CSC-211 Multifunction Protection IED Product Guide
CSC-211 Multifunction Protection IED Product Guide
CSC-211 Multifunction Protection IED Product Guide
Product guide
CSC-211 Multifunction Protection IED
Version:V1.01
Issued Date:2019.01
Note: the company keeps the right to perfect the instruction. If equipment does not agree
with the instruction at anywhere, please contact our company in time. We will provide you
with corresponding service.
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different commercial
proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is
not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify
us as soon as possible.
The data contained in this manual is intended solely for the product description and is not to be deemed to
be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure
that our products are developed to the latest technological standards as a result; it is possible that there
may be some differences between the hardware/software product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Email: [email protected]
Website: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
2 / 40
CSC-211 Multifunction Protection IED
CSC-211 is selective, reliable and high speed protection IED with rich functions to cover following
applications:
Protection, bay control unit, MU(Merging Unit), and SCU(Smart control Unit) in one IED;
Robust hardware with excellent EMC performance and IP54 protection under -40℃ to 70℃
operating temperature;
3 / 40
Application
46NU
50 3I >>> MEASUREMENT
PIOC 46NI
50BF 3I>BF
RBRF 51Ns/67Ns 3INE>
CONTROL
49 Ith
PTTR 32
ENERGY METER
37 CALCULATED
55
46
Disturbance
64 UE> recording
STATION
COMMUNICATION
- RS232/485
79 O→I 25
- RJ45/FO
RREC RSYN - IEC61850
- IEC60870-5-103
4 / 40
Function
Function ANSI Code Qty. Description
Directional overcurrent protection 50,51,67 1 4 stages; Directional/unidirectional; Definite time/inverse
time characteristic; 5 IEC curves, 7 ANSI curves and 1
user defined inverse time curve; Inrush block;
Directional earth fault protection 50N, 51N, 1 4 stages; Directional/Unidirectional; Definite time /
67N Inverse time characteristic; 5 IEC curves, 7 ANSI curves
and 1 user defined inverse time curve; 3 phase current
inputs/Single current input;
Sensitive directional earth fault 50Ns, 51Ns, 1 4 stages; Directional/Unidirectional; Definite time /
protection 67Ns Inverse time characteristic; 5 IEC curves, 7 ANSI curves
and 1 user defined inverse time curve; 3 phase current
inputs/Single current input;
Negative sequence overcurrent 46 1 4 stages; Definite time/Inverse time characteristic; 5 IEC
curves, 7 ANSI curves and 1 user defined inverse time
curve;
Switch onto fault protection 50SOTF 1 1 stage
Zero sequence overvoltage 59N 1 4 stages; Definite time / Inverse time characteristic;
Negative sequence overvoltage 59NS 1 4 stages; Definite time / Inverse time characteristic;
5 / 40
Function
Auto-reclosing 79 2 4 shots;
Fault locator 1
Lockout 86
Programmable logic
Note 1: the number in “Qty.” column is the maximum quantity of function module is able to
offer.
6 / 40
Function
Characteristic of overcurrent directional element
Forward 90° IA
ΦPh_Char
0°
U BC_Ref
IA Reverse
stage relevantly;
Characteristic of zero sequence directional
Inrush restraint set for each stage element.
7 / 40
Function
4 stages; Characteristic of the sensitive earth fault directional
element by U0/I0-Φ
Definite time/invers time characteristic set
for each stage;. Sensitive earth fault directional element with
Cos Φ principle
11 kinds of IEC and ANSI inverse time
characteristic curves as well as optional 90°
IS
user defined characteristic
90° - I NS
Forward
Bisector
- IS
ΦNS_Char 0°
Characteristic of the sensitive earth fault directional
3U0_Ref element by Cos Φ
8 / 40
Function
59 Overvoltage protection
4 stages Phase-earth voltage or phase-phase
voltage inputs
definite time/inverse time characteristic
selectable for each stage;
27 Undervoltage protection
4 stages voltage inputs
9 / 40
Function
Transfer trip command to the remote line Settable CB Aux contacts checking
end in second stage
Current criteria checking (including phase
Internal/ external initiation current, zero and negative sequence
current)
Single/three phase CBF initiation
Legend:
Opened CB IFAULT
Closed CB
Trip
Bus Line1 Line2 LineN
Legend:
IFAULT Trip
Relay Opened CB
Closed CB
10 / 40
Function
The STUB protection is enabled when the
open position of the disconnector;
Legend:
Closed CB
IFAULT IFAULT
Line Line
A B
79 Auto-reclosing
11 / 40
Function
Up to 2 AR modules to support 2 CBs in Internal/external AR initiation
one IED
Single/three phase AR operation
4 shots automatic reclosing (selectable)
CB ready supervision
Individually settable dead time for three
CB Aux. contact supervision
phase and single phase fault and for each
shot Cooperation with internal synch-check
function for reclosing command
37 Undercurrent protection
To avoid capacitor bank charging the bus 3 phase current inputs;
when bus voltage falling down.
1 stages;
12 / 40
Function
4 stages CB position checking
GOOSE message-Block
outgoing feeders in accordance with
IEC61850;
B
Trip
Relay C
13 / 40
Function
Operating principle when fault on the Busbar
A
Relay A
Trip
Relay B
Relay C
14 / 40
Automation
Support SV, GOOSE service of process DNP 3.0;
layer application in accordance with
MODBUS
IEC61850-8-1, -9-2, -9-2LE,
Support several time synchronizing way,
Support MMS, GOOSE service of station
include:
layer and bay layer application in
accordance with IEC61850-8-1, IRIG-B electrical/optical;
HMI
Switch
Protection
IED
Switch Switch
Indoor
Outdoor
SCU AMU+SCU AMU+SCU
Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP; Station layer: MMS/GOOSE; PRP;
Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP; Bay layer: GOOSE; PRP;
Process layer: Process bus, GOOSE; PRP; Process layer: SV/GOOSE; PRP; Process layer: Process bus, SV/GOOSE; PRP;
15 / 40
Tools
AESP tools is the user-friendly software tool bar, and protection characteristic diagram
sets. AESP covers all works for the whole life graphically and precise data in pointed
cycle of protection IEDs, include, instant.
Setting and parameter
Disturbance analysis by Fisewave
Monitoring
Logic programming by Nuclide
IED configuration by IO master;
Single line diagram painter;
IEC 61850 system engineering manager
Its features are as follows:
Fault analysis with fault records in curves, Password-protected access for different
circle diagrams, vector diagrams, harmonic operation and different roles;
16 / 40
Hardware
Up to 12 AC Current Inputs and 6 Voltage Up to 3 RJ45 Ethernet ports );
Inputs; Up to 2 RS485 ports;
Up to 42 Binary Inputs, include independent 1 IRIG-B / Pulse time synchronization port;
BIs; 1 RJ45 front test port
Up to40 Output relays, with 4 switchable 22 programmable LED
NO/NC contacts; Up to 4 customer defined function key;
Up to 7 Ethernet optical ports, for SV, 4U 19” or 4U 1/2 19” case;
GOOSE, MMS and other automation
services;
Front view
Rear view
17 / 40
Hardware
D
A 177
B 259.2
A
C 232.7
D 226
C Unit mm
Dimension of case
18 / 40
Specification
IEC60255-27 110V
AC current measurement
DL/T478-2013
Item Data Thermal overload 180V, continuously;
Rated current Ir 1A and 5A capacity Vph-e 400V for 60s.
Operating range of (0 ~ 100) Ir IEC60255-27
protection CT DL/T478-2013
19 / 40
Specification
IEC60255-1 100V, 220V AC Static power consumption ≤ 18W
Maximum contact voltage 250V AC/DC IEC60255-1
IEC60255-1 Maximum load power ≤ 20W
Current carrying capacity General relay:
consumption
IEC60255-1 5A continuous,
IEC60255-1
10A, 1s on,15s off
30A, 200ms on,15s off
Power output relay:
Ethernet communication
10A continuous, Item Data
30A, 200ms on,15s off Max. ports number 3
Making capacity General relay: Electrical Ethernet port type RJ45
IEC60255-1 1100W(DC) at L/R>40ms Maximum transmission 100M
1000VA(AC) distance of Ethernet cable
Power output relay: Optical Ethernet port type LC
1250W (DC)
Fiber optic cable type Multi-mode
2000VA(AC)
Optic wavelength 1310 nm
Breaking capacity General relay:
Optic received sensitivity -34 dBm
IEC60255-1 0.2A, at Vr.aux=220V,
Emitter electric level >-11 dBm;
L/R≤40ms;
Maximum transmission 2kM
0.4A, at Vr.aux=110V,
distance of optical fiber
L/R≤40ms;
Transmission rate for 100Mbit/s
1000VA, at Vr.AC;
IEC61850
Power output relay:
Transmission rate for DNP 100Mbit/s
0.25A, at Vr.aux=220V,
3.0
L/R≤40ms;
0.45A, at Vr.aux=110V,
L/R≤40ms; Serial communication
1200VA, at Vr.AC;
Item Data
Pick up time General relay: Number 2
IEC60255-1 ≤5ms
Port type Extract twisted pair
Power output relay:
Maximum transmission 1.0km
≤5ms
distance
Drop off time ≤10ms
Voltage withstand test 500V earthing AC voltage
IEC60255-1
Transmission rate for Default setting 9600 bps;
IEC60870-5-103 Minimum: 1200bps;
Auxiliary power maximum: 19200bps
Item Data
Time synchronization
Rated voltage Vr.aux 100V to 250V DC/AC
IEC60255-1 24/48V DC Item Data
20 / 40
Specification
IRIG-B signal format IRIG-B000 IEC60255-5 Auxiliary power
IRIG-B Port type Twisted-pair connection or EN60255-5 supply port;
optical fibers ANSIC37.90 Enclosure port;
IRIG-B signal voltage level Differential signal input GB/T15145-2001 Input and output
DL/T478-2013 ports;
Inter-substation communication Functional earth
port;
Item Data 500V, 50Hz, at rated
Ports number 1~2 voltage ≤63V, Tested on:
Fiber optic cable type Single-mode Communication port;
Optic wavelength 1310 nm, when the Impulse voltage 5kV, at rated voltage>60V,
transmission distance <60 km IEC60255-5 Tested on:
1550 nm, when the IEC60255-27 Auxiliary power
transmission distance >60 km EN60255-5 supply port;
Optic received -34 dBm ANSIC37.90 Enclosure port;
sensitivity GB/T15145-2001 Input and output
Emitter electric level >-11 dBm, at length <40 kM DL/T478-2013 ports;
>-4 dBm, at length 40~60 kM Functional earth
>-5 dBm, at length 60~80 kM port;
>-3 dBm, at length 80~100 kM 1kV, at rated voltage≤60V,
>-0 dBm, at length 100~120 tested on:
kM Communication port;
Fiber optic connector LC Insulation resistance ≥100MΩ,500V,
type IEC60255-5
Data transmission rate 64 kbit/s, G703 IEC60255-27
2,048 kbit/s, G703-E1 EN60255-5
Max. transmission 120 kM ANSIC37.90
distance GB/T15145-2001
DL/T478-2013
EMC test
IEC60255-27
Insulation Basic insulation
IEC60255-27 Item Data
Power frequency high 2KV, 50Hz, at rated IEC61000-4-2 ±8kV air gap discharge;
voltage withstand test voltage > 63V, Tested on: Radiated, Criteria A;
21 / 40
Specification
radio-frequency Class IV; Communication ports;
electromagnetic field 10 V/m(r.m.s.), 80%,AM (1 Power frequency Class V
immunity test kHz) magnetic field immunity 30A / m Continuous;
IEC60255-26:2013 Frequency sweep: test 300A/m, from 1s to 3s; Test
IEC61000-4-3 80 MHz – 1 GHz; 1.4 GHz – 2.7 IEC60255-26:2013 on:
GHz IEC61000-4-8 Enclosure ports;
spot frequencies (MHz): Power frequency Zone A
80; 160; 380; 450; 900; 1850; immunity test 300V, CM; 150V, DM;
2150. IEC60255-26:2013; Test on:
Electrical fast Class A IEC61000-4-16 Binary input ports;
transient/burst immunity 4KV peak voltage; Slow damped oscillatory Class III
test Tested on: wave immunity test 2.5 kV CM ; 1 kV DM;
IEC60255-26:2013, Auxiliary power supply (1MHz) IEC60255-26: Tested on:
IEC61000-4-4 port; 2013 Auxiliary power supply
ANSI/IEEE C37.90.1 Enclosure port; IEC61000-4-18 port;
Input and output ports; ANSI/IEEEC37.90.1 Input and output ports;
Functional earth port; 1 kV CM ; 0 kV DM;
2KV peak voltage; Tested on:
Tested on: Communication ports
Communication port; Fast damped oscillatory Level 4
Surge (impact) immunity Class A,Level IV wave immunity test 4 kV, at 3MHz, 10MHz,
test 4.0kV, Line-to-earth; IEC61000-4-18 30MHz.
IEC60255-26:2013, 2.0kV, Line-to-line; Tested on:
IEC61000-4-5 Tested on: Auxiliary power supply
Auxiliary power supply port;
port; Input and output ports;
Enclosure port; Pulse magnetic field Class V
Input and output ports; immunity 1000A/m
Functional earth port; IEC61000-4-9
4.0kV, Line-to-earth; Damped oscillation Class V
Tested on: magnetic field immunity 100A/m
Communication ports; test
Test for Immunity to 10 V/m(r.m.s.), 80%,AM (1 IEC61000-4-10
conducted disturbances, kHz) Conducted emission Class A;
induced by Frequency sweep: 150kHz– IEC60255-26:2013 0.15MHz to 0.50MHz;
radio-frequency fields 80MHz CISPR22 0.50MHz to 30MHz;
IEC60255-26:2013 Spot frequencies: 27MHz and Tested on:
IEC61000-4-6 68MHz; Auxiliary power supply
Tested on: port;
Auxiliary power supply Radiated emission Class A;
port; IEC60255-26:2013 30MHz to 230MHz;
Input and output ports; CISPR11 230MHz to 1GHz;
Functional earth port;
DC voltage dips 20 ms at 0% residual voltage;
22 / 40
Specification
IEC60255-26:2013 200 ms at 40% residual Mechanical endurance, Unloaded, 10,000 times
IEC 61000-4-11 voltage; Unloaded (switching frequency is 3Hz);
IEC 61000-4-29 500 ms at 70% residual IEC60255-1 Making, ≥1000;
voltage; Breaking, ≥1000
AC voltage dips At 60Hz: Current carrying capacity 5A continuous,
IEC60255-26:2013 1.0 cycle at 0% residual IEC60255-1 30A, 200ms on,15s off
IEC 61000-4-11 voltage; Making capacity 1000W(DC) at Vr.aux,
IEC 61000-4-29 12 cycle at 40% residual IEC60255-1 L/R>40ms
voltage,; 1000VA(AC)
30 cycle at 70% residual Breaking capacity 30W, at Vr.aux, L/R≤40ms;
voltage; IEC60255-1 1000VA, at Vr.AC;
At 50Hz:
Contact circuit resistance 30mΩ
1.0 cycle at 0% residual
IEC60255-1
voltage;
Contact insulation test AC1000V,1min
10 cycle at 40% residual
(AC dielectric strength )
voltage,;
IEC60255-1
25 cycle at 70% residual
Maximum temperature 70℃
voltage;
that operation allows
DC voltage interruptions 5 s, at 0% residual voltage;
IEC60255-1
IEC60255-26:2013
23 / 40
Specification
Maximum temperature 70℃ 8-35 Hz: 1g acceleration
that operation allows (horizontal axis)
IEC60255-1 8-35 Hz: 0,5g acceleration
(vertical axis)
Mechanical test Frequency sweep 1
octave/min
Item Data
1 sweep cycle in each axis
Sinusoidal vibration Class 1
Relay energized
response test 10-60 Hz: ± 0.035 mm
IEC60255-21-1 amplitude
EN60255-21-1 60-150 Hz: 0,5g acceleration
Environmental test
Frequency sweep: 1 Item Data
octave/min Cold test - Operation -40°C, 96 hours, rated load
1 sweep cycle in each axis IEC60255-27
Relay energized IEC60068-2-1
Sinusoidal vibration Class 1 Cold test – Storage -40°C, 96 hours
endurance test 10 Hz to 150 Hz: 1 g IEC60255-27
IEC60255-21-1 20 sweep cycle in each axis IEC60068-2-1
EN60255-21-1 Relay non-energized Dry heat test – Operation +70°C, 96 hours, rated
Shock response test Class 1 IEC60255-27 load
IEC60255-21-2 Acceleration 5g, duration 11 IEC60068-2-2
EN 60255-21-2 ms. Dry heat test – Storage +70°C, 96 hours
3 shocks in each direction (6 IEC60255-27
shocks in each axis) IEC60068-2-2
Relay energized
Change of temperature Test Nb, figure 2, 5 cycles
Shock withstand test Class 1 IEC60255-27 -40°C / +70°C
IEC60255-21-2 Acceleration 15g, duration 11 IEC60068-2-14
EN 60255-21-2 ms.
Damp heat static test +40°C, 95% r.h. 10 days,
3 shocks in each direction (6 IEC60255-27 rated load
shocks in each axis)
IEC60068-2-78
Relay non-energized
Damp heat cyclic test +55°C, 97% r.h. 6 cycles,
Bump test Class 1
IEC60255-27 rated load
IEC60255-21-2 Acceleration 10g, duration 16
IEC60068-2-30
EN 60255-21-2 ms
1000 bumps in each direction
CE Certification
(2000 bumps in each axis)
Relay non-energized Item Data
Seismic test Class 1 EMC EN61000-6-2 and
IEC60255-21-3 1-8 Hz: ± 3.5 mm amplitude EN61000-6-4(EMC steering
(horizontal axis) committee 2004/108/EC)
1-8 Hz: ± 1.5 mm amplitude LVD EN60255-27(LVD2006/95EC)
(vertical axis)
24 / 40
Specification
50, 51, 67, Directional overcurrent Angle range of Operating 170°
protection area
Characteristic angle 0°to 90°, step 1°
Item Data ≤ ±1°, at phase to phase
voltage >2V
Definite time characteristic
Inrush current blocking element
0.05 Ir to 40.00 Ir
Current Max. current setting 0.05 In to 40.00 In
≤ ±2% setting or ±0.02Ir
≤ ±2% setting or ±0.02In
0.00s to 100.00s, step 0.01s without inrush current
Time delay of definite
≤ ±1% setting or ≤ +40ms, at
time characteristic blocking
200% operating setting
Reset ratio ≥ 0.95 Ratio of second 0.07 to 0.50, step 0.01
Reset time ≤ 40ms harmonics to
Inverse time characteristic fundamental current
0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir
Inverse time Normal inverse; 50N, 51N, 67N Directional earth fault
characteristic in Very inverse; protection
accordance with Extremely inverse;
Item Data
IEC60255-151 Long inverse Three phase currents or
Current inputs
≤ ±5% or ≤ +50ms , at 2 single current
<I/ISETTING < 20 Definite time characteristic
0.05 Ir to 40.00 Ir
Inverse time Inverse; Current
≤ ±2% setting or ±0.02Ir
characteristic in Short inverse; 0.00s to 100.00s, step 0.01s
Time delay ≤ ±1% setting or ≤ +40ms, at
accordance with Long inverse; 200% operating setting
ANSI/IEEE C37.112 Moderately inverse; Reset ratio ≥ 0.95
Very inverse; Reset time ≤ 40ms
Extremely inverse; Inverse time characteristic
Definite inverse 0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir
≤ ±5% setting or ≤ +50ms, at
Inverse time Normal inverse;
2 <I/ISETTING < 20,
characteristic in Very inverse;
User-defined A
T=( i + B) k accordance with Extremely inverse;
characteristic in ( )P −1
I_SET
IEC60255-151 Long inverse
accordance with ≤ ±5% setting or ≤ + 50ms, at
IEC60255-151
IEC60255-151 2 <I/ISETTING < 20
≤ ±5% setting or ≤ + 50ms, at 2
Time factor of 0.001 to 1000.000, step 0.001
<I/ISETTING < 20
characteristic, A
Inverse time Inverse;
Tine Delay of 0.00s to 100.00s, step 0.01s characteristic in Short inverse;
characteristic, B
accordance with Long inverse;
Index of characteristic, P 0.01 to 10.00, step 0.01 ANSI/IEEE C37.112 Moderately inverse;
Time constant of 0.025 to 1.500, step 0.001 Very inverse;
characteristic, T Extremely inverse;
Reset mode of inverse
Instantaneous Definite inverse
time characteristic
Reset ratio ≥ 0.95 ANSI/IEEE C37.112,
Reset time ≤ 40ms ≤ ±5% setting or ≤ + 50ms, at 2
Directional element <I/ISETTING < 20
25 / 40
Specification
User-defined A Current for sensitive CT 0.005 to 1.000 A , step 0.001
T=( i + B) k
characteristic in ( )P −1 input A
I_SET
directional earth fault protection Time constant of 0.025 to 1.500, step 0.001
characteristic, T
Item Data Reset mode of inverse
instantaneous
Current input From sensitive CT or cable time characteristic
Reset ratio ≥ 0.95
type CT
Reset time ≤ 40ms
Definite time characteristic
Directional element
Current for sensitive CT 0.005 to 1.000 A , step 0.001
principles I cos Φ and Φ (V0 / I0)”
input A
Direction measurement IE and VE measured
≤ ±2 % setting or 1 mA
or 3V0 calculated
Time delay of definite 0.00s to 100.00, step 0.01 s
3U0 Minimum voltage 2.00 to 100.00 V, step 0.01 V
time characteristic ≤ ±1 % setting value or ≤
threshold ≤ ±2 % setting for measured
+40ms, at 200% operating
voltage;
setting
≤ ±2 % setting for calculated
Reset ratio ≥ 0.95
voltage
Reset time ≤ 40ms
Characteristic angle 0°to 90°, step 1°
Inverse time characteristic
26 / 40
Specification
Φ_SEFChar ≤ ±1° characteristic, T
Operating area range 160°, Reset mode of inverse
instantaneous
time characteristic
≤ ±1°
Reset ratio ≥ 0.95
Reset time ≤ 40ms
50NS, 51NS, 67NS,
Negative-sequence overcurrent 37, Undercurrent protection
protection
Item Data
Item Data Current
0.05 Ir to 40.00 Ir
≤ ±2% setting or ±0.02Ir
Definite time characteristic
0.00s to 100.00s, step 0.01s
0.05 Ir to 40.00 Ir Time delay of definite
Current ≤ ±1% setting or ≤ +40ms, at
≤ ±2% setting or ±0.02Ir time characteristic
200% operating setting
0.00s to 100.00s, step 0.01s Reset ratio ≤ 1.05
Time delay of definite
≤ ±1% setting or ≤ +40ms, at
time characteristic Reset time ≤ 40ms
200% operating setting
Reset ratio ≥ 0.95
Reset time ≤ 40ms 49, Thermal overload protection
Inverse time characteristic
0.05 Ir to 40.00 Ir Item Data
Current
≤ ±2% setting or ±0.02Ir 0.05 Ir to 40.00 Ir
Current
Inverse time Normal inverse; ≤ ±2% setting or ±0.02Ir
Heating time constant 1-9999s
characteristic in Very inverse;
Cooling time constant 0.1-10
accordance with Extremely inverse;
IEC60255-151 Long inverse I eq2
IEC low temperature t ln 2 2
≤ ±5% or ≤+ 50ms, at 2 curve I eq I
<I/ISETTING < 20 ≤ ±5% setting or ≤+50ms
Inverse time Inverse;
I eq2 I P2
characteristic in Short inverse; IEC high temperature t ln 2 2
accordance with Long inverse;
curve I eq I
ANSI/IEEE C37.112 Moderately inverse; ≤ ±5% setting or ≤+50ms
Very inverse;
Extremely inverse;
24, Overexcitation protection
Definite inverse Item Data
≤ ±5% setting or ≤ +50ms, at
Reference voltage Un 10V/120V
2 <I/ISETTING < 20, ≤ ±2% setting or ±1V
User-defined A
T=( + B) k Definite time characteristic
i
characteristic in ( )P −1
I_SET
V/F 1.00 to 1.70
accordance with ≤ ±5% setting or ≤ + 50ms, at
≤ ±2% setting or ±0.01
IEC60255-151 2 <I/ISETTING < 20
Time delay 0.00s to 9999.00s, step 0.01s
Time factor of 0.001 to 1000.000, step 0.001
≤ ±5% setting or +80ms
characteristic, A
Reset ratio ≥0.96
Tine Delay of 0.00s to 100.00s, step 0.01s
Reset time ≤80ms
characteristic, B
Inverse time characteritic
Index of characteristic, P 0.01 to 10.00, step 0.01
V/F 1.00 to 1.70
Time constant of 0.025 to 1.500, step 0.001
≤ ±2% setting or ±0.01
27 / 40
Specification
Time delay 0.00s to 9999.00s, step 0.01s ≤ ±5% setting or ≤ +50ms, at
≤ ±5% setting or ≤ +80ms 2 <U/Uset < 20.
V/F characteristic value 1.05 /1.10 /1.15 /1.20 /1.25 User-defined curve ≤ ±5% setting or ≤ +50ms, at
/1.30 /1.35 /1.40 /1.45 /1.50 2 <U/Uset < 20.
/1.55 /1.60 /1.65 /1.7 Time factor of 0.001 to 10.000, step 0.001
≤ ±5% setting or ≤ ±80ms characteristic, A
Reset mode of inverse Tine Delay of 0.00s to 100.00s, step 0.01s
instantaneous
time characteristic
Reset ratio ≥ 0.96 characteristic, B
28 / 40
Specification
Normal inverse time; 2 <U2/U2set < 20.
Abnormal inverse time; ANSI standard curve Standard inverse time;
Extreme inverse time; Short inverse time
User-defined inverse time; Long inverse time;
≤ ±5% setting or ≤ +50ms, at Normal inverse time;
2 <U0/U0set < 20. Abnormal inverse time;
User-defined curve ≤ ±5% setting or ≤ +50ms, at Extreme inverse time;
2 <U0/U0set < 20. User-defined inverse time;
Time factor of 0.001 to 10.000, step 0.001 ≤ ±5% setting or ≤ +50ms, at
characteristic, A 2 <U2/U2set < 20.
Tine Delay of 0.00s to 100.00s, step 0.01s User-defined curve ≤ ±5% setting or +50ms, at 2
characteristic, B <U2/U2set < 20.
Index of characteristic, P 0.01 to 10.00, step 0.01 Time factor of 0.001 to 10.000, step 0.001
Time constant of 0.025 to 1.500, step 0.001 characteristic, A
characteristic, T Tine Delay of 0.00s to 100.00s, step 0.01s
Reset mode of characteristic, B
instantaneous
characteristic
Index of characteristic, P 0.01 to 10.00, step 0.01
Reset ratio ≥ 0.95
Time constant of 0.025 to 1.500, step 0.001
Reset time ≤ 50ms
characteristic, T
Reset mode of inverse
47, Negative-sequence overvoltage time characteristic
instantaneous
Voltage 0.0V to 100 V, step 0.1 V Reset ratio 1.00 to 2.00, step 0.01
≤ ±2% setting or ± 0.1V Time delay 0.00s to 120.00s, step 0.01s
IEC standard curve Normal inverse time; ≤ ±1 % setting or ≤ +50ms
Abnormal inverse time; at 80% voltage setting
Extreme inverse time; Reset time ≤ 50ms
Long inverse time; Inverse time characteritic
≤ ±5% setting or ≤ +50ms, at phase-to-earth voltages 5.0 to 150.0 V, step 0.1 V
29 / 40
Specification
≤ ±2% setting or ± 0.1V Voltage input Phase to phase voltage
Phase to phase voltage 10.0 to 150.0 V, step 0.1 V voltage 1.00 to 100.00 V, step 0.1V
≤ ±2% setting or ± 0.1V ≤ ±2% setting or ± 0.1V
Invers time characteristic ≤ ±5% setting or ≤ +50ms, at Time delay 0.00s to 100.00s, step 0.01s
in accordance with 0.05 <U2/U2set < 0.5. ≤ ±1% setting or ≤ +50ms, at
IEC60255-127 200% operating setting
User-defined curve ≤ ±5% setting or ≤ +50ms, at Reset ratio ≥ 0.95
0.05 <U2/U2set < 0.5 Reset time ≤ 50ms
Time factor of 0.001 to 10.000, step 0.001
characteristic, A 51UC, Unbalance current protection
Tine Delay of 0.00s to 100.00s, step 0.01s
Item Data
characteristic, B
Current 0.05 Ir to 40.00 Ir
Index of characteristic, P 0.010 to 10.000, step 0.005
≤ ±2% setting or ±0.02Ir
Time constant of 0.025 to 1.500, step 0.001
Time setting 0.00s to 100.00s, step 0.01s
characteristic, T
≤ ±1% setting or ≤ +40 ms, at
Reset mode instantaneous
200% operating setting
Reset ratio ≥ 0.95 Reset ratio ≥ 0.95
Reset time ≤ 50ms
Reset time ≤ 40ms
Filtering ratio of the 3rd >100 Time delay of stage 1 0.00s to 100.00 s, step 0.01s
harmonic ≤ ±1% setting or ≤ +40 ms, at
200% operating setting
59UV, Unbalance voltage protection Time delay of stage 2 0.00s to 100.00 s, step 0.01s
≤ ±1% setting or ≤ +40 ms, at
Item Data 200% operating setting
30 / 40
Specification
Reset ratio ≥ 0.95 Reset ratio ≥ 0.95
Reset time ≤ 15ms Reset time ≤ 40ms
31 / 40
Specification
81DF, Frequency change rate ≤±20mHz
protection Δα- angle difference 1 °to 80 °, step of 1 °
(α2>α1; α2<α1)
Minimum measuring 0.05s to 100.00 s, step 0.01s
Item Data time
≤ ±1% setting or ≤ +40 ms
0.1 to 20Hz/s
Change of rate Δf/Δt Maximum synchronous 0.00s to 60.00 s, step 0.01s
≤±0.5Hz/s check broadening time
0.00s to 60.00s, step 0.01s ≤ ±1% setting or ≤ +40 ms
Constant time
≤ ±1% setting or ≤ +100 ms
Upper limit of frequency 0.1 to 20Hz/s 79, Autoreclosing
change rate ≤±0.5Hz/s
Item Data
Lower limit of frequency 0.1 to 20Hz/s 1 to 4
Shots of reclosing
change rate ≤±0.5Hz/s
Reclosing initiated Internal protection startups
10 to 100V, step 0.1V inputs External binary input
voltage
≤±2% setting or ± 0.1V
Time for each shot of 0.00s~100.00s, step of 0.01 s
reclosing ≤ ±1% setting or ≤ +100 ms
50SOTF, Switch onto fault protection Reclosing confirmation 0.50 s~100.00s, step of 0.01 s
Time 0.00s to 100.00s, step 0.01s Equal breaking time 0.50 s~100.00s, step of 0.01 s
32 / 40
Specification
51LS, Load shedding by overload ≤ ±1% setting or ≤ +100 ms,
at 80% setting
Item Data
Reset Δf =︱fset - freset︱ Approx. 20mHz
0.05 Ir to 40.00 Ir
Current
≤ ±2% setting or ±0.02Ir 0.1 to 20Hz/s
0.00s to 100.00s, step 0.01s Change of rate Δf/Δt
Time delay of definite ≤±0.5Hz/s
≤ ±1% setting or ≤ +40ms, at
time characteristic
200% operating setting 10V to 120V, step 0.1V
Voltage
Reset ratio ≥ 0.95 ≤±2% setting or ± 0.1V
Reset time ≤ 40ms
Blocking element 97FF, VT secondary circuit
Frequency changing rate 0.3Hz/s~20Hz/s,step supervision
Δf/Δt 0.01Hz/s
Voltage change rate, 2V/s~200V/s, step 0.01V/s Item Data
Δu/Δt ≤ ±3% setting or ±1V/s Phase current 0.05Ir to 0.20Ir, step 0.01A
≤ ±2% setting or ±0.02Ir
81LS, Load shedding underfrequency Zero or negative 0.05Ir to 0.20Ir, step 0.01A
33 / 40
Ordering Code
Ordering code Description
Product Family
Hardware architecture
DA SV Input / GOOSE IO
Language
EC English + Chinese
Protocols
X Null
A IEC61850
B IEC61870-5-103
C MODBUS
D DNP 3.0
34 / 40
Ordering Code
97FF: Symmetrical and asymmetrical VT Fuse Fail Detection;
CTFF: CT-Secondary Current Supervision ;
DR: Disturbance recorder;
FP: Faulty phase indication;
35 / 40
Ordering Code
DR: Disturbance recorder;
FP: Faulty phase indication;
94-1/3: Single- and/or three-pole tripping logic;
36 / 40
Ordering Code
X Null-Breaker protection function group
Control function
X NULL-Control function
CB control;
Isolator control;
A
Programmable Interlock logic;
Remote/local control switch;
Power Supply
Communication port
37 / 40
Ordering Code
Qty. of RS485/IRIG-B:1;
Qty. of RS485:1;
RS232-Printer port:1;
Qty. of modules:1;
Ip (1A&5A, 40Ir):4;
AA
Is (1A&5A, 1.2Ir):1;
U (180V,star):4;
Qty. of modules:2;
Ip (1A&5A, 40Ir):4;
AB Is (1A&5A, 1.2Ir):1;
Im(2Ir) :3;
U (180V,star):4;
Qty. of modules:1;
AC
Ip (1A&5A, 40Ir):3;
Qty. of modules:2;
Ip (1A&5A, 40Ir):5;
Is (1A&5A, 1.2Ir):1;
AD
Im(2Ir) :3;
U (180V,star):7;
AI (4-20mA):2;
Qty. of modules:2;
Ip (1A&5A, 40Ir):7;
Is (1A&5A, 1.2Ir):1;
AE
Im(2Ir) :3;
U (180V,star):5;
AI (4-20mA):2;
38 / 40
Ordering Code
Internal Failure alarm relay, 2 NC:1;
39 / 40
Ordering Code
Signal relay, 2 NO with common terminal: 2;
General relay alarm relay, 2 NO:1;
Internal Failure alarm relay, 2 NC:1;
Accessories
X Null
40 / 40