DWC7894 11 08 - 00
DWC7894 11 08 - 00
DWC7894 11 08 - 00
SCHEDULE:
CLAMPS
1 TC1 CLAMP, T/COMP 23,5 mm - 26,5 mm 0DEG 23,5 mm - 26,5 mm D-DT-6010 SHT 1 REV 7
8 SPC2 CLAMP, B/COMP 26,5 mm PALM 45DEG 26,5 mm D-DT-6018 SHT 2 REV 4
12 ACC4 COVER, ACRYLIC 480 x 160 mm ACC4 480 mm x 160 mm D-DT-6055 SHT 1 REV 2
C C
13 YC6 CLAMP, Y/COMP 2 x 38,3 mm - 38 mm 90DEG 38,3 mm - 38 mm D-DT-6013 SHT 3 REV 6
3
17 TBSC80-127 CLAMP, BUS COUPLER TBSC80-127 80 mm D-DT-6086 SHT 1 REV 5
10 10 10
5 12
D 6 11
13 19 ----- CLAMP, CABLE DBL 50-75 mm { P/PROP BLK 50 mm - 75 mm { D-DT-8019 SHT 3 REV 4 D
7
14 20 ----- CLAMP, CABLE 50-75 mm { POLYPROP BLK 50 mm - 75 mm { D-DT-8019 SHT 2 REV 4
5 5 5 8 5 5
6
21 CRS S2 SPACER COND 38,3 mm - 150 mm CRS S2 38,3 mm - 150 mm D-DT-6087 SHT 1 REV 5
8 21
2 15 16 17 22
P2 P1 P1 P2 22 TBEC/P-80 END CAP TBEC 80 PLAIN NO F/CLAMP 80 mm D-DT-6040 SHT 1 REV 4
24 23 TBEC/C-120 END CAP TBEC 120 COND WITH F/CLAMP 120 mm D-DT-6040 SHT 2 REV 4
18 18
4 4 4 9 24 EPC38 CLAMP, PEG AL CENT 38,3 mm 38,3 mm D-DT-6115 SHT 1 REV 1
F F
31 SPC4 CLAMP, B/COMP 38,3 mm PALM 0DEG 38,3 mm D-DT-6018 SHT 1 REV 4
132 kV 6 m TERMINAL SUPPORT
32 SPC5 CLAMP, B/COMP 38,3 mm PALM 45DEG 38,3 mm D-DT-6018 SHT 2 REV 4
132/11 kV TRANSFORMER
33 TBEC/P-120 END CAP TBEC 120 PLAIN NO F/CLAMP 120 mm D-DT-6040 SHT 1 REV 4
NOTES:
G G
2 500 4 500 3 500 3 500 2 500 3 000 2 500 3 500 3 500 4 500 6 550
1. EQUIPMENT NOT FITTED WITH 26 mm{ or 38 mm{ CONNECTION PRONGS MUST BE FITTED WITH
TINNED 26 mm{ OR 38 mm{ BRASS PRONGS DRILLED AND TAPPED TO APPROPRIATE SIZES.
2. ALL SURFACE AREAS OF CONDUCTOR OR CONTACT AREA OF CONNECTION CLAMPS MUST BE TREATED AS
DESCRIBED PRIOR TO MAKING A CLAMPED OR CRIMPED CONNECTION.
132 kV BUSBARS 1A AND 1B WITH BUS SECTION a) APPLY THIN LAYER OF NON OXIDE GREASE TO SURFACE AREA.
b) BRUSH NON OXIDE GREASED AREA THOROUGHLY WITH A CLEAN WIRE BRUSH.
c) WIPE SURFACE AREA CLEAN WITH RAG AND IMMEDIATELY APPLY A FRESH LAYER
OF NON OXIDE GREASE TO CLEAN SURFACE AREA.
H CENTIPEDE CONDUCTOR CENTIPEDE CONDUCTOR
H
d) FIT CLAMP TO CONNECTOR PRONG OR CONDUCTOR AND TORQUE TO:
BUS SECTION - BULL CONDUCTOR d.1) 8 mm GALVANIZED STEEL BOLTS - 15 Nm.
d.2) 10 mm GALVANIZED STEEL BOLTS - 26 Nm.
d.3) 12 mm GALVANIZED STEEL BOLTS - 45 Nm.
26 10 10 10 25 25 10 10 10 26
33 d.4) 8 mm S/STEEL BOLTS - 20 Nm.
33
27 27 d.5) 10 mm S/STEEL BOLTS - 35 Nm.
30 30
28 31 28
d.6) 12 mm S/STEEL BOLTS - 60 Nm.
d.7) 8 mm ALUMINIUM BOLTS - 10 Nm.
/ /
132 kV BUSBAR ISOLATOR
132 kV ISOLATOR
L L
CARBON SUBSTATION
AUTH:
132/11 kV
5 000 5 000 3 000 3 000 3 000 2 500 2 500 3 000 3 000 3 000 5 000 5 000
DATE: / /
CHKD:
SECTIONS AND CLAMPS LAYOUT
M
M
DATE: / / SET SHEET REVISION
SCALE 1 : 100
DRAWN: C. HAGAN
THIS DRAWING IS THE
PROPERTY OF ESKOM DATE: 15/11/2010
D-WC-7894 11 8 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A1L