0% found this document useful (0 votes)
21 views29 pages

REN UM-WI-004 DA16200 AT GUI Tool User Manual Rev 1v7 MAT 20210906

The document provides instructions for using a GUI tool to configure and test a DA16200 wireless module in different modes, including certification, TX/RX test, network, and OTP modes. It describes how to connect the module, select firmware, configure operation modes, perform wireless scanning and connectivity tests, and transfer TCP, UDP and MQTT data. Screenshots and step-by-step explanations are provided for common tasks.

Uploaded by

Ioana Marc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views29 pages

REN UM-WI-004 DA16200 AT GUI Tool User Manual Rev 1v7 MAT 20210906

The document provides instructions for using a GUI tool to configure and test a DA16200 wireless module in different modes, including certification, TX/RX test, network, and OTP modes. It describes how to connect the module, select firmware, configure operation modes, perform wireless scanning and connectivity tests, and transfer TCP, UDP and MQTT data. Screenshots and step-by-step explanations are provided for common tasks.

Uploaded by

Ioana Marc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

User Manual

DA16200 AT GUI Tool


UM-WI-004
UM-WI-004
DA16200 AT GUI Tool

Contents
Contents ............................................................................................................................................... 2
Figures .................................................................................................................................................. 3
1 Terms and Definitions ................................................................................................................... 4
2 References ..................................................................................................................................... 4
3 Introduction.................................................................................................................................... 5
3.1 Certification Mode ................................................................................................................. 5
3.2 Network Mode ....................................................................................................................... 5
3.3 OTP Mode ............................................................................................................................. 5
4 How to Connect ............................................................................................................................. 6
4.1 USB to Serial Driver .............................................................................................................. 6
5 DA16200 SDK or Firmware Selection .......................................................................................... 6
6 How to Run GUI with DA16200 EVK ............................................................................................ 7
6.1 Connection and Running....................................................................................................... 7
6.2 COM Port and Baud Rate Configuration............................................................................... 9
6.3 RF Certification Mode ......................................................................................................... 10
6.4 TX Test Mode ...................................................................................................................... 11
6.5 RX Test Mode ..................................................................................................................... 12
7 Network Mode .............................................................................................................................. 14
7.1 Station Mode ....................................................................................................................... 15
7.2 AP Mode ............................................................................................................................. 17
7.3 Data Transfer (TCP/UDP) ................................................................................................... 18
7.3.1 TCP Server .......................................................................................................... 19
7.3.2 TCP Client ........................................................................................................... 20
7.3.3 UDP Session ....................................................................................................... 20
7.3.4 Data Exchange .................................................................................................... 21
7.3.5 Data Transfer on DPM Mode ............................................................................... 22
7.4 MQTT Client ........................................................................................................................ 23
7.4.1 Configuration ....................................................................................................... 23
7.4.2 Data Exchange .................................................................................................... 24
7.4.3 MQTT on DPM Mode ........................................................................................... 24
7.5 TLS Setting ......................................................................................................................... 25
8 OTP Mode Setup .......................................................................................................................... 26
Revision History ................................................................................................................................ 27

User Manual Revision 1.7 03-Mar-2022

CFR0012 2 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

Figures
Figure 1: DA16200 EVK GUI ................................................................................................................. 5
Figure 2: Development Kit Connections ................................................................................................ 7
Figure 3: AT GUI ................................................................................................................................... 8
Figure 4: RS232 Setup – Disconnected ................................................................................................ 9
Figure 5: RS232 Setup – Connected .................................................................................................... 9
Figure 6: Debug Console – Connected ................................................................................................. 9
Figure 7: Certification Mode Configuration .......................................................................................... 10
Figure 8: Tx Test Mode Configuration ................................................................................................. 11
Figure 9: Debug Console – TX Mode .................................................................................................. 11
Figure 10: Start and Stop TX ............................................................................................................... 12
Figure 11: Debug Console – Sart TX .................................................................................................. 12
Figure 12: Debug Console – Stop TX ................................................................................................. 12
Figure 13: Rx Configuration................................................................................................................. 13
Figure 14: Network Mode Configuration.............................................................................................. 14
Figure 15: Setup Window – Station Mode ........................................................................................... 15
Figure 16: Station Mode – SCAN ........................................................................................................ 15
Figure 17: Station Mode – Choose AP and Connect .......................................................................... 16
Figure 18: Debug Console – C onnect to AP ...................................................................................... 16
Figure 19: Setup Window – AP Mode ................................................................................................. 17
Figure 20: AP Configuration ................................................................................................................ 17
Figure 21: Debug Console – AP Configuration ................................................................................... 18
Figure 22: DHCP Configuration ........................................................................................................... 18
Figure 23: Debug Console – DHCP Configuration .............................................................................. 18
Figure 24: Data Transfer Tab .............................................................................................................. 19
Figure 25: TCP Server Open ............................................................................................................... 19
Figure 26: TCP Server Connection with a Client ................................................................................ 19
Figure 27: TCP Client Connection to a Server .................................................................................... 20
Figure 28: UDP Session Open ............................................................................................................ 20
Figure 29: TCP Server Data Transfer ................................................................................................. 21
Figure 30: TCP Client Data Transfer ................................................................................................... 21
Figure 31: UDP Session Data Transfer ............................................................................................... 21
Figure 32: TCP/UDP Data Reception .................................................................................................. 22
Figure 33: DPM Mode Setting ............................................................................................................. 22
Figure 34: MQTT Client Tab ................................................................................................................ 23
Figure 35: MQTT PUBLISH Transfer .................................................................................................. 24
Figure 36: MQTT PUBLISH Reception ............................................................................................... 24
Figure 37: TLS Setting Tab ................................................................................................................. 25
Figure 38: OTP Mode .......................................................................................................................... 26

User Manual Revision 1.7 03-Mar-2022

CFR0012 3 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

1 Terms and Definitions


AP Access Point
AT AT Command Interpreter Software Subsystem, or Attention
CoAP Constrained Application Protocol
DHCP Dynamic Host Configuration Protocol
EVK Evaluation Kit
GUI Graphical User Interface
HTTP Hypertext Transfer Protocol
MFC Microsoft Foundation Class
MQTT Message Queuing Telemetry Transport
OTP One-Time Programmable
PC Personal Computer
QFN Quad Flat No-Lead
SDK Software Development Kit
SSID Service Set IDentifier
STA STAtion
TCP Transmission Control Protocol
TLS Transport Layer Security
UART Universal Asynchronous Receiver Transmitter
UDP User Datagram Protocol
USB Universal Serial Bus

2 References
[1] DA16200, Datasheet, Dialog Semiconductor
[2] DA16200, SDK Programmer Guide, User Manual, Dialog Semiconductor
[3] DA16200, EVK User Guide, Dialog Semiconductor
[4] DA16200, AT Command User Guide, Dialog Semiconductor

User Manual Revision 1.7 03-Mar-2022

CFR0012 4 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

3 Introduction
The DA16200 GUI tool lets users control the DA16200 EVK in a GUI environment. There are three
modes of operation: Certification mode, Network mode, and OTP mode (see Figure 1).

Figure 1: DA16200 EVK GUI

3.1 Certification Mode


This mode is for Wi-Fi RF test (Tx power, Rx sensitivity, and so on) also known as “TEST Mode”.

3.2 Network Mode


With Network mode, the Station or AP mode of the DA16200 is tested.
● AP mode: Soft-AP test with configurable parameters like SSID, security, DHCP Server, and so
on
● Station mode: STA test to search and connect to an Access Point and check/test the STA
function
After the network mode is set, the user can test the TCP/UDP or the MQTT and manage the TLS
certificates.
● Data Transfer: message exchange through the TCP Server/Client, and UDP session
● MQTT Client: message exchange through the MQTT protocol
● TLS Setting: management of TLS certificate that is set (e.g. Root CA, Client Certificate, Client
Private Key)

3.3 OTP Mode


This mode is for power calibration and temperature calibration with OTP memory location.
User Manual Revision 1.7 03-Mar-2022

CFR0012 5 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

4 How to Connect

4.1 USB to Serial Driver


The DA16200 evaluation board supports USB to serial interface. The user connects to DA16200
EVK with the PC through a micro-USB cable and then two COM ports will be detected automatically.
One (UART0) is for console command and the other (UART1) is for AT command. Normally, the
higher number COM port is for AT commands and the lower number COM port is for the console.
● Required the FT232 Driver installation for Windows
○ In most cases, it will be installed automatically
The FTDI driver for the FT2232 FTDI chip used on DA16200 EVK is available for download at the
following link: http://www.ftdichip.com/Drivers/CDM/CDM21224_Setup.zip
● See the EVK User Guide [3] to find information about the UART1 port. AT GUI tool uses UART1
port
● To update with a new DA16200 firmware, see the DA16200 EVK User Guide [3]

5 DA16200 SDK or Firmware Selection


There are several types of SDK and firmware for DA16200 such as Generic and Manufacture that
can be found in DA16200 SDK/Image packages. Consider the kinds of tests you plan to determine
which SDK or firmware should be picked up.
● Certification or OTP Mode:
○ SDK: DA16200_SDK_Manufacture_QFN_xxx.zip
○ Firmware: DA16200_IMG_Manufacture_QFN
● Network Mode:
○ SDK: DA16200_SDK_Generic_QFN xxx.zip
– The __SUPPORT_ATCMD__ where can be found in config_generic_sdk.h file should be
enabled.
[\apps\da16200\get_started\inc\config_generic_sdk.h]

// AT-CMD features
#define __SUPPORT_ATCMD__ // Support AT-CMD

○ Firmware: ATCMD firmware should be picked such as


DA16200_IMG_Generic_QFN_ATCMD, DA16200_IMG_Generic_FcCSP_LP_ATCMD or
DA16200_IMG_Generic_FcCSP_NP_ATCMD depending on SoC package type

User Manual Revision 1.7 03-Mar-2022

CFR0012 6 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

6 How to Run GUI with DA16200 EVK

6.1 Connection and Running


DA16200 AT GUI program is a single executable file.

NOTE
If there is an error with the message “a DLL file (e.g. vcruntime140.dll or mfc1400u.dll) is missing”, then install
Microsoft Visual Studio redistributable package (https://www.microsoft.com/en-
us/download/details.aspx?id=48145) or copy the .dll file into the Windows system folder
(C:\Windows\System32 or C:\Windows\SysWOW64).

The program setup sequence is:


1. Connect the DA16200 Development Kit to the host PC as shown in
2.
3. Figure 2.

Figure 2: Development Kit Connections

NOTE
See the EVK User Guide [3] to know which port to use.

User Manual Revision 1.7 03-Mar-2022

CFR0012 7 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

4. Start the AT GUI program.

Figure 3: AT GUI

User Manual Revision 1.7 03-Mar-2022

CFR0012 8 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

6.2 COM Port and Baud Rate Configuration


1. When the AT GUI program runs, the connection status is red (not connected). If the program
does not detect any COM port, click the Refresh button to refresh the COM Port. See Figure 4.

Figure 4: RS232 Setup – Disconnected

2. Select a COM port and click the OPEN button and wait for a few seconds. See Figure 5 and
Figure 6.
○ The connection status will soon change to a green color and the Connection Status field
shows “Connected” in a green color. This means that communication is OK

Figure 5: RS232 Setup – Connected

○ In the Debug Console window (in the black box), the message “Echo on” is shown

Figure 6: Debug Console – Connected

User Manual Revision 1.7 03-Mar-2022

CFR0012 9 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

6.3 RF Certification Mode


To enable certification mode:
1. Open the Settings tab. See Figure 7.
2. In the RF Mode area, select the Certification Mode check box.

Figure 7: Certification Mode Configuration

User Manual Revision 1.7 03-Mar-2022

CFR0012 10 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

6.4 TX Test Mode


1. Open the Certification Mode tab. See Figure 8.

Figure 8: Tx Test Mode Configuration

2. Click the Mode Select button (Figure 8). A confirmation message is shown as in Figure 9. This is
a normal state.

Figure 9: Debug Console – TX Mode

3. Select the Data Rate, Channel, and Power for the purpose of the test.
○ Packet mode: this is the normal test mode with packet generation mode. Offers the
possibility to adjust duty of RF Burst at time domain
○ Cont mode: Continuous TX out mode. This mode is for TX power test and so on. In this
mode, TX packet is generated continuously over 95% duty cycle
○ CW mode: Only single sinewave tone out mode. This mode is for freq err check
○ Data Rate: Choose modulation type to test
○ Power: Select or tune the power level. (“0” step is Maximum). The difference between power
steps is about 0.8~1 dB/1step
○ Size: You can adjust the duty rate with this number. However, the size is not linear as the
number, so to set the exact number you need equipment like a spectrum analyzer to check
the value. (Equipment setting is set to zero span setting or burst mode setting)

User Manual Revision 1.7 03-Mar-2022

CFR0012 11 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

To do TX packet generation:
● To start and stop TX packet generation, use the Start TX button and the Stop TX button. If you
want to make changes for another condition, click Stop TX before a new test is started

Start TX Stop TX

Figure 10: Start and Stop TX

For example: there is a test setting with 802.11n MCS7, channel 1, 100 bytes packet and power
grade 0.
● When the Start TX button is clicked, messages as shown in Figure 11 will be shown

Figure 11: Debug Console – Sart TX

● When you click the Stop TX button, messages as shown in Figure 12 will be shown

Figure 12: Debug Console – Stop TX

6.5 RX Test Mode


The settings are made in the RX Setting area. See Figure 13.

User Manual Revision 1.7 03-Mar-2022

CFR0012 12 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

● Channel: Support CH1 ~ CH13


● Test Time: Maximum 3600 s (Duration is 1 second fixed)

Figure 13: Rx Configuration

● RX Packet Rate
○ FCS + PHY + Overflow packet / Total packet = Error rate

User Manual Revision 1.7 03-Mar-2022

CFR0012 13 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7 Network Mode
To enable network mode:
1. Open the Settings tab.
2. Select the Network Mode checkbox. See Figure 14.

Figure 14: Network Mode Configuration

User Manual Revision 1.7 03-Mar-2022

CFR0012 14 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7.1 Station Mode


1. In the Mode Select: field, select Station Mode.
○ The network mode is changed. Next, DA16200 reboots and the station mode setup window
opens. See Figure 15

Figure 15: Setup Window – Station Mode

2. Click the Scan button to scan APs. See Figure 16.

Figure 16: Station Mode – SCAN

User Manual Revision 1.7 03-Mar-2022

CFR0012 15 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

3. When scanning is finished, choose one AP in the list. See Figure 17.
4. Click the Connect button.
5. If required by the security mode of the AP, fill in a password or key index.

Figure 17: Station Mode – Choose AP and Connect

Figure 18: Debug Console – C onnect to AP

User Manual Revision 1.7 03-Mar-2022

CFR0012 16 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7.2 AP Mode
1. In the Mode Select field, select AP Mode.
○ The network mode changes, DA16200 reboots and the AP Mode setup window opens. See
Figure 19

Figure 19: Setup Window – AP Mode

2. Set the fields SSID, Password, Country, Channel, and Security mode. See Figure 20.
3. Click the Confirm button.

Figure 20: AP Configuration


User Manual Revision 1.7 03-Mar-2022

CFR0012 17 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

○ The Debug Console window messages appears as shown in Figure 21

Figure 21: Debug Console – AP Configuration

4. In the DHCP Server area, make the required settings for the IP addresses and click the Confirm
button. See Figure 22.
○ When a client is connected, the MAC address will be shown as in Figure 23

Figure 22: DHCP Configuration

Figure 23: Debug Console – DHCP Configuration

7.3 Data Transfer (TCP/UDP)


The DA16200 GUI tool provides data transfer functions with TCP/UDP. Before messages are sent
with this tool, connect the DA16200 to an access point as shown in Section 7.1. Then click the Data

User Manual Revision 1.7 03-Mar-2022

CFR0012 18 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

Transfer tab. If DA16200 succeeds to connect to an AP, the IP address will be filled in.
See Figure 24.

Figure 24: Data Transfer Tab

The DA16200 provides three kinds of sessions: TCP server, TCP client, and UDP session. The user
can use these three simultaneously.

7.3.1 TCP Server


To use TCP server, fill in a port number and click the Connect button on the TCP Server line. When
a server is opened, the X will change to O. See Figure 25.

Figure 25: TCP Server Open

The user can connect to the DA16200 TCP server with tools for data exchange like the IO Ninja.
When a client connects successfully, its information will be shown as in Figure 26. The DA16200
TCP server can accept up to eight client sessions.

Figure 26: TCP Server Connection with a Client

User Manual Revision 1.7 03-Mar-2022

CFR0012 19 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7.3.2 TCP Client


To connect to a TCP server, fill in the IP address and port number of the server and click the
Connect button on the TCP Client line. When the DA16200 TCP client succeeds to connect, the X
will change to O. See Figure 27.

Figure 27: TCP Client Connection to a Server

7.3.3 UDP Session


To open a UDP session, fill in a port number and click the Start button. When the DA16200 TCP
client succeeds to connect, the X will change to O. See Figure 28. TODO:

Figure 28: UDP Session Open

User Manual Revision 1.7 03-Mar-2022

CFR0012 20 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7.3.4 Data Exchange


To send a message to a peer, first select a session. Each session is slightly different in method.
● TCP Server: Select the TCP Server checkbox > Select the destination IP in the drop-down list >
Type a message > Click the Send button (see Figure 29)

Figure 29: TCP Server Data Transfer

● TCP Client: Select the TCP Client checkbox > Type a message > Click the Send button
(see Figure 30)

Figure 30: TCP Client Data Transfer

● UDP Session: Select the UDP Session checkbox > Enter the destination IP and port number >
Type a message > Click the Send button (see Figure 31)

Figure 31: UDP Session Data Transfer


User Manual Revision 1.7 03-Mar-2022

CFR0012 21 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

When a session receives a message from a peer, the message is shown in the message window.
See Figure 32.

Figure 32: TCP/UDP Data Reception

7.3.5 Data Transfer on DPM Mode


The DA16200 GUI provides TCP/UDP sockets operation in DPM (DA16200 power-save) mode. See
Figure 33.

Figure 33: DPM Mode Setting

● DPM Button: DPM mode Start/End


● DPM_STATUS: DPM state (Disabled / DPM init… / DPM Sleep / DPM wake-up)
● Sleep Button: DA16200 returns to DPM sleep state (only available DPM wake-up state)
To initiate TCP/UDP sockets in DPM mode:
1. Open sockets user wants to.
2. Click the DPM button to start DPM mode.
3. After all sockets are ready in DPM mode, the DPM_STATUS will change to "DPM sleep".
When DA16200 in DPM sleep state receives a TCP or UDP messages from a peer, it is shown in the
message window like in Figure 32.
To send a message in DPM Sleep status:
1. Wake up DA16200 with the switch. The DPM_STATUS will change to "DPM wake-up".
2. Select the session to send, type a message, and click the Send button.
3. After sending messages, click the Sleep button. The DPM_STATUS will change to "DPM sleep".
1.
To exit DPM mode:
1. Wake up DA16200 with the switch. The DPM_STATUS will change to "DPM Wake-up".
2. Click the Sleep button. The DPM_STATUS will change to "Disabled".

User Manual Revision 1.7 03-Mar-2022

CFR0012 22 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

7.4 MQTT Client


The DA16200 GUI tool provides data transfer functions with MQTT protocol. Before messages are
sent with this tool, connect the DA16200 to an access point as shown in Section 7.1. Click
the MQTT Client tab.

7.4.1 Configuration
Before a connection is made to an MQTT broker, set the required fields for the connection
information. See Figure 34.

Figure 34: MQTT Client Tab

1. Broker IP address
2. Broker port number
3. Subscriber topics (up to 4)
4. Publisher topic
5. Sending PINGREQ cycle (second)
6. Login ID
7. Login password
8. MQTT QoS (0~2)
9. TLS use (0 or 1)
10. Reset all configuration to default

User Manual Revision 1.7 03-Mar-2022

CFR0012 23 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

When the DA16200 MQTT client succeeds to connect, the letter X will change to O. Moreover, the
user can send a PUBLISH message to the broker or receive a message.

7.4.2 Data Exchange


To exchange a message with the broker, connect the MQTT Client.
To send a PUBLISH, type the message and click the PUBLISH button. See Figure 35.

Figure 35: MQTT PUBLISH Transfer

When the client receives a message from the broker, the message is displayed in the message
window. See Figure 36.

Figure 36: MQTT PUBLISH Reception

7.4.3 MQTT on DPM Mode


The DA16200 GUI provides MQTT client operation in DPM mode. There is the DPM mode setting as
shown in Figure 33 in MQTT Client tab.
To initiate MQTT client in DPM mode:
1. After setting up, connect to a MQTT Broker.
2. Click the DPM button to start DPM mode.
3. After the MQTT client session is ready in DPM mode, the DPM_STATUS will change to "DPM
sleep".
When DA16200 in DPM sleep state receives a PUBLISH from the broker, it is shown in the message
window like Figure 36.
To send a message in DPM Sleep status:
1. Wake up DA16200 with the switch. The DPM_STATUS will change to "DPM wake-up".
2. Type a message and click the PUBLISH button.
3. After sending messages, click the Sleep button. The DPM_STATUS will change to "DPM sleep".

User Manual Revision 1.7 03-Mar-2022

CFR0012 24 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

And to exit DPM mode:


1. Wake up DA16200 with the switch. The DPM_STATUS will change to "DPM Wake-up".
2. Click the Sleep button. The DPM_STATUS will change to "Disabled".

7.5 TLS Setting


The user can store a TLS certificate that is set with this tool for MQTT, HTTPs, CoAPs, and so on.
There are three kinds of items: Root CA, Client Certificate, and Private Key.
DA16200 can only process Privacy Enhanced Mail type(.pem). To enter the certificates directly, input
the text and click the Upload button with the TLS item selection. If this is done successfully,
<Content exists> will appear in the window. See Figure 37.
If the user has TLS certificate files with PEM type, click File Search and select the file. The text will
be loaded in the window.

Figure 37: TLS Setting Tab

User Manual Revision 1.7 03-Mar-2022

CFR0012 25 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

8 OTP Mode Setup


To enable OTP mode:
1. Open the OTP Mode tab.
2. Click the OPT Enable checkbox
○ The current OTP data is as shown in Figure 38

Figure 38: OTP Mode

Power calibration and temperature calibration has been completed for the chipset by Dialog and it
may not need to be done by the customer.
Freq Offset cal: the range of frequency offset calibration is 0x0 ~ 0x7F.
MAC Address Setup
DA16200 has 4 slots to store MAC addresses. The 1st slot is written by Dialog. The user can use 3
slots to write their own MAC address. The MAC address written in the OTP must be an even number.
it is used for WLAN0 MAC address (for STA interface), and the next number is automatically used for
WLAN1 MAC address (for Soft-AP interface).
To write the MAC address, give a MAC address in the first empty slot and click the Write button, then
the new address substitutes for the previous address.

User Manual Revision 1.7 03-Mar-2022

CFR0012 26 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

Revision History
Revision Date Description
1.7 28-Mar-2022 Update logo, disclaimer, copyright.
1.6 19-Aug-2021 Applied changes to SDK folder hierarchy
1.5 06-Jan-2021 Revised as the user interface changes of the tool.
1.4 21-Aug-2020 4.3.5 Data Transfer on DPM Mode Modification
4.4.3 MQTT on DPM Mode Modification
Figure 36: MQTT Client Tab Change
Figure 45: Solution Explorer Tab
1.3 06-Apr-2020 TCP/UDP, MQTT, and TLS added, GUI Build added
1.2 31-Oct-2019 Finalized for publication
1.1 15-Oct-2019 Editorial review
1.0 03-Jul-2019 First Release.

User Manual Revision 1.7 03-Mar-2022

CFR0012 27 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

Status Definitions

Status Definition

DRAFT The content of this document is under review and subject to formal approval, which may result in modifications or
additions.
APPROVED The content of this document has been approved for publication.
or unmarked

RoHS Compliance
Dialog Semiconductor’s suppliers certify that its products are in compliance with the requirements of Directive 2011/65/EU of the European
Parliament on the restriction of the use of certain hazardous substances in electrical and electronic equipment. RoHS certificates from our
suppliers are available on request.

User Manual Revision 1.7 03-Mar-2022

CFR0012 28 of 29 © 2022 Renesas Electronics


UM-WI-004
DA16200 AT GUI Tool

Important Notice and Disclaimer


RENESAS ELECTRONICS CORPORATION AND ITS SUBSIDIARIES (“RENESAS”) PROVIDES TECHNICAL SPECIFICATIONS AND
RELIABILITY DATA (INCLUDING DATASHEETS), DESIGN RESOURCES (INCLUDING REFERENCE DESIGNS), APPLICATION OR OTHER
DESIGN ADVICE, WEB TOOLS, SAFETY INFORMATION, AND OTHER RESOURCES “AS IS” AND WITH ALL FAULTS, AND DISCLAIMS
ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE, OR NON-INFRINGEMENT OF THIRD PARTY INTELLECTUAL PROPERTY RIGHTS.

These resources are intended for developers skilled in the art designing with Renesas products. You are solely responsible for (1) selecting the
appropriate products for your application, (2) designing, validating, and testing your application, and (3) ensuring your application meets
applicable standards, and any other safety, security, or other requirements. These resources are subject to change without notice. Renesas
grants you permission to use these resources only for development of an application that uses Renesas products. Other reproduction or use of
these resources is strictly prohibited. No license is granted to any other Renesas intellectual property or to any third party intellectual property.
Renesas disclaims responsibility for, and you will fully indemnify Renesas and its representatives against, any claims, damages, costs, losses, or
liabilities arising out of your use of these resources. Renesas' products are provided only subject to Renesas' Terms and Conditions of Sale or
other applicable terms agreed to in writing. No use of any Renesas resources expands or otherwise alters any applicable warranties or warranty
disclaimers for these products.

Corporate Headquarters
TOYOSU FORESIA, 3-2-24 Toyosu Contact Information

Koto-ku, Tokyo 135-0061, Japan For further information on a product, technology, the most
www.renesas.com up-to-date version of a document, or your nearest sales
office, please visit:
https://www.renesas.com/contact/

Trademarks

Renesas and the Renesas logo are trademarks of Renesas Electronics


Corporation. All trademarks and registered trademarks are the property
of their respective owners.

User Manual Revision 1.7 03-Mar-2022

CFR0012 29 of 29 © 2022 Renesas Electronics

You might also like