Setting Manual Relay Ge Multilin 350 GH

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 31

Setting GH

OCR TD GFR TD
I> 300 Io> 50
Curve IEC Curve A (SIT) Curve IEC Curve A (SIT)
TMS 0.06 TMS 0.06
OCR Moment GFR Moment
I>> 1000 Io>> 200
t>> 0 to>> 0
CT TERPASANG 400 A
5A

ACTUAL VALUES A1 STATUS CLOCK

CONTACT INPUTS

OUTPUT RELAYS
LOGIC ELEMENTS
VIRTUAL INPUTS

C INPUT SUMMARY

OUT RELAYS SUMARY

LOGIC ELEM SUMMARY

A2 METERING CURRENT

VOLTAGE
POWER

ENERGY

THERMAL CAP

CLEAR ENERGY

A3 RECORDS EVENT RECORD

TRSNDIENT RECORDS
CLEAR EVENT REC

CLEAR TRANST REC

CLEAR THERM CAP

A4 TARGET MESSAGES No Active Targets

QUICK SETUP RELAY STATUS

NOMINAL FREQUENCY
HZ

PH CT PRIMARY
400 A

GND CT PRIMARY A
400

VT CONNECTION
Wye

VT SEC VOLTAGE
58 V

VT RATIO
200 : 1

AUX VT SECONDARY
58 V

AUX VT RATIO
200 : 1

PH TOC FUNCTION PH TOC PICKUP


Trip 0.750 xCT
OCR TD
PH TOC CURVE
IEC Curve A

PH TOC TDM
0.06 TMS
(Setting Terrendah)
GND TOC FUNCTION GROUND TOC PICKUP
Trip 0.125 xCT
GFR TD
GROUND TOC CURVE
IEC Curve A

GROUND TOC TDM


0.06 TMS
(Setting Terrendah)
NTRL TOC FNCTN
Disabled

PH IOC1 FUNCTION PH IOC1 PICKUP


Trip 2.50 x CT
OCR MOMENT

GND IOC1 FNCTN GND IOC1 PICKUP


Trip 0.50 x CT
GFR MOMENT

NTRL IOC1 FNCTN


Disabled

SETPOINTS S1 RELAY SETUP CLOCK


setting waktu

PASSWORD SECURITY

COMMUNICATION

EVENT RECORDER
TRANSIENT RCDR
FRONT PANEL

INSTALLATION

S2 SYSTEM SETUP CURRENT SENSING

VOLTAGE SENSING
POWER SYSTEM

BREAKER

USER CURVE

FLEXCURVE A

FLEXCURVE B

S3 PROTECTION SETPOINT GROUP 1

S4 CONTROLS

S5 INPUTS/OUTPUTS
MAINTENANCE M1 RELAY INFO RELAY NAME
Feeder Name

ORDER CODE

MAIN FIRMWARE REV


1.5

MAIN BUILD DATE

MAIN BUILD TIME

SERIAL NUMBER

M3 BKR MAINTENANCE

M4 BKR MONITOR

M5 RELAY MAINT
M6 FACTORY SERVICE
GE MULTILIN 350

Power Suply A1 -
B1 +

Tegangan
60 sd 300 VAC
84 sd 250 VDC

Arus
R E5
S E6
T E7
N E8

Ground (Jamper) D5
D6
D7
D8

Trip A2
A3

ID Pel
Nama
Alamat
Daya 0 KVA
Tarip
Trf Pel 0 KVA
CT Terpasang 400
Ib 0 A
Trafo Pel 0 KVA
In Trafo 0 A
CURRENT DATE PEMERIKSAAN WAKTU KERJA RELAY O

CURRENT TIME Kriteria Waktu


TDL 2003
1.05 Iset > 3600
52a (CI#1) 1.2 Iset < 1200
OFF 1.5 Iset < 600
4 Iset di koordinasikan
52b (CI#2) PEMERIKSAAN WAKTU KERJA RELAY O
OFF
OVER CURRENT
CONTACT INPUT 3
OFF MENURUT RUMUS
Arus di
Pengujian Relay
CONTACT INPUT 4
(Ampere)
OFF 1.5 Iset 450.00
2 Iset 600.00
CONTACT INPUT 5 3 Iset 900.00
OFF 4 Iset 1200.00

CONTACT INPUT 6 GROUND FAULT


OFF MENURUT RUMUS
Arus di
Pengujian Relay
CONTACT INPUT 7
(Ampere)
OFF 1.5 Iset 75.00
2 Iset 100.00
CONTACT INPUT 8 3 Iset 150.00
OFF 4 Iset 200.00

CONTACT INPUT 9
OFF

CONTACT INPUT 10
OFF

TRIP
OFF

CLOSE
OFF

OUTPUT RELAY 3
OFF

OUTPUT RELAY 4
OFF

OUTPUT RELAY 5
OFF

OUTPUT RELAY 6
OFF

OUTPUT RELAY 7
ON

LOGIC ELEMENT 1
OFF

LOGIC ELEMENT 2
OFF

LOGIC ELEMENT 3
OFF

LOGIC ELEMENT 4
OFF

LOGIC ELEMENT 5
OFF

LOGIC ELEMENT 6
OFF

LOGIC ELEMENT 7
OFF

LOGIC ELEMENT 8
OFF

LOGIC ELEMENT 9
OFF

LOGIC ELEMENT 10
OFF

LOGIC ELEMENT 11
OFF

LOGIC ELEMENT 12
OFF

LOGIC ELEMENT 13
OFF

LOGIC ELEMENT 14
OFF

LOGIC ELEMENT 15
OFF

LOGIC ELEMENT 16
OFF

VIRTUAL INPUT 1
OFF

VIRTUAL INPUT 2
OFF
SD
VIRTUAL INPUT 32
OFF

PH A CURRENT

PH B CURRENT

PH C CURRENT

NTRL CURRENT

GND CURRENT

AN VOLTAGE

BN VOLTAGE

CN VOLTAGE

AB VOLTAGE

BC VOLTAGE
CA VOLTAGE

NTRL VOLTAGE

NEG. SEQ. VOLTAGE

ZERO SEQ. VOLTAGE

AUX VOLTAGE

FREQUENCY

3 ph REAL POWER

3 ph REAKTIVE POWER

3 ph APPARENT PWR

POWER FACTOR

POSITIVE WATTHOUR

NEGATIVE WATTHOUR

POSITIVE VARHOUR

NEGATIVE VARHOUR

THERM CAP PH A

THERM CAP PH B

THERM CAP PH C

CLEAR ENERGY

E 32 (TERAKHIR)

E 1 (PERTAMA)

FORCE TRIGGER?

TOTAL RECORDS
AVALIEBLE RECORDS

LAST CLEARED

CLEAR

CLEAR

CLEAR
DATE (MM/DD/YYYY)

TIME (HH:MM:SS)

LOC SETPOINTS PSWD

LOC CONTROLS PSWD

RS485

MODBUS PROTOCOL

IEC60870-5-103

PICKUP EVENTS
Disabled

DROPOUT EVENTS
Disabled

TRIP EVENTS
Enabled

ALARM EVENTS
Enabled

CONTROL EVENTS
Enabled

CONTACT INPUTS
Enabled

LOGIC ELEMENTS
Enabled

VIRTUAL INPUTS
Enabled

SETTING DATE/TIME
Enabled

BUFFER SETUP
1 x 192

TRIGGER MODE
Overwrite

TRIGGER POSITION
20%

TRIGGER ON PKP
Off

TRIGGER ON DPO
Off

TRIGGER ON TRIP
Off

TRIGGER ON ALARM
Off
TRIGGER ON INPUT 1
Off

TRIGGER ON INPUT 2
Off

TRIGGER ON INPUT 3
Off

FLASH MESSAGE TIME


5 s

MESSAGE TIMEOUT
30 s

SCREE SAVER
Off

LED BKR OPEN COLOR


Green

LED BKR CLSD COLOR


Green

RELAY NAME
Feeder Name

RELAY STATUS
Ready

PHASE CT PRIMARY
400 A

GROUND CT PRIMARY
400 A

VT CONNECTION
Wye

VT SECONDARY
58 V

VT RATIO
200 : 1
AUX VT INPUT
Vab VT

AUX VT SECONDARY
58 V

AUX VT RATIO
200 : 1

NOMINAL FREQUENCY
50 Hz

SYSTEM ROTATION
ABC

52a CONTACT
Disabled

52b CONTACT
Disabled

BKR CONNECTED
Disabled

Program using
Enervista Software

Program using
Enervista Software

Program using
Enervista Software

PHASE TOC PH TOC FUNCTION


(Time Delay Over Current) Trip
OCR TD
PH TOC PKP
0.75 x CT

PH TOC CURVE
IEC Curve A

PH TOC TDM
0.06 TMS
PH TOC RESET
Instantanesous

OUTPUT RELAY 3
Do Not Operate

OUTPUT RELAY 4
Do Not Operate

OUTPUT RELAY 5
Do Not Operate

OUTPUT RELAY 6
Do Not Operate

BLOCK 1
Off

BLOCK 2
Off

BLOCK 3
Off

PHASE IOC 1 PHASE IOC1 FUNFTION


(Instant Over Current) Trip
OCR Moment
PH IOC PKP
2.50 x CT

PH IOC DELAY
0.00 s

OUTPUT RELAY 3
Do Not Operate

OUTPUT RELAY 4
Do Not Operate

OUTPUT RELAY 5
Do Not Operate

OUTPUT RELAY 6
Do Not Operate

BLOCK 1
Off
BLOCK 2
Off

BLOCK 3
Off

PHASE IOC2 PH IOC2 FUNCTION


(Tidak di Setting) Disabled

GROUND TOC GND TOC FUNCTION


GFR TD Trip

GND TOC PKP


0.13 x CT

GND TOC CURVE


IEC Curve A

GND TOC TDM


0.06 TMS

GND TOC RESET


Instantaneous

GND TOC DIRECTION


Disabled

OUTPUT RELAY 3
Do Not Operate

OUTPUT RELAY 4
Do Not Operate

OUTPUT RELAY 5
Do Not Operate

OUTPUT RELAY 6
Do Not Operate

BLOCK 1
Off

BLOCK 2
Off

BLOCK 3
Off
GROUND IOC1 GND IOC FUNCTION
(GFR MOMENT) Trip

GND IOC PKP


0.50 x CT

GND IOC DELAY


0.00 s

GND IOC DIRECTION


Disabled

OUTPUT RELAY 3
Do Not Operate

OUTPUT RELAY 4
Do Not Operate

OUTPUT RELAY 5
Do Not Operate

OUTPUT RELAY 6
Do Not Operate

BLOCK 1
Off

BLOCK 2
Off

BLOCK 3
Off

GROUND IOC2 GND IOC2 FUNCTION


(TIDAK DI SETTING) Disabled

GND DIR GND DIR FUNCTION


Tidak Disetting Disabled

NEUTRAL TOC NTRL TOC FUNCTION


Tidak Disetting Disabled

NEUTRAL IOC1 NTRL IOC1 FUNCTION


Tidak Disetting Disabled
NEUTRAL IOC 2 NTRL IOC2 FUNTION
Tidak Disetting Disabled

NTRL DIR NTRL DIR FUNCTION


Tidak Disetting Disabled

PHASE UV PH UV FUNCTION
Tidak Disetting Disabled

PHASE OV PH OV FUNCTION
Tidak Disetting Disabled

NEUTRAL OV NTRL OV FUNTION


Tidak Disetting Disabled

NEGATIVE SEQ. OV NEG SEQ OV FUNCTN


Tidak Disetting Disabled

AUXILIARY UV AUX UV FUNCTION


Tidak Disetting Disabled

AUXILIARY OV AUX OV FUNCTION


Tidak Disetting Disabled

UNDER-FREQUENCY1 UNDERFREQ 1 FUNC


Tidak Disetting Disabled

UNDER-FREQUENCY2 UNDERFREQ 2 FUNC


Tidak Disetting Disabled

OVER-FREQUENCY1 OVERFREQ 1 FUNCTN


Tidak Disetting Disabled

OVER-FREQUENCY2 OVERFREQ 2 FUNCTN


Tidak Disetting Disabled

THERMAL MODEL THERMAL MDL FUNC


Setting Thermal Trip

THERMAL MDL PKP


0.00 x CT

THERMAL MDL ALARM


80 %

HEAT TIME CONSTANT


13 min

COOL TIME CONSTANT


5

OUTPUT RELAY 3
Do Not Operate

OUTPUT RELAY 4
Do Not Operate

OUTPUT RELAY 5
Do Not Operate

OUTPUT RELAY 6
Do Not Operate

BLOCK 1
Off

BLOCK 2
Off

BLOCK 3
Off
PENGUJIAN RELAY
I > OCR 0.75 Io > GFR 0.1 SETTING OVER LOAD
Curve IEC Curve A Curve IEC Curve A Thermal MDL PKP 0.00
Delay (TMS) 0.06 Delay (TMS) 0.06 Thermal MDL Alarm 80
Heat Time Constant 13
I >> OCR M 2.50 Io >> GFR M 0.5 Cool Time Constant 5

5 Delay 0.00 Delay 0.00


Merk Relay GE
Type MULTILIN 350
SN
TU KERJA RELAY OVERLOAD HASIL PENGUJIAN

Arus Uji
Kriteria Waktu Arus di Arus Injek (Ampere)
Relay (A) (Ampere)
1.05 xI set 0.00 0.00
1.2 xI set 0.00 0.00
1.5 xI set 0.00 0.00
di koordinasikan 4 xI set 0.00 0.00
TU KERJA RELAY OCR/GFR HASIL PENGUJIAN

NURUT RUMUS MENURUT ALAT UJI


Arus Injek Waktu Trip Arus (Ampere) Waktu Trip (Detik)
(Ampere) (detik) R-S R-T S-T R-S R-T
5.6 1.032
7.5 0.602
11.3 0.378
15.0 0.299

NURUT RUMUS MENURUT ALAT UJI


Arus Injek Waktu Trip Arus (Ampere) Waktu Trip (Detik)
(Ampere) (detik) R-N S-N T-N R-N S-N
0.9 1.032
1.3 0.602
1.9 0.378
2.5 0.299

Depok,
Penguji

(.......................................................)
OVER LOAD
x CT
%
min
min

waktu trip
(detik)

ktu Trip (Detik)


S-T

ktu Trip (Detik)


T-N

nguji

......................)