal-plastic composite containers that consist of a metal frame supporting a plastic container).
Since the only evaluation IBCs need to pass is performance-based testing, there is very little consistency
in the design of IBCs produced by various manufacturers. A series of fire tests sponsored by the
manufacturers clearly showed that the fire performance of a particular type of IBC could not be generalized.
This is likely due to the variability of the designs.
Composite IBC: IBCs consisting of a blow-molded plastic bottle enclosed within a steel cage.
Plastic IBC: IBC with a plastic bottle surrounded by a plastic frame.
Bag-In-box IBC: IBC consisting of a plastic bag inside a corrugated box.
Liquid: A material that does not have a defined shape at room temperature unless it is stored in a container.
These materials flow freely when released. (e.g., water, honey, heptane).
Non-Ignitable liquid: A liquid that does not burn or exhibit a flash point.
Open area fraction: The amount of open space between and around barrels in plan view, taking account
of flue spaces but not aisles, as shown in Figure A.1.
Fig. A.1. Plan view (white area represents open area fraction)
Prefabricated ignitable liquid storage building (PILSB): A structure designed to provide a safe, secure
storage area with secondary containment for chemicals and hazardous waste materials. These units allow
personnel entry. They are designed for the indoor and outdoor storage and dispensing of ignitable liquids. FM
Approved storage buildings are of noncombustible construction, and some are of fire-rated construction.
Additional details are provided in the Approval Guide.
Relieving-style container: A relieving-style container will release excess internal pressure without a
significant release of the stored liquid when exposed to a fire. The pressure relief prevents the violent rupture
of the container. It is also critical that the pressure relief does not allow significant liquid release. At this point
in time (2011), only metal portable tanks (now included in the general container category of IBCs) are
specifically listed or FM Approved to vent under fire exposure. The determination for all other container types
is qualitative.
1. Some examples of relieving-style containers are:
• A metal 55 gal (230 L) drum fitted with plastic plugs in both the 2 in. (51 mm) and 3/4 in. (1.9 cm)
openings in the top of the drum. Testing by FM Global and others using nylon and polyethylene fusible
closures has shown that the fusible closure will fail when exposed to a fire and prevent a significant
pressure buildup in the drum as well as maintain the overall drum integrity. Full-scale fire tests on
metal drums filled with heptane and fitted with plastic fusible closures has shown that the relieving
action will allow for greater palletized storage heights.
• A metal 5 gal (25 L) tight head pail (i.e., top and bottom are permanently attached to sides) with
plastic pour spout. Most tight head 5 gal (25 L) containers are relieving-style. Testing has shown
that the plastic pour spout will melt and allow the container to vent and prevent the full release of
the stored liquid.
• A metal 5 gal (25 L) lug head pail (i.e., top is held in place by friction and lug tabs on cover, similar
to a large paint can) with plastic pour spout. Same performance as the tight head container.
• A metal 1 gal (4 L) F-style (rectangular) can with either a plastic spout or a soldered metal spout.
Both spout arrangements will fail in a fire and allow internal pressure to vent while preventing the
release of the liquid.
• A metal 1 gal (4 L) friction lid can (e.g., circular paint cans). The friction lid will pop off when exposed
to fire. In many cases, the lid will only move slightly, allowing pressure relief without significant liquid
release. In some cases the lids move away from the container, allowing liquid to spray out during
the release and sprinkler water to enter the can and displace the stored liquid. The small can size
minimizes this negative performance.
• Metal IBCs that meet DOT/UN rules.
2. Some examples of non-relieving-style containers or containers that are not acceptable as relieving-style
are:
• A metal 55 gal (230 L) drum fitted with metal plugs in both the 2 in. (51 mm) and 3/4 in. (1.9 cm)
openings in the top of the drum. This container will not release internal pressure early in a fire. The
end result of a sealed drum exposed to fire is the violent failure of the container.
• A metal 55 gal (230 L) drum fitted with a plastic plug in an opening located in the side of the drum
or a plastic container of any size. Both container types will vent any pressure buildup; however, they
will also release the stored liquid.
• A metal 5 gal (25 L) tight head pail (i.e., top and bottom are permanently attached to sides) with
metal caps over opening. This container will not vent pressure buildup early in a fire.
• A metal 5 gal (25 L) lug head pail (i.e., top is held in place by friction and lug tabs on cover, similar
to a large paint can) with metal caps over the opening. The top of this type of container will vent
pressure buildup similar to the 1 gal (4 L) paint can. However, the lid tends to release at a higher
pressure and the venting of the lid results in a large quantity of liquid release. Also, once open,
sprinkler water will enter the container and displace the stored liquid. The quick response sprinkler-
based fire protection scheme for metal containers could fail to control the fire if several 5 gal (25 L)
containers release their contents.
• A metal 1 gal (4 L) F-style (rectangular) can with crimped-on metal spout. These containers have
failed violently during full-scale fire tests.
Semi-solid: A material that has a defined shape at room temperature without containment, but can be forced
to flow with pressure. (e.g., butter, paste ink, gels).
Solid: A material that has a defined shape at room temperature and cannot be forced to flow with pressure.
(e.g., wood, plastic, glass, wax). Materials with a melting point above 150°F [66°C], can be treated as a solid.
Specific gravity: The ratio of the weight of a substance to the weight of the same volume of another
substance. The specific gravity for ignitable liquids is provided using water as a basis. Specific gravities less
than 1 indicate the liquid is lighter than, and will float on top of, water. Conversely, specific gravities greater
than 1 indicate the liquid will sink in water. This information permits a determination of what effect water will
have on an ignitable liquid fire. Liquids heavier than water will sink, indicating water would extinguish a fire
involving this liquid (cover liquid and smother fire). Liquids lighter than water will float, indicating the fire would
not be extinguished but could be spread by water if adequate drainage is not provided.
Stable liquid: A liquid that does not self-react or polymerize.
Storage lockers for ignitable liquids: A storage unit for various size ignitable liquid containers that does
not allow personnel to enter the structure. These lockers are FM Approved for outdoor use only.
Storage Cabinet for ignitable liquids: These cabinets are for the storage of ignitable liquids in containers
not exceeding 55 gal (210 L) capacity. Total cabinet capacity is limited to 120 gal (455 L). Maximum storage
of liquids in drums is limited to vertical orientation of drums to preclude self-dispensing. FM Approved cabinets
are equipped with a 2 in. (51 mm) deep, leak-tight, sump or pan. Each cabinet has also passed a 10-minute
exposure fire test according to a time-temperature relationship described in ASTM E152 in which internal
temperature (at top center) cannot exceed 325°F (163°C). Additional details are provided in the Approval
Guide.
Uncartoned storage: Containers of liquid that are arranged on pallets without cardboard boxes are
considered uncartoned storage for the purposes of this data sheet. This type of storage usually consists of
containers arranged on trays or sheets layered on a pallet and held in place with shrink-wrapping. Uncartoned
storage also applies to any storage that does not meet the definition of cartoned storage.
Unstable liquid: A liquid that, in its pure state or as commercially produced or transported, will vigorously
polymerize, decompose, undergo condensation reaction, or become self-reactive under condition of shock,
pressure, or temperature.
Vapor density: The weight of a volume of pure vapor or gas (with no air present) compared to the weight
of an equal volume of dry air at the same temperature and pressure. It is calculated as the ratio of the
molecular weight of the gas to the average molecular weight of air, 29. A vapor density figure less than 1
indicates the vapor is lighter than air. A figure greater than 1 indicates the vapor is heavier than air. Ignitable
liquids produce vapor that is heavier than air. The vapor will collect at floor level and exhibit fluid properties
(i.e., it will flow to low points and accumulate). Flammable vapor, if not removed by ventilation, can flow to
an ignition source and flash back to the vapor source.
J. Added vertical barriers as an alternative option to extending protection for Fire Protection Scheme A
and Fire Protection Scheme F.
K. Completed various grammar and editorial revisions to clarify/correct the existing text.
January 2021. This interim update added guidance for FM Approved composite IBCs.
October 2020. This document has been completely revised. Major changes include the following:
A. Revised the definition of “ignitable liquid” to be consistent with Data Sheet 7-32, Ignitable Liquid
Operations.
B. Provided a definition for very high flash point liquids (in the atypical liquids section) to replace the
previous guidance for liquids with a flash point at or above 450°F (232°C). As part of this change, the flash
point threshold has been lowered to 414°F (212°C).
C. Added guidance for the storage and protection of FM Approved composite intermediate bulk containers.
D. Revised figure (Fig. 2.2.1.1) and table (Table 2.2.1.1) for location and construction of ignitable liquid
storage areas.
E. Clarified the intent of drainage and containment (Section 2.2.2 and Tables 2.2.2.1.A and 2.2.2.1.B).
F. Clarified guidance for FM Approved prefabricated ignitable liquids storage buildings (PILSBs) and
storage lockers (Section 2.2.3).
G. Revised ventilation recommendations. Ventilation is now only required for storage occupancies
containing liquids with a boiling point below 100°F (38°C), storage occupancies with poorly maintained
and leaking containers, and storage occupancies with dispensing operations (Section 2.3.2).
H. Added guidance on flue spaces (Section 2.3.3) that is aligned with Data Sheet 8-9.
I. Added a new section to consolidate guidance on in-rack sprinklers (Section 2.4.1.5).
J. Added protection guidance for rack storage of metal drums where the roof height exceeds 30 ft (9.1
m) (Sections 2.4.3.1.1 and 2.4.4.1.1).
K. Revised the options for rack storage protection for any flash point, uncartoned, small metal containers
(6.5 gal [25 L] or less) based on fire testing (Table 2.4.4.1.A). Face sprinklers are now recommended
for double-row and multiple-row rack storage.
L. Added guidance for shelf storage of ignitable liquids in plastic or glass containers (Section 2.4.5.2).
M. Added protection for propylene glycol and ethylene glycol in composite IBCs (Table 2.4.6.1) and plastic
drums (Table 2.4.7.3.2).
N. Added protection criteria for rack and palletized storage of distilled spirits in wooden barrels (Sections
2.4.8 and 2.4.9).
O. Revised electrical equipment ratings (Table 2.8.1).
P. Clarified guidance on when balancing is recommended with Scheme A (Section D.2.2.1).
Q. Added more figures for protection options (e.g., for single-row racks) and revised other figures to provide
consistency.
R. Renumbered tables and figures based on section numbers.
April 2020. Interim revision. Minor editorial changes were made.
January 2018. Interim revision. Lowered the flash point threshold of very high flaspoint liquids from 500°F
(260°C) to 450°F (232°C).
July 2014. Interim revision. The following changes were made:
A. Added new protection options for palletized storage of Group 3 water-miscible liquid in 59 oz (1.75 L)
glass or plastic bottles for the following storage and roof height combinations:
• 17 ft (5.2 m) (max) of storage in a 30 ft (9 m) building
• 17 ft (5.2 m) (max) of storage in a 40 ft (12 m) building
6. Revised in-rack sprinkler design criteria to be based on a flow instead of a pressure. Also included
the use of larger orifice sprinklers, which will allow for lower in-rack sprinkler discharge pressures. A
minimum discharge pressure of 10 psi (0.7 bar) has been defined.
7. Provided protection criteria for high flash point (≥ 200°F [93°C] ) liquids and alcohols in composite IBCs
in racks.
8. Changed all ceiling sprinkler recommendations to provide a K11.2 (K160) or larger sprinkler in
accordance with the requirements of NFPA 13, Standard for the Installation of Sprinkler Systems.
9. Added an option for protecting multiple-row rack storage of steel drums.
10. Revised protection criteria in Table 4 (previously Table 6) for two-high palletized metal IBCs containing
liquids with a flash point at or above 200°F (93°C).
11. Based on the results of full-scale fire tests, eliminated standard response protection criteria for
palletized storage of uncartoned small metal containers (6.5 gal [25 L] or less) regardless of liquid type.
12. Added a new Table 5 for rack storage of metal IBCs.
13. Provided a protection option for small metal containers (6.5 gal [25 L] or less) using Scheme A.
14. Provided protection for rack storage of low flash point liquids in up to 1 gal (4 L) plastic containers.
15. Added protection criteria for liquids with a flash point below 200°F (93°C) in 0.5 oz (15 ml) and 2 oz
(60 ml) plastic containers.
16. Added protection criteria for Group 1 water-miscible liquids in 6 oz (180 ml), 6.5 gal (25 L), and 60
gal (230 L) plastic containers.
17. Revised protection for palletized liquids with a flash point above 450°F (232°C) in Table 17 to better
reflect full-scale fire testing:
a) Increased standard response sprinkler protection for 15 ft (4.6 m) high storage in a 30 ft (9.1 m)
building for containers up to 6.5 gal (25 L).
b) Increased standard response protection for 5 ft (1.5 m) high storage in a 30 ft (9.1 m) building for
containers up to 6.5 gal (25 L).
c) Added protection for 20 ft (6 m) high storage in a 30 ft (9.1 m) building for 1 gal (4 L) containers.
d) Added protection for 15 ft (4.6 m) high storage in a 30 ft (9.1 m) building for 48 oz (1.4 L) containers.
18. Added new protection for rack storage of cartoned cooking oils in 35 ft (11 m) high racks in a 40 ft
(12 m) building.
19. Revised protection for palletized water-miscible liquids in Table 18:
a) Glass and plastic bottles are differentiated due to the very poor performance of glass.
b) Group 3 in glass bottles has been severely limited due to a lack of successful testing.
c) Group 4 protection has been modified. One option was removed (specific application sprinkler
protection), and the protection for standard response sprinklers was increased and the sprinkler
temperature was changed to ordinary.
20. Revised in-rack protection requirements for steel drum storage of liquids with a flash point greater
than or equal to 200°F (93°C) to align with in-rack arrangements for lower flash point liquid storage.
21. Reduced the hose stream requirement to 250 gpm (950 L/min) for certain cases with Scheme A
protection criteria.
September 2004. Metric values in figures for fire protection Scheme A were corrected.
May 2004. Eliminated the exclusion for plastic or glass bottles that are 2 oz (60 ml) or less in size. Recent
full-scale fire tests have demonstrated that even small plastic or glass bottles that are filled with an ignitable
liquid can produce a severe fire hazard. New protection criteria has been added in Table 16a.
September 2003. The following changes have been made for this revision:
1. Provided information on the FM Approved fusible plugs for relieving-style drums.
2. Revised the title of Table 8 to eliminate the lower container size limit of 6.5 gal (25 L). The protection
criteria in this table can be applied to smaller containers.
3. Revised protection criteria in Table 10 for rack storage of small metal containers. Provided criteria for
high temperature ceiling sprinklers.
September 2002. Fire protection tables have been revised to be consistent with the new sprinkler approval
categories.
May 2000. This document has been reorganized to provide a consistent format. In addition to the reformatting
the following technical changes have been made:
1. New fire protection for products with less than or equal to 50% water-miscible liquid have been added.
All of the water-miscible liquid fire protection criteria for rack storage have been incorporated into two
new tables.
2. Space separation distances between low value unprotected ignitable liquid buildings and main buildings
has been clarified.
3. ELO sprinklers have been expanded to include all control mode, area density spray sprinklers with a
K-factor greater than or equal to K11.2 (K160).
4. Clarified use of ignitable liquid storage cabinets in warehouse areas.
September 1999. Minor Technical Revisions
May 1999. The document represents a complete rewrite of this data sheet. All previous recommendations
were re-evaluated. Significant changes in the fire protection recommendations have been incorporated. The
recommended criteria better reflect recent test results and have eliminated a number of inconsistencies in
the old criteria. Fire protection design drawings have been provided to help clarify recommendations. The
majority of the fire protection criteria is provided in tabular format.
= Rack Structure
= Rack Structure
= Rack Structure
5 ft. (1.5 m)
Fig. D.2.1.7. Multiple-row rack sprinkler layout: drum protection scheme (elevation view)
Fig. D.2.1.8. Multiple-row rack sprinkler layout: drum protection scheme (plan view)
LQ PP
Minimum
LQ PP
Minimum
LQ PP
Minimum
LQ PP
Minimum
LQ PP
Minimum
5 ft. (1.5 m)
Fig. D.2.1.18. Double-row rack sprinkler layout: small metal containers (with face sprinklers)
Fig. D.2.1.19. Double-row rack sprinkler layout: small metal containers (no face sprinklers)
Fig. D.2.1.20. Multiple-row rack sprinkler layout: small metal containers (elevation view)
Fig. D.2.1.21. Multiple-row rack sprinkler layout: small metal containers (plan view)
5 ft. (1.5 m)
Fig. D.2.1.22. Single-row rack sprinkler layout: water-miscible liquids in small metal containers
Fig. D.2.1.23. Double-row rack sprinkler layout: water-miscible liquids in small metal containers
Fig. D.2.1.24. Multiple-row rack sprinkler layout: water-miscible liquids in small metal containers
(elevation view)
Fig. D.2.1.25. Multiple-row rack sprinkler layout: water-miscible liquids in small metal containers (plan view)
5 ft. (1.5 m)
Fig. D.2.1.26. Single-row rack sprinkler layout: quick response sprinklers protection scheme
Fig. D.2.1.27. Double-row rack sprinkler layout: quick response sprinklers protection scheme
5 ft. (1.5 m)
Fig. D.2.1.28. Single-row rack sprinkler layout: quick response sprinklers protection scheme
Fig. D.2.1.29. Double-row rack sprinkler layout: quick response sprinklers protection scheme
5 ft. (1.5 m)
Fig. D.2.1.30. Single-row rack sprinkler layout: quick response sprinklers protection scheme
Fig. D.2.1.31. Double-row rack sprinkler layout: quick response sprinklers protection scheme
5 ft. (1.5 m)
Fig. D.2.1.32. Single-row rack sprinkler layout: quick response sprinklers protection scheme
Fig. D.2.1.33. Double-row rack sprinkler layout: quick response sprinklers protection scheme
Fig. D.2.1.34. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (plan view)
Fig. D.2.1.35. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (elevation view)
Fig. D.2.1.36. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (plan view)
Fig. D.2.1.37. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (elevation view)
Fig. D.2.1.38. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (plan view)
Fig. D.2.1.39. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (elevation view)
Fig. D.2.1.40. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (plan view)
Fig. D.2.1.41. Multiple-row rack sprinkler layout: quick response sprinklers protection scheme (elevation view)
8 in. (200mm)
Fig. D.2.1.48. In-rack sprinkler layout for distilled spirits in wooden barrels (plan view)
LQ PP
Fig. D.2.1.49. In-rack sprinkler layout for distilled spirits in wooden barrels (elevation view)
Table D.2.2.1.3. Liquid-Container Combinations for Use With Scheme A Without Balancing the Ceiling and In-rack Designs
Flash Point/ Liquid Type Container Size Container Type
Any ≤6.5 gal (25 L) Metal
<200°F (93°C) ≤2 oz (60 ml) Plastic/glass
Very high flash point ≤60 gal (230 L) Plastic
≥200°F (93°C) ≤6.5 gal (25 L) Plastic/glass
Groups 1 and 2 water miscible ≤1 gal (3.8 L) Plastic/glass
Groups 3 and 4 water miscible ≤6.5 gal (25 L) Plastic/glass
D.2.2.1.4 For the liquid-container combinations provided in Table D.2.2.1.4 provide the following:
D.2.2.1.4.1 If all racks in the cutoff room are not protected with the same level of protection, extend the
horizontal barrier and in-rack sprinkler protection at least two rack bays, approximately 16 ft (4.9 m) beyond
the liquid storage and to racks on each side of the storage.
D.2.2.1.4.2 Balance the ceiling sprinkler demand provided in the appropriate protection table and the in-rack
sprinkler demand at the point of connection.
D.2.2.1.4.3 Provide a 500 gpm (1900 L/min) hose stream allowance.
D.2.2.1.4.4 Provide the fire protection water demand for a 1-hour duration.
D.2.2.1.4.5 Design ceiling sprinklers in accordance with the appropriate protection table.
Table D.2.2.1.4. Liquid-Container Combinations for Use With Scheme A Where Balancing the Ceiling and In-rack Designs
is Needed
Flash Point/ Liquid Type Container Size Container Type
Group 1 & 2 water miscible >1 gal (4 L) Plastic/glass
2 - 5 ft.
(0.6 - 1.5 m)
2 - 5 ft.
(0.6 - 1.5 m)
4 - 10 ft.
(1.2 - 3 m)
2 - 5 ft.
(0.6 - 1.5 m)
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
4 - 10 ft.
(1.2 - 3 m)
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
D.2.2.4.4.1 Design the in-rack sprinklers to provide a minimum flow of 45 gpm (170 L/min) out of the
hydraulically most remote.
A. Eight (8) sprinklers (e.g., four face sprinklers and four flue sprinklers in a DRR) if one horizontal barrier
level is provided.
B. Five (5) sprinklers per tier and up to twenty (20) if two or more horizontal barrier levels are provided.
D.2.2.4.4.2 Protect all racks in the cutoff room with the same level of protection.
D.2.2.4.4.3 Arrange the room to ensure there will not be any on-floor storage.
D.2.2.4.4.4 Balance the ceiling sprinkler demand and the in-rack sprinkler demand at the point of connection.
D.2.2.4.4.5 Provide a 500 gpm (1900 L/min) hose stream allowance.
D.2.2.4.4.6 Provide the fire protection water demand for a 1-hour duration.
D.2.2.4.5 For liquids with a flash point below 200°F (93°C) in plastic containers of 1 gal (4 L) or less, provide
the following:
This protection approach has only been tested for rack storage. It is unknown if palletized storage can be
protected with a ceiling-based foam-water sprinkler system. Since pallet loads are transported into and out
of racks and a fire involving even a single pallet load could damage the building, this approach should only
be used in well-cutoff rooms.
D.2.2.4.5.1 Design the in-rack sprinklers to provide a minimum flow of 60 gpm (227 L/min) out of the
hydraulically most remote.
A. Six (6) sprinklers (e.g., three face sprinklers and three flue sprinklers in a DRR) if one horizontal barrier
level is provided.
B. Eight (8) sprinklers (e.g., two face sprinklers and two flue sprinklers on two levels in a DRR) if two or
more horizontal barrier levels are provided.
D.2.2.4.5.2 Protect all racks in the cutoff room with the same level of protection.
D.2.2.4.5.3 Arrange the room to ensure there will not be any on-floor storage.
D.2.2.4.5.4 Storage is permitted above the fourth rack tier but is limited to products that can be protected
by Scheme A.
D.2.2.4.5.4.1 Protection above the first tier can either continue with Scheme D for the full height of the rack
or use Scheme A for the full height of the rack.
D.2.2.4.5.5 Balance the ceiling sprinkler demand and the in-rack sprinkler demand at the point of connection.
D.2.2.4.5.6 Provide a 500 gpm (1900 L/min) hose stream allowance.
D.2.2.4.5.7 Provide the fire protection water demand for a 1-hour duration.
D.2.2.4.5.8 Provide an FM Approved foam-water sprinkler system for the ceiling and in-rack protection.
2 - 5 ft.
(0.6 - 1.5 m)
2 - 5 ft.
(0.6 - 1.5 m)
4 - 10 ft.
(1.2 - 3m)
2 - 5 ft.
(0.6 - 1.5m)
2 - 5 ft.
5 ft. (1.5 m)
(0.6 - 1.5 m)
LQ PP
2 - 5 ft.
(0.6 - 1.5 m)
LQ PP
2. Protect racks across the aisle by providing a line of face sprinklers at 4 to 5 ft (1.2 to 1.5 m) on-line
spacing at the 10 ft (3 m) elevation. Design the face sprinklers for six (6) sprinklers operating, each
discharging 30 gpm (114 L/min.). Balance this demand with the Scheme F protection.
Solid Barrier
2 - 5 ft.
(0.6 - 1.5 m)
3 in (76 mm)
Gap at Uprights
Fig. D.2.2.6.1a. Single row rack sprinkler layout: fire protection scheme F
Solid Barrier
2 - 5 ft.
(0.6 - 1.5 m)
3 in (76 mm)
Gap at Uprights
Fig. D.2.2.6.1b. Single row rack sprinkler alternate layout: fire protection scheme F
Solid Barrier
4 - 10 ft.
(1.2 - 3 m)
9 ft. (2.7 m)
2 - 5 ft.
(0.6 - 1.5 m)
3 in (76 mm)
Gap at Uprights
A. Provide fireproofing rated for one hour or the expected fire duration, whichever is greater. Provide
fireproofing that is rated for a hydrocarbon fire exposure. (See Data Sheet 1-21)
B. Provide automatic (fusible link) sidewall sprinklers or water spray protection for the full height of the
column, as shown in Figure E.1.B and described below:
i. Stagger the nozzles on opposite sides of a wide-flange column on 20 ft (6.1 m) centers.
ii. Wet the reentrant space (web and flanges)(shown by black outline in Figure E.1) to cool the column
effectively.
iii. Provide a minimum 0.3 gpm/ft2 (12 mm/min) over the wetted area of the column (″wetted area″ is
the surface area on the three sides of the reentrant space formed by the column web and flanges).
The wetted area protected by a sprinkler extends from the sprinkler down to the next sprinkler on the
same side of the column.
iv. Where obstructions to run down are present, provide additional sprinklers below the obstructions.