Air System Sizing Summary for 12 DX - POWER BACKUP

Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023


Prepared by: HVAC 01:48p. m.

Air System Information


Air System Name 12 DX - POWER BACKUP Number of zones 1
Equipment Class SPLT AHU Floor Area 869.4 ft²
Air System Type SZCAV Location Toluca, Mexico

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data User-Modified Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.1 Tons Load occurs at Jul 1700
Total coil load 25.5 MBH OA DB / WB 79.9 / 61.9 °F
Sensible coil load 24.2 MBH Entering DB / WB 72.5 / 57.8 °F
Coil CFM at Jul 1700 1500 CFM Leaving DB / WB 52.0 / 50.6 °F
Max block CFM 1500 CFM Coil ADP 49.7 °F
Sum of peak zone CFM 1500 CFM Bypass Factor 0.100
Sensible heat ratio 0.950 Resulting RH 46 %
CFM/Ton 705.4 Design supply temp. 52.0 °F
ft²/Ton 408.8 Zone T-stat Check 0 of 1 OK
BTU/(hr·ft²) 29.4 Max zone temperature deviation 2.3 °F
Water flow @ 10.0 °F rise N/A

Central Heating Coil Sizing Data


Max coil load 27.9 MBH Load occurs at Des Htg
Coil CFM at Des Htg 1500 CFM BTU/(hr·ft²) 32.1
Max coil CFM 1500 CFM Ent. DB / Lvg DB 65.6 / 89.2 °F
Water flow @ 20.0 °F drop N/A

Supply Fan Sizing Data


Actual max CFM 1500 CFM Fan motor BHP 0.00 BHP
Standard CFM 1094 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 1.73 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 52 CFM CFM/person 26.08 CFM/person
CFM/ft² 0.06 CFM/ft²

Hourly Analysis Program 5.10 Page 1 of 8


Zone Sizing Summary for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

Air System Information


Air System Name 12 DX - POWER BACKUP Number of zones 1
Equipment Class SPLT AHU Floor Area 869.4 ft²
Air System Type SZCAV Location Toluca, Mexico

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data User-Modified Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
037 POWER BACKUP 1500 1500 1.73 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
037 POWER BACKUP 29.5 Jul 1700 26.5 869.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
037 POWER BACKUP
037 POWER BACKUP 1 29.5 Jul 1700 2101 26.5 869.4 2.42

Hourly Analysis Program 5.10 Page 2 of 8


Ventilation Sizing Summary for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

No data is available for this report. Space by space ventilation calculations were not performed for this air system because it uses the 'user-defined' sizing option. With this option
the system outdoor ventilation air flow is specified directly by the user. Therefore, space-by-space calculations are not performed.

Hourly Analysis Program 5.10 Page 3 of 8


Air System Design Load Summary for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.9 °F / 61.9 °F HEATING OA DB / WB 28.4 °F / 23.4 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 241 ft² 2423 - 241 ft² 4090 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 869 ft² 3412 - 869 ft² 13302 -
Partitions 180 ft² 283 - 180 ft² 1102 -
Ceiling 869 ft² 2047 - 869 ft² 7981 -
Overhead Lighting 939 W 3204 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4347 W 14832 - 0 0 -
People 2 590 910 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2679 91 0% 0 0
>> Total Zone Loads - 29471 1001 - 26475 0
Zone Conditioning - 23924 1001 - 26349 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1500 CFM 0 - 1500 CFM 0 -
Ventilation Load 52 CFM 316 277 52 CFM 1584 0
Supply Fan Load 1500 CFM 0 - 1500 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 24240 1278 - 27932 0
Central Cooling Coil - 24240 1279 - 0 0
Central Heating Coil - 0 - - 27932 -
>> Total Conditioning - 24240 1279 - 27932 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 4 of 8


System Psychrometrics for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

July DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 79.9 0.01214 52 400 316 277
Vent - Return Mixing Outlet 72.5 0.01066 1500 865 - -
Central Cooling Coil Outlet 52.0 0.01042 1500 865 24240 1279
Central Heating Coil Outlet 52.0 0.01042 1500 865 0 -
Supply Fan Outlet 52.0 0.01042 1500 865 0 -
Cold Supply Duct Outlet 52.0 0.01042 1500 865 - -
Zone Air - 72.2 0.01061 1500 882 23924 1001
Return Plenum Outlet 72.2 0.01061 1500 882 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.788 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 3463.3 BTU/(hr-CFM)
Site Altitude = 8466.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
037 POWER BACKUP 29471 Cooling 23924 72.2 1500 882 0 0

Hourly Analysis Program 5.10 Page 5 of 8


System Psychrometrics for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 28.4 0.00235 52 400 -1584 0
Vent - Return Mixing Outlet 65.6 0.00235 1500 671 - -
Central Cooling Coil Outlet 65.6 0.00235 1500 671 0 0
Central Heating Coil Outlet 89.2 0.00235 1500 671 27932 -
Supply Fan Outlet 89.2 0.00235 1500 671 0 -
Cold Supply Duct Outlet 89.2 0.00235 1500 671 - -
Zone Air - 66.9 0.00235 1500 681 -26349 0
Return Plenum Outlet 66.9 0.00235 1500 681 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.788 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 3463.3 BTU/(hr-CFM)
Site Altitude = 8466.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
037 POWER BACKUP -26475 Heating -26349 66.9 1500 681 0 0

Hourly Analysis Program 5.10 Page 6 of 8


System Psychrometrics for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

Location: Toluca, Mexico


Altitude: 8466.0 ft.
Data for: July DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014
1
0.012
34 2
5
0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.10 Page 7 of 8


System Psychrometrics for 12 DX - POWER BACKUP
Project Name: NAVE COSMETICOS - JUNIO 2023 06/25/2023
Prepared by: HVAC 01:48p. m.

Location: Toluca, Mexico


Altitude: 8466.0 ft.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010

0.008

0.006

0.004
1 2 5 34
0.002

0.000
30 40 50 60 70 80 90
Temperature ( °F )

Hourly Analysis Program 5.10 Page 8 of 8