Alstom P642: 1.system Config
Alstom P642: 1.system Config
Alstom P642: 1.system Config
Device Info
Name/Description: MiCOM P643 Manufacture: ALSTOM
Device Type: Transformer differential protection Serial/Model:
Device Address:
Substation Name:
Substation Address:
1.System Config
Test Parameter
Output Type: Power Amp Binary Type: Relay Contact
Current: 6*35A Voltage: 4*310V
2.StateSequencer
Test Parameter
State1 (1/1)
V A-N 0.000V;
0.000°;
50.000Hz;
V B-N 0.000V;
240.000°;
50.000Hz;
V C-N 0.000V;
120.000°;
50.000Hz;
V X-N 0.000V;
0.000°;
50.000Hz;
IA 0.710A;
0.000°;
50.000Hz;
IB 0.710A;
240.000°;
50.000Hz;
IC 0.710A;
120.000°;
50.000Hz;
(2)I A 0.000A;
0.000°;
50.000Hz;
(2)I B 0.000A;
240.000°;
50.000Hz;
(2)I C 0.000A;
120.000°;
50.000Hz;
Trigger Time;
1.050s;
Bi-input
Bi-output
Test Result
Repeat0
B.In 1 B.In 2 B.In 3 B.In 4 B.In 5 B.In 6 B.In 7 B.In 8
State1 NoTrip NoTrip NoTrip NoTrip NoTrip NoTrip NoTrip NoTrip