Setting Manual Relay Ge Multilin 350 GH
Setting Manual Relay Ge Multilin 350 GH
Setting Manual Relay Ge Multilin 350 GH
OCR TD GFR TD
I> 300 Io> 50
Curve IEC Curve A (SIT) Curve IEC Curve A (SIT)
TMS 0.06 TMS 0.06
OCR Moment GFR Moment
I>> 1000 Io>> 200
t>> 0 to>> 0
CT TERPASANG 400 A
5A
CONTACT INPUTS
OUTPUT RELAYS
LOGIC ELEMENTS
VIRTUAL INPUTS
C INPUT SUMMARY
A2 METERING CURRENT
VOLTAGE
POWER
ENERGY
THERMAL CAP
CLEAR ENERGY
TRSNDIENT RECORDS
CLEAR EVENT REC
NOMINAL FREQUENCY
HZ
PH CT PRIMARY
400 A
GND CT PRIMARY A
400
VT CONNECTION
Wye
VT SEC VOLTAGE
58 V
VT RATIO
200 : 1
AUX VT SECONDARY
58 V
AUX VT RATIO
200 : 1
PH TOC TDM
0.06 TMS
(Setting Terrendah)
GND TOC FUNCTION GROUND TOC PICKUP
Trip 0.125 xCT
GFR TD
GROUND TOC CURVE
IEC Curve A
PASSWORD SECURITY
COMMUNICATION
EVENT RECORDER
TRANSIENT RCDR
FRONT PANEL
INSTALLATION
VOLTAGE SENSING
POWER SYSTEM
BREAKER
USER CURVE
FLEXCURVE A
FLEXCURVE B
S4 CONTROLS
S5 INPUTS/OUTPUTS
MAINTENANCE M1 RELAY INFO RELAY NAME
Feeder Name
ORDER CODE
SERIAL NUMBER
M3 BKR MAINTENANCE
M4 BKR MONITOR
M5 RELAY MAINT
M6 FACTORY SERVICE
GE MULTILIN 350
Power Suply A1 -
B1 +
Tegangan
60 sd 300 VAC
84 sd 250 VDC
Arus
R E5
S E6
T E7
N E8
Ground (Jamper) D5
D6
D7
D8
Trip A2
A3
ID Pel
Nama
Alamat
Daya 0 KVA
Tarip
Trf Pel 0 KVA
CT Terpasang 400
Ib 0 A
Trafo Pel 0 KVA
In Trafo 0 A
CURRENT DATE PEMERIKSAAN WAKTU KERJA RELAY O
CONTACT INPUT 9
OFF
CONTACT INPUT 10
OFF
TRIP
OFF
CLOSE
OFF
OUTPUT RELAY 3
OFF
OUTPUT RELAY 4
OFF
OUTPUT RELAY 5
OFF
OUTPUT RELAY 6
OFF
OUTPUT RELAY 7
ON
LOGIC ELEMENT 1
OFF
LOGIC ELEMENT 2
OFF
LOGIC ELEMENT 3
OFF
LOGIC ELEMENT 4
OFF
LOGIC ELEMENT 5
OFF
LOGIC ELEMENT 6
OFF
LOGIC ELEMENT 7
OFF
LOGIC ELEMENT 8
OFF
LOGIC ELEMENT 9
OFF
LOGIC ELEMENT 10
OFF
LOGIC ELEMENT 11
OFF
LOGIC ELEMENT 12
OFF
LOGIC ELEMENT 13
OFF
LOGIC ELEMENT 14
OFF
LOGIC ELEMENT 15
OFF
LOGIC ELEMENT 16
OFF
VIRTUAL INPUT 1
OFF
VIRTUAL INPUT 2
OFF
SD
VIRTUAL INPUT 32
OFF
PH A CURRENT
PH B CURRENT
PH C CURRENT
NTRL CURRENT
GND CURRENT
AN VOLTAGE
BN VOLTAGE
CN VOLTAGE
AB VOLTAGE
BC VOLTAGE
CA VOLTAGE
NTRL VOLTAGE
AUX VOLTAGE
FREQUENCY
3 ph REAL POWER
3 ph REAKTIVE POWER
3 ph APPARENT PWR
POWER FACTOR
POSITIVE WATTHOUR
NEGATIVE WATTHOUR
POSITIVE VARHOUR
NEGATIVE VARHOUR
THERM CAP PH A
THERM CAP PH B
THERM CAP PH C
CLEAR ENERGY
E 32 (TERAKHIR)
E 1 (PERTAMA)
FORCE TRIGGER?
TOTAL RECORDS
AVALIEBLE RECORDS
LAST CLEARED
CLEAR
CLEAR
CLEAR
DATE (MM/DD/YYYY)
TIME (HH:MM:SS)
RS485
MODBUS PROTOCOL
IEC60870-5-103
PICKUP EVENTS
Disabled
DROPOUT EVENTS
Disabled
TRIP EVENTS
Enabled
ALARM EVENTS
Enabled
CONTROL EVENTS
Enabled
CONTACT INPUTS
Enabled
LOGIC ELEMENTS
Enabled
VIRTUAL INPUTS
Enabled
SETTING DATE/TIME
Enabled
BUFFER SETUP
1 x 192
TRIGGER MODE
Overwrite
TRIGGER POSITION
20%
TRIGGER ON PKP
Off
TRIGGER ON DPO
Off
TRIGGER ON TRIP
Off
TRIGGER ON ALARM
Off
TRIGGER ON INPUT 1
Off
TRIGGER ON INPUT 2
Off
TRIGGER ON INPUT 3
Off
MESSAGE TIMEOUT
30 s
SCREE SAVER
Off
RELAY NAME
Feeder Name
RELAY STATUS
Ready
PHASE CT PRIMARY
400 A
GROUND CT PRIMARY
400 A
VT CONNECTION
Wye
VT SECONDARY
58 V
VT RATIO
200 : 1
AUX VT INPUT
Vab VT
AUX VT SECONDARY
58 V
AUX VT RATIO
200 : 1
NOMINAL FREQUENCY
50 Hz
SYSTEM ROTATION
ABC
52a CONTACT
Disabled
52b CONTACT
Disabled
BKR CONNECTED
Disabled
Program using
Enervista Software
Program using
Enervista Software
Program using
Enervista Software
PH TOC CURVE
IEC Curve A
PH TOC TDM
0.06 TMS
PH TOC RESET
Instantanesous
OUTPUT RELAY 3
Do Not Operate
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
PH IOC DELAY
0.00 s
OUTPUT RELAY 3
Do Not Operate
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
OUTPUT RELAY 3
Do Not Operate
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
GROUND IOC1 GND IOC FUNCTION
(GFR MOMENT) Trip
OUTPUT RELAY 3
Do Not Operate
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
PHASE UV PH UV FUNCTION
Tidak Disetting Disabled
PHASE OV PH OV FUNCTION
Tidak Disetting Disabled
OUTPUT RELAY 3
Do Not Operate
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
PENGUJIAN RELAY
I > OCR 0.75 Io > GFR 0.1 SETTING OVER LOAD
Curve IEC Curve A Curve IEC Curve A Thermal MDL PKP 0.00
Delay (TMS) 0.06 Delay (TMS) 0.06 Thermal MDL Alarm 80
Heat Time Constant 13
I >> OCR M 2.50 Io >> GFR M 0.5 Cool Time Constant 5
Arus Uji
Kriteria Waktu Arus di Arus Injek (Ampere)
Relay (A) (Ampere)
1.05 xI set 0.00 0.00
1.2 xI set 0.00 0.00
1.5 xI set 0.00 0.00
di koordinasikan 4 xI set 0.00 0.00
TU KERJA RELAY OCR/GFR HASIL PENGUJIAN
Depok,
Penguji
(.......................................................)
OVER LOAD
x CT
%
min
min
waktu trip
(detik)
nguji
......................)