Schedule of Laods
Schedule of Laods
Schedule of Laods
2 Lighting Outlet 11 1100 230 4.78 3.826 15 2-2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE
3 Convenience Outlet 8 2880 180 12.52 10.016 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
4 Convenience Outlet 4 1440 180 6.26 5.009 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
5 Convenience Outlet 2 1100 1900 8.26 6.608 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
6 Convenience Outlet 2 2800 2800 12.17 9.736 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
2 Lighting Outlet 7 700 230 3.04 2.435 15 2-2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE
3 Convenience Outlet 9 3240 180 12.52 11.270 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
4 Convenience Outlet 1 1119 230 14.09 12.16 30 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
5 Convenience Outlet 1 746 230 2.87 8.12 30 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
6 Convenience Outlet 1 746 230 3.24 8.12 30 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
2 Lighting Outlet 2 720 180 3.13 2.504 20 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
1200 watts / 230 volts = 5.22 amperes 1440 watts / 230 volts = 6.26 amperes
5.22 amperes x 80% = 4.176 amperes 6.26 amperes x 80% = 5.009 amperes
CB = 15 amperes CB = 20
2-2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
11 outlets x 100 = 1100 watts 1-unit electric stove at 1.1kw = 1100 watts
1100 watts / 230 volts = 4.78 amperes 1 unit refrigerator 0.8kw = 800 watts
2-2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE 1900 watts / 230 volts = 8.26 amperes
8 outlets x 2 plug = 16 pieces 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
12.52 amperes x 80% = 10.016 amperes 2-unit laundry machine at 1.4kw = 2800 watts
2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE 12.17 amperes x 80% = 9.736 amperes
CB = 20 amperes 14.09 amperes x 80% = 11.270 amperes
2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE CB = 20 amperes
Second Floor Computations of Load 2-3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE