MSHA ACRI2011 Criteria For IS Active Voltage Current Power Source 2008
MSHA ACRI2011 Criteria For IS Active Voltage Current Power Source 2008
MSHA ACRI2011 Criteria For IS Active Voltage Current Power Source 2008
1.0 PURPOSE
2.0 SCOPE
These requirements apply to any circuit that uses some form of active voltage or
current limiting in whole or in part to provide an intrinsically safe output.
3.0 REFERENCES
3.3. 30 CFR Part 20 “Electric Mine Lamps Other Than Standard Cap Lamps”
3.7. ACRI2001 “Criteria for the Evaluation and Test of Intrinsically Safe
Apparatus and Associated Apparatus”
4.0 DEFINITIONS
5.0 CRITERIA
5.1. In addition to this criteria, the circuit must comply with all other applicable
parts of ACRI2001.
5.2. Documentation.
5.2.2.1. The maximum voltage and current settings for each active circuit
affecting intrinsic safety. This includes active limiting stages that
indirectly affect the output voltage and current, di/dt circuits, etc.
5.2.2.3. Maximum acceptable directly connected load capacitance for zero, one,
and two fault conditions.
5.2.2.4. Maximum source inductance appearing at the output terminals for zero,
one, and two fault conditions and the associated minimum resistance
for these conditions.
5.3.1. All components of each protection circuit affecting intrinsic safety shall be
operated, in normal operation, at not more than 2/3 of their rated current,
voltage, or power, as appropriate (ref. ACRI2001 section 8.1.1). Special
attention must be applied to the evaluation of duplicative protection
circuits, since for most cases, it can be assumed that current, voltage, and
power are not shared among the duplicated circuits. Instead, due to
tolerances in the settings, only one of the duplicated circuits trips or
activates.
For example, there are three active current limiting circuits that limit the
current to 2, 4, and 6 amperes to three equivalent zener diodes. In
accordance with ACRI2001 section 8.1.1, the zener diodes need to each be
rated 3A (2/3 rating at 2 amperes). However, to determine adequacy after
application of two faults (short circuit failure of the 2 and 4 ampere
current limiting circuits), each zener diode must be capable of
5.3.3. When a single sense resistor is shared for multiple protection circuits, the
sense resistor must be connected to each protection circuit through
separate circuit board traces so that one common trace failure does not
disable all protection circuits. The resistor must also comply with
ACRI2001 as a protective current limiting resistor. Note: Infallible traces
are not an acceptable alternative according to ACRI2001.
5.3.4. Circuits which are powered from an AC line and are not powered through
a protective transformer as defined in ACRI2001 must have input
protection that passes a two fault analysis per ACRI2001 for the AC line
voltage.
5.3.5. Since it is not feasible to conduct a spark ignition test at the instant an
overvoltage condition occurs, the overvoltage protection circuit shall be
accepted on the basis of its response time. The response time is
considered the time at which the maximum input fault voltage exceeds
the maximum trip voltage and returns to less than or equal to the
maximum trip voltage. For purposes of the test, the maximum input fault
voltage shall be simulated with a DC input voltage equal to the maximum
DC input voltage or maximum peak AC input voltage. A response time
of 100μS or less is acceptable without additional testing or justification
provided there is no damage that would affect intrinsic safety. Response
times in excess of 100μS shall be justified. The response time of the
overvoltage protection circuit of the non-safety factored version shall be
documented by means of an oscilloscope trace.
Note: The test shall be conducted by applying the worst case input
voltage and applying the two worst case faults according to ACRI2001.
Subsequent faults as a result of this test are not countable.
5.3.6. Where active circuit settings that affect intrinsic safety are adjustable, the
adjustable components must be inaccessible to the user and resistant to
vibration.
5.3.7. The maximum source inductance appearing at the output terminals for
zero, one, and two fault conditions and the associated minimum
resistance for these conditions shall be verified. This data will be used in
the evaluation of the future connected inductive loads and either
compared with published spark ignition curves or tested to determine
acceptability.
5.4.1. One fully assembled version of the power source in marketable form for
testing and comparison to the drawings. If any of the circuitry is
encapsulated, then a second unencapsulated sample must also be
submitted for measurements and application of faults.
5.4.2. One fully assembled version of the safety-factored power source. If any of
the circuitry is encapsulated, then the submitted sample shall be
unencapsulated for measurements and application of faults. The
following requirements shall be included in the construction of the safety-
factored power source:
5.4.2.1. An electrical safety factor is required for all spark ignition tests of zero
and one faults. A safety factor obtained through the use of a more easily
ignitable gas is not acceptable. The safety-factored version of the power
source shall be adjusted to provide 1.5 times the output energy. This is
typically achieved by increasing the voltage/current by 1.225 times
each, with unaltered shut-down speed. Power sources employing
special features such as di/dt circuits shall also have these circuits safety
factored if necessary to achieve a 1.5 factor of safety on energy. Note:
The shut-down time may vary slightly due to the change in
voltage/current. If considered to be providing a less than desirable
safety factor, then the shut-down time will need to be decreased.
5.5.1. Voltage and current measurements at critical stages of the circuit such as
output of the transformer, output of the rectifier, output of the rectifier
plus capacitance, output of the overvoltage protection, output of the
overcurrent protection, etc. Note: it may be necessary to open circuit
downstream circuitry to prevent any affect on the desired measurements.
5.5.2. Load lines (e.g. output voltage versus output current for varying resistive
loads including open circuit and short circuit) with all critical faults that
would affect the output characteristics. The purpose of these load lines is
5.5.3. Oscilloscope traces of the output waveforms with all critical faults that
would affect the output characteristics. Additional oscilloscope traces
must be obtained to confirm special features of the power source such as a
di/dt circuit. The purpose of obtaining the oscilloscope traces is to
compare the safety-factored and non-safety-factored traces for similarity,
and to record the speed of the tested circuits for future reference.
5.6.1. Testing should be conducted with only one of the identical duplicated
circuits to prove adequacy and reliability unless including multiple
circuits can be proven to be a more severe condition. Note: This may be a
more stringent test (e.g. two faults with a safety factor), but may be used if
it simplifies testing. Failure to pass this test does not imply the circuit is
unsafe. If a failure occurs, additional consideration to the worst case test
will need to be made.
5.6.2. Testing shall be conducted at 1.2 times the nominal input voltage (AC or
DC) unless testing at the nominal input voltage or less can be proven to be
a more severe condition.
5.7.1. The power source must be subjected to a minimum of 4,000 short circuit
make sparks, and 4,000 maximum current break sparks. Two
characteristics of active power sources may prevent a single continuous
spark ignition test of 1,000 revolutions to be the most severe test. If the
power source exhibits either of the following characteristics, then the
spark ignition testing of the power source output must include the
prescribed additional test(s). Note: Segmenting the test(s) is allowed (e.g.
four 1,000 cycle segments) provided a calibration is obtained before and
after each segment.
• If the active protected circuit shuts down on the first make short circuit
of the spark test apparatus, and does not reset quickly enough to the
maximum open circuit voltage between the break short circuit and the
next make short circuit of the apparatus, then the additional test
described by section 5.7.1.1 must be conducted.
5.7.1.1. The make-spark ignition test may either require stopping the electrodes
off of the disc to allow adequate time for the power source to reset or
reducing the quantity of electrodes to prevent stopping and starting of
the spark test apparatus. An oscilloscope trace shall be obtained and
included with the spark ignition test sheet to confirm adequate reset
time was allotted during the spark ignition test.
Note: The standard disc with the two grooves must be utilized during
all spark ignition testing.
Below is a table listing the approximate reset times at 80RPM for the
quantity of electrodes installed, and the scope trace from which these
were calculated. The scope trace was obtained at 80RPM with four
electrodes installed using a non-typical disc without the two required
grooves.
4 55mS
2 242.5mS
1 617.5mS
5.7.1.2. The break-spark ignition test may be conducted by either of the two
following methods:
5.7.1.2.2. By stopping the electrode on the disc, reducing the variable resistive
load to obtain safety-factored current, and then starting the spark test
apparatus to initiate the break-spark.
5.7.3. If a power source includes features such as a di/dt circuit, then special
consideration has to be given to devising a spark ignition test that
simulates the worst case resistive loading condition for a make or break
spark. A detailed understanding of the operation of the circuit is required
to properly configure the spark test.
Alternatively, the di/dt circuit could be bypassed for testing. Failing the
spark ignition test with a triplicated di/dt circuit bypassed does not
necessarily constitute a failure.
5.7.5. Repeat the tests described by sections 5.7.1 through 5.7.4 using the non-
safety-factored power supply.
5.8. Conditions of Use. The approval letter shall include the following
conditions of use for active circuits that are not application specific:
5.8.2. If the power source has multiple output voltage and/or current settings,
then all MSHA approved power sources must be marked so the user can
5.9.1. The maximum voltage and current settings for each active circuit affecting
intrinsic safety. This includes active limiting stages that indirectly affect
the output voltage and current, di/dt circuits, etc.
5.9.2. The maximum non-safety-factored output voltage and output current for
the power source with zero, one, and two faults applied. A circuit using
identical triplicate circuits could have the same voltage and current for
each quantity of faults.
5.9.3. Maximum acceptable directly connected load capacitance for zero, one,
and two fault conditions. As an alternative for application specific power
sources, the worst case situation(s) may be tested.
5.9.4. Maximum source inductance appearing at the output terminals for zero,
one, and two fault conditions and the associated minimum resistance for
these conditions. As an alternative for application specific power sources,
the worst case situation(s) may be tested.