CHP 2 Fault Calculation
CHP 2 Fault Calculation
per unit
Ω
Prepared by: Ismael K. Saeed
Therefore the impedance of the transmission line is
per unit
The impedance diagram for the circuit is shown in Figure in which the switch S
indicates the fault.
The motor draws a load current at rated voltage and rated MVA with 0.9 lagging
power factor. Therefore
Then the subtransient voltages of the motor and the generator are
per unit
per unit
per unit
Therefore while the load current was 1603.8 A, the fault current is 7124.7 A.
Solution: Base kV 11
Base MVA 25
X'pu 0.16
pu fault MVA from one alternator =1/X'pu
pu fault MVA from one alternator 6.25pu(MVA)
Fault MVA 156.25
156.25MVA
number of
alternators 4
Total fault MVA 625MVA
j1 p.u
pu equivalent circuit
Reduce the circuit by combining two parallel branches and converting delta into star
as follows:
c0 c1
c a1 a1
a2
c2 b1
a0
Zero Seq.components
c1 a
a0 b0
b c0
Negative Seq.components
b0 b2
c2
b2
b1 a2
2- L-to-L Fault −𝑗 3 𝐸
𝐼𝑓 =
𝑍1 + 𝑍2 + 𝑍𝑓
3- L-to-G Fault 3𝐸
𝐼𝑓 =
𝑍1 + 𝑍2 + 𝑍𝑜`
4- L-to-L-to-G Fault 3𝐸 𝑍2
𝐼𝑓 = − ∗
𝑍1 + (𝑍2 //𝑍𝑜` ) 𝑍2 + 𝑍𝑜`
𝒘𝒉𝒆𝒓𝒆 𝒁`𝒐 = 𝒁𝟎 Prepared
+ 𝟑 by: 𝒁𝒏Ismael
+K.𝟑Saeed
𝒁𝒇
Solution
The Positive sequence network is drawn similar to the single line diagram with the
generator and the synchronous motor being replaced by their internal emf and
impedance.